Top Banner
513 01 3305 00 1/29/15 INSTALLATION INSTRUCTIONS R410A Single Package Air Conditioner RAS090 150 These instructions must be read and understood completely before attempting installation. DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product. DANGER Immediate hazards which will result in severe personal injury or death. WARNING Hazards or unsafe practices which could result in severe personal injury or death. CAUTION Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or operation. Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal word CAUTION is used throughout this manual in the following manner: Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures on product labels. WARNING Safety Labeling and Signal Words ! CAUTION WARNING ! ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury and/or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF posi- tion. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignitions sources away from refrigerants and oils. ! WARNING ! CAUTION CUT HAZARD Failure to follow this caution may result in personal in- jury Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts. UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. R410A refrigerant systems operate at higher pressures than standard R22 systems. Do not use R22 service equipment or components on R410A refrigerant equipment. ! WARNING
37

INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

Sep 09, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

513 01 3305 00 1/29/15

INSTALLATION INSTRUCTIONSR−410A Single Package Air Conditioner

RAS090 − 150

These instructions must be read and understood completely before attempting installation.

DANGER, WARNING, CAUTION, andNOTEThe signal words DANGER, WARNING,CAUTION, and NOTE are used to identify levels ofhazard seriousness. The signal word DANGER isonly used on product labels to signify an immediatehazard. The signal words WARNING, CAUTION,and NOTE will be used on product labels andthroughout this manual and other manuals that mayapply to the product.

DANGER − Immediate hazards which will result insevere personal injury or death.

WARNING − Hazards or unsafe practices whichcould result in severe personal injury or death.

CAUTION − Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.

NOTE − Used to highlight suggestions which willresult in enhanced installation, reliability, oroperation.

Signal Words in Manuals

The signal word WARNING is used throughout thismanual in the following manner:

The signal word CAUTION is used throughout thismanual in the following manner:

Signal Words on Product Labeling

Signal words are used in combination with colorsand/or pictures on product labels.

WARNING

Safety Labeling and Signal Words

!

CAUTION

WARNING

!

! WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury and/or death.

Before installing, modifying, or servicing system, mainelectrical disconnect switch must be in the OFF posi-tion. There may be more than 1 disconnect switch.Lock out and tag switch with a suitable warning label.

PERSONAL INJURY AND ENVIRONMENTALHAZARD

Failure to follow this warning could cause personalinjury or death.

Relieve pressure and recover all refrigerant beforesystem repair or final unit disposal.

Wear safety glasses and gloves when handlingrefrigerants. Keep torches and other ignitionssources away from refrigerants and oils.

! WARNING

! CAUTIONCUT HAZARD

Failure to follow this caution may result in personal in-jury

Sheet metal parts may have sharp edges or burrs. Usecare and wear appropriate protective clothing andgloves when handling parts.

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personalinjury, death and/or equipment damage.

R−410A refrigerant systems operate at higherpressures than standard R−22 systems. Do notuse R−22 service equipment or components onR−410A refrigerant equipment.

! WARNING

Page 2: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

2 513 01 3305 00Specifications subject to change without notice.

IMPORTANT − READ BEFORE INSTALLING1. Read and become familiar with these installation

instructions before installing this unit.2. Be sure the installation conforms to all applicable local and

national codes.3. These instructions contain important information for the

proper maintenance and repair of this equipment. Retainthese instructions for future use.

CONTENTS

SAFETY CONSIDERATIONS 2. . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 − Plan for Unit Location 3. . . . . . . . . . . . . . . . . . . . . .

Step 2 − Plan for Sequence of Unit Installation 7. . . . . . . . .

Step 3 − Inspect unit 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 4 − Provide Unit Support 8. . . . . . . . . . . . . . . . . . . . . . .

Step 5 − Field Fabricate Ductwork 10. . . . . . . . . . . . . . . . . .

Step 6 − Rig and Place Unit 10. . . . . . . . . . . . . . . . . . . . . . . .

Step 7 − Convert to Horizontal and Connect Ductwork 11.

Step 8 − Install Outside Air Hood 11. . . . . . . . . . . . . . . . . . .

Step 9 − Install External Condensate Trap &Piping 13. . . .

Step 10 − Make Electrical Connections 14. . . . . . . . . . . . . .

Step 11 − Adjust Factory−Installed Options 35. . . . . . . . . . .

Step 12 − Install Accessories 35. . . . . . . . . . . . . . . . . . . . . . .

UNIT START−UP CHECKLIST 36. . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONSImproper installation, adjustment, alteration, service,maintenance, or use can cause explosion, fire, electricalshock or other conditions which may cause personal injuryor property damage. Consult a qualified installer, serviceagency, or your distributor or branch for information orassistance. The qualified installer or agency must usefactory−authorized kits or accessories when modifying thisproduct. Refer to the individual instructions packaged withthe kits or accessories when installing.

Follow all safety codes. Wear safety glasses and workgloves. Use quenching cloths for brazing operations andhave a fire extinguisher available. Read these instructionsthoroughly and follow all warnings or cautions attached tothe unit. Consult local building codes and appropriate

national electrical codes (in USA, ANSI/NFPA70, NationalElectrical Code (NEC); in Canada, CSA C22.1) for specialrequirements.

Recognize safety information. This is the safety−alert symbol . When you see this symbol in instructions ormanuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING,CAUTION, and NOTE. These words are used with thesafety−alert symbol. DANGER identifies the most serioushazards which will result in serious injury or death. WARNINGsignifies a hazard which could result in serious injury or death.CAUTION is used to identify unsafe practices which mayresult in minor personal injury or product and propertydamage. NOTE is used to highlight suggestions which willresult in enhanced installation, reliability, or operation.

These instructions cover minimum requirements and conformto existing national standards and safety codes. In someinstances, these instructions exceed certain local codes andordinances, especially those that may not have kept up withchanging residential construction practices. We require theseinstructions as a minimum for a safe installation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal injuryor death.

Before performing service or maintenance operations onunit, always turn off main power switch to unit and installlockout tag. Unit may have more than one power switch.

! WARNING

INSTALLATION

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal injury,death and/or equipment damage.

R−410A refrigerant systems operate at higher pressuresthan standard R−22 systems. Do not use R−22 serviceequipment or components on R−410A refrigerantequipment.

! WARNING

!

Page 3: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

3513 01 3305 00 Specifications subject to change without notice.

MODEL NOMENCLATUREMODEL SERIES R A S 0 9 0 H D A A 0 A G A

Position Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14R = Rooftop

A = Air Conditioning (Cooling Only)G = Gas/Electric Type

S = Standard ASHRAE 90.1-2010 Efficiency Efficiency

091 = 90,000 = 7.5 Tons (One Compressor)101 = 102,000 = 8.5 Tons (One Compressor)121 = 120,000 = 10 Tons (One Compressor)090 = 90,000 = 7.5 Tons (Two Compressors)102 = 102,000 = 8.5 Tons (Two Compressors)120 = 120,000 = 10 Tons (Two Compressors)150 = 150,000 = 12.5 Tons (Two Compressors) Nominal Cooling Capacity

H = 208/230-3-60L = 460-3-60S = 575-3-60 Voltage

0 = No Heat Heating CapacityA = Standard MotorB = High Static Motor Motor OptionA = NoneB = Economizer w/Bara-relief, OA Temp Sensor

Outdoor Air Options / Control (See specifications for details)

0A = No OptionsFactory Installed Options (See specifications for details)

A = Aluminum / Copper Cond & Evap Coil (RTPF)G = Alum / Alum Cond & Alum / Cu Evap (MCHX-Microchannel))

Standard Condenser / Evaporator Coil Configuration (See specifications for details)

A = Sales Digit

Jobsite Survey

Complete the following checks before installation.

1. Consult local building codes and the NEC (NationalElectrical Code) ANSI/NFPA 70 for special installationrequirements.

2. Determine unit location (from project plans) or selectunit location.

3. Check for possible overhead obstructions which mayinterfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (curb orother) that provides for the minimum clearances required for

safety. This includes the clearance to combustible surfaces,unit performance and service access below, around andabove unit as specified in unit drawings. See Fig. 1.

Unit may be installed directly on wood flooring or on ClassA, B, or C roof−covering material when roof curb is used.

Select a unit mounting system that provides adequateheight to allow installation of condensate trap perrequirements. Refer to Step 9 — Install ExternalCondensate Trap and Line – for required trap dimensions.

Roof mount —Check building codes for weight distribution requirements.Unit operating weight is shown in Table 1.

Page 4: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

4 513 01 3305 00Specifications subject to change without notice.

FIGURE 1 Service Clearance Dimensional Drawing

C

BA

D

LOCATION DIMENSION CONDITION

A

48-in (1219 mm)

18-in (457 mm)

18-in (457) mm

12-in (305 mm)

Unit disconnect is mounted on panel

No disconnect, convenience outlet option

Recommended service clearance

Minimum clearance

B

42-in (1067 mm)

36-in (914 mm)

Special

Surface behind servicer is grounded (e.g., metal, masonry wall)

Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)

Check sources of flue products within 10-ft of unit fresh air intake hood

C36-in (914 mm)

18-in (457 mm)

Side condensate drain is used

Minimum clearance

D

48-in (1219 mm)

42-in (1067 mm)

36-in (914 mm)

Special

No flue discharge accessory installed, surface is combustible material

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)

Check for adjacent units or building fresh air intakes within 10-ft (3 m) of this unit's flue outlet

NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead obstruction or for vertical clearances.

Table 1—Operating Weights

UNIT / COIL TYPEUNITS LB (KG)

090/091 101/102 120/121 150

RAS 730 (331) 855 (388) 865 (393) 1075 (489)

OPTIONS & ACCESSORES

Economizer

�Vertical 75 (34) 75 (34) 75 (34) 75 (34)

�Horizontal 122 (55) 122 (55) 122 (55) 122 (55)

Powered Outlet 35 (16) 35 (16) 35 (16) 35 (16)

Curb

�14-in/356 mm 143 (65) 143 (65) 143 (65) 143 (65)

�24-in/610 mm 245 (111) 245 (111) 245 (111) 245 (111)

* Weights represent the RTPF models.

Page 5: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

FIGURE 2 Base Unit Dimensions: RAS090−121

/091

101/ /1

21

/091

101/ /1

21

5513 01 3305 00 Specifications subject to change without notice.

Page 6: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

6 513 01 3305 00Specifications subject to change without notice.

Base Unit Dimensions: RAS150Figure 2A

Page 7: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

7513 01 3305 00 Specifications subject to change without notice.

Unit Dimensional Drawing (Cont.)

FIGURE 3

/091101/

/121

/091

101//121

Unit Dimensional Drawing (Cont.)

Figure 3 (Cont.)

Step 2 — Plan for Sequence of Unit InstallationThe support method used for this unit will dictate differentsequences for the steps of unit installation. For example, oncurb−mounted units, some accessories must be installed onthe unit before the unit is placed on the curb. Review thefollowing for recommended sequences for installation steps.Curb−mounted installation —

Install roof curbInstall field−fabricated ductwork inside curbInstall accessory thru−base service connection package, ifused, (affects curb and unit) (refer to accessoryinstallation instructions for details)Prepare condensate drain connection to suit plannedcondensate line routing (refer to Step 9 for details)Rig and place unit

Install outdoor air hoodInstall condensate line trap and pipingMake electrical connectionsInstall other accessories

Pad−mounted installation —Prepare pad and unit supportsCheck and tighten the bottom condensate drainconnection plugRig and place unitInstall outdoor air hoodConvert unit to side duct connection arrangementInstall field−fabricated ductwork at unit duct openingsInstall condensate line trap and pipingMake electrical connections

Page 8: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

8 513 01 3305 00Specifications subject to change without notice.

Install other accessoriesFrame−mounted installation —

Frame−mounted applications generally follow thesequence for a curb installation. Adapt as required to suitspecific installation plan.

Step 3 — Inspect unitInspect unit for transportation damage. File any claim withtransportation agency.Confirm before installation of unit that voltage, amperageand circuit protection requirements listed on unit data plateagree with power supply provided.

Step 4 — Provide Unit SupportRoof Curb Mount —Accessory roof curb details and dimensions are shown inFig. 4. Assemble and install accessory roof curb inaccordance with instructions shipped with the curb.NOTE:The gasketing of the unit to the roof curb is critical fora watertight seal. Install gasket supplied with the roof curbas shown in Fig. 4. Improperly applied gasket can alsoresult in air leaks and poor unit performance.Curb should be level. This is necessary for unit drain tofunction properly. Unit leveling tolerances are show in Fig. 5.Refer to Accessory Roof Curb Installation Instructions foradditional information as required.

Install insulation, cant strips, roofing felt, and counterflashing as shown. Ductwork must be attached to curb andnot to the unit. The accessory thru−the−base power and gasconnection package must be installed before the unit is seton the roof curb.If electric and control wiring is to be routed through thebasepan, attach the accessory thru−the−base serviceconnections to the basepan in accordance with theaccessory installation instructions.Slab Mount (Horizontal Units Only) —Provide a level concrete slab that extends a minimum of 6in. (150 mm) beyond unit cabinet. Install a gravel apron infront of condenser coil air inlet to prevent grass and foliagefrom obstructing airflow.NOTE:Horizontal units may be installed on a roof curb ifrequired.

Alternate Unit Support (In Lieu of Curb or Slab Mount)—A non−combustible sleeper rail can be used in the unit curbsupport area. If sleeper rails cannot be used, support thelong sides of the unit with a minimum of 3 equally spaced4−in. x 4−in. (102 mm x 102 mm) pads on each side.

Page 9: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

9513 01 3305 00 Specifications subject to change without notice.

