Top Banner
GERAN Installation Base Transceiver Station Equipment IMN:BS 21 A50016-G5100-A364-01-7631
55
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • GERAN

    InstallationBase Transceiver Station Equipment

    IMN:BS 21

    A50016-G5100-A364-01-7631

  • 2 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fce

    f Important Notice on Product SafetyDANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION INSTRUCTIONS.The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the system must comply with the applicable safety standards.Hazardous voltages are present at the AC power supply lines in this electrical equipment. Some components may also have high operating temperatures.Failure to observe and follow all installation and safety instructions can result in serious personal injury or property damage.Therefore, only trained and qualified personnel may install and maintain the system.

    The same text in German:Wichtiger Hinweis zur ProduktsicherheitLEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.In diesen Anlagen stehen die Netzversorgungsleitungen unter gefhrlicher Spannung. Einige Komponenten knnen auch eine hohe Betriebstemperatur aufweisen.Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Krperverletzungen oder Sachschden fhren.Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

    Caution:This equipment has been tested and found to comply with EN 301489. Its class of conformity is defined in table A30808-X3247-X910-*-7618, which is shipped with each product. This class also corresponds to the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor-dance with the relevant standards referenced in the manual Guide to Documentation, may cause harmful inter-ference to radio communications.For system installations it is strictly required to choose all installation sites according to national and local require-ments concerning construction rules and static load capacities of buildings and roofs.For all sites, in particular in residential areas it is mandatory to observe all respectively applicable electromagnetic field / force (EMF) limits. Otherwise harmful personal interference is possible.

    Trademarks:All designations used in this document can be trademarks, the use of which by third parties for their own purposes could violate the rights of their owners.

    Copyright (C) Siemens AG 2006Issued by the Communications GroupHofmannstrae 51D-81359 Mnchen

    Technical modifications possible.Technical specifications and features are binding only insofar as they are specifically and expressly agreed upon in a written contract.

    Copyright (C) Siemens AG 2006Issued by the Communications GroupHofmannstrae 51D-81359 Mnchen

    Technical modifications possible.Technical specifications and features are binding only insofar as they are specifically and expressly agreed upon in a written contract.

  • A50016-G5100-A364-01-7631

    3

    IMN:BS 21

    Id:0900d80580070fce

    Table of ContentsThis document has 55 pages.

    Reason for Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1 Purpose of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.2 Tasks of the Base Transceiver Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.3 Standard Technical Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.4 Types of Base Transceiver Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.5 Installation Prerequisites. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.6 Handling of the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.7 Installation Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.8 Ancilliary Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    2 BS 21 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.1 Position in the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.2 Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.2.1 Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132.3 Site Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132.4 Construction View of the BS 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142.5 Equipment Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.5.1 Transportation, Loading and Unloading of the BS 21 . . . . . . . . . . . . . . . . . 152.6 Mounting of the BS 21 Shelter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.7 Security Features and Door Opening Procedures . . . . . . . . . . . . . . . . . . . 172.8 External Cabling Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.8.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.8.2 Ground and Power Supply Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . 202.8.2.1 Connecting of the BS21E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222.8.2.2 Connecting of the BS21U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232.8.3 Requirements for External Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252.8.4 Abis-Interface - PCM Link Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262.8.4.1 Abis-Interface for 120 Ohm Cable Impedance . . . . . . . . . . . . . . . . . . . . . . 262.8.4.2 Abis-Interface for 75 Ohm Cable Impedance . . . . . . . . . . . . . . . . . . . . . . . 282.8.4.3 Abis-Interface without OVPT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292.8.5 Serial Interface - Signalling Link Terminal . . . . . . . . . . . . . . . . . . . . . . . . . 302.8.6 Shelter Alarm Interface - Signalling Link Terminal . . . . . . . . . . . . . . . . . . . 312.8.7 Operator Alarm Interface - Signaling Link Terminal . . . . . . . . . . . . . . . . . . 322.8.8 Local Maintenance Terminal (LMT) Interface . . . . . . . . . . . . . . . . . . . . . . . 342.9 Board Insert Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342.9.1 Mounting Position of Boards and Modules . . . . . . . . . . . . . . . . . . . . . . . . . 352.9.2 Transmission Equipment located outside the BS21 . . . . . . . . . . . . . . . . . . 372.9.3 Transmission Equipment inside the BS21 . . . . . . . . . . . . . . . . . . . . . . . . . 372.9.3.1 Installation of Microwave Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372.9.3.2 Installation of NTPM or CSU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 382.10 System Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392.10.1 Duplex Combiner Kit (DUKIT) - RXAMCO . . . . . . . . . . . . . . . . . . . . . . . . . 392.10.2 RXAMCO - TPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

