WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Important Safety InformationItisyourresponsibilitytoensurethatthiscontrolissafelyinstalledaccordingtoallapplicablecodesandstandards.tekmarisnotresponsiblefordamagesresultingfromimproperinstallationand/ormaintenance.
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Thecontrol canbemountedonastandardDINrail.Firstremovethecontrolfromitsbaseandthen,using the hooks and spring cliponthebackofthecontrol,mountitontotheDINrail.Thiswillbeapopularoptionforthosewhoprefertomountthecontrolinsidealargerelectricalpanel.TheDINSnapKitM9303issoldseparately.
The wiring can enter thebottomorthebackoftheenclosure.Knock-outspro-videdinthebaseallowthewiringtoberuninconduitup to the enclosure. Thebase also has holes thatlineupwith themountingholes of most commonelectricalboxes.
Low-Voltage Wiring-------------------------------------------------------------------------------------Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) long, for the following equipment:• Outdoortemperaturesensor• Mixsupplysensor• Boilersensor• Single-stageon/offboiler• Modulatingboiler0-10V(dc)or4-20mA• Mixingvalveormixinginjectionpumpusinga0-10V(dc)
or4-20mAsignal.
Pull three conductor 18 AWG LVT cable, up to 500 feet (150 m) long, for the following equipment:• MixingvalvesusingafloatingactionsignalPull four conductor 18 AWG LVT cable, up to 500 feet (150 m) long, for the following equipment:• SnowSensor095• Two-stageon/offboilerPull the Snow/Ice Sensor 090 or 094 cable to the control.
Line-Voltage Wiring------------------------------------------------------------------------------------Pull two conductor 14 AWG cable, up to 500 feet (150 m) long, for the following equipment:• Systempump• Boilerpump• Heatexchangeron/offinjectionpump• Variablespeedinjectionpump
Strapped to PipeTheUniversalSensorcanbestrappeddirectlytothepipeusingthecabletieprovided.Insulationshouldbeplacedaroundthesensortoreducetheeffectofaircurrentsonthesensormeasurement.
Mounting the Boiler and System Sensors--------------------------------------------------------------
Mounting the Mix Supply Sensor-----------------------------------------------------------------------Themixsupplysensorisusedwhenoperatingamixingvalveoravariablespeedinjectionpumpisinstalled.• Ifapplicable,connectthemixsupplysensortoterminals14and15.
Mounting the Boiler Sensor----------------------------------------------------------------------------
Wiring the Analog Mixing Output-----------------------------------------------------------------------Thecontrolcanoperateamixingvalvebyprovidinga0-10V(dc)ora4-20mAsignaltothevalveactuatingmotor.• Ifapplicable,connectthemixingactuatorpositive(+)toterminal1.• Ifapplicable,connectthemixingactuatornegative(-)toterminal2.
thetemperaturemeasuredbythesensor.Thesensorandthermometerreadingsshouldbeclose.Ifthetestmeterreadsaveryhighresistance,theremaybeabrokenwire,apoorwiringconnectionoradefectivesensor.Iftheresistanceisverylow,thewiringmaybeshorted,theremaybemoistureinthesensororthesensormaybedefective.Totestforadefectivesensor,measuretheresistancedirectlyatthesensorlocation.Do not apply voltage to a sensor at any time as damage to the sensor may result.
Testing the Control WiringRemovethefrontcoverfromthecontrol.Testing the Power-------------------------------• Useanelectricalmetersettomeasure(ac)voltage.• MeasurebetweentheLandNterminals.• Thereadingshouldbe115V(ac)+/–10%.Hand Manual Override---------------------------ThecontrolincludesaHandManualOverridemenutocheckifthecontrol’srelaysareoperatingandthatthecontroliswiredcorrectlytothesnowmeltingequipment.Step1: PressSettingsbutton.Step2: PressOverridebutton.Step3: PressManualOverride.Step4: SelectManualOverridetoHand.Step5: PressBackbutton.Step6: Thefollowingoutputscanbeoperated:• SystemPumprelay• HeatRelay• BoilerStage1relay• BoilerStage2relay• BoilerModulation0-10V(dc)or4-20mAsignal• MixSystemOutput0-10V(dc)or4-20mAsignal• MixSystemOutputfloatingactionrelays• MixSystemOutputvariable-speedinjectionpump
For each relay output• Useanelectricalmetersettomeasure(ac)voltage.• Measurebetweentherelaywiringterminals.• Whentherelayisoff,thevoltageshouldbe115V(ac).• Whentherelayison,thevoltageshouldbe0V(ac).For the Boiler Modulation• UseanelectricalmetersettomeasureV(dc)ormA.• SettheBoilerModulationto100%.• Thevoltagebetweenthe+and–wiringterminalsshouldbe
0V(dc)or4mA.For the Mix System Output – Floating Action• Useanelectricalmetersettomeasure(ac)voltage.• SettheMixOutputto100%.Thefloatingactionopenwiring
Manual Override – Maximum HeatInhydronicapplicationmodes,thecontrolincludesaMaximumHeatoperationwherethecontroloperatesthesnowmeltingsystemtomaintainthemaximumallowedheatingsetpoints.Thisallowstestingofthesnowmeltingsystemduringwarmweather.