FIGURE 4 Roof Curb Details

7/16

"[1

1]

4 9/

16"

[115

.5]

1/4"

[7.0

]

"A"

1 3/

4"[4

4.5]

1 3/

4"[4

4.4]

20-3

/4"

[513

]IN

SID

E

"A"

81 3

/4"

[207

6.3]

53 1

/2"

[135

8.9]

1 3/

4"[4

4.5]

40 3

/16"

[102

0.8]

2 1/

4"[5

7.2]

26"

[660

.4]

4 3/

16"

[106

.0]

6 3/

64"

[153

.5]

32 9

/16"

[827

.1]

23 1

/16"

[585

.8]

31 1

7/32

"[8

00.9

]1

3/4"

[44.

5]

15 1

3/16

"[4

01.6

]

11.4

2"[2

90.0

]

1 3/

4"[4

4.4]

3"[7

6.2]

2-3/

8"[6

1]

14 3

/4"

[374

.7]

6' 6

-1/4

"[1

987.

5]

1-3

/4"

TY

P [4

4.5]

4' 2

"[1

270.

0]

15 1

5/32

[392

.9]

1.00

"[2

5.4]

CR

BTM

PW

R00

2A01

3/4"

[19]

NP

T1

1/4"

[31.

7] N

PT

CR

RFC

UR

B00

4A01

CO

NN

EC

TOR

PK

G. A

CC

.G

AS

CO

NN

EC

TIO

N T

YP

EG

AS

FIT

TIN

GP

OW

ER

WIR

ING

FI

TTIN

GC

ON

TRO

L W

IRIN

G

FITT

ING

AC

CE

SS

OR

Y C

ON

VE

NIE

NC

E

OU

TLE

T W

IRIN

G C

ON

NE

CTO

R

THR

U T

HE

CU

RB

1/2"

[12.

7] N

PT

1/2"

[12.

7] N

PT

CR

BTM

PW

R00

4A01

THR

U T

HE

BO

TTO

M

RO

OF

CU

RB

AC

CE

SS

OR

Y #

A

CR

RFC

UR

B00

3A01

14"

[356

]

24"

[610

]

RE

V

50H

J405

012

C

NO

TES

:1.

RO

OFC

UR

B A

CC

ES

SO

RY

IS S

HIP

PE

D D

ISA

SS

EM

BLE

D.

2. IN

SU

LATE

D P

AN

ELS

: 25.

4 [1

"] TH

K. P

OLY

UR

ETH

AN

E F

OA

M, 4

4.5

[1-3

/4] #

DE

NS

ITY

.3.

DIM

EN

SIO

NS

IN [

] A

RE

IN M

ILLI

ME

TER

S.

4. R

OO

FCU

RB

: 18

GA

GE

STE

EL.

5. A

TTA

CH

DU

CTW

OR

K T

O C

UR

B. (

FLA

NG

ES

OF

DU

CT

RE

ST

ON

CU

RB

).6.

SE

RV

ICE

CLE

AR

AN

CE

4 F

EE

T O

N E

AC

H S

IDE

.7.

D

IRE

CTI

ON

OF

AIR

FLO

W.

8. C

ON

NE

CTO

R P

AC

KA

GE

CR

BTM

PW

R00

2A01

IS F

OR

TH

RU

-TH

E-C

UR

B G

AS

TY

PE

P

AC

KA

GE

CR

BTM

PW

R00

4A01

IS F

OR

TH

RU

-TH

E-B

OTT

OM

TY

PE

GA

S C

ON

NE

CTI

ON

S.

TYP

ICA

L (4

) SID

ES

SU

PP

LY A

IRR

ETU

RN

AIR

RO

OFI

NG

MA

TER

IAL

(FIE

LD S

UP

PLI

ED

)

CA

NT

STR

IP(F

IELD

SU

PP

LIE

D)

RO

OFI

NG

FE

LT(F

IELD

SU

PP

LIE

D)

CO

UN

TER

FLA

SH

ING

(FIE

LD S

UP

PLI

ED

)

UN

ITG

AS

KE

T(S

UP

PLI

ED

WIT

H C

UR

B)

RIG

ID IN

SU

LATI

ON

(FIE

LD S

UP

PLI

ED

)

DU

CT

(FIE

LD S

UP

PLI

ED

)

NA

IL (F

IELD

SU

PP

LIE

D)

VIE

W "B

"C

OR

NE

R D

ETA

IL

SE

CTI

ON

TH

RU

SID

E

SE

E V

IEW

"B

"

GA

S S

ER

VIC

E P

LATE

TH

RU

TH

E C

UR

B

DR

ILL

HO

LE

2" [5

0.8]

@

AS

SE

MB

LY (I

F R

EQ

UIR

ED

) (S

EE

NO

TE #

8)

SE

E N

OTE

#2

12-1

/2" [

317.

5] W

IDE

INS

ULA

TED

DE

CK

PA

NE

LS

9-15

/16"

[252

.4] W

IDE

INS

ULA

TED

DE

CK

PA

NE

L

SU

PP

LY A

IRR

ETU

RN

AIR

SU

PP

LY A

IRO

PE

NIN

G

RE

TUR

N A

IRO

PE

NIN

G

Page 10: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

10 513 01 3305 00Specifications subject to change without notice.

FIGURE 5 Unit Leveling Tolerances

MAXIMUM ALLOWABLE

A−B B−C A−C0.5”(13) 1.0” (25) 1.0” (25)

Step 5 — Field Fabricate DuctworkCabinet return-air static pressure (a negative condition) shallnot exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in.wg (112 Pa) without economizer.For vertical ducted applications, secure all ducts to roof curband building structure. Do not connect ductwork to unit.Insulate and weatherproof all external ductwork, joints, androof openings with counter flashing and mastic inaccordance with applicable codes.Ducts passing through unconditioned spaces must beinsulated and covered with a vapor barrier.If a plenum return is used on a vertical unit, the returnshould be ducted through the roof deck to comply withapplicable fire codes.

For units with accessory electric heaters: Horizontal applicationsrequire a minimum clearance to combustible surfaces of 1−in(25 mm) from duct for first 12−in (305 mm) away from unit.Vertical applications do not require a minimum clearance.

A minimum clearance is not required around ductwork.

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in damage toroofing materials.

Membrane roofs can be cut by sharp sheet metaledges. Be careful when placing any sheet metal partson such roof.

CAUTION!

For Units with Accessory Electric Heaters —

All installations require a minimum clearance to combustiblesurfaces of 1−in (25 mm) from duct for first 12−in (305 mm)away from unit.

Outlet grilles must not lie directly below unit discharge.

NOTE:A 90−degree elbow must be provided in the ductworkto comply with UL (Underwriters Laboratories) code for usewith electric heat.

PERSONAL INJURY HAZARD

Failure to follow this warning could cause personalinjury.

For vertical supply and return units, tools or parts coulddrop into ductwork and cause an injury. Install a90−degree turn in the return ductwork between the unitand the conditioned space. If a 90−degree elbow cannotbe installed, then a grille of sufficient strength anddensity should be installed to prevent objects fromfalling into the conditioned space. Due to electricheater, supply duct will require 90−degree elbow.

! WARNING

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are notrequired if top crating is left on unit. Rollers may be used tomove unit across a roof. Level by using unit frame as areference. See Table 1 and Fig. 5 for additional information.

Lifting holes are provided in base rails as shown in Fig. 6.Refer to rigging instructions on unit.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipmentdamage.

All panels must be in place when rigging. Unit is notdesigned for handling by fork truck.

CAUTION!

Before setting the unit onto the curb, recheck gasketing oncurb.

FIGURE 6 Rigging Details

Page 11: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

11513 01 3305 00 Specifications subject to change without notice.

UNITMAX WEIGHT

DIMENSIONS

A B C

LB KG IN MM IN MM IN MM

RAS091 1290 586 88.0 2235 40.0 1015 41.5 1055

RAS101 1410 641 88.0 2235 39.5 1005 49.5 1255

RAS121 1515 689 88.0 2235 41.0 1040 49.5 1255

RAS090 1410 641 88.0 2235 41.0 1040 41.5 1055

RAS102 1525 693 88.0 2235 40.5 1030 49.5 1255

RAS120 1565 711 88.0 2235 40.0 1015 49.5 1255

RAS150 1720 782 88.0 2235 28.5 725 53.0 1345

NOTES:

1. Dimensions in ( ) are in millimeters.

2. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.

3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Positioning on Curb

Position unit on roof curb so that the following clearancesare maintained: 1/4 in. (6.4 mm) clearance between the roofcurb and the base rail inside the front and rear, 0.0 in.clearance between the roof curb and the base rail inside onthe duct end of the unit. This will result in the distancebetween the roof curb and the base rail inside on thecondenser end of the unit being approximately equal to Fig.4, section C−C.

Although unit is weatherproof, guard against water fromhigher level runoff and overhangs.

UNIT DAMAGE HAZARD

Failure to follow this caution may result inequipment damage.

All panels must be in place when rigging. Unit isnot designed for handling by fork truck.

CAUTION!

After unit is in position, remove rigging skids and shippingmaterials.

Step 7 — Convert to Horizontal and ConnectDuctwork (when required)

Unit is shipped in the vertical duct configuration. Unit withoutfactory−installed economizer may be field−converted tohorizontal ducted configuration. To convert to horizontalconfiguration, remove screws from side duct opening coversand remove covers. Using the same screws, install coverson vertical duct openings with the insulation−side down.Seals around duct openings must be tight. See Fig. 7.

FIGURE 7 HORIZONTAL CONVERSION PANELS

Field−supplied flanges should be attached to horizontal ductopenings and all ductwork should be secured to the flanges.Insulate and weatherproof all external ductwork, joints, androof or building openings with counter flashing and mastic inaccordance with applicable codes.

Do not cover or obscure visibility to the unit’s informativedata plate when insulating horizontal ductwork.

Step 8 — Install Optional Outside Air Hood

Economizer Hood Removal and Setup

1. The hood is shipped in knock−−down form and locatedin the return air compartment. It is attached to theeconomizer using two plastic tie−wraps.

2. To gain access to the hood, remove the filter accesspanel. (See Fig. 8.)

3. Locate and cut the (2) plastic tie−−wraps, being carefulto not damage any wiring. (See Fig. 9.)

4. Carefully lift the hood assembly through the filter accessopening and assemble per the steps outlined inEconomizer Hood and Two–Position Hood.

Page 12: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

12 513 01 3305 00Specifications subject to change without notice.

FIGURE 8 Typical Access Panel Locations

Filter Access Panel

Outdoor Air Opening and Indoor Coil Access Panel

FIGURE 9 Economizer Wiring

Economizer

Cut Plastic Ties(2) Places

Remove Hood Parts

Motorized 2−Position Damper Hood (Optional) —

1. The hood is shipped in knock−down form andassembled to a metal support tray using plastic stretchwrap. Located in the return air compartment, theassembly’s metal tray is attached to the basepan andalso attached to the damper using two plastic tie−wraps.

2. To gain access to the hood, remove the filter accesspanel. (See Fig. 8.)

3. Locate the (2) screws holding the metal tray to thebasepan and remove. Locate and cut the (2) plastictie−wraps securing the assembly to the damper. (SeeFig. 10.) Be careful to not damage any wiring or cuttie−wraps securing any wiring.

4. Carefully lift the hood assembly (with metal tray) throughthe filter access opening and assemble per the stepsoutlined in Economizer Hood and Two–Position Hood onpage 11.

FIGURE 10 Damper Details

Hood Parts

Plastic Tie WrapQty (2)

Screws for Metal TrayQty (2)

Economizer Hood and Two Position Hood (Optional)

NOTE:If the power exhaust accessory is to be installed onthe unit, the hood shipped with the unit will not be used andmust be discarded. Save the aluminum filter for use in thepower exhaust hood assembly.

1. The indoor coil access panel will be used as the top ofthe hood. Remove the screws along the sides andbottom of the indoor coil access panel. See Fig. 11.

FIGURE 11 Indoor Coil Access Panel Relocation

TOPPANEL

INDOORCOILACCESSPANEL

CAULKHERE

TOPPANEL

INDOORCOILACCESSPANEL

Page 13: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

13513 01 3305 00 Specifications subject to change without notice.

2. Swing out indoor coil access panel and insert the hoodsides under the panel (hood top). Use the screwsprovided to attach the hood sides to the hood top. Usescrews provided to attach the hood sides to the unit.See Fig. 12.

3. Remove the shipping tape holding the economizerbarometric relief damper in place.

4. Insert the hood divider between the hood sides. SeeFig. 12 and 13. Secure hood divider with 2 screws oneach hood side. The hood divider is also used as thebottom filter rack for the aluminum filter.

5. Open the filter clips which are located underneath thehood top. Insert the aluminum filter into the bottom filterrack (hood divider). Push the filter into position past theopen filter clips. Close the filter clips to lock the filter intoplace. See Fig. 13.

6. Caulk the ends of the joint between the unit top paneland the hood top.

7. Replace the filter access panel.

FIGURE 12 Economizer Hood Construction

B

TOPPANEL

INDOOR COILACCESS PANEL

19 1/16”SCREW

HOOD DIVIDER

LEFTHOODSIDE

33 3/8”(848mm)

(483mm)

FIGURE 13 Economizer Filter Installation

DIVIDER

BAROMETRICRELIEF

CLEANABLEALUMINUMFILTER

FILTER

HOOD

FILTERCLIP

OUTSIDEAIR

Step 9 — Install External Condensate Trap andLine

The unit has one 3/4-in. condensate drain connection on theend of the condensate pan and an alternate connection onthe bottom. See Fig. 14. Unit airflow configuration does notdetermine which drain connection to use. Either drainconnection can be used with vertical or horizontalapplications.