  • 4 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fce

    2.10.3 TPU - PA Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422.10.4 PA - DUKIT Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432.11 Antenna Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442.11.1 Transmit/Receive Antenna Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 442.11.2 Receive Antenna Connections (diversity) . . . . . . . . . . . . . . . . . . . . . . . . . . 452.11.3 Identification of Antenna Feeder Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 452.11.4 Mounting of the Cabel Entry Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462.12 Rack Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472.12.1 Connections between the Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 482.13 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512.13.1 Spare parts for BS 21E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512.13.2 Spare Parts for BS 21U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532.14 Post Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542.14.1 Disposal of Electrical and Electronic Equipment . . . . . . . . . . . . . . . . . . . . . 55

  • A50016-G5100-A364-01-7631

    5

    IMN:BS 21

    Id:0900d80580070fce

    List of FiguresFigure 1 ESD Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 2 Position of the BS21 within the SBS . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 3 BS21 site configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 4 Front view of the BS 21 (without front door) . . . . . . . . . . . . . . . . . . . . . 14Figure 5 Drilling template for BS 21 mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 6 EMI- panel BS21E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Figure 7 EMI-panel BS21U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Figure 8 Cable entry BS 21, cable assignment and max. diameter . . . . . . . . . . . 20Figure 9 Ground- and power supply connections of BS21E (example) . . . . . . . . 21Figure 10 Ground- and power supply connections of BS21U . . . . . . . . . . . . . . . . 22Figure 11 Screw terminal for connecting of external backup batteries . . . . . . . . . 23Figure 12 WAGO terminal block for AC and DC power supply . . . . . . . . . . . . . . . 24Figure 13 OVPT with terminal block (120 Ohm) . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 14 OVPT with SMA connectors (75 Ohm) . . . . . . . . . . . . . . . . . . . . . . . . . 28Figure 15 Preparation of 75 Ohm coaxial cable. . . . . . . . . . . . . . . . . . . . . . . . . . . 29Figure 16 Location of the code keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Figure 17 BS 21, full equipped with mounting unit numbering. . . . . . . . . . . . . . . . 36Figure 18 Abis connection with external transmission equipment . . . . . . . . . . . . . 37Figure 19 Abis connection with internal microwave . . . . . . . . . . . . . . . . . . . . . . . . 38Figure 20 Abis connection with internal NTPM or CSU . . . . . . . . . . . . . . . . . . . . . 38Figure 21 System cabling BS 21, overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Figure 22 DUKIT - RXAMCO connections (incl. diversity) . . . . . . . . . . . . . . . . . . . 40Figure 23 Cable routes for RXAMCO - TPU connections (incl. diversity) . . . . . . . 41Figure 24 Cable routes for TPU - PA connections. . . . . . . . . . . . . . . . . . . . . . . . . 42Figure 25 Cable routes for PA - DUKIT connections . . . . . . . . . . . . . . . . . . . . . . . 43Figure 26 Antenna cabling BS 21 (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Figure 27 Cell numbering (top view to the antenna pole) . . . . . . . . . . . . . . . . . . . 46Figure 28 Mounting of the cable entry cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Figure 29 Minimum site dimensions for BS21 rack extension . . . . . . . . . . . . . . . . 48Figure 30 Jumper cable connections between the BS21 racks . . . . . . . . . . . . . . . 49

  • 6 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fce

    List of TablesTable 1 Pinning of the 120 V AC terminal block . . . . . . . . . . . . . . . . . . . . . . . . . 24Table 2 Pinning of the terminal block for connecting external batteries. . . . . . . . 25Table 3 Pinning of Abis-interface (OVPT 120 Ohm) . . . . . . . . . . . . . . . . . . . . . . 27Table 4 Pinning of PCM line monitoring interface (SUB-D9,female) . . . . . . . . . . 28Table 5 Pinning of the Abis-interface cable without OVPT (SubD 25 connector) 29Table 6 Pinning of the Serial Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Table 7 Pinning of the shelter alarm interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Table 8 Pinning of the Alarm Connection Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Table 9 Pinning of the operator alarm interface (OAL) . . . . . . . . . . . . . . . . . . . . 33Table 10 Signal meaning, operator alarm interface . . . . . . . . . . . . . . . . . . . . . . . . 33Table 11 Pinning of the LMT interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Table 12 Cover plate dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Table 13 Code keys of RF and core modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Table 14 DUKIT - RXAMCO connections (incl. diversity) . . . . . . . . . . . . . . . . . . . 40Table 15 Routing variants for RXAMCO - TPU connections (incl. diversity) . . . . . 41Table 16 Routing variants for TPU - PA connections . . . . . . . . . . . . . . . . . . . . . . 43Table 17 Routing variants for PA - DUKIT connections. . . . . . . . . . . . . . . . . . . . . 43Table 18 Label colours of antenna feeders for BS61 with DUCOM. . . . . . . . . . . . 45Table 19 Label colours of antenna feeders for BS61 with HYCOM or FICOM . . . 45Table 20 Connections between the racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Table 21 Connections for TX/RX path of extended BS21 . . . . . . . . . . . . . . . . . . . 50