For the Mix Output – Analog Mixing• UseanelectricalmetersettomeasureV(dc)ormA.• SettheMixOutputto100%.• Thevoltagebetweenthe+and–wiringterminalsshouldbe
SYSTEM IN OVERRIDE / SYSTEM IN EXERCISING• Thecontrolisinamanualoverridefortesting,commissioningorexercising.• Thedescriptionfieldexplainswhichtypeofoverrideisactive.
Status Menu NavigationStep1:PresstheStatusbuttonontheHomeScreen.Step2:PresseithertheSystem,SlaborWeatherbutton.Step3:Pressupordownbuttonstoscrollthroughthelist.
BOILER MIN MODULATIONSettheboilerminimummodulationoftheboilerburner.Conditions:Availablewhen1)ApplicationModeissettoBoilerorBoiler+Mix,and2)BoilerTypeissettoMod.
BOILER MOTOR SPEEDSetthetimerequiredforthemodulatingburneractuatingmotortofullyopenthegasvalveorramptheburnerfanspeedfromofftofullspeed.Setto30secondsunlessotherwiserecommendedbytheboilermanufacturer.Conditions:Availablewhen1)ApplicationModeissettoBoilerorBoiler+Mix,and2)BoilerTypeissettoMod.
EMS SIGNAL MINIMUMThestartingvoltagefortheEMSboilersignal.ThisvoltagecorrespondstotheEMSLowTemperaturesetting.Checktheboilermanufacturer’smanualforthestartingvoltagefortheEMSsignalrange.Conditions:Availablewhen1)BoilerTypeissettoEMS,and2)BoilerModulationTypeissetto0-10V.
EMS HIGH TEMPERATURETheEMSboilertargettemperaturethatcorrespondsto10V(dc)or20mA.Checktheboilermanufacturer’smanualforthemaximumEMStargettemperature.Conditions:AvailablewhenBoilerTypeissettoEMS.
MIX MOTOR SPEEDSetthetimethatthemixingactuatingmotorrequirestooperatefromfullyclosedtofullyopen.Checkthemixingactuatormotorinstructionmanualforthemotorspeedtime.Conditions:Availablewhen1)ApplicationModeissettoMixingorBoiler+Mix,and2)MixingTypeissettoFloating,0-10V,or4-20mA.
AWAY SCENE SelectifthecontrolshouldacceptorignoretheawaycommandfromthemobileapporfromatekmarNetsystem.Conditions:Alwaysavailable.
OfforOnDefault=On Installer
TN4 SYSTEM PUMP SelectifthesystempumplocatedonthetekmarNetSystemControlshouldoperatewhenthesnowmeltzoneisheating.Conditions:Availablewhenthe670isconnectedtoothercontrolsusingtekmarNetcommunication.
SYSTEM PUMPManuallyturnonthesystempumpduringtheHANDManualOverride.Conditions:Availablewhen1)ApplicationModeissettoPWMZone,Boiler,MixingorBoiler+Mix,and2)ManualOverrideissettoHand.
HAND DURATIONSelecttheamountoftimethattheHANDOverrideisineffectbeforereturningtoAutomaticoperation.Conditions:AvailablewhenManualOverrideissettoHand.
0:10to72:00hours
Default=0:10hour
UserInstaller
MAX HEAT DURATIONSelecttheamountoftimethatMaxHeatisineffectbeforereturningtoAutomaticoperation.Conditions:Availablewhen1)ApplicationModeissettoPWMZone,Boiler,MixingorBoiler+Mix,and2)ManualOverrideissettoMaxHeat.
