A8205A
04/16
Copyright 2016, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Reproduction in whole or in part without the express written permission of Sargent Manufacturing Company is prohibited.
Warning 1 Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Industry Canada: This Class B digital apparatus meets all requirements of the Canadian Interference Causing Equipment Regulations. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Cet appareillage numérique de la classe B répond à toutes les exigences de l’interférence canadienne causant des règlements d’équipement. L’opération est sujette aux deux conditions suivantes: (1) ce dispositif peut ne pas causer l’interférence nocive, et (2) ce dispositif doit ac-cepter n’importe quelle interférence reçue, y compris l’interférence qui peut causer l’opération peu désirée.
“This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator and your body. This transmitter must not be co-located or operating in con-junction with any other antenna or transmitter.”
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain ap-proved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.
Conformément à la réglementation d’Industrie Canada, le présent émetteur radio peut fonctionner avec une antenne d’un type et d’un gain maximal (ou inférieur) approuvé pour l’émetteur par Industrie Canada. Dans le but de réduire les risques de brouillage radioélectrique à l’intention des autres utilisateurs, il faut choisir le type d’antenne et son gain de sorte que la puissance isotrope rayonnée équivalente (p.i.r.e.) ne dépasse pas l’intensité nécessaire à l’établissement d’une communication satisfaisante.
Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening, and SARGENT Manufactur-ing makes no representations or warranties concerning what such impact may be in any specific situation. When retrofitting any portion of an existing fire rated opening, or specifying and installing a new fire-rated opening, please consult with a code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
FCC
To avoid possible damage from electrostatic discharge (ESD), some basic precautions should be used when handling electronic components:
• Minimize build-up of static by touching and/or maintaining contact with unpainted metal surfaces such as door hinges, latches, and mounting plates especially when mounting electronic components such as readers and controllers onto the door.
• Leave components (reader and controller) protected in their respective anti-static bags until ready for installation
• Do not touch pins, leads or solder connections on the circuit boards
• Key override standard with 8977 [#46 (1-3/4”) mortise cylinder supplied]
Hardware Specifications3
Electronic Specifications4
• Complete lockset with on-board memory
• multiCLASS SE reader and/or keypad
• ADA compliant
• Outside lever is unlocked through access control credentials only
• May be used for indoor and outdoor applications
• Exit Device always allows immediate egress
• UL Listed for panic and available UL Listed for fire-rated openings (12- option)
• SARGENT exit devices furnished for 1-3/4” standard (specify 31- and thickness for thicker doors)
• ANSI/BHMA A156.25 Listed Grade 1 Compliant
• Available with ET Trim only (many lever designs available)
The SARGENT IN220 Exit device combines superior aesthetics with the energy efficiency and streamlined architecture of Power-over-Ethernet (PoE) access control. PoE-enabled access control allows facilities to leverage existing network infrastructure for enhanced security and easier, more cost-effective installations. Featuring multiCLASS SE® technology, it supports multiple credential types, including mobile devices, for a future-proof solution that is convenient and secure.
NOTE: A weather-protective gasket is required for outdoor applications.
*UL testing was conducted on product powered by UL Listed model 9001GR/AC injector; manufactured by Microsemi Corp.
• Input Power: PoE Class 1 Device, as defined by IEEE 802.3af, requires less than 3.84 watts over structured cabling
• Multiple time zone and holiday access scheduling
• First-in unlock or automatic unlock configu-ration, based on specified time schedule
• 2,400 users per lock; 10,000 event audit trail
• Privacy button
• Power Requirements: 55VDC, 90mA
• HID® multiCLASS SE® technology offers support for the following credentials:• 2.4 GHz credential compatibility:
A. PoE frame harness assemblyB. PoE data hinge from McKinney (patent pending)C. PoE door harness* from McKinneyD. IN220 PoE Lock E. DPS: Door Position Switch (Needed on Cylindrical and Exits only) * Door width determines length
Components and wire harness supplied by McKinney. Suggested installation:
RJ45-M
Molex-M
Cabl
e: C
at 5
e or
hig
her
24 A
WG
, 10
0ohm
B-Splice Crimp Connector
Ceiling
Supplied by CI
Cut end / ceiling-side PoE harness:
TIA/EIA 568-B Standard Wiring
1 2 3 4 5 6 7 8
Do not confuse pair numbers with pin numbers. A pair number is used for reference only (eg: 10BaseT Ethernet uses pairs 2 & 3). The pin numbers indicate actual physical locations on the plug and jack.