When using the standard side drain connection, ensure thered plug in the alternate bottom connection is tight. Do thisbefore setting the unit in place. The red drain pan can betightened with a 1/2−in. square socket drive extension.

To use the alternate bottom drain connection, remove thered drain plug from the bottom connection (use a 1/2−in.square socket drive extension) and install it in the side drainconnection.

FIGURE 14 Condensate Drain Pan (Side View)

DRAIN(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARDSIDE DRAIN

ALTERNATEBOTTOM DRAIN

The piping for the condensate drain and external trap canbe completed after the unit is in place. See Fig. 15.

FIGURE 15 Condensate Drain Piping Details

NOTE: Trap should be deep enough to offset maximum unit staticdifference. A 4” (102) trap is recommended.

MINIMUM PITCH1” (25mm) PER10’ (3m) OF LINE

BASE RAIL

OPENVENT

TO ROOFDRAIN

DRAIN PLUG

ROOFCURB

SEE NOTE

2˝ (51) MIN

All units must have an external trap for condensatedrainage. Install a trap at least 4-in. (102 mm) deep andprotect against freeze-up. If drain line is installeddownstream from the external trap, pitch the line away fromthe unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not usea pipe size smaller than the unit connection (3/4-in.).

Page 14: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

14 513 01 3305 00Specifications subject to change without notice.

Step 10 — Make Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury or death.

Do not use gas piping as an electrical ground. Unitcabinet must have an uninterrupted, unbroken electricalground to minimize the possibility of personal injury if anelectrical fault should occur. This ground may consist ofelectrical wire connected to unit ground lug in controlcompartment, or conduit approved for electrical groundwhen installed in accordance with NEC (NationalElectrical Code); ANSI/NFPA 70, latest edition (inCanada, Canadian Electrical Code CSA [CanadianStandards Association] C22.1), and local electrical codes.

! WARNING

Field Power Supply —All units except 208/230-v units are factory wired for thevoltage shown on the nameplate. If the 208/230-v unit is tobe connected to a 208-v power supply, the controltransformer must be rewired by moving the black wire withthe 1/4-in. female spade connector from the 230−vconnection and moving it to the 200-v 1/4-in. male terminalon the primary side of the transformer. Refer to unit labeldiagram for additional information. Field power wires will beconnected line−side pressure lugs on the power terminalblock or at factory−installed option non−fused disconnect.Field power wires are connected to the unit at line−sidepressure lugs on compressor contactor C and indoor fancontactor IFC (see wiring diagram label for control boxcomponent arrangement) or at factory−installed optionnon−fused disconnect switch. Max wire size is #2 AWG(copper only).NOTE:TEST LEADS − Unit may be equipped with shortleads (pigtails) on the field line connection points oncontactor C or optional disconnect switch. These leads arefor factory run−test purposes only; remove and discardbefore connecting field power wires to unit connectionpoints. Make field power connections directly to lineconnection pressure lugs only.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in intermittentoperation or performance satisfaction.

Do not connect aluminum wire between disconnect switchand furnace. Use only copper wire. (See Fig. 16.)

! WARNING

FIGURE 16 Disconnect Switch and Unit

COPPER

WIRE ONLY

ELECTRICDISCONNECT

SWITCH

ALUMINUMWIRE

Units Without Factory−Installed Disconnect —

When installing units, provide a disconnect switch per NEC(National Electrical Code) of adequate size. Disconnectsizing data is provided on the unit informative plate. Locateon unit cabinet or within sight of the unit per national or localcodes. Do not cover unit informative plate if mounting thedisconnect on the unit cabinet.

Convenience Outlets (Non−Powered) —

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personalinjury or death.

Units with convenience outlet circuits may use multipledisconnects. Check convenience outlet for power statusbefore opening unit for service. Locate its disconnectswitch, if appropriate, and open it. Tag−out this switch, ifnecessary.

! WARNING

An optional non−powered convenience outlet are offered onRAS models: Non−powered provide a 125−volt GFCI(ground−fault circuit−interrupter) duplex receptacle rated at15−A behind a hinged waterproof access cover, located onthe end panel of the unit. See Fig. 17.

FIGURE 17 Non−Powered Convenience Outlet Location

Installing Weatherproof Cover –

A weatherproof while-in-use cover for the factory-installedconvenience outlets is now required by UL standards. Thiscover cannot be factory-mounted due its depth; it must beinstalled at unit installation. For shipment, the convenienceoutlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s controlbox. The kit includes the hinged cover, a backing plate andgasket.

DISCONNECT ALL POWER TO UNIT ANDCONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet;discard the blank cover.

Page 15: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

15513 01 3305 00 Specifications subject to change without notice.

Loosen the two screws at the GFCI duplex outlet, untilapproximately 1/2-in (13 mm) under screw heads areexposed. Press the gasket over the screw heads. Slip thebacking plate over the screw heads at the keyhole slots andalign with the gasket; tighten the two screws until snug (donot over-tighten). Mount the weatherproof cover to the backing plate as shownin Fig. 18. Remove two slot fillers in the bottom of the coverto permit service tool cords to exit the cover. Check for fullclosing and latching.

FIGURE 18 Weatherproof Cover Installation

RECEPTACLENOT INCLUDED

COVER – WHILE-IN-USE WEATHERPROOF

BASE PLATE FOR GFCI RECEPTACLE

Non−powered type: This type requires the field installationof a general−purpose 125−volt 15−A circuit powered from asource elsewhere in the building. Observe national and localcodes when selecting wire size, fuse or breakerrequirements and disconnect switch size and location.Route 125−v power supply conductors into the bottom of theutility box containing the duplex receptacle.

FIGURE 19 Thru−Base Connection Fittings

Optional Thru−Base Connections —

This accessory (field installed) service connection kitconsists of a 1−1/4−in and a 1/2−in electrical bulkheadconnector, all must be installed in the embossed (raised)section of the unit basepan in the condenser section. The1/2−in bulkhead connector enables the low−voltage controlwires to pass through the basepan. The 1−1/4−in electricalbulkhead connector allows the high−voltage power wires topass through the basepan. See Fig. 19.

Note: This must be installed prior to mounting unit onroof curb.

Check tightness of connector lock nuts before connectingelectrical conduits.

Field−supplied and field−installed liquid tight conduitconnectors and conduit may be attached to the connectorson the basepan. Pull correctly rated high voltage and lowvoltage through appropriate conduits. Connect the powerconduit to the internal disconnect (if unit is so equipped) orto the external disconnect (through unit side panel). A holemust be field cut in the main control box bottom on the leftside so the 24−v control connections can be made. Connectthe control power conduit to the unit control box at this hole.

Units without Thru−Base Connections —

1. Install power wiring conduit through side panelopenings. Install conduit between disconnect andcontrol box.

2. Install power lines to terminal connections.

Voltage to compressor terminals during operation must bewithin voltage range indicated on unit nameplate. See Table3. On 3−phase units, voltages between phases must bebalanced within 2% and the current within 10%. Use theformula shown in the legend for Table 3, Note 2 todetermine the percent of voltage imbalance. Operation onimproper line voltage or excessive phase imbalanceconstitutes abuse and may cause damage to electricalcomponents. Such operation would invalidate any applicablewarranty.

Field Control Wiring —

The RAS unit requires an external temperature controldevice. This device typically applied with a commercialthermostat (field−supplied) with both occupied andunoccupied setpoints at a minimum.

Thermostat —

Install an approved accessory commercial thermostataccording to installation instructions included with theaccessory. For complete economizer function, select atwo−stage cooling thermostat. Locate the thermostataccessory on a solid wall in the conditioned space to senseaverage temperature in accordance with the thermostatinstallation instructions.

If the thermostat contains a logic circuit requiring 24−vpower, use a thermostat cable or equivalent single leads ofdifferent colors with minimum of seven leads. If thethermostat does not require a 24−v source (no “C”connection required), use a thermostat cable or equivalentwith minimum of six leads. Check the thermostat installationinstructions for additional features which might requireadditional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (AmericanWire Gage) insulated wire (35�C minimum). For 50 to 75 ft.(15 to 23 m), use no. 16 AWG insulated wire (35�C

Page 16: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

16 513 01 3305 00Specifications subject to change without notice.

minimum). For over 75 ft. (23 m), use no. 14 AWG insulatedwire (35�C minimum). All wire sizes larger than no. 18 AWGcannot be directly connected to the thermostat and willrequire a junction box and splice at the thermostat.

Unit without thru−base connection kit —

Pass the thermostat control wires through the hole providedin the corner post; then feed the wires through the racewaybuilt into the corner post to the control box. Pull the wiresover to the terminal strip on the upper−left corner of theControls Connection Board. See Fig. 20 and 21.

FIGURE 20 Typical Low Voltage Control Connections

TypicalThermostatConnections

CentralTerminal Board

W1

Y2

Y1

R

W2

G

C

X

W1

Y2

Y1

R

W2

G

C

X

T–STAT

C

W2

G

W1

O/B/Y2

R

Y1

(Note 1)

Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2.Note 2: W2 connection not required on units with single-stage heating. Field Wiring

(Note 2)

FIGURE 21 Field Control Wiring Raceway

RACEWAY

HOLE IN END PANEL (HIDDEN)

NOTE:If thru−the−bottom connections accessory is used,refer to the accessory installation instructions for informationon routing power and control wiring.

Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stageand 0.14 amp for second−stage heating, when available.

Electric Heaters

RAS units may be equipped with field−installed accessoryelectric heaters. The heaters are modular in design, withheater frames holding open coil resistance wires strungthrough ceramic insulators, line−break limit switches and acontrol contactor. One or two heater modules may be usedin a unit.Not all available heater modules may be used in every unit.Use only those heater modules that are UL listed for use ina specific size unit. Refer to the label on the unit cabinet forthe list of approved heaters.Heater modules are installed in the compartment below theindoor (supply) fan outlet. Access is through the indooraccess panel. Heater modules slide into the compartmenton tracks along the bottom of the heater opening. See Fig.22, Fig. 23 and Fig. 24.Unit heaters are marked with Heater Model Numbers. Butheaters are ordered as and shipped in cartons marked witha corresponding heater Sales Package part number. SeeTable 2 for correlation between heater Model Number andSales Package part number.NOTE:The value in position 9 of the part number differsbetween the sales package part number (value is 1) and abare heater model number (value is 0).

FIGURE 22 Typical Access Panel Location

DISCONNECT MOUNTINGLOCATION

UNIT BLOCK-OFFPANEL

OUTDOORACCESS PANEL

INDOORACCESSPANEL

Page 17: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

17513 01 3305 00 Specifications subject to change without notice.

FIGURE 23 Typical Component Location

DISCONNECTMOUNTINGLOCATION

EMT OR RIGID CONDUIT(FIELD-SUPPLIED)

SINGLEPOINT BOX

CENTERPOST

HEATERCOVERS

HEATERMOUNTINGBRACKET

HEATERMODULE(LOCATION 2)

HEATERMODULE(LOCATION 1)

SINGLE POINTBOXMOUNTINGSCREW

BRACKET ANDCONDUITDRIP BOOT

MAINCONTROLBOX

CONTROL WIRE TERMINAL BLOCK

MANUAL RESETLIMIT SWITCH

FIGURE 24 Typical Module Installation

TRACK

FLANGE

Table 2—Heater Model Number

Bare Heater Model Number C R H E A T E R 0 0 1 A 0 0

Heater Sales Package PNOIncludes: Bare Heater Carton and packing materials Installation sheet

C R H E A T E R 1 0 1 A 0 0

Single Point Boxes and Supplementary Fuses — Whenthe unit MOCP device value exceeds 60−A, unit−mountedsupplementary fuses are required for each heater circuit.These fuses are included in accessory Single Point Boxes,with power distribution and fuse blocks. The single point boxwill be installed directly under the unit control box, just to theleft of the partition separating the indoor section (withelectric heaters) from the outdoor section. The Single PointBox has a hinged access cover. See Fig. 25. The SinglePoint Box also includes a set of power taps and pigtails tocomplete the wiring between the Single Point Box and theunit’s main control box terminals. Refer to the accessoryheater and Single Point Box installation instructions fordetails on tap connections.All fuses on RAS units are 60−A. (Note that all heaters arequalified for use with a 60−A fuse, regardless of actualheater ampacity, so only 60−A fuses are necessary.)Single Point Boxes without Fuses — Unit heaterapplications not requiring supplemental fuses require aspecial Single Point Box without any fuses. The accessorySingle Point Boxes contain a set of power taps and pigtailsto complete the wiring between the Single Point Box and theunit’s main control box terminals. Refer to accessory heaterand Single Point Box installation instructions for details ontap connections.

FIGURE 25 Typical Single Point Installation

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

1113

2123

OD

22.2

3123

ISTED AIRNDITIONINGUIP ACCESS 346N.

P / N 2- 5610-4 REV

1113

2123

CONTROLBOX

BUSHING

SINGLEPOINT BOXMOUNTINGSCREWS

FOAMBUSHING

DRIP BOOTBRACKETMOUNTINGSCREWS

HEATERRELAYS

POWERWIRES

HEATERMOUNTINGSCREWS

Low−Voltage Control Connections — Pull the low−voltagecontrol leads from the heater module(s) − VIO and BRN(two of each if two modules are installed; identify for Module#1) − to the 4−pole terminal board TB4 located on theheater bulkhead to the left of Heater #1. Connect the VIOlead from Heater #1 to terminal TB4−1. For 2 stage heating,

Page 18: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

18 513 01 3305 00Specifications subject to change without notice.

connect the VIO lead from Heater #2 to terminal TB4−2. For1 stage heating with 2 heater modules connect the VIO leadfrom both Heater #1 and #2 to terminal TB4−1. Connectboth BRN leads to terminal TB4−3. See Fig. 26.