Sequence of OperationSnow Melting OverviewAsnowmeltingsystemcanofferasafe,convenient,andcosteffectivewayofremovingsnowandicefromthesnowmeltingslabandsimilarsurfaces.Safetyisincreasedbyactivatingthesnowmeltingsystemassoonasthesnowfallsratherthanwaitingformechanicalsnowremovalaftersnowhasaccumulated.Thiseliminatessliphazardsandreducestheriskofinjurybymechanizedsnowmeltingequipment,therebyreducingpotentialliabilitycosts.Theeliminationofsnowplowequipmentandcorrosivesaltsalsoreducesdamagetotheslabsurfaceandtotheenvironment.Whencontrolledcorrectly,snowmeltingsystemscanbecostcompetitivecomparedtomechanicalsnowremoval.Thesnowmeltingcontrolcanoperateinoneoffourdifferentways:
Melt – Automatic Start and StopAutomaticstartandstopoperationrequirestheinstallationofaSnow/IceSensor090(65'or20mcable)or094(208'or63mcable).Thesensorisinstalledin-slablevelwiththemeltingsurface.Thecontrolcontinuallymonitorsthesensorforthepresenceofmoistureandslabtemperatureconditionsinwhichsnoworicemaybepresent.Whenmoistureisdetected,thecontrolshows“SensorWaterStatus–Wet”intheSlabStatusmenu.Whenthesensorisdrythecontrolshows“SensorWaterStatus–Dry”.ThecontrolincludesaSensitivitysettingintheTemperaturesmenuthatallowstheinstallertoadjusttheamountofmoisturerequiredtostartandstopthemeltingoperation.Inareaswithlowamountsofdustand/orairpollution,thesensitivitymayneedtobeincreased.ThedefaultsensitivitysettingisAuto.Thissettingallowsthecontroltoautomaticallydeterminethebestsuitablesensitivity
PushSTOPButton
090or094andSlabDryandAddMeltTimeElapses
or
Idle
Off WWSD
MobileAppStopButton
Gateway482or485StopMessage
090or094DetectsWater
ExitsCWCOMelt
Suspended
EntersCWCO
Melting
AutoStart/AutoStop
settingfortheinstallation.Whenmoistureisdetectedandtheslabandoutdoortempera-turesareatorbelowfreezing,thecontrolwillautomaticallystartthesnowmeltingsystem.Asthesnoworicemeltsandtheslabdriesoff,thesensoralsodriesoffatthesametime.Whenthesensorisdry,thesnowmeltsystemautomaticallyshutsoff.Iftherearelowspotsontheslabsurfacethatdryoffslowerthanthesensor,additionalmeltingruntimecanbeincludedbyadjustingtheAdditionalMeltTimesettingintheTemperaturesmenu.If the snow melting system is manually stopped, the snow/ice sensor must fully dry before it is able to detect a new snow fall and automatically start the snow melting system.
Auto Storm--------------------------------------ThecontrolautomaticallychecksanInternetweatherservicetodeterminethesnowfallforecastforaregionbasedupontheUSZIPorCanadianpostalcode.WhentheStormfeatureisonandsnowfallispredicted,thecontrolautomaticallyheatstheslabtothestormsetting.WhenconnectedusingtekmarNet,a670canautomaticallystartthestormoperationonaSnowMeltingControl654.Todothissetthe670andthe654tousethesameStormGroupnumber.
Electric Priority Levels---------------------------------------------------------------------------------Electricsnowmeltingoffersthreelevelsofpriority:None,ConditionalandFull.TheNoneandFullpriorityoptionsfunctionthesameaswiththehydronicoperation.TheConditionalpriorityisuniquetoelectricaloperation.Thehighestpriorityzoneoperatesfirst.Wheneverthehighestpriorityzoneshuts
Electric OperationTheApplicationModeshouldbesettoElectricwhenoperatinganelectricheatingcable.Thecontroloperatestheheatrelayona20-minutepulsewidthmodulationcycle.Theheatrelayinturnactivatesalinevoltageelectricalcontactortoenergizetheelectricalcableheaterinstalledintheslab.Therelayontimeisdeterminedbythecalculatedslabtargetandbythemeasuredslabtemperaturereading.Astheslabtemperaturereachestheslabtarget,theon-timepercycleoftherelayisreducedtopreventtheslabtemperaturefromovershooting.Ifnoslabsensorisinstalledtherelayremainson100%ofthetimeuntiltheMeltoperationhascompleted.IdleandStormoperationarenotavailablewhenaslabsensorisnotinstalled.Theelectricoperationrequirestheinstallationofanoutdoorsensor.Aslabsensorishighlyrecommendedinordertoreduceoperatingcosts.