  • A50016-G5100-A364-01-7631

    7

    IMN:BS 21 Reason for Update

    Id:0900d805800d0faf

    Reason for UpdateIssue History

    Issue 01, release-independent, valid with starting Release BR 5.0

    Issue Date SummaryIssue history for this document with order number A30808-X3247-G364-*-76311 01/2000 First issue for external use2 09/2005 Second issue for external use3 10/2005 Third issue for external use4 11/2005 Fourth issue for external useIssue history for this document with order number A50016-G5100-A364-*-763101 11/2006 New document number

  • 8 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d805800d0faf

    Reason for Update

  • A50016-G5100-A364-01-7631

    9

    IMN:BS 21 Introduction

    Id:0900d80580070fa4

    1 Introduction

    1.1 Purpose of the ManualThis document is intended to give information necessary to the installation of the Base Transceiver Stations for the SBS Base Station System (BSS).It contains the description of all steps to install the BTS on site and integrate it into the required infrastructure: Power supply PCM - Network Grounding Receive / transmit antenna system Alarm connections Base constructionsFor installation of equipment not supplied by Siemens (battery chargers, antennas, power supplies,microwave etc.) refer to site specific documentation or vendor instruc-tions provided with other equipment.

    1.2 Tasks of the Base Transceiver StationsThe Base Transceiver Station performs the following main tasks in accordance with the GSM-requirement (D900) or DCS-standards (D1800) or PCS standards (D1900): Provides the RF-link connection to the mobile stations (MS) Supports various cell types (omni and sector cells) Provides the PCM link connection to the Base Station Controller (BSC) via a terres-

    trial line (in this case symmetric pair or coaxial cable is used) or microwave (addi-tional equipment is therefore required)

    Submultiplexing on the Abis-interface

    1.3 Standard Technical Features Full software download capability Full rate and half rate Traffic Channels are supported GSM primary/extended Band ; DCS Band; PCS Band Hybrid combiners, Duplex combiners and Filter combiners for antenna combining

    available Outstanding Rx sensitivity

    !WARNINGThe CE declaration of conformity for the product will be fulfilled if the setup and cabling is undertaken in accordance with the specification in the manual and the documentation listed there, such as mounting instructions, cable lists etc.Where necessary, account should be taken of project-specific documentation. Deviations from the specifications or independent changes during setup, such as use of cable types with lower screening values, for example, can lead to the CE requirements being violatad. In such cases the CE declaration of conformity is invalidated and the responsibility passes to the person who has caused the deviations.

  • 10 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fa4

    Introduction

    16/64 kBit signalling channels and minimised signalling load on Abis LMT-operation with full O&M functionality at a transmission rate of 64 kBit Modular capacity increase of sites

    1.4 Types of Base Transceiver StationsThe Base Transceiver Stations are a modular family of BTS-products and based on the same hardware components: for indoor operation: BS 60 (D900, D1800, D1900): max 6 carrier per rack, serves

    up to 3 cells, max. 6 carrier per cell for indoor operation: BS 20 (D900, D1800): max 2carrier per rack, serves up to 2

    cells, max. 2 carrier per cell for outdoor operation: BS 61 (D900, D1800, D1900): max 6 carrier per rack, serves

    up to 3 cells, max. 6 carrier per cell for outdoor operation: BS 21(D900, D1800,D1900): max 2 carrier per rack, serves

    up to 2 cells, max. 2 carrier per cell for outdoor operation: BS 22(D900, D1800): max 2 carrier per rack, serves up to 2

    cells, max. 2 carrier per cell for indoor and outdoor operation: BS 11 (D900, D1800): max 2 carrier per rack,

    serves up to 2 cells, max. 2 carrier per cell

    1.5 Installation PrerequisitesIt is absolute required that the installer pays attention to the valid EMC instructions.All other equipment on site must be CE designated and must provide interfaces for con-necting of external cables conformable to EMC instructions.

    1.6 Handling of the ModulesAll boards and modules must be handled with extreme care as each one contains elec-trostatically sensitive devices (ESD). The modules are marked with the ESD-label.

    Figure 1 ESD Symbol

    These are sensitive to static discharge.Notice: Avoid handling the modules in a high-static environment When handling the modules, do not touch connector contacts An earthed high-impedance wrist strap must be worn when handling modules. Use the socket at the racks for wrist strap connection. The modules must be transported in appropriate packing

    1.7 Installation ToolsThe correct rack installation is carried out with the aid of the following tools: Standard toolkit for BSS-installation Spirit-level

  • A50016-G5100-A364-01-7631

    11

    IMN:BS 21 Introduction

    Id:0900d80580070fa4

    Plumb bob Torque spanner for SMA connectors (1.0 N/cm) Torque spanner for SMC connectors (0.35 N/cm) Security Bit Set (for outdoor equipment)For installation of power supply, transmission equipment, antennas, cableways and other infrastructure equipment, additional tools could be necessary.