Frame-SideHarness
Assembly(15' length)
24AWG Stranded
Drain Wire for
Earth Ground in 15' Frame
Harness
Cable drain wire
concealed in shrink tubing
Frame Harness Installation
1. Feed cut end of harness into hole on hinge-side through single access hole.
2. Push one connector back through the hole and feed into the other access hole.Each of the hinge-side harness connectors should end up threaded through a different access hole and matched to the same size pin connector from the door harness:
NOTE: Exit chassis harness consists of a 6-pin female connector and two different-sized ground lugs (Fig. 3A)
1. Feed 6-pin connector and larger ground lug straight through to outside of door (Fig. 3A, B) while feeding smaller ground lug into wire hole, up through wire channel and out through inside of door (Fig. 3C).
DO NOT PINCH THE WIRE HARNESS.
2. Begin to secure the exit chassis with through bolts to the ET trim using (2) 1/4 -20 x 2-3/8” flat head machine screws.
Inside of Door
(2) 1/4 x 2-3/8”Flathead MachineScrews (secures ET)
1. Tuck excess cable into wire hole on inside of door.
2. Secure the mounting assembly while ensuring proper alignment of outside reader and fully tighten the (2) through- bolts on the inside of the door to secure the reader and plate to the door.
Secure the following connectors to their respective terminals (Fig. 10A, B):
A. Secure the 4-pin DPS connector.
B. Secure the 10-pin lock body assembly connector.
CAUTION - Do not touch or allow debris to enter connector contacts.
Secure Mounting Plate
IMPORTANT: Do not run wires through bottom hole in plate (Fig. 10A, B) - it will damage wires and the controller connector. Route wires around flange, do not route wires through the flange hole (Fig. 10B).
C. Secure the 24-pin card reader connector (Fig. 10B).
10 Installation of Connectors
D. Crimp* RJ45 to Cat 5e cable from hinge (Fig. 10C).
*For more detail, refer to section (5) ‘Installation Wiring’, “A - Frame Harness Installation”.
Ground Lugs
DPS (4-pin)A
Lock Body (10-pin)
Fig. 10A
B
Reader (24-pin)
Board-to-Board Connector
Fig. 10B
TIA/EIA 568-B Standard Wiring
1 2 3 4 5 6 7 8
Do not confuse pair numbers with pin numbers. A pair number is used for reference only (eg: 10BaseT Ethernet uses pairs 2 & 3). The pin numbers indicate actual physical locations on the plug and jack.
1. Insert top tabs of controller into slots on mounting plate (Fig. 11A).
2. Ensure proper alignment of board-to-board connectors while pivoting bottom of controller toward door until tab on bottom snaps securely into place on mounting plate.
CAUTION: To avoid possible damage to board-to-board connectors, care should be taken when securing controller to mounting plate. If there is resistance when securing, detach controller to determine cause before re-attaching controller.
Fig. 11B
4. Remove pull tab from its position beneath the coin cell by pulling on tab in direction of arrows printed on tab (Fig. 11B).
3. Connect RJ45 male connector to female RJ45 port on controller board (Fig. 11B).
12 Inside Cover Installation1. Assemble cover by hooking top edge on inside mounting plate.2. Carefully press bottom of cover toward door without pinching wires.3. Secure the cover with the security allen wrench.
(2) 1/4 x 2-3/8”Flathead MachineScrews (secures ET)
Exit ChassisFig. 3A
1. Slide mortise lock into door and loosely secure with (2) flat head screws.
NOTE: Exit chassis harness consists of a 6-pin female connector and two different-sized ground lugs (Fig. 3A)
2. Feed 6-pin connector and larger ground lug straight through to outside of door (Fig. 3A, B) while feeding smaller ground lug into wire hole, up through wire channel and out through inside of door (Fig. 3A).
DO NOT PINCH THE WIRE HARNESS.