FIGURE 26 Accessory Electric Heater Control Connections

ORN

BRN

FieldConnections

HR1: On Heater 1 in Position #1HR2: On Heater 2 in Position #2 (if installed)

2

3

12

1 3

VIO

ORN VIO BRN

VIO BRN BRNVIO

2TB4

VIO HR2

HR1

BRN

VIO BRN

Elec Htr

CTB

CONTLBOARD

SMOKE DETECTORSSmoke detectors are available as factory−installed optionson RAS models. Smoke detectors may be specified forSupply Air only without or with economizer. All componentsnecessary for operation are factory−provided and mounted.The unit is factory−configured for immediate smoke detectorshutdown operation; additional wiring or modifications to unitterminal board may be necessary to complete the unit andsmoke detector configuration to meet project requirements.

SystemThe smoke detector system consists of a four−wirecontroller and one or two sensors. Its primary function is toshut down the rooftop unit in order to prevent smoke fromcirculating throughout the building. It is not to be used as alife saving device.

ControllerThe controller (see Fig. 27) includes a controller housing, aprinted circuit board, and a clear plastic cover. The controllercan be connected to one or two compatible duct smokesensors. The clear plastic cover is secured to the housingwith a single captive screw for easy access to the wiringterminals. The controller has three LEDs (for Power, Troubleand Alarm) and a manual test/reset button (on the coverface).

SensorThe sensor (see Fig. 28) includes a plastic housing, aprinted circuit board, a clear plastic cover, a sampling tubeinlet and an exhaust tube. The sampling tube (when used)

and exhaust tube are attached during installation. Thesampling tube is shipped in the blower section and is wiretied to the blower housing. See Fig. 29. The clear plasticcover permits visual inspections without having todisassemble the sensor. The cover attaches to the sensorhousing using four captive screws and forms an airtightchamber around the sensing electronics. Each sensorincludes a harness with an RJ45 terminal for connecting tothe controller. Each sensor has four LEDs (for Power,Trouble, Alarm and Dirty) and a manual test/reset button (onthe left−side of the housing).Air is introduced to the duct smoke detector sensor’ssensing chamber through a sampling tube that extends intothe HVAC duct and is directed back into the ventilationsystem through a (shorter) exhaust tube. The difference inair pressure between the two tubes pulls the sampled airthrough the sensing chamber. When a sufficient amount ofsmoke is detected in the sensing chamber, the sensorsignals an alarm state and the controller automatically takesthe appropriate action to shut down fans and blowers,change over air handling systems, notify the fire alarmcontrol panel, etc.The sensor uses a process called differential sensing toprevent gradual environmental changes from triggering falsealarms. A rapid change in environmental conditions, such assmoke from a fire, causes the sensor to signal an alarmstate but dust and debris accumulated over time does not.For installations using two sensors, the duct smoke detectordoes not differentiate which sensor signals an alarm ortrouble condition.

FIGURE 27 Controller Assembly

Duct smoke sensorcontroller

Fastener(2X)

Controller cover

Conduit nuts(supplied by installer)

Conduit support plate

Cover gasket(ordering option)

Conduit couplings(supplied by installer)

Terminal block cover

Controller housingand electronics

Alarm Power

Test/resetswitch

Trouble

Page 19: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

19513 01 3305 00 Specifications subject to change without notice.

FIGURE 28 Smoke Detector Sensor

Duct smoke sensor

Exhaust tube

Intakegasket

Cover gasket(ordering option)

TSD-CO2(ordering option)

Sensor housingand electronics

Sensor cover

Magnetictest/reset

switch

AlarmTrouble

PowerDirty

Smoke Detector Locations

Supply Air — The Supply Air smoke detector sensor islocated to the left of the unit’s indoor (supply) fan. See Fig.29. Access is through the fan access panel. There is nosampling tube used at this location. The sampling tube inletextends through the side plate of the fan housing (into ahigh pressure area). The controller is located on a bracket tothe right of the return filter, accessed through the lift−off filterpanel.

FIGURE 29Typical Supply Air Smoke Detector SensorLocations

ROTATIO

N

Return Air Sampling Tube(Shipping Location)

Hot Gas ReHeat Connections

Hot Gas ReHeat – Space RH Controller —

The Hot Gas ReHeat dehumidification system requires afield−supplied and −installed space relative humidity controldevice. This device may be a separate humidistat control(contact closes on rise in space RH above control setpoint)or a combination thermostat−humidistat control device withisolated contact set for dehumidification control. Thehumidistat is normally used in applications where atemperature control is already provided.To connect the humidistat:

1. Route the humidistat 2−conductor cable (field−supplied)through the hole provided in the unit corner post.

2. Feed wires through the raceway built into the cornerpost (see FIGURE 21) to the 24−v barrier located on theleft side of the control box. The raceway provides theUL−required clearance between high−voltage and low−voltage wiring.

3. Use wire nuts to connect humidistat cable to two PINKleads in the low–voltage wiring as shown in FIGURE 32.

To connect the Thermidistat device:1. Route the Thermidistat multi−conductor thermostat

cable (field−supplied) through the hole provided in theunit corner post.

2. Feed wires through the raceway built into the cornerpost (See FIGURE 21) to the 24−v barrier located onthe left side of the control box. The raceway providesthe UL−required clearance between high−voltage andlow−voltage wiring.

3. The Thermidistat has dry contacts at terminals D1 andD2 for dehumidification operation (see FIGURE 33) Thedry contacts must be wired between CTB terminal Rand the PINK lead to the LTLO switch withfield−supplied wire nuts. Refer to the installationinstructions included with the thermidistat device.

% RELATIVE HUMIDITY

FIGURE 30 − Accessory Field−Installed Humidistat

Page 20: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

20 513 01 3305 00Specifications subject to change without notice.

FIGURE 31 − Thermidistat

EconoMi$er X (Factory−Installed Option) —

For details on operating RAS units equipped with thefactory−installed EconoMi$er X option, refer toFactory−Installed Economizers for RGH/RAH/RHH/RGS/RAS/RHS Rooftop Units, 3 to 27.5 Nominal Tons. EconomizerSupplement Related to California Title 24 (Literature No.50901350201, or later).

C150021

FIGURE 32 −Typical Hot Gas ReHeat Adaptive Dehumidification System Humidistat Wiring

Page 21: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

21513 01 3305 00 Specifications subject to change without notice.

RcRhW1

GY2C

O/W2/BY1

OATRRS

SRTNHUM

D1D2V+Vg

X*

C

G

W2

W1

Y2

Y1

R

THERMIDISTAT

THERMOSTAT

*Connection not required.

H FIOP

C09298

FIGURE 33 −Typical Rooftop Unit with Hot Gas ReHeat Adaptive Dehumidification System

Page 22: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

22 513 01 3305 00Specifications subject to change without notice.

Table 3—Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S091 (

1-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 40/40 60/60 38/38 208 44/43 60/60 43/42 212

117A 7.8/10.4 21.7/25.0 40/40 60/60 38/38 208/208 44/43 60/60 43/42 212/212

110A 12.0/16.0 33.4/38.5 49/55 60/60 44/50 208/208 53/59 60/60 49/54 212/212

111A 18.6/24.8 51.7/59.7 72/81 80/90 65/74 208/208 76/86 80/90 70/79 212/212

112A 24.0/32.0 66.7/77.0 90/103 90/110 83/94 208/208 95/108 100/110 87/99 212/212

112A+117A 31.8/42.4 88.4/102.0 117/134 125/150 108/123 208/208 122/139 125/150 112/127 212/212

MED

NONE - - 43/43 60/60 42/42 244 47/47 60/60 46/46 248

117A 7.8/10.4 21.7/25.0 43/43 60/60 42/42 244/244 47/47 60/60 46/46 248/248

110A 12.0/16.0 33.4/38.5 53/59 60/60 48/54 244/244 57/64 60/70 52/58 248/248

111A 18.6/24.8 51.7/59.7 76/85 80/90 69/78 244/244 80/90 80/90 73/83 248/248

112A 24.0/32.0 66.7/77.0 94/107 100/110 86/98 244/244 99/112 100/125 91/102 248/248

112A+117A 31.8/42.4 88.4/102.0 121/138 125/150 111/127 244/244 126/143 150/150 116/131 248/248

HIGH

NONE - - 48/47 60/60 48/47 260 52/51 60/60 52/51 264

117A 7.8/10.4 21.7/25.0 48/48 60/60 48/47 260/260 52/52 60/60 52/51 264/264

110A 12.0/16.0 33.4/38.5 59/64 60/70 54/59 260/260 64/69 70/70 58/63 264/264

111A 18.6/24.8 51.7/59.7 82/91 90/100 75/83 260/260 87/96 90/100 79/88 264/264

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 260/260 106/117 110/125 97/108 264/264

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 260/260 133/149 150/150 122/136 264/264

460-

3-

60

STD

NONE - - 20 30 19 122 22 30 21 124

116A 13.9 16.7 24 30 22 122 27 30 24 124

113A 16.5 19.8 28 30 26 122 31 35 28 124

114A 27.8 33.4 45 45 41 122 48 50 43 124

115A 33.0 39.7 53 60 49 122 55 60 51 124

114A+116A 41.7 50.2 66 70 61 122 69 70 63 124

MED

NONE - - 22 30 21 140 23 30 23 142

116A 13.9 16.7 27 30 24 140 29 30 26 142

113A 16.5 19.8 30 30 28 140 33 35 30 142

114A 27.8 33.4 47 50 43 140 50 50 45 142

115A 33.0 39.7 55 60 50 140 58 60 53 142

114A+116A 41.7 50.2 68 70 63 140 71 80 65 142

HIGH

NONE - - 24 30 23 148 26 30 25 150

116A 13.9 16.7 29 30 27 148 32 35 29 150

113A 16.5 19.8 33 35 30 148 35 35 32 150

114A 27.8 33.4 50 50 46 148 52 60 48 150

115A 33.0 39.7 58 60 53 148 60 60 55 150

114A+116A 41.7 50.2 71 80 65 148 73 80 67 150

575-

3-

60

STD

NONE - - 15 20 14 89 18 25 18 93

118A 17.0 20.4 28 30 25 89 33 35 30 93

119A 34.0 40.9 54 60 49 89 58 60 53 93

MED

NONE - - 16 20 15 104 20 25 19 108

118A 17.0 20.4 29 30 27 104 34 35 31 108

119A 34.0 40.9 55 60 50 104 60 60 55 108

HIGH

NONE - - 19 25 18 118 22 30 23 122

118A 17.0 20.4 33 35 30 118 38 40 34 122

119A 34.0 40.9 59 60 53 118 63 70 58 122

See “Legend and Notes for Tables 3 on page 34.

Page 23: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

23513 01 3305 00 Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S090 (

2-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 39/39 50/50 41/40 210 43/43 50/50 45/45 214

117A 7.8/10.4 21.7/25.0 39/39 50/50 41/40 210/210 43/43 50/50 45/45 214/214

110A 12.0/16.0 33.4/38.5 49/55 50/60 44/50 210/210 53/59 60/60 49/54 214/214

111A 18.6/24.8 51.7/59.7 72/81 80/90 65/74 210/210 76/86 80/90 70/79 214/214

112A 24.0/32.0 66.7/77.0 90/103 90/110 83/94 210/210 95/108 100/110 87/99 214/214

112A+117A 31.8/42.4 88.4/102.0 117/134 125/150 108/123 210/210 122/139 125/150 112/127 214/214

MED

NONE - - 42/42 50/50 44/44 246 46/46 50/50 49/49 250

117A 7.8/10.4 21.7/25.0 42/42 50/50 44/44 246/246 46/47 50/50 49/49 250/250

110A 12.0/16.0 33.4/38.5 53/59 60/60 48/54 246/246 57/64 60/70 52/58 250/250

111A 18.6/24.8 51.7/59.7 76/85 80/90 69/78 246/246 80/90 80/90 73/83 250/250

112A 24.0/32.0 66.7/77.0 94/107 100/110 86/98 246/246 99/112 100/125 91/102 250/250

112A+117A 31.8/42.4 88.4/102.0 121/138 125/150 111/127 246/246 126/143 150/150 116/131 250/250

HIGH

NONE - - 48/47 60/50 50/49 262 51/51 60/60 55/54 266

117A 7.8/10.4 21.7/25.0 48/48 60/50 50/49 262/262 51/52 60/60 55/54 266/266

110A 12.0/16.0 33.4/38.5 59/64 60/70 54/59 262/262 64/69 70/70 58/63 266/266

111A 18.6/24.8 51.7/59.7 82/91 90/100 75/83 262/262 87/96 90/100 79/88 266/266

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 262/262 106/117 110/125 97/108 266/266

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 262/262 133/149 150/150 122/136 266/266

460-

3-

60

STD

NONE - - 18 20 19 104 20 25 21 106

116A 13.9 16.7 24 25 22 104 27 30 24 106

113A 16.5 19.8 28 30 26 104 31 35 28 106

114A 27.8 33.4 45 45 41 104 48 50 43 106

115A 33.0 39.7 53 60 49 104 55 60 51 106

114A+116A 41.7 50.2 66 70 61 104 69 70 63 106

MED

NONE - - 20 25 21 122 22 25 23 124

116A 13.9 16.7 27 30 24 122 29 30 26 124

113A 16.5 19.8 30 30 28 122 33 35 30 124

114A 27.8 33.4 47 50 43 122 50 50 45 124

115A 33.0 39.7 55 60 50 122 58 60 53 124

114A+116A 41.7 50.2 68 70 63 122 71 80 65 124

HIGH

NONE - - 22 25 23 130 24 30 25 132

116A 13.9 16.7 29 30 27 130 32 35 29 132

113A 16.5 19.8 33 35 30 130 35 35 32 132

114A 27.8 33.4 50 50 46 130 52 60 48 132

115A 33.0 39.7 58 60 53 130 60 60 55 132

114A+116A 41.7 50.2 71 80 65 130 73 80 67 132

575-

3-

60

STD

NONE - - 13 15 13 77 17 20 17 81

118A 17.0 20.4 28 30 25 77 33 35 30 81

119A 34.0 40.9 54 60 49 77 58 60 53 81

MED

NONE - - 14 15 14 92 18 20 19 96

118A 17.0 20.4 29 30 27 92 34 35 31 96

119A 34.0 40.9 55 60 50 92 60 60 55 96

HIGH

NONE - - 17 20 17 106 21 25 22 110

118A 17.0 20.4 33 35 30 106 38 40 34 110

119A 34.0 40.9 59 60 53 106 63 70 58 110

See “Legend and Notes for Tables 3 on page 34.