    1.8 Ancilliary MaterialThe following ancilliary materials are needed : plumb line colophony adhesive tape (yellow/green, green, blue, red, orange, white) cable fasteners wire end sleeves for 16 mm copper wires cable lugs M8

  • 12 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2 BS 21 Installation

    2.1 Position in the SystemThe BS21 interconnects the MS via the Um interface with the trunk network via the Abis interface.

    Figure 2 Position of the BS21 within the SBS

    2.2 Site RequirementsPrior to the commencement of the installation, the site must have been prepared as follows: The site specific-base construction must have been mounted. A concrete base of sufficiently large to accommodate shelter size and weight is

    needed for rural sites. The distance between the enclosure sides and vertical faces i.e. walls etc. should

    be restricted to 500 mm minimum.This avoid the risk of air flow restrictions into the cooling system. Adequate clearence should be provisioned in front of the enclosure in order that the shelter door may fully opened. Adequate clearence should be pro-visioned above the BS21 in order that the roof may be suffciently opened for service, maintenance or replacement purposes.

    The installation area should be clear of standing water, fallen leaves, mud and building debris. Check the location for possibility of flood disasters and exessive fall of snow.

    Measurements should be taken against unauthorized access. The lightning and grounding systems must be complete. All installation works of 230 V/120 VAC(BS21E/BS21U) power supply ,including a

    ground fault indicator (GFI/FI) in each phase, must be finished.The BS 21 shelter should be mounted, after all other work to create the required infra-structure (antennas/antenna cabling,PCM lines...) is complete.Note, that the installation of the BS 21U is not allowed without plinth and cable entry cover!

    Um interface

    Abisinterface

    Asubinterface

    Ainterface

    SBS

  • A50016-G5100-A364-01-7631

    13

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.2.1 Environmental ConditionsThe location of a site may directly effect the correct operation of the base station.In terms of exessive salt contamition situations it is recommended not to place the BS21 close to coastal areas in order to avoid necessarily of shorter maintenance intervals. It is recommended to keep a distance of about > 1000 m to coast. Enclosures on coastal sites should not be installed with the right hand side air intakes facing directly into pre-vailing sea winds or spray.Installation under trees and foliage is not recommended due to increased levels of insects etc. which may be drawn into the cooling system by the fans.In areas of much fall of snow the base station should be placed at an socket or at the mast with an appropriate height, so that the air intake (lower grille) will not be blocket by snow.

    In potential areas subject to flooding the base station should not be placed on ground, because the base station is not protected against water ingress on bottom.Sites located close to exessive airborne dust clouds i.e. cement, coal deposits etc. should also be minimised in order to avoid contamination of the cooling system and increased maintenance.The max. open air temperature must not exeed 45C/117F.

    2.3 Site ConfigurationAdditional equipment is necessary for the operation of the BS21 on site.

    Figure 3 BS21 site configuration

    T X / R X Antennas

    BS21

    Antenna feedercables

    230 V AC/50 Hz BS21E120 V AC/60 Hz BS21U

    ground connection

    Microwave equipment *

    PCM lines *

    AC countermain breaker

    external alarm donators ***) dependent on type of network integration

    **) optinal connection

    FI / GFI

  • 14 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2.4 Construction View of the BS 21The BS equipment is housed in the shelter with the dimensions 950 mm x 870mm x 485 mm (HxWxD). The additional plinth (H=100 mm) can be equipped with shock absorbers. The same rack type is used for D900/D1800 and D1900 equipment.Max. 2 carriers can be installed per rack ; this fully equipped BS weighs approx.170 kg (boards and modules 43 kg/ transportation weight inc. plinth 125 kg). The complete equipped enclosure also contains the required transmission equipment, AC/DC converters, backup batteries.The integrated climate control system guarantees proper outdoor operation (temp.range: -45 C - +45 C as per ETSI 4.1E; BS21U up to +47C).The product has been evaluated for protection against water splashed the enclosure from any direction. The product has been evaluated for ingress protection, according to IP 54. Refer to IEC 529 (Degree of Protection Provided by Enclosures) for limitations in outdoor installation.

    Figure 4 Front view of the BS 21 (without front door)

    AIR INLET

    FAN UNIT

    AIR OUTLET

    aco

    ust

    ic a

    ttenn

    ua

    tor

    space reservation fortransmission equipment

    backupbattery

    BBSI

    G

    BBSI

    G

    ALCO

    LI MCL

    KCC

    TRL

    PAPA TPU

    TPU

    GPS

    U

    RXA

    MCO

    RXA

    MCO

    RXA

    MCO

    RXA

    MCO

    DCP

    A

    DCP

    AD

    CTPU

    DCT

    PU

    HEcontrolboard

    DC AC

    0 1 0 0 1 1AC/DCconverters

    0 1

    heatexchanger

    shelter cover

    TX/RX connectorsAC service socketLMT connector

    DUKITconnectionpanel

    Fuse Panel

    plinthshock absorber(optional)