Boiler and Mixing OperationTheApplicationModeshouldbesettoBoiler+Mixwhenamixingvalveoramixinginjectionpumpisinstalledtoregulatethesupplywatertemperaturetothesnowmeltingsystemwithadedicatedboilerplant.Inthiscase,thecontroloperatesboththemixingdeviceandthededicatedboileratthesametime.ThecontrolcalculatestheSlabTargettemperaturebasedontheoutdoorairtemperatureandtheMelting,IdlingorStormSetpoint.ThecontrolthendeterminestheMixSystemTargetbasedontheSlabTargetrequirements.ThecontrolthendeterminestherequiredBoilerTargetthatisrequiredtomeettheMixSystemTarget.RefertotheBoilerandMixingOperationsectionsfordetailedinformationontheboilerandmixingoperation.
TEMPERATURE MENU SAVE ERRORThecontrolfailedtoreadtheTemperaturesmenusettingsfrommemoryandhasreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheTemperaturesmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheTemperaturesmenu.
SYSTEM SETUP MENU SAVE ERRORThecontrolfailedtoreadtheSystemSetupmenusettingsfrommemoryandhasreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheSystemSetupmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheSystemSetupmenu.
BOILER SETUP MENU SAVE ERRORThecontrolfailedtoreadtheBoilerSetupmenusettingsfrommemoryandhasreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheBoilerSetupmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheBoilerSetupmenu.
MIXING SETUP MENU SAVE ERRORThecontrolfailedtoreadtheMixingSetupmenusettingsfrommemoryandhasreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheMixingSetupmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheMixingSetupmenu.
tekmarNet MENU SAVE ERRORThecontrolfailedtoreadthetekmarNetmenusettingsfrommemoryandhasreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsinthetekmarNetmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsinthetekmarNetmenu.
WiFi MENU SAVE ERRORThecontrolfailedtoreadtheWiFimenusettingsfrommemoryandhasreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheWiFimenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheWiFimenu.
MAX MELT DAYS ERRORThecontrolhasoperatedinmeltingforthetimesetbyMaximumMeltDayssettinglocatedintheSystemSetupmenu.Thiserrorisusuallycreatedwhenthereisamechanicalsystemfailureresultinginthesnowmeltslabnotheatingcorrectly.CleartheerrormessagebytouchingtheCancelbuttonwhileviewingtheerrormessage.UsetheManualOverridemenutomanuallycheckthateachcomponentofthemechanicalsystemisoperatingcorrectly.Ifnecessary,changetheMaximumMeltDayssettingtoalongertimeperiodortoOff.
OUTDOOR SENSOR OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadtheOutdoorSensor070onterminals16and18.ThiserrormayalsooccurwhenusingtheoutdoortemperaturefromatekmarNetsystem.Thecontrolcontinuestooperateandassumesanoutdoortemperatureof32°F(0°C).EnergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)aredisabled.Checktheoutdoorsensorwireforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacetheoutdoorsensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
OUTDOOR SENSOR SHORT CIRCUIT ERRORDuetoashortcircuit,thecontrolisunabletoreadtheOutdoorSensor070onterminals16and18.Thecontrolcontinuestooperateandassumesanoutdoortemperatureof32°F(0°C).EnergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)aredisabled.Checktheoutdoorsensorwireforshortcircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacetheoutdoorsensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
MIX SUPPLY SENSOR OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadtheMixSupplySensor082onterminals15and16.Thecontrolstopsoperationanddoesnotprovideanyheat.Checkthesystemsupplysensorwireforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethemixsupplysensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
MIX SUPPLY SENSOR SHORT CIRCUIT ERRORDuetoashortcircuit,thecontrolisunabletoreadtheMixSupplySensor082onterminals15and16.Thecontrolstopsoperationanddoesnotprovideanyheat.Checkthesystemsupplysensorwireforshortcircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethemixsupplysensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
BOILER SENSOR OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadtheBoilerSensor082onterminals16and17.Whenapplicationmodeissettoboilerorboiler+mixthecontrolstopsoperation.Inallotherapplicationmodes,thecontrolcontinuestoheatthesnowmeltingsystembutdoesnotcontroltheboileroperatingtemperature.Checktheboilersensorwireforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacetheboilersensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
BOILER SENSOR SHORT CIRCUIT ERRORDuetoashortcircuit,thecontrolisunabletoreadtheBoilerSensor082onterminals16and17.Whenapplicationmodeissettoboilerorboiler+mixthecontrolstopsoperation.Inallotherapplicationmodes,thecontrolcontinuestoheatthesnowmeltingsystembutdoesnotcontroltheboileroperatingtemperature.Checktheboilersensorwireforshortcircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacetheboilersupplysensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SLAB SENSOR OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadtheSlabSensor072or073onterminals7and10.IdlingandstormaredisabledandenergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)areoperatedusingtheoutdoortemperatureonly.Checktheslabsensorwireforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacetheslabsensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.Iftheslabsensorhasbeenintentionallyremoved,settheslabsensorsettinginthesystemsetupmenutooff.