Page 24: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

24 513 01 3305 00Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S101 (

1-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 46/45 60/60 43/43 239 47/47 60/60 48/47 243

117A 7.8/10.4 21.7/25.0 46/45 60/60 43/43 239/239 47/47 60/60 48/47 243/243

110A 12.0/16.0 33.4/38.5 49/55 60/60 44/50 239/239 53/59 60/60 49/54 243/243

111A 18.6/24.8 51.7/59.7 72/81 80/90 65/74 239/239 76/86 80/90 70/79 243/243

112A 24.0/32.0 66.7/77.0 90/103 90/110 83/94 239/239 95/108 100/110 87/99 243/243

112A+117A 31.8/42.4 88.4/102.0 117/134 125/150 108/123 239/239 122/139 125/150 112/127 243/243

MED

NONE - - 47/47 60/60 45/45 260 51/51 60/60 50/49 264

117A 7.8/10.4 21.7/25.0 47/47 60/60 45/45 260/260 51/51 60/60 50/49 264/264

110A 12.0/16.0 33.4/38.5 51/57 60/60 46/52 260/260 56/62 60/70 51/56 264/264

111A 18.6/24.8 51.7/59.7 74/83 80/90 67/76 260/260 78/88 80/90 72/81 264/264

112A 24.0/32.0 66.7/77.0 92/105 100/110 85/96 260/260 97/110 100/110 89/101 264/264

112A+117A 31.8/42.4 88.4/102.0 120/136 125/150 110/125 260/260 124/141 125/150 114/129 264/264

HIGH

NONE - - 51 60 50 289 55 80 54 293

117A 7.8/10.4 21.7/25.0 51/51 60/60 50/50 289/289 55/55 80/80 54/54 293/293

110A 12.0/16.0 33.4/38.5 55/62 60/70 51/56 289/289 60/67 80/80 55/61 293/293

111A 18.6/24.8 51.7/59.7 78/88 80/90 72/81 289/289 83/93 90/100 76/85 293/293

112A 24.0/32.0 66.7/77.0 97/110 100/110 89/101 289/289 102/115 110/125 93/105 293/293

112A+117A 31.8/42.4 88.4/102.0 124/141 125/150 114/129 289/289 129/146 150/150 118/134 293/293

460-

3-

60

STD

NONE - - 23 30 22 117 25 30 24 119

116A 13.9 16.7 24 30 22 117 27 30 24 119

113A 16.5 19.8 28 30 26 117 31 35 28 119

114A 27.8 33.4 45 45 41 117 48 50 43 119

115A 33.0 39.7 53 60 49 117 55 60 51 119

114A+116A 41.7 50.2 66 70 61 117 69 70 63 119

MED

NONE - - 24 30 23 127 26 30 25 129

116A 13.9 16.7 26 30 23 127 28 30 25 129

113A 16.5 19.8 29 30 27 127 32 35 29 129

114A 27.8 33.4 46 50 42 127 49 50 44 129

115A 33.0 39.7 54 60 50 127 57 60 52 129

114A+116A 41.7 50.2 67 70 62 127 70 70 64 129

HIGH

NONE - - 26 30 25 142 28 40 27 144

116A 13.9 16.7 28 30 25 142 30 40 27 144

113A 16.5 19.8 32 35 29 142 34 40 31 144

114A 27.8 33.4 49 50 45 142 51 60 47 144

115A 33.0 39.7 57 60 52 142 59 60 54 144

114A+116A 41.7 50.2 70 70 64 142 72 80 66 144

575-

3-

60

STD

NONE - - 19 30 17 91 22 30 22 95

118A 17.0 20.4 28 30 25 91 33 35 30 95

119A 34.0 40.9 54 60 49 91 58 60 53 95

MED

NONE - - 19 30 18 95 23 30 22 99

118A 17.0 20.4 28 30 26 95 33 35 30 99

119A 34.0 40.9 54 60 49 95 59 60 54 99

HIGH

NONE - - 20 30 19 106 24 30 23 110

118A 17.0 20.4 29 30 27 106 34 35 31 110

119A 34.0 40.9 55 60 50 106 60 60 55 110

See “Legend and Notes for Tables 3 on page 34.

Page 25: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

25513 01 3305 00 Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSE orHACR BRKR

DISC. SIZE

MCAMAX FUSE orHACR BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S102 (

2-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 40/40 50/50 42/42 225 44/44 50/50 46/46 229

117A 7.8/10.4 21.7/25.0 40/40 50/50 42/42 225/225 44/44 50/50 46/46 229/229

110A 12.0/16.0 33.4/38.5 49/55 50/60 44/50 225/225 53/59 60/60 49/54 229/229

111A 18.6/24.8 51.7/59.7 72/81 80/90 65/74 225/225 76/86 80/90 70/79 229/229

112A 24.0/32.0 66.7/77.0 90/103 90/110 83/94 225/225 95/108 100/110 87/99 229/229

112A+117A 31.8/42.4 88.4/102.0 117/134 125/150 108/123 225/225 122/139 125/150 112/127 229/229

MED

NONE - - 42/42 50/50 44/44 246 46/46 60/50 48/48 250

117A 7.8/10.4 21.7/25.0 42/42 50/50 44/44 246/246 46/46 60/50 48/48 250/250

110A 12.0/16.0 33.4/38.5 51/57 60/60 46/52 246/246 56/62 60/70 51/56 250/250

111A 18.6/24.8 51.7/59.7 74/83 80/90 67/76 246/246 78/88 80/90 72/81 250/250

112A 24.0/32.0 66.7/77.0 92/105 100/110 85/96 246/246 97/110 100/110 89/101 250/250

112A+117A 31.8/42.4 88.4/102.0 120/136 125/150 110/125 246/246 124/141 125/150 114/129 250/250

HIGH

NONE - - 46 50 48 275 50 60 52 279

117A 7.8/10.4 21.7/25.0 46/46 50/50 48/48 275/275 50/50 60/60 52/52 279/279

110A 12.0/16.0 33.4/38.5 55/62 60/70 51/56 275/275 60/67 60/70 55/61 279/279

111A 18.6/24.8 51.7/59.7 78/88 80/90 72/81 275/275 83/93 90/100 76/85 279/279

112A 24.0/32.0 66.7/77.0 97/110 100/110 89/101 275/275 102/115 110/125 93/105 279/279

112A+117A 31.8/42.4 88.4/102.0 124/141 125/150 114/129 275/275 129/146 150/150 118/134 279/279

460-

3-

60

STD

NONE - - 19 20 19 118 20 25 21 120

116A 13.9 16.7 24 25 22 118 27 30 24 120

113A 16.5 19.8 28 30 26 118 31 35 28 120

114A 27.8 33.4 45 45 41 118 48 50 43 120

115A 33.0 39.7 53 60 49 118 55 60 51 120

114A+116A 41.7 50.2 66 70 61 118 69 70 63 120

MED

NONE - - 20 25 20 128 21 25 22 130

116A 13.9 16.7 26 30 23 128 28 30 25 130

113A 16.5 19.8 29 30 27 128 32 35 29 130

114A 27.8 33.4 46 50 42 128 49 50 44 130

115A 33.0 39.7 54 60 50 128 57 60 52 130

114A+116A 41.7 50.2 67 70 62 128 70 70 64 130

HIGH

NONE - - 21 25 22 143 23 25 24 145

116A 13.9 16.7 28 30 25 143 30 30 27 145

113A 16.5 19.8 32 35 29 143 34 35 31 145

114A 27.8 33.4 49 50 45 143 51 60 47 145

115A 33.0 39.7 57 60 52 143 59 60 54 145

114A+116A 41.7 50.2 70 70 64 143 72 80 66 145

575-

3-

60

STD

NONE - - 16 20 16 85 19 25 20 89

118A 17.0 20.4 28 30 25 85 33 35 30 89

119A 34.0 40.9 54 60 49 85 58 60 53 89

MED

NONE - - 16 20 16 89 20 25 20 93

118A 17.0 20.4 28 30 26 89 33 35 30 93

119A 34.0 40.9 54 60 49 89 59 60 54 93

HIGH

NONE - - 17 20 17 100 21 25 21 104

118A 17.0 20.4 29 30 27 100 34 35 31 104

119A 34.0 40.9 55 60 50 100 60 60 55 104

See “Legend and Notes for Tables 3 on page 34.

Page 26: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

26 513 01 3305 00Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S121 (

1-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 48/48 60/60 46/46 290 52/52 60/60 50/50 294

117A 7.8/10.4 21.7/25.0 48/48 60/60 46/46 290/290 52/52 60/60 50/50 294/294

110A 12.0/16.0 33.4/38.5 51/57 60/60 46/52 290/290 56/62 60/80 51/56 294/294

112A 24.0/32.0 66.7/77.0 92/105 100/110 85/96 290/290 97/110 100/110 89/101 294/294

112A+117A 31.8/42.4 88.4/102.0 120/136 125/150 110/125 290/290 124/141 125/150 114/129 294/294

112A+110A 37.6/50.0 104.2/120.3 139/129 150/150 128/146 290/290 144/134 150/150 132/150 294/294

MED

NONE - - 52 60 50 319 55 80 55 323

117A 7.8/10.4 21.7/25.0 52/52 60/60 50/50 319/319 55/55 80/80 55/55 323/323

110A 12.0/16.0 33.4/38.5 55/62 60/80 51/56 319/319 60/67 80/80 55/61 323/323

112A 24.0/32.0 66.7/77.0 97/110 100/110 89/101 319/319 102/115 110/125 93/105 323/323

112A+117A 31.8/42.4 88.4/102.0 124/141 125/150 114/129 319/319 129/146 150/150 118/134 323/323

112A+110A 37.6/50.0 104.2/120.3 144/134 150/150 132/151 319/319 149/139 150/150 136/155 323/323

HIGH

NONE - - 55/54 80/80 54/53 321 58/58 80/80 58/57 325

117A 7.8/10.4 21.7/25.0 55/54 80/80 54/53 321/321 58/58 80/80 58/57 325/325

110A 12.0/16.0 33.4/38.5 59/64 80/80 54/59 321/321 64/69 80/80 58/63 325/325

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 321/321 106/117 110/125 97/108 325/325

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 321/321 133/149 150/150 122/136 325/325

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 321/321 152/141 175/175 140/157 325/325

460-

3-

60

STD

NONE - - 26 40 25 146 28 40 27 148

116A 13.9 16.7 26 40 25 146 28 40 27 148

113A 16.5 19.8 29 40 27 146 32 40 29 148

115A 33.0 39.7 54 60 50 146 57 60 52 148

114A+116A 41.7 50.2 67 70 62 146 70 70 64 148

115A+113A 50.0 60.1 65 70 73 146 67 70 75 148

MED

NONE - - 28 40 27 161 30 45 29 163

116A 13.9 16.7 28 40 27 161 30 45 29 163

113A 16.5 19.8 32 40 29 161 34 45 31 163

115A 33.0 39.7 57 60 52 161 59 60 54 163

114A+116A 41.7 50.2 70 70 64 161 72 80 66 163

115A+113A 50.0 60.1 67 80 75 161 69 80 77 163

HIGH

NONE - - 29 45 28 162 31 45 30 164

116A 13.9 16.7 29 45 28 162 32 45 30 164

113A 16.5 19.8 33 45 30 162 35 45 32 164

115A 33.0 39.7 58 60 53 162 60 60 55 164

114A+116A 41.7 50.2 71 80 65 162 73 80 67 164

115A+113A 50.0 60.1 69 80 76 162 71 80 79 164

575-

3-

60

STD

NONE - - 19 30 18 95 23 30 22 99

118A 17.0 20.4 28 30 26 95 33 35 30 99

119A 34.0 40.9 54 60 49 95 59 60 54 99

118A+119A 51.0 61.3 64 70 73 95 69 80 77 99

MED

NONE - - 20 30 19 106 24 30 23 110

118A 17.0 20.4 29 30 27 106 34 35 31 110

119A 34.0 40.9 55 60 50 106 60 60 55 110

118A+119A 51.0 61.3 65 70 74 106 70 80 78 110

HIGH

NONE - - 23 30 22 120 26 30 26 124

118A 17.0 20.4 33 35 30 120 38 40 34 124

119A 34.0 40.9 59 60 53 120 63 70 58 124

118A+119A 51.0 61.3 69 80 77 120 74 80 81 124

See “Legend and Notes for Tables 3 on page 34.