    cable entryblock

  • A50016-G5100-A364-01-7631

    15

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.5 Equipment DeliveryThe shelter and the plinth are delivered mounted on a timber/polyurethan transportation pallet with the overall dimensions 1500 mm x 1300 mm x 700 mm (HxWxD). The pallet is bolted directly to the shelter frame. Bolt holes are located in the framework lower cross-member front and rear, 6 positions. Depending on the pre-installed modules inside the shelter, the pallet can weigh up to approx. 125 kg.The BS21 is suitably protected for transportation using a combination of bubble-wrap/ polystyrene bufferswithin an outer cardboard casing. The individual support plinth is separately packed and than taped on top of the enclosure casing ready for transporting.Additional cartons contain all equipment parts weigh over 1.00 kg:RF modules: Power Amplifiers Transceive Processor Units Power Supply Equipment AC/DC Converters Cabel Entry CoverThe transmission equipment are not content of the delivery.All crates have information printed on them for identification of delivery.Handle each carton containing installation materials with extreme caution to avoid tipping.

    2.5.1 Transportation, Loading and Unloading of the BS 21The shelter crate should be transported on an air-suspensioned truck, equipped with a capable of carrying min.1.0 tonnes payload, 4 WD recommended. For loading and unloading a forklift truck or an articulated tyre crane should be used.Movement of the shelter should be supervised by personnel qualified in heavy lifting and safety. All personnel must be properly attired, wearing a safety helmet, safety boots and protective gloves.To load the shelter onto the transporting vehicle, proceed as follows: Maneuver the forklift truck, with its forks lowered, to the center of the base of the

    shipping crate. When the forklift is in the correct position, an adjustable strap has to be positioned

    around the crate and secured to the forklift mast eyebolts. Pull the strap tight. If the shelter has to be transported without the shipping crate, insert packing

    between the forklift tower and the shelter for protection. Raise the crate until it is at a suitable height to load onto the transporting vehicle. Lower the crate onto the transporting vehicle. Remove the strap and packing. Secure the crate to the transporting vehicle. (This operation is the responsibility of

    the company transporting the crate.)To unload the crate from the vehicle use a tyre crane and proceed with the following steps: Release the straps etc. securing the crate to the transporting vehicle. Maneuver the crane boom into position exactly above the center of the shipping

    crate.

  • 16 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    Wind two lifting straps around crate and the wooden support and hang up the ends at the crane hook.

    Raise the crate to clear the transporting vehicle and lower it to the ground in the vicinity of the base construction or concrete base onto which it is to be located.

    Open the crate and take out the plinth (basement of the shelter). After that remove all packing material protecting the shelter.

    2.6 Mounting of the BS 21 ShelterBefore starting installation , read the following information in the site documentation: the installation point of the shelter, the connection point for AC mains, the connection points to the grounding system, the planned antenna configuration on site, the type of network integration.The basement must be used for fixing the support plinth to a foundation or other types of base construction. The fixing points of the support plinth are located in the bottom return flange and are accessed trough clearence holes in the topface of the plinth.Pro-ceed as follows: Mark the plinth-outline and holes on the foundation/base construction. Using the

    plinth as a template. Drill the 6 holes 14 mm at the marked points. Insert the dowels (concrete base

    only). Secure the plinth to the foundation/base construction with six M8 bolts and washers.

    Check the correct horizontal position of the plinth, using the spirit level. The tensile strength of the bolts must be not less than 64 kp/mm2.

    Lift or slide the rack carefully off the base of the shipping crate. Lift the shelter on to the fixed plinth. Open the front door of the shelter. Fix the shelter to the plinth.Insert the five M 6 screws through the holes at the shelter

    base into the tapped holes of the plinth and tighten the screws with a socket wrench.

    22 22

    2222

    100

    100

    435870

    485

    15/ 35

  • A50016-G5100-A364-01-7631

    17

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Figure 5 Drilling template for BS 21 mounting

    2.7 Security Features and Door Opening ProceduresAll exterior fixings for the BS21 are hex headed pin-torque bolts. Removal of these requires an appropriate hex pin-torque driver. Cabinet roof fixings are all accessed from inside the enclosure. The left-hand roof hinge is reversed to prevent illicit removal of the roof assembly.Each of the cabinet doors utilises a 3 point bar locking system, which secures the doors in the top, center and bottom position. The locking of the door is achieved via an EMKA Euro Cylinder. 3 off EMKA Euro Cylinder keys are supplied suitably bagged-up and tapped within the cabinet.Further an EMKA angled 8 mm drive key for operation of the 3 point bar locking system is supplied suitably bagged-up and tapped within the cabinet.A door locking alarm system is fitted to both doors and will trigger a remote alarm should the doors be opened in any manner other than that for which they were designed. The alarm system gives warning of doors in closed or open position.The locking mechanism of the cabinet has a factory fitted posi-head self-tapping security screw in place, which ensures that the cabinet cannot be inadvertently locked with the cylinder keys inside, either during factory build, transportation or installation.The opening of the doors is as follows: Insert the 8 mm square drive key and the Euro Cylinder key. Turn Cylinder key 1/2 turn clockwise to the spring position (resistance against the

    key) Holding the Cylinder key on the spring, turn the 8mm square drive key 1/4 turn clock-

    wise - this operates the 3 point bar locking system. Release the Euro Cylinder key.The closing of the doors is as follows: Turn the 8mm square drive key 1/4 turn anti-clockwise (this moves the 3 point bar

    locking system to the locked position). Ensure that the locking bar has correctly engaged behind the top and bottom

    keepers. Turn the Euro Cylinder key 1/2 turn anti-clockwise and remove.