SLAB SENSOR SHORT CIRCUIT ERRORDuetoashortcircuit,thecontrolisunabletoreadtheSlabSensor072or073onterminals7and10.IdlingandStormaredisabledandenergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)areoperatedusingtheoutdoortemperatureonly.Checktheslabsensorwireforshortcircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacetheslabsensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR YELLOW WIRE OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadtheyellowwireconnectedtotheSnow/IceSensor090or094,ortheSnowSensor095onterminals7and9.Thecontrolcannolongerautomaticallydetectsnoworice,butmanualstartofthesnowmeltingsystemisstillavailable.Checkthesnow/icesensororsnowsensoryellowandblackwiresandanywiresplicesforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BLUE WIRE OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadthebluewireconnectedtotheSnow/IceSensor090or094,ortheSnowSensor095onterminals7and8.Thecontrolcannolongerautomaticallydetectsnoworice,butmanualstartofthesnowmeltingsystemisstillavailable.Checkthesnow/icesensororsnowsensorblueandblackwiresandanywiresplicesforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BLUE WIRE SHORT CIRCUIT ERRORDuetoashortcircuit,thecontrolisunabletoreadthebluewireconnectedtotheSnow/IceSensor090or094,ortheSnowSensor095onterminals7and8.Thecontrolcannolongerautomaticallydetectsnoworice,butmanualstartofthesnowmeltingsystemisstillavailable.Firstcheckthesnow/icesensororsnowsensorfordirtordebris.Theringstructureofthesensormayneedcleaningwithhotsoapywaterandanylonbrush.Rinsewithwater.Second,checkthesnow/icesensororsnowsensorblueandblackwiresandanywiresplicesforshortcircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BROWN WIRE OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadthebrownwireconnectedtotheSnow/IceSensor090or094onterminals7and10.IdlingandStormisdisabledandenergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)areoperatedusingtheoutdoortemperatureonly.Checkthesnow/icesensorbrownandblackwiresforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BROWN WIRE SHORT CIRCUIT ERRORDuetoashortcircuit,thecontrolisunabletoreadthebrownwireconnectedtotheSnow/IceSensor090or094onterminals7and10.IdlingandStormisdisabledandenergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)areoperatedusingtheoutdoortemperatureonly.Checkthesnow/icesensorbrownandblackwiresforshortcircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
System is Idling IdlingheatstheslabwhenthetemperaturefallsbelowtheIdletemperature.
System is MeltingDuringcoldweathercutoff(CWCO),thesystemisshutoff.Ifitshutsoffduringameltcycle,thesystemresumesmeltingoncetheoutdoortemperatureisaboveCWCO.
System is Off Systemhasbeenmanuallystoppedandtheautomaticsnow/icesensorneverdried,therebypreventingthesystemfromautomaticallystarting.
Frequently Asked Questions
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: Watts.com/prop65
All specifications are subject to change without notice
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowl-edges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Prod-uct is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twen-ty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict prod-uct liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its cus-tomers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold
tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or war-ranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of the Product; or if the Prod-uct was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTU-ALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURA-BILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa-tion regarding the appropriate Representative.