Page 27: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

27513 01 3305 00 Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S120 (

2-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 46/46 60/60 48/47 285 50/49 60/60 52/52 289

117A 7.8/10.4 21.7/25.0 46/46 60/60 48/47 285/285 50/49 60/60 52/52 289/289

110A 12.0/16.0 33.4/38.5 51/57 60/60 48/52 285/285 56/62 60/70 52/56 289/289

112A 24.0/32.0 66.7/77.0 92/105 100/110 85/96 285/285 97/110 100/110 89/101 289/289

112A+117A 31.8/42.4 88.4/102.0 120/136 125/150 110/125 285/285 124/141 125/150 114/129 289/289

112A+110A 37.6/50.0 104.2/120.3 139/129 150/150 128/146 285/285 144/134 150/150 132/150 289/289

MED

NONE - - 50 60 52 314 53 60 56 318

117A 7.8/10.4 21.7/25.0 50/50 60/60 52/52 314/314 53/53 60/60 56/56 318/318

110A 12.0/16.0 33.4/38.5 55/62 60/70 52/56 314/314 60/67 60/70 56/61 318/318

112A 24.0/32.0 66.7/77.0 97/110 100/110 89/101 314/314 102/115 110/125 93/105 318/318

112A+117A 31.8/42.4 88.4/102.0 124/141 125/150 114/129 314/314 129/146 150/150 118/134 318/318

112A+110A 37.6/50.0 104.2/120.3 144/134 150/150 132/151 314/314 149/139 150/150 136/155 318/318

HIGH

NONE - - 53/52 60/60 55/54 316 56/55 60/60 60/59 320

117A 7.8/10.4 21.7/25.0 53/52 60/60 55/54 316/316 56/55 60/60 60/59 320/320

110A 12.0/16.0 33.4/38.5 59/64 60/70 55/59 316/316 64/69 70/70 60/63 320/320

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 316/316 106/117 110/125 97/108 320/320

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 316/316 133/149 150/150 122/136 320/320

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 316/316 152/141 175/175 140/157 320/320

460-

3-

60

STD

NONE - - 23 30 23 136 25 30 26 138

116A 13.9 16.7 26 30 23 136 28 30 26 138

113A 16.5 19.8 29 30 27 136 32 35 29 138

115A 33.0 39.7 54 60 50 136 57 60 52 138

114A+116A 41.7 50.2 67 70 62 136 70 70 64 138

115A+113A 50.0 60.1 65 70 73 136 67 70 75 138

MED

NONE - - 25 30 26 151 26 30 28 153

116A 13.9 16.7 28 30 26 151 30 30 28 153

113A 16.5 19.8 32 35 29 151 34 35 31 153

115A 33.0 39.7 57 60 52 151 59 60 54 153

114A+116A 41.7 50.2 70 70 64 151 72 80 66 153

115A+113A 50.0 60.1 67 80 75 151 69 80 77 153

HIGH

NONE - - 26 30 27 152 28 30 29 154

116A 13.9 16.7 29 30 27 152 32 35 29 154

113A 16.5 19.8 33 35 30 152 35 35 32 154

115A 33.0 39.7 58 60 53 152 60 60 55 154

114A+116A 41.7 50.2 71 80 65 152 73 80 67 154

115A+113A 50.0 60.1 69 80 76 152 71 80 79 154

575-

3-

60

STD

NONE - - 17 20 17 93 20 25 21 97

118A 17.0 20.4 28 30 26 93 33 35 30 97

119A 34.0 40.9 54 60 49 93 59 60 54 97

118A+119A 51.0 61.3 64 70 73 93 69 80 77 97

MED

NONE - - 17 20 18 104 21 25 22 108

118A 17.0 20.4 29 30 27 104 34 35 31 108

119A 34.0 40.9 55 60 50 104 60 60 55 108

118A+119A 51.0 61.3 65 70 74 104 70 80 78 108

HIGH

NONE - - 20 25 21 118 24 30 25 122

118A 17.0 20.4 33 35 30 118 38 40 34 122

119A 34.0 40.9 59 60 53 118 63 70 58 122

118A+119A 51.0 61.3 69 80 77 118 74 80 81 122

See “Legend and Notes for Tables 3 on page 34.

Page 28: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

28 513 01 3305 00Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S150 (

2-

sta

ge

co

olin

g)

Un

its p

rod

uce

d o

n o

r aft

er

02/1

6/2

01

5

208/2

30-

3-

60

208/2

30-

3-

60

STD

NONE - - 63/63 80/80 65/65 389 66/66 80/80 69/69 393

117A 7.8/10.4 21.7/25.0 63/63 80/80 65/65 389/389 66/66 80/80 69/69 393/393

110A 12.0/16.0 33.4/38.5 63/63 80/80 65/65 389/389 66/66 80/80 69/69 393/393

112A 24.0/32.0 66.7/77.0 94/107 100/110 86/98 389/389 99/112 100/125 91/102 393/393

112A+117A 31.8/42.4 88.4/102.0 121/138 125/150 111/127 389/389 126/143 150/150 116/131 393/393

112A+110A 37.6/50.0 104.2/120.3 141/131 150/150 129/148 389/389 146/136 150/150 134/152 393/393

MED

NONE - - 65 80 68 403 69 80 72 407

117A 7.8/10.4 21.7/25.0 65/65 80/80 68/68 403/403 69/69 80/80 72/72 407/407

110A 12.0/16.0 33.4/38.5 65/65 80/80 68/68 403/403 69/69 80/80 72/72 407/407

112A 24.0/32.0 66.7/77.0 97/110 100/110 89/101 403/403 102/115 110/125 93/105 407/407

112A+117A 31.8/42.4 88.4/102.0 124/141 125/150 114/129 403/403 129/146 150/150 118/134 407/407

112A+110A 37.6/50.0 104.2/120.3 144/134 150/150 132/151 403/403 149/139 150/150 136/155 407/407

HIGH

NONE - - 68/67 80/80 71/70 405 72/71 80/80 75/74 409

117A 7.8/10.4 21.7/25.0 68/67 80/80 71/70 405/405 72/71 80/80 75/74 409/409

110A 12.0/16.0 33.4/38.5 68/67 80/80 71/70 405/405 72/71 80/80 75/74 409/409

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 405/405 106/117 110/125 97/108 409/409

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 405/405 133/149 150/150 122/136 409/409

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 405/405 152/141 175/175 140/157 409/409

460-

3-

60

STD

NONE - - 29 35 30 193 31 40 32 195

116A 13.9 16.7 29 35 30 193 31 40 32 195

113A 16.5 19.8 30 35 30 193 33 40 32 195

115A 33.0 39.7 55 60 50 193 58 60 53 195

114A+116A 41.7 50.2 68 70 63 193 71 80 65 195

115A+113A 50.0 60.1 66 70 74 193 68 80 76 195

MED

NONE - - 30 40 31 200 32 40 33 202

116A 13.9 16.7 30 40 31 200 32 40 33 202

113A 16.5 19.8 32 40 31 200 34 40 33 202

115A 33.0 39.7 57 60 52 200 59 60 54 202

114A+116A 41.7 50.2 70 70 64 200 72 80 66 202

115A+113A 50.0 60.1 67 80 75 200 69 80 77 202

HIGH

NONE - - 31 40 33 201 33 40 35 203

116A 13.9 16.7 31 40 33 201 33 40 35 203

113A 16.5 19.8 33 40 33 201 35 40 35 203

115A 33.0 39.7 58 60 53 201 60 60 55 203

114A+116A 41.7 50.2 71 80 65 201 73 80 67 203

115A+113A 50.0 60.1 69 80 76 201 71 80 79 203

575-

3-

60

STD

NONE - - 22 25 23 147 26 30 27 151

118A 17.0 20.4 29 30 27 147 34 35 31 151

119A 34.0 40.9 55 60 50 147 60 60 55 151

118A+119A 51.0 61.3 65 70 74 147 70 80 78 151

MED

NONE - - 22 25 23 147 26 30 27 151

118A 17.0 20.4 29 30 27 147 34 35 31 151

119A 34.0 40.9 55 60 50 147 60 60 55 151

118A+119A 51.0 61.3 65 70 74 147 70 80 78 151

HIGH

NONE - - 25 30 26 161 29 35 30 165

118A 17.0 20.4 33 35 30 161 38 40 34 165

119A 34.0 40.9 59 60 53 161 63 70 58 165

118A+119A 51.0 61.3 69 80 77 161 74 80 81 165

See “Legend and Notes for Tables 3 on page 34.

Page 29: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

29513 01 3305 00 Specifications subject to change without notice.

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data with Single Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S150 (

2-

sta

ge

co

olin

g)

Un

its p

rod

uce

d o

n o

r p

rio

r to

02/1

5/2

01

5

208/2

30-

3-

60

208/2

30-

3-

60

STD

NONE - - 62/62 80/80 64/64 376 66/66 80/80 69/69 380

117A 7.8/10.4 21.7/25.0 62/62 80/80 64/64 376/376 66/66 80/80 69/69 380/380

110A 12.0/16.0 33.4/38.5 62/62 80/80 64/64 376/376 66/66 80/80 69/69 380/380

112A 24.0/32.0 66.7/77.0 94/107 100/110 86/98 376/376 99/112 100/125 91/102 380/380

112A+117A 31.8/42.4 88.4/102.0 121/138 125/150 111/127 376/376 126/143 150/150 116/131 380/380

112A+110A 37.6/50.0 104.2/120.3 141/131 150/150 129/148 376/376 146/136 150/150 134/152 380/380

MED

NONE - - 64 80 67 390 68 80 71 394

117A 7.8/10.4 21.7/25.0 64/64 80/80 67/67 390/390 68/68 80/80 71/71 394/394

110A 12.0/16.0 33.4/38.5 64/64 80/80 67/67 390/390 68/68 80/80 71/71 394/394

112A 24.0/32.0 66.7/77.0 97/110 100/110 89/101 390/390 102/115 110/125 93/105 394/394

112A+117A 31.8/42.4 88.4/102.0 124/141 125/150 114/129 390/390 129/146 150/150 118/134 394/394

112A+110A 37.6/50.0 104.2/120.3 144/134 150/150 132/151 390/390 149/139 150/150 136/155 394/394

HIGH

NONE - - 67/66 80/80 70/69 392 71/70 80/80 75/74 396

117A 7.8/10.4 21.7/25.0 67/66 80/80 70/69 392/392 71/70 80/80 75/74 396/396

110A 12.0/16.0 33.4/38.5 67/66 80/80 70/69 392/392 71/70 80/80 75/74 396/396

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 392/392 106/117 110/125 97/108 396/396

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 392/392 133/149 150/150 122/136 396/396

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 392/392 152/141 175/175 140/157 396/396

460-

3-

60

STD

NONE - - 31 40 32 189 33 40 34 191

116A 13.9 16.7 31 40 32 189 33 40 34 191

113A 16.5 19.8 31 40 32 189 33 40 34 191

115A 33.0 39.7 55 60 50 189 58 60 53 191

114A+116A 41.7 50.2 68 70 63 189 71 80 65 191

115A+113A 50.0 60.1 66 70 74 189 68 80 76 191

MED

NONE - - 32 40 33 196 34 40 35 198

116A 13.9 16.7 32 40 33 196 34 40 35 198

113A 16.5 19.8 32 40 33 196 34 40 35 198

115A 33.0 39.7 57 60 52 196 59 60 54 198

114A+116A 41.7 50.2 70 70 64 196 72 80 66 198

115A+113A 50.0 60.1 67 80 75 196 69 80 77 198

HIGH

NONE - - 33 40 34 197 35 40 36 199

116A 13.9 16.7 33 40 34 197 35 40 36 199

113A 16.5 19.8 33 40 34 197 35 40 36 199

115A 33.0 39.7 58 60 53 197 60 60 55 199

114A+116A 41.7 50.2 71 80 65 197 73 80 67 199

115A+113A 50.0 60.1 69 80 76 197 71 80 79 199

575-

3-

60

STD

NONE - - 23 30 23 142 27 30 28 146

118A 17.0 20.4 29 30 27 142 34 35 31 146

119A 34.0 40.9 55 60 50 142 60 60 55 146

118A+119A 51.0 61.3 65 70 74 142 70 80 78 146

MED

NONE - - 23 30 23 142 27 30 28 146

118A 17.0 20.4 29 30 27 142 34 35 31 146

119A 34.0 40.9 55 60 50 142 60 60 55 146

118A+119A 51.0 61.3 65 70 74 142 70 80 78 146

HIGH

NONE - - 26 30 27 156 29 35 31 160

118A 17.0 20.4 33 35 30 156 38 40 34 160

119A 34.0 40.9 59 60 53 156 63 70 58 160

118A+119A 51.0 61.3 69 80 77 156 74 80 81 160

See “Legend and Notes for Tables 3 on page 34.

Page 30: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

30 513 01 3305 00Specifications subject to change without notice.

