Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational SchemesScott Dahman, P.E., IEEE member

PowerWorld Corporation

1

Page 2: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• Modern methods model GIC as DC voltage sources in transmission lines

• With pertinent parameters, GIC computation is a straightforward linear calculation

GIC Modeling

Page 3: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• The dc GICs are superimposed upon the ac currents.  In transformers this can push the flux into saturation for part of the ac cycle

• This can cause large harmonics; in the positive sequence(e.g., power flow and transient stability) these harmonics can be represented by increased reactive power losses on the transformer.  

Transformer Saturation and Losses

Image Source: Craig Stiegemeier, JASON Presentation, June 2011

Page 4: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

NERC Planning Requirements• Vulnerability Assessment of the system for its ability to withstand a Benchmark GMD Event without causing a wide area blackout, voltage collapse, or damage to transformers

• Transformer thermal impact assessment to ensure that all high‐side, wye grounded transformers connected at 200kV or higher will not overheat based on the Benchmark GMD Event

4

Source: North American Electric Reliability Corporation, TPL-007-1 Technical Conference, July 2014

Page 5: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• A large GMD could substantially affect power system flows and voltages

• Studies allow for testing various mitigation strategies– Operational mitigation could include redispatching generation to avoid long distance power transfers and reducing transformer loading values, and opening devices to limit GIC flows

– Longer‐term strategies could include installation of GIC blocking devices (such as capacitors) on transformer neutrals and/or series capacitor compensation on long transmission lines

Power System Planning for GMD

Page 6: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

GMD‐Induced Voltage Collapse

• We can examine the behavior of the system by stressing the GMD‐induced surface electric field

• As the E‐field increases, GIC transformer reactive power losses increase and system voltages decrease

• We can plot voltage vs. E‐field until reliability criteria are violated or until voltage collapses

6

Page 7: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• Eastern Interconnect power flow model, peak load conditions

• NOTE: The examples that follow contain no specific parameters for transformers or substation grounding resistance; results are hypothetical and for illustration only

Uniform Electric Field Example

Page 8: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• Examine GIC transformer reactive power losses at constant E‐field magnitude at various orientations

• Worst‐case for this system is 75 degrees

Worst‐Case E‐field Orientation

Page 9: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

GIC Q‐V Curve• Plot bus voltage vs. E‐field to examine the effect of increasing GIC transformer reactive power losses

0.86

0.87

0.88

0.89

0.90

0.91

0.92

0.93

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0

Volta

ge at Low

est  pu

 Voltage Bus, 230kV

+ Nom

inal

Field Strength (V/km)

Page 10: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

Increasing E‐Field Magnitude:Wide‐Area AC Bus Voltage Drop Contour

2 V/km 3 V/km

4 V/km 5 V/km

Page 11: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

Mitigation for Voltage Collapse

• Transformer neutral blocking– Placing capacitive or resistive device in series with the transformer neutral to effectively create an open circuit for quasi‐DC GIC currents

• Opening transmission lines or transformers 

11

Page 12: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

Transformer GIC Sensitivities• The sensitivity of a transformer’s effective GIC current with respect to the GIC E‐field on transmission lines may be expressed as [1]

12

Effective,r,r T r

T

dId

-1= C G B SE• where 

– Cr is a column vector of conductances for transformer r,– G is the real GIC DC bus admittance matrix,– and B is the transmission line conductance‐distance matrix

• This is a fast computation due to the sparsity of the vector and matrices in the sensitivity calculation

• A small number of nearby transmission facilities are often responsible for a large percentage of GIC in transformers

[1] T. J. Overbye, K. S. Shetye, T. R. Hutchins, Q. Qiu, J. D. Weber, “Power Grid Sensitivity Analysis of Geomagnetically Induced Currents,” IEEE Trans. on Power Systems, vol. 28, no.4, pp. 4821-4828, November 2013.

Page 13: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• Applying this analysis to the Eastern Interconnect example to the set of transformers in the substation with the greatest GIC Mvar losses

Transformer GIC Sensitivities

Four lines are responsible for 75% of the transformer GIC; opening some or all of these lines can be an effective mitigation strategy for off-peak load conditions

Page 14: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

• Blocking the neutrals of transformers with the highest GIC neutral currents can reduce GIC Mvar losses and improve performance

• Neutral blocking in one transformer can often lead to increases in GIC flow in nearby transformers

• It is assumed that neutral blocking would be applied to all transformers in a substation in which any transformer is blocked

Transformer Neutral Blocking

Page 15: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

Greedy Neutral Blocking Heuristic• Do until n substations protected

– Place neutral blocking on all transformers in the msubstations with the greatest sum of transformer neutral GIC

– Recalculate GIC flows• Repeat

• Can also use other criteria for blocking selection:– transformer effective GIC current– transformer GIC Mvar loss– changes in bus voltage or dV/dQ sensitivity– reactive power reserve margin (for generator substations)

15

Page 16: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

Eastern Interconnect Example• Perform with m=5; first 2 iterations:

16

Iteration Substation Neutral Amps Mvar Losses

1 Conemaugh 500 160 62

1 Keystone 500 140 66

1 Cuthbert 138 108 8

1 Sunbury 500 98 17

1 Dickerson 230 95 8

2 A29 500 88 35

2 Three Mile Island 500 88 34

2 New Freedom 500 87 44

2 Steel City 500 85 24

2 Juniata 500 85 36

Page 17: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

GIC Q‐V Curves with Blocking17

0.85

0.86

0.87

0.88

0.89

0.90

0.91

0.92

0.93

0.0 2.0 4.0 6.0 8.0 10.0

Volta

ge at Low

est  pu

 Voltage Bus, 230kV

+ Nom

inal

Field Strength (V/km)

Base

5 Substations

10 Substations

15 Substations

20 Substations

25 Substations

Voltage collapse margin improves from 6.0 V/km to 9.1 V/km

Page 18: Improving GMD Induced Power System Voltage Stability with and ... · Improving GMD‐Induced Power System Voltage Stability with Transformer Neutral Blocking and Operational Schemes

Opportunities for Future Work

• Examine sensitivity of transformer GIC effective current to transformer neutral blocking– Analogous to line outage distribution factors (LODF) used in AC power flow and contingency analysis

• Combine these with bus voltage sensitivities to develop better blocking algorithms

18