    2.8 External Cabling Activities

    2.8.1 OverviewThis chapter provides information required for installing the external cables between the BS 21 and the infrastructure equipment.

    The rack cannot function without the following cable connections:- CEE socket => connection point of 230 V AC (BS21E)

    WAGO terminal block => connection point of 120 V AC (BS21U)- ground bolt => foundation grounding system

  • 18 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    All interfaces are located at the EMI-panel, accessible after removing of the top of the shelter, except the ground screws. The cable entry on the left is the access for all external cables.Note (for installation of the BS21U only): Before starting installation of Data Circuits and External Interconnection Cables pay attention to the 1996 NEC, Section 725-41(a)(4). This document will consider ITE Limited Power Sources equivalent to NEC Class 2 sources for purposes of applying Article 725 wiring requirements. If data circuits could not use Article 725 wiring methods, then they would have to comply with the require-ments in Chapter 1 thru 4 of the NEC.Transient voltage surge surpression and primary protectors are not required at the entry of the wiring to the BS21U if the exposed wiring is limited to less or equal 140 feet. Refer to NEC Article 725 c) and 800-30 for proper clearance of data wiring from power and lightning conductors. The corresponding Canadian Electric Codes (CEC) sections to NEC 800-30 are CEC 60-200 and 60-202. The corresponding CEC sections to NEC 725c) are CEC 16-200 thru 16-256.Refer before starting the installation of the antenna connections to NEC Article 810. The corresponding CEC Articles to NEC 810 is Section 54.Removal of the roof the shelter is as follows: With shelter door open,release the 3-off roof retaining screws. Open the roof and release the earth cable. Undo the screws securing the right-hand hinge of the roof. Slide roof off left-hand hinge. Remove hinges from roof and swap to opposite side (fixing points already provi-

    sioned).Fit only left-hand hinge to roof.After all external cable connections are installed, for re-fitting of the roof proceed in the following steps: Slide roof hinge onto enclosure left-hand hinge pin. Slide second roof hinge onto right-hand hinge pin. Secure right-hand hinge to roof panel 2-off M5 x 16mm fixings. Re-fit earth cable.

    - Abis interface => PCM links (if NTPMs or CSU are installed)- microwave indoor units => W-outdoor units (if W-equipment is

    installed)- transmit/receive antenna con-

    nectors=> transmit/receive antennas

    optional:- serial interface => signalling link terminal- external alarm interface => external alarm donators- receive antenna connectors => receive antennas (in case of antenna diver-

    sity)- external backup batteries => terminal block (BS21E)

    external backup batteries => WAGO terminal block (BS21U)

  • A50016-G5100-A364-01-7631

    19

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Close roof and secure in 3 positions.

    Figure 6 EMI- panel BS21E

    Figure 7 EMI-panel BS21U

    Before installing the external cables and the cable entry cover will be used, mount the brackets and the cable holders at the lefthand side panel of the shelter as described in section 2.11.4. of this manual. After that prepare the cable entry in the following stages: Release 8-off fixings securing the top of the cable entry assembly (4-off M5 x 70mm

    and 4-off M5 x 45mm). Take note of the positioning of the cable entry blanking plugs.

    Serial Interface (SI)plate for microwave connectors

    CEE socket 230 V AC 16 A

    OvervoltageProtectionANT 0

    ANT 1

    ANTDIV 0

    ANTDIV 1

    transmit/receive antenna

    connectors

    receive antennas(diversity)

    Abis Interface

    cable accessfront side

    rear side

    terminal block for external battery

    tracing interface for Abis-lines

    stripes for extension cabling

    Operator Alarm Interface with ACK*

    hole for optical fibre cable

    Serial Interface (SI)tracing interfaces for Abis lines

    OvervoltageProtection

    Abis Interface

    cable access clamps for external battery

    stripes for extension cabling

    PE-plate

    ANTDIV 1

    ANTDIV 0

    ANT 0

    ANT 1

    transmit/receive antennaconnectors

    ground screw for top-cover

    transmit/receive antennasconnectors (diversity)

    ground screw for top-cover

    *) Alarm Connection Kitclamps for power supply cable

    Operator Alarm Interface with ACK*

  • 20 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    Slip off the sealing rings and slip them on the cables. If the cables have a smaller diameter, increase the diameter by a tape to the cut out size