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data with 2−Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

MCAMAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S090 (

2-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 40/40 50/50 41/41 197 44/43 50/50 46/46 201

117A 7.8/10.4 21.7/25.0 40/40 50/50 41/41 197/197 44/43 50/50 46/46 201/201

110A 12.0/16.0 33.4/38.5 49/56 50/60 45/51 197/197 54/60 60/60 49/55 201/201

111A 18.6/24.8 51.7/59.7 72/82 80/90 66/75 197/197 77/87 80/90 70/79 201/201

112A 24.0/32.0 66.7/77.0 91/104 100/110 83/95 197/197 96/108 100/110 88/99 201/201

112A+117A 31.8/42.4 88.4/102.0 118/135 125/150 108/124 197/197 123/140 125/150 113/128 201/201

MED

NONE - - 43/42 50/50 45/44 227 46/46 50/50 49/48 231

117A 7.8/10.4 21.7/25.0 43/42 50/50 45/44 227/227 46/46 50/50 49/48 231/231

110A 12.0/16.0 33.4/38.5 53/58 60/60 48/53 227/227 58/63 60/70 53/58 231/231

111A 18.6/24.8 51.7/59.7 76/85 80/90 69/78 227/227 81/90 90/90 74/82 231/231

112A 24.0/32.0 66.7/77.0 95/106 100/110 87/98 227/227 99/111 100/125 91/102 231/231

112A+117A 31.8/42.4 88.4/102.0 122/138 125/150 112/126 227/227 126/142 150/150 116/131 231/231

HIGH

NONE - - 48/47 60/50 50/49 262 51/51 60/60 55/54 266

117A 7.8/10.4 21.7/25.0 48/48 60/50 50/49 262/262 51/52 60/60 55/54 266/266

110A 12.0/16.0 33.4/38.5 59/64 60/70 54/59 262/262 64/69 70/70 58/63 266/266

111A 18.6/24.8 51.7/59.7 82/91 90/100 75/83 262/262 87/96 90/100 79/88 266/266

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 262/262 106/117 110/125 97/108 266/266

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 262/262 133/149 150/150 122/136 266/266

460-

3-

60

STD

NONE - - 19 20 19 97 20 25 21 99

116A 13.9 16.7 25 25 23 97 27 30 25 99

113A 16.5 19.8 29 30 26 97 31 35 28 99

114A 27.8 33.4 46 50 42 97 48 50 44 99

115A 33.0 39.7 54 60 49 97 56 60 51 99

114A+116A 41.7 50.2 67 70 61 97 69 70 63 99

MED

NONE - - 20 25 20 113 21 25 22 115

116A 13.9 16.7 26 30 24 113 28 30 26 115

113A 16.5 19.8 30 30 27 113 32 35 29 115

114A 27.8 33.4 47 50 43 113 49 50 45 115

115A 33.0 39.7 55 60 50 113 57 60 52 115

114A+116A 41.7 50.2 68 70 62 113 70 70 64 115

HIGH

NONE - - 22 25 23 130 24 30 25 132

116A 13.9 16.7 29 30 27 130 32 35 29 132

113A 16.5 19.8 33 35 30 130 35 35 32 132

114A 27.8 33.4 50 50 46 130 52 60 48 132

115A 33.0 39.7 58 60 53 130 60 60 55 132

114A+116A 41.7 50.2 71 80 65 130 73 80 67 132

575-

3-

60

STD

NONE - - 14 15 14 79 18 20 19 83

118A 17.0 20.4 29 30 27 79 34 35 31 83

119A 34.0 40.9 55 60 50 79 60 60 55 83

MED

NONE - - 16 20 16 92 19 25 21 96

118A 17.0 20.4 32 35 29 92 36 40 33 96

119A 34.0 40.9 57 60 52 92 62 70 57 96

HIGH

NONE - - 18 20 18 106 22 25 23 110

118A 17.0 20.4 34 35 31 106 38 40 35 110

119A 34.0 40.9 59 60 54 106 64 70 59 110

See “Legend and Notes for Tables 4 on page 34.

Page 31: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

31513 01 3305 00 Specifications subject to change without notice.

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data with 2−Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S102 (

2-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 41/41 50/50 43/42 212 45/45 50/50 47/47 216

117A 7.8/10.4 21.7/25.0 41/41 50/50 43/42 212/212 45/45 50/50 47/47 216/216

110A 12.0/16.0 33.4/38.5 49/56 50/60 45/51 212/212 54/60 60/60 49/55 216/216

111A 18.6/24.8 51.7/59.7 72/82 80/90 66/75 212/212 77/87 80/90 70/79 216/216

112A 24.0/32.0 66.7/77.0 91/104 100/110 83/95 212/212 96/108 100/110 88/99 216/216

112A+117A 31.8/42.4 88.4/102.0 118/135 125/150 108/124 212/212 123/140 125/150 113/128 216/216

MED

NONE - - 42/42 50/50 44/44 216 46/46 60/50 48/48 220

117A 7.8/10.4 21.7/25.0 42/42 50/50 44/44 216/216 46/46 60/50 48/48 220/220

110A 12.0/16.0 33.4/38.5 51/57 60/60 47/52 216/216 56/62 60/70 51/56 220/220

111A 18.6/24.8 51.7/59.7 74/84 80/90 68/76 216/216 79/88 80/90 72/81 220/220

112A 24.0/32.0 66.7/77.0 93/105 100/110 85/96 216/216 97/110 100/110 89/101 220/220

112A+117A 31.8/42.4 88.4/102.0 120/136 125/150 110/125 216/216 125/141 125/150 114/129 220/220

HIGH

NONE - - 46/45 60/50 48/47 266 50/49 60/60 53/52 270

117A 7.8/10.4 21.7/25.0 46/45 60/50 48/47 266/266 50/49 60/60 53/52 270/270

110A 12.0/16.0 33.4/38.5 56/61 60/70 51/56 266/266 60/66 60/70 55/60 270/270

111A 18.6/24.8 51.7/59.7 79/87 80/90 72/80 266/266 83/92 90/100 76/84 270/270

112A 24.0/32.0 66.7/77.0 97/109 100/110 89/100 266/266 102/114 110/125 93/104 270/270

112A+117A 31.8/42.4 88.4/102.0 124/140 125/150 114/129 266/266 129/145 150/150 118/133 270/270

460-

3-

60

STD

NONE - - 19 25 20 111 21 25 22 113

116A 13.9 16.7 25 25 23 111 27 30 25 113

113A 16.5 19.8 29 30 26 111 31 35 28 113

114A 27.8 33.4 46 50 42 111 48 50 44 113

115A 33.0 39.7 54 60 49 111 56 60 51 113

114A+116A 41.7 50.2 67 70 61 111 69 70 63 113

MED

NONE - - 20 25 21 114 22 25 23 116

116A 13.9 16.7 26 30 24 114 28 30 26 116

113A 16.5 19.8 30 30 27 114 32 35 29 116

114A 27.8 33.4 47 50 43 114 49 50 45 116

115A 33.0 39.7 55 60 50 114 57 60 52 116

114A+116A 41.7 50.2 68 70 62 114 70 70 64 116

HIGH

NONE - - 21 25 22 139 23 25 24 141

116A 13.9 16.7 27 30 25 139 30 30 27 141

113A 16.5 19.8 31 35 28 139 34 35 30 141

114A 27.8 33.4 48 50 44 139 51 60 46 141

115A 33.0 39.7 56 60 51 139 58 60 53 141

114A+116A 41.7 50.2 69 70 63 139 72 80 65 141

575-

3-

60

STD

NONE - - 17 20 17 87 21 25 21 91

118A 17.0 20.4 29 30 27 87 34 35 31 91

119A 34.0 40.9 55 60 50 87 60 60 55 91

MED

NONE - - 17 20 18 91 21 25 22 95

118A 17.0 20.4 30 30 27 91 35 35 32 95

119A 34.0 40.9 56 60 51 91 61 70 55 95

HIGH

NONE - - 18 20 19 100 22 25 23 104

118A 17.0 20.4 32 35 29 100 36 40 33 104

119A 34.0 40.9 57 60 52 100 62 70 57 104

See “Legend and Notes for Tables 4 on page 34.

Page 32: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

32 513 01 3305 00Specifications subject to change without notice.

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data with 2−Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S120 (

2-

sta

ge

co

olin

g)

208/2

30-

3-

60

STD

NONE - - 46/46 60/60 48/47 255 50/50 60/60 52/52 259

117A 7.8/10.4 21.7/25.0 46/46 60/60 48/47 255/255 50/50 60/60 52/52 259/259

110A 12.0/16.0 33.4/38.5 51/57 60/60 48/52 255/255 56/62 60/70 52/56 259/259

112A 24.0/32.0 66.7/77.0 93/105 100/110 85/96 255/255 97/110 100/110 89/101 259/259

112A+117A 31.8/42.4 88.4/102.0 120/136 125/150 110/125 255/255 125/141 125/150 114/129 259/259

112A+110A 37.6/50.0 104.2/120.3 140/129 150/150 128/146 255/255 144/134 150/150 132/151 259/259

MED

NONE - - 50/49 60/60 52/51 305 54/53 60/60 56/55 309

117A 7.8/10.4 21.7/25.0 50/49 60/60 52/51 305/305 54/53 60/60 56/55 309/309

110A 12.0/16.0 33.4/38.5 56/61 60/70 52/56 305/305 60/66 60/70 56/60 309/309

112A 24.0/32.0 66.7/77.0 97/109 100/110 89/100 305/305 102/114 110/125 93/104 309/309

112A+117A 31.8/42.4 88.4/102.0 124/140 125/150 114/129 305/305 129/145 150/150 118/133 309/309

112A+110A 37.6/50.0 104.2/120.3 144/133 150/150 132/150 305/305 149/138 150/150 137/154 309/309

HIGH

NONE - - 53/52 60/60 55/54 316 56/55 60/60 60/59 320

117A 7.8/10.4 21.7/25.0 53/52 60/60 55/54 316/316 56/55 60/60 60/59 320/320

110A 12.0/16.0 33.4/38.5 59/64 60/70 55/59 316/316 64/69 70/70 60/63 320/320

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 316/316 106/117 110/125 97/108 320/320

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 316/316 133/149 150/150 122/136 320/320

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 316/316 152/141 175/175 140/157 320/320

460-

3-

60

STD

NONE - - 23 30 24 122 25 30 26 124

116A 13.9 16.7 26 30 24 122 28 30 26 124

113A 16.5 19.8 30 30 27 122 32 35 29 124

115A 33.0 39.7 55 60 50 122 57 60 52 124

114A+116A 41.7 50.2 68 70 62 122 70 70 64 124

115A+113A 50.0 60.1 65 70 73 122 68 80 76 124

MED

NONE - - 24 30 25 147 26 30 27 149

116A 13.9 16.7 27 30 25 147 30 30 27 149

113A 16.5 19.8 31 35 28 147 34 35 30 149

115A 33.0 39.7 56 60 51 147 58 60 53 149

114A+116A 41.7 50.2 69 70 63 147 72 80 65 149

115A+113A 50.0 60.1 67 80 75 147 69 80 77 149

HIGH

NONE - - 26 30 27 152 28 30 29 154

116A 13.9 16.7 29 30 27 152 32 35 29 154

113A 16.5 19.8 33 35 30 152 35 35 32 154

115A 33.0 39.7 58 60 53 152 60 60 55 154

114A+116A 41.7 50.2 71 80 65 152 73 80 67 154

115A+113A 50.0 60.1 69 80 76 152 71 80 79 154

575-

3-

60

STD

NONE - - 18 20 19 95 22 25 23 99

118A 17.0 20.4 30 30 27 95 35 35 32 99

119A 34.0 40.9 56 60 51 95 61 70 55 99

118A+119A 51.0 61.3 66 70 75 95 71 80 79 99

MED

NONE - - 19 25 20 104 23 25 24 108

118A 17.0 20.4 32 35 29 104 36 40 33 108

119A 34.0 40.9 57 60 52 104 62 70 57 108

118A+119A 51.0 61.3 67 80 76 104 72 80 80 108

HIGH

NONE - - 21 25 22 118 25 30 26 122

118A 17.0 20.4 34 35 31 118 38 40 35 122

119A 34.0 40.9 59 60 54 118 64 70 59 122

118A+119A 51.0 61.3 70 80 78 118 74 80 82 122

See “Legend and Notes for Tables 4 on page 34.

Page 33: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

33513 01 3305 00 Specifications subject to change without notice.