3. Begin to secure the exit chassis with through bolts to the ET trim using (2) 1/4 -20 x 2-3/8” flat head machine screws.
1. Tuck excess cable into wire hole on inside of door.
2. Secure the mounting assembly while ensuring proper alignment of outside reader and fully tighten the (2) through- bolts on the inside of the door to secure the reader and plate to the door.
Secure the following connectors to their respective terminals (Fig. 9A, B):
A. Secure the 4-pin DPS connector.
B. Secure the 10-pin lock body assembly connector.
CAUTION - Do not touch or allow debris to enter connector contacts.
Secure Mounting Plate
IMPORTANT: Do not run wires through bottom hole in plate (Fig. 9A, B) - it will damage wires and the controller connector. Route wires around flange, do not route wires through the flange hole (Fig. 9B).
C. Secure the 24-pin card reader connector (Fig. 9B).
9 Installation of Connectors
D. Crimp* RJ45 to Cat 5e cable from hinge (Fig. 9C).
*For more detail, refer to section (5) ‘Installation Wiring’, “A - Frame Harness Installation”.
Ground Lugs
DPS (4-pin)A
Lock Body (10-pin)
Fig. 9A
B
Reader (24-pin)
Board-to-Board Connector
Fig. 9B
TIA/EIA 568-B Standard Wiring
1 2 3 4 5 6 7 8
Do not confuse pair numbers with pin numbers. A pair number is used for reference only (eg: 10BaseT Ethernet uses pairs 2 & 3). The pin numbers indicate actual physical locations on the plug and jack.
10 Installation of Inside Component Assembly 1. Insert top tabs of controller into slots on mounting plate (Fig. 10A, B).
2. Ensure proper alignment of board-to-board connectors while pivoting bottom of controller toward door until tab on bottom snaps securely into place on mounting plate.
CAUTION: To avoid possible damage to board-to-board connectors, care should be taken when securing controller to mounting plate. If there is resistance when securing, detach controller to determine cause before re-attaching controller.
Fig. 10B
4. Remove pull tab from its position beneath the coin cell by pulling on tab in direction of arrows printed on tab (Fig. 10B).
3. Connect RJ45 male connector to female RJ45 port on controller board (Fig. 10B).
12 Inside Cover Installation1. Assemble cover by hooking top edge on inside mounting plate.2. Carefully press bottom of cover toward door without pinching wires.3. Secure the cover with the security allen wrench.
Inside Cover
Inside of Door
Security Allen Screw
1. Retrieve harness from end of rail. Note: Harness has limited travel and can be damaged.
2. Attach harness to female connector on chassis.
3. Install rail and screws per exit device instructions. Note: This view shows rim exit device version.
Operational Check 9 IMPORTANT: Be sure to test functions prior to closing door.In all cases, perform the following checks:1. Ensure that inside lever retracts latch.
• For units with cylinders, the following checks apply:Insert key into cylinder and rotate:a. There should be no friction against lock case or any other
obstructions. If friction or binding occurs, re-adjust cylinder to eliminate issues.
b. The key should retract the latch and the key should rotate freely.c. The key should extend and retract the deadbolt.
• For units without a keypad, add card using LCT software* and test. • For units with a keypad, add pin and card using LCT software* and test.
2. LED signaling:• After using a valid credential, a green flash followed by three fast
amber flashes indicates a low power condition. • Check the input voltage. • If the input voltage is low, disconnect the lock from the power source
and check the power source voltage. If the power source voltage is correct, inspect the lock wiring for a possible short.
If the lock loses power, it will flash rapid blue for approximately one minute. Lock will default to programmed fail safe or fail secure.
After that, the lock will no longer be functional.3. When you have completed the tests, close the door, ensuring latchbolt fully
extends into strike plate without binding.
*Refer to Network and Lock Configuration Tool user manual (WFMN1) for information on how to configure and program locks.
HID and iCLASS are registered trademarks of HID Global Corporation.
Founded in the early 1800s, SARGENT® is a market leader in locksets, cylinders, door closers, exit devices,electro-mechanical products and access control systems for new construction, renovation, and replacement applications.The company’s customer base includes commercial construction, institutional, and industrial markets.