    Retain all parts for the later installation. Arrange the cables during in accordance of figure 2.7. After cable installation is finished, setup the top and secure it in place using 8-off

    fixings (4-off M5 x 70mm and 4-off M5 x 45mm).If the external cabling must be fitted into the shelter from right-hand side, the cable entry assembly must be moved to the opposite side of shelters top: Release 8-off fixings securing the top of the cable entry assembly (4-off M5 x 70mm

    and 4-off M5 x 45mm) Take note of the positioning of the cable entry blanking plugs. Release 8-off fixings securing the base of the cable entry assembly (8-off M5 x

    45mm) and carefully remove from the shelter. Position cable entry base to shelter right-hand side and secure using 8-off fixings (8-

    off M5 x 45mm). Ensure cabling entry blanking plugs of unused fittings located in correct positions. After cable installation is finished, proceed for setup of cable entry assembly top part

    as described above.

    Figure 8 Cable entry BS 21, cable assignment and max. diameter

    2.8.2 Ground and Power Supply ConnectionsA mains cable, equipped with a 3-pole CEE plug,DIN 49462/ VDE 0623, is required for connecting the BS21E to the connection point of the 230 V AC/ 50 Hz/10 A power supply or the (optional) junction box.The AC supply of the BS21U is based on a 2 phase system (120 V AC/ 60 Hz/20 A). The incoming mains cable must be connected at the 5 pin WAGO terminal block, located on the EMI panel. To disconnect the BS21U from mains in case of falscurrent earth fault, a UL Listed 20A ground fault indicator (GFI) have to be installed externally for each phase. For the same purpose is a 16 A false current protection switch (FI) needed for the BS21E. Use copper conductors for all AC power lines! Diameter/resistance of wires

    microwave antenna, d= 14,5 mmmicrowave antenna, d= 11,0 mmtransmit/receive antenna, d= 17,0 mm

    Abis cable d= 11,0 mmexternal backup battery d= 14,5 mmAC power cable d= 14,5 mmserial interface cable d= 11,0 mmoperator alarm cable d= 11,0 mm

    front side rear side

  • A50016-G5100-A364-01-7631

    21

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    depend on length of AC connection according to VDE 0100 in order to ensure correct interworking of external false current protection switch device and lightning protection device.If the cable type must be changed (main cable in ground / flexible connecting cable), a junction box equipped with screw terminals should be used. The cable end which have to be connected to the terminals must be equipped with wire end sleeves.Before starting connection procedure of the base station, check that no voltage is present at the AC mains cable! Make sure that the main breaker are switched off and unauthorised switching activities are impossible to do!This warning must appear in the original German text:Vor Anschlu des 230 V Einspeisungskabels ist sicherzustellen, da das Kabel span-nungsfrei ist. Die Hauptsicherungen sind zu unterbrechen. Es sind geeignete Manah-men gegen unbefugtes Einschalten der Netzspannung zu treffen.The following figures are intended to give an overview of the power supply and ground connections of BS21E/BS21U.

    Figure 9 Ground- and power supply connections of BS21E (example)

    junction boxwith screw terminals

    AC counter/main breaker

    16 A + FI

    external batteries

    (optional)

    (optional)

    BS 21Edistance 2,00 m : NYCY 3x1,5 RE/2,5

    NYCY 3x4RE/4

    NYCW Y 2x10/RE 10

    distance < 2 ,00 m :

    48 V DC

    230 V AC

    H07V-R 16 m m2

    (in metal conduit or cable raceway)

    battery plus poleconnectedto ground

  • 22 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    Figure 10 Ground- and power supply connections of BS21U

    2.8.2.1 Connecting of the BS21ETo connect the BS 21E shelter with the AC mains connection point proceed in following steps: Open the top cover. Refer to the site documentation for the required information about type and location

    of the 230 V AC connection point. Check the actual distance between CEE socket and the connection point. Cut the cable to the required length. Fix a 3-pole/16A CEE plug at the end, that is to be connected to the mains input.

    Follow the assembly instructions for the plug and the handling instructions for the cable which has to be used.

    Lead the prepared cable through the cable entry at the top of the shelter. Insert the plug into the CEE socket. Lead the main cable to the connection point for 230 V AC.Note that the type and location of the mains connection point are subject to modification. They are dependent on site and customer requirements. A description of the connecting procedure does not form part of this manual. In any case the shelter must be protected by a 16A main breaker. For further information refer to the site documentation and use the corresponding manufacturer documents.The BS 21E shelter must be connected to the ground system in accordance to IEC 1024-1 and VDE 0185. For this purpose a ground bolt M8 located at the right- hand side panel is provided. Depending on the site construction (e.g. steel frame for roof-top instal-lation, concrete foundation for rural sites), the shelter has to be connected directly to the ground system or via a short ground jumper. If 16 mm copper wire (e.g. PVC-wire H07V-R 16 yellow/green) should be used, the distance must be less than 2 metres.