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data with 2−Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S150 (

2-

sta

ge

co

olin

g)

Un

its p

rod

uce

d o

n o

r aft

er

02/1

6/2

01

5

208/2

30-

3-

60

STD

NONE - - 63/62 80/80 65/64 370 67/66 80/80 70/69 374

117A 7.8/10.4 21.7/25.0 63/62 80/80 65/64 370/370 67/66 80/80 70/69 374/374

110A 12.0/16.0 33.4/38.5 63/62 80/80 65/64 370/370 67/66 80/80 70/69 374/374

112A 24.0/32.0 66.7/77.0 95/106 100/110 87/98 370/370 99/111 100/125 91/102 374/374

112A+117A 31.8/42.4 88.4/102.0 122/138 125/150 112/126 370/370 126/142 150/150 116/131 374/374

112A+110A 37.6/50.0 104.2/120.3 141/131 150/150 130/147 370/370 146/135 150/150 134/152 374/374

MED

NONE - - 65/64 80/80 68/67 394 69/68 80/80 72/71 398

117A 7.8/10.4 21.7/25.0 65/64 80/80 68/67 394/394 69/68 80/80 72/71 398/398

110A 12.0/16.0 33.4/38.5 65/64 80/80 68/67 394/394 69/68 80/80 72/71 398/398

112A 24.0/32.0 66.7/77.0 97/109 100/110 89/100 394/394 102/114 110/125 93/104 398/398

112A+117A 31.8/42.4 88.4/102.0 124/140 125/150 114/129 394/394 129/145 150/150 118/133 398/398

112A+110A 37.6/50.0 104.2/120.3 144/133 150/150 132/150 394/394 149/138 150/150 137/154 398/398

HIGH

NONE - - 68/67 80/80 71/70 405 72/71 80/80 75/74 409

117A 7.8/10.4 21.7/25.0 68/67 80/80 71/70 405/405 72/71 80/80 75/74 409/409

110A 12.0/16.0 33.4/38.5 68/67 80/80 71/70 405/405 72/71 80/80 75/74 409/409

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 405/405 106/117 110/125 97/108 409/409

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 405/405 133/149 150/150 122/136 409/409

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 405/405 152/141 175/175 140/157 409/409

460-

3-

60

STD

NONE - - 29 35 30 184 31 40 32 186

116A 13.9 16.7 29 35 30 184 31 40 32 186

113A 16.5 19.8 30 35 30 184 32 40 32 186

115A 33.0 39.7 55 60 50 184 57 60 52 186

114A+116A 41.7 50.2 68 70 62 184 70 70 64 186

115A+113A 50.0 60.1 65 70 73 184 68 80 76 186

MED

NONE - - 30 40 31 196 32 40 33 198

116A 13.9 16.7 30 40 31 196 32 40 33 198

113A 16.5 19.8 31 40 31 196 34 40 33 198

115A 33.0 39.7 56 60 51 196 58 60 53 198

114A+116A 41.7 50.2 69 70 63 196 72 80 65 198

115A+113A 50.0 60.1 67 80 75 196 69 80 77 198

HIGH

NONE - - 31 40 33 201 33 40 35 203

116A 13.9 16.7 31 40 33 201 33 40 35 203

113A 16.5 19.8 33 40 33 201 35 40 35 203

115A 33.0 39.7 58 60 53 201 60 60 55 203

114A+116A 41.7 50.2 71 80 65 201 73 80 67 203

115A+113A 50.0 60.1 69 80 76 201 71 80 79 203

575-

3-

60

STD

NONE - - 24 30 24 147 27 30 29 151

118A 17.0 20.4 32 35 29 147 36 40 33 151

119A 34.0 40.9 57 60 52 147 62 70 57 151

118A+119A 51.0 61.3 67 80 76 147 72 80 80 151

MED

NONE - - 24 30 24 147 27 30 29 151

118A 17.0 20.4 32 35 29 147 36 40 33 151

119A 34.0 40.9 57 60 52 147 62 70 57 151

118A+119A 51.0 61.3 67 80 76 147 72 80 80 151

HIGH

NONE - - 25 30 26 161 29 35 31 165

118A 17.0 20.4 34 35 31 161 38 40 35 165

119A 34.0 40.9 59 60 54 161 64 70 59 165

118A+119A 51.0 61.3 70 80 78 161 74 80 82 165

See “Legend and Notes for Tables 4 on page 34.

Page 34: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

34 513 01 3305 00Specifications subject to change without notice.

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data with 2−Speed Indoor Fan MotorU

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER***A00Nom(kW)

FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCAMAX FUSEor HACR

BRKR

DISC. SIZEMCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

RA

S150 (

2-

ata

ge

co

olin

g)

Un

its p

rod

uce

d o

n o

r p

rio

r to

02/1

5/2

01

5

208/2

30-

3-

60

STD

NONE - - 62/61 80/80 65/64 357 66/65 80/80 69/68 361

117A 7.8/10.4 21.7/25.0 62/61 80/80 65/64 357/357 66/65 80/80 69/68 361/361

110A 12.0/16.0 33.4/38.5 62/61 80/80 65/64 357/357 66/65 80/80 69/68 361/361

112A 24.0/32.0 66.7/77.0 95/106 100/110 87/98 357/357 99/111 100/125 91/102 361/361

112A+117A 31.8/42.4 88.4/102.0 122/138 125/150 112/126 357/357 126/142 150/150 116/131 361/361

112A+110A 37.6/50.0 104.2/120.3 141/131 150/150 130/147 357/357 146/135 150/150 134/152 361/361

MED

NONE - - 64/63 80/80 67/66 381 68/67 80/80 72/70 385

117A 7.8/10.4 21.7/25.0 64/63 80/80 67/66 381/381 68/67 80/80 72/70 385/385

110A 12.0/16.0 33.4/38.5 64/63 80/80 67/66 381/381 68/67 80/80 72/70 385/385

112A 24.0/32.0 66.7/77.0 97/109 100/110 89/100 381/381 102/114 110/125 93/104 385/385

112A+117A 31.8/42.4 88.4/102.0 124/140 125/150 114/129 381/381 129/145 150/150 118/133 385/385

112A+110A 37.6/50.0 104.2/120.3 144/133 150/150 132/150 381/381 149/138 150/150 137/154 385/385

HIGH

NONE - - 67/66 80/80 70/69 392 71/70 80/80 75/74 396

117A 7.8/10.4 21.7/25.0 67/66 80/80 70/69 392/392 71/70 80/80 75/74 396/396

110A 12.0/16.0 33.4/38.5 67/66 80/80 70/69 392/392 71/70 80/80 75/74 396/396

112A 24.0/32.0 66.7/77.0 101/113 110/125 92/103 392/392 106/117 110/125 97/108 396/396

112A+117A 31.8/42.4 88.4/102.0 128/144 150/150 117/132 392/392 133/149 150/150 122/136 396/396

112A+110A 37.6/50.0 104.2/120.3 148/137 150/150 135/153 392/392 152/141 175/175 140/157 396/396

460-

3-

60

STD

NONE - - 30 40 31 180 32 40 33 182

116A 13.9 16.7 30 40 31 180 32 40 33 182

113A 16.5 19.8 30 40 31 180 32 40 33 182

115A 33.0 39.7 55 60 50 180 57 60 52 182

114A+116A 41.7 50.2 68 70 62 180 70 70 64 182

115A+113A 50.0 60.1 65 70 73 180 68 80 76 182

MED

NONE - - 31 40 33 192 33 40 35 194

116A 13.9 16.7 31 40 33 192 33 40 35 194

113A 16.5 19.8 31 40 33 192 34 40 35 194

115A 33.0 39.7 56 60 51 192 58 60 53 194

114A+116A 41.7 50.2 69 70 63 192 72 80 65 194

115A+113A 50.0 60.1 67 80 75 192 69 80 77 194

HIGH

NONE - - 33 40 34 197 35 40 36 199

116A 13.9 16.7 33 40 34 197 35 40 36 199

113A 16.5 19.8 33 40 34 197 35 40 36 199

115A 33.0 39.7 58 60 53 197 60 60 55 199

114A+116A 41.7 50.2 71 80 65 197 73 80 67 199

115A+113A 50.0 60.1 69 80 76 197 71 80 79 199

575-

3-

60

STD

NONE - - 24 30 25 142 28 30 30 146

118A 17.0 20.4 32 35 29 142 36 40 33 146

119A 34.0 40.9 57 60 52 142 62 70 57 146

118A+119A 51.0 61.3 67 80 76 142 72 80 80 146

MED

NONE - - 24 30 25 142 28 30 30 146

118A 17.0 20.4 32 35 29 142 36 40 33 146

119A 34.0 40.9 57 60 52 142 62 70 57 146

118A+119A 51.0 61.3 67 80 76 142 72 80 80 146

HIGH

NONE - - 26 30 27 156 30 35 32 160

118A 17.0 20.4 34 35 31 156 38 40 35 160

119A 34.0 40.9 59 60 54 156 64 70 59 160

118A+119A 51.0 61.3 70 80 78 156 74 80 82 160

LEGEND:CO − Convenient outletDISC − DisconnectFLA − Full load ampsIFM − Indoor fan motorLRA − Locked rotor ampsMCA − Minimum circuit ampsMOCP − Maximum over current protectionPE − Power exhaustUNPWRD CO − Unpowered convenient outletNOTES:

4. In compliance with NEC requirements for multimotor and combinationload equipment (refer to NEC Articles 430 and 440), the overcurrent pro­tective device for the unit shall be fuse or HACR breaker. Canadian unitsmay be fuse or circuit breaker.

5. Unbalanced 3‐Phase Supply VoltageNever operate a motor where a phase imbalance in supply voltage isgreater than 2%. Use the following formula to determine the percentageof voltage imbalance.

% Voltage Imbalance = 100 xmax voltage deviation from average voltage

average voltage

AB = 224 vBC = 231 vAC = 226 v

Average Voltage =(224 + 231 + 226)

=681

3 3

= 227

Determine maximum deviation from average voltage.(AB) 227 – 224 = 3 v Maximum deviation is 4 v.. . . . . . . .(BC) 231 – 227 = 4 v Determine percent of voltage imbalance.. . . . . . . .

% Voltage Imbalance = 100 x4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum al-lowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%, contactyour local electric utility company immediately.

Page 35: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

35513 01 3305 00 Specifications subject to change without notice.

FIGURE 34 Wiring for Optional Economizer

Economizer 2 Position Damper Unit Without Economizer or2 Position Damper

Step 11 — Adjust Factory−Installed Options

Smoke Detector —

Smoke detector will be connected at the ControlsConnections Board, at terminals marked “SmokeShutdown”. Remove jumper JMP 3 when ready to energizeunit.

Economizer Occupancy Switch —

Refer to Fig. 30 for general economizer wiring. Externaloccupancy control is managed through a connection on theControls Connections Board.

If external occupancy control is desired, connect a timeclock or remotely controlled switch (closed for Occupied,open for Unoccupied sequence) at terminals markedOCCUPANCY. Remove or cut jumper JMP 2 to completethe installation.

Step 12 — Install Accessories, As Required

Available accessories include:

Roof CurbThru−base connection kit (must be installed before unit isset on curb)Manual outside air damperTwo−Position motorized outside air damperEconomizer (with control and integrated barometric relief)Winter start kitPower exhaustOutdoor enthalpy sensorDifferential enthalpy sensorCO2 sensorLow ambient controlHood−type hail guardPhase monitor control

Refer to separate installation instructions for information oninstalling these accessories.

Page 36: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

36 513 01 3305 00Specifications subject to change without notice.

UNIT START-UP CHECKLIST(Remove and Store in Job File)

MODEL NO.: SERIAL NO.:

I. PRE-START-UP� VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT

� VERIFY INSTALLATION OF OUTDOOR AIR HOOD

� VERIFY INSTALLATION OF FLUE EXHAUST AND INLET HOOD

� VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS

� VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT

� CHECK THAT INDOOR−AIR FILTERS ARE CLEAN AND IN PLACE

� CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE

� VERIFY THAT UNIT IS LEVEL

� CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT

� VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED

� VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRRECT DIRECTION

� VERIFY INSTALLATION OF THERMOSTAT

II. START-UPELECTRICAL

SUPPLY VOLTAGE L1−L2 L2−L3 L3−L1

COMPRESSOR AMPS 1 L1 L2 L3

COMPRESSOR AMPS 2 L1 L2 L3

SUPPLY FAN AMPS L1 L2 L3

TEMPERATURES

OUTDOOR−AIR TEMPERATURE �F DB (DRY BULB)

RETURN−AIR TEMPERATURE �F DB �F WB (WET BULB)

COOLING SUPPLY AIR TEMPERATURE �F

PRESSURES

REFRIGERANT SUCTION CIRCUIT A PSIG

CIRCUIT B PSIG

REFRIGERANT DISCHARGE CIRCUIT A PSIG

CIRCUIT B PSIG

� VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS

GENERAL

� ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS (IF EQUIPPED)

� VERIFY SMOKE DETECTOR UNIT SHUTDOWN BY UTILIZING MAGNET TEST

Page 37: INSTALLATION INSTRUCTIONS R 410A Single Package Air ...R−410A Single Package Air Conditioner RAS090 − 150 These instructions must be read and understood completely before attempting

37513 01 3305 00 Specifications subject to change without notice.

III. HOT GAS REHEAT START-UPSTEPS

� 1. CHECK CTB FOR JUMPER 5, 6, 7JUMPER 5, 6, 7 MUST BE CUT AND OPEN

� 2. OPEN HUMIDISTAT CONTACTS

� 3. START UNIT IN COOLING (CLOSE Y1)OBSERVE AND RECORD

A. SUCTION PRESSURE PSIG

B. DISCHARGE PRESSURE PSIG

C. ENTERING AIR TEMPERATURE �F

D. LIQUID LINE TEMPERATUREAT OUTLET OR REHEAT COIL �F

E. CONFRIM CORRECT ROTATION FOR COMPRESSOR

F. CHECK FOR CORRECT RAMP−UP OF OJUTDOOR FAN MOTOR AS CONDENSER COIL WARMS

� 4. CHECK UNIT CHARGE PER CHARGING CHART

� 5. SWITCH UNIT TO HIGH−LATENT MODE (SUBCOOLER) BY CLOSING HUMIDISTAT WITH Y1 CLOSED

OBSERVE

� A. REDUCTION IN SUCTION PRESSURE (5 TO 7 PSI EXPECTED)

� B. DISCHARGE PRESSURE UNCHANGED

� C. LIQUID TEMPERATURE DROPS TO 50 TO 55�F RANGE

� D. LSV SOLENOID ENGERIZED (VALVE CLOSES)

� 6. SWITCH UNIT TO DEHUMID (REHEAT) BY OPENING Y1

OBSERVE

� A. SUCTION PRESSURE INCREASES TO NORMAL COOLING LEVEL

� B. DISCHARGE PRESSURE DECREASES (35 TO 50 PSI)

� C. LIQUID TEMPERATURE RETURNS TO NORMAL COOLNG LEVEL

� D. LSV SOLENOID ENERGIZED (VALVE CLOSES)

� E. DSV SOLENOID ENERGIZED, VALVE OPENS

� 7. WITH UNIT IN DEHUMID MODE CLOSE W1COMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE−ENERGIZED

� 8. OPEN W1 RESTORE UNIT TO DEHUMID MODE

� 9. OPEN HUMIDISTAT INPUTCOMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE−ENERGIZED

� 10. RESTORE SETPOINTS FOR THERMOSTAT AND HUMIDISTAT

REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS

Copyright 2015 International Comfort ProductsLewisburg, TN 37091 USA