    external batteries(optional)

    BS 21U

    NYCW Y 2x10/RE 10

    distance < 2 ,00 m :

    H07V-R 16 m m2

    L1,L2,N,PE

    120 V ACAC counter

    distance < 2,00 m :H05RR-F 4 G2,5distance > 2,00m : NYCY 4 x 2,5RE/2,5

    2x ground fault indicator 20 A

    (in metal conduit or cable raceway)

    battery plus poleconnected toground

  • A50016-G5100-A364-01-7631

    23

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Connect the BS 21E shelter and ground system as follows: Use the nearest connection points of the ground system. Ascertain the distances between the connection point of the ground system and the

    ground bolt of the shelter. Cut the cables to the required length. Remove the cable covering at the end to connect to the ground bolt (length approx.

    10 mm) and fix a cable lug M8. Connect the prepared cable end to the ground bolt. Tighten the nut firmly.A backup batterie should be mounted inside the shelter for taking over the -48 V DC supply function either in case of primary power loss or in case of AC/DC converter failure. The required connecting cables are already installed at the factory. For exten-sion of the backup time, additional batteries outside the BS 21E shelter could be used.The connection is made as follows: Determine the actual cable length between the location of these batteries and the

    terminal block at the SCAP. Cut the cable (e.g. NYCWY 2x10/RE 10) to the required length. Connect the prepaired cable to the terminal block. Lead the cable through the cable entry forward to the external batteries.

    Figure 11 Screw terminal for connecting of external backup batteries

    2.8.2.2 Connecting of the BS21UThe BS21U provides a ground bolt for ground connection according NEC Section 810-58(b). The dimensions of the required ground conductor has to be not less than 10 AWG (American Wire Gauge).All other supply connectors should be not less than 12 AWG. The BS21U has to be connected to the site specific ground system before starting the installation of power supply wires. The ground resistance must be less than 10 Ohm. Pay attention to the label adjancent to the Power Input Terminal Block: HIGH LEAKAGE CURRENT- Earth connection essential before connecting supply

    to EMI filter 02(connection already installed)

    from external backup batteries

    terminal block Kl 02 "48 V DC"

    clamp 04 05 06

    L/+ N/-

  • 24 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    After connection the BS21U to AC or DC power supply sources, in parts of basestation equipment hazardous energy levels do exist. A label, located on the fuse panel gives instruction how to deenergize the BS21U:TO DEENERGIZE ENTIRE UNIT: 1) Switch Bat.off first on fuse panel to Deenergize DC circuit 2) Switch FU06 and FU07 to Deenergize AC circuitThe WAGO-terminal block for the 120 V AC mains input is located on the EMI panel below the roof. To connect the BS21U shelter with the AC mains connection point proceed in the follow-ing stages: Check the actual distance between terminal block and the connection point. Cut the cable to the required length. Remove the insulation of the cable and cut back the wire insulation at the end; that

    is to be connected to the terminal block. The wires must be equipped with wire end sleeves.

    Lead the prepared cable through the cable entry at the top of the shelter. Insert matching wires into the WAGO terminals. Lead the main cable to the connection point for 120 V AC.

    Figure 12 WAGO terminal block for AC and DC power supply

    Each phase must be protected by a UL listed 20 A ground fault indicator. For further information refer to the site documentation and use the corresponding manufacturer documents.The BS 21U shelter must be connected to the ground system. For this purpose a ground bolt M8 is provided. This bolt is located at the lower right hand side panel. Depending

    AC cable for BS21U Label Pin RemarksN 05a 04-05 bridged

    neutral conductor (blue) N 04a 04-05 bridged120 V AC (brown/black) L2 03a120 V AC (black) L1 02aprotective conductor (y/g) PE 01a

    Table 1 Pinning of the 120 V AC terminal block

    LP3

    LP2

    LP1

    - 48 V+0 V

    to externalback-up battery

    N

    L1PE

    L2120 V AC2 phase powersupply

  • A50016-G5100-A364-01-7631

    25

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    on the site construction (e.g. steel frame for roof-top installation, concrete foundation for rural sites), the shelter has to be connected directly to the ground system or via a short ground jumper. If 16 mm copper wire (e.g. PVC-wire H07V-R 16 yellow/green) should be used, the distance must be less than 2 metres.Connect the BS 21U shelter and ground system as follows: Use the nearest connection points of the ground system. Ascertain the distances between the connection point of the ground system and the

    ground bolt of the shelter and cut the cable to the required length. Remove the cable covering at the end to connect to the ground bolt (length approx.

    10 mm) and fix a cable lug M8. Connect the prepared cable end to the ground bolt and tighten the nut firmly. Connect the grounding strip (cable entry) with the external earth bolt by earth cable.Detailed information about the ground system on site and the connecting procedure is to be found in the site-specific documentation.A backup batterie could be mounted inside the front door for taking over the -48 V DC supply function either in case of primary power loss or in case of AC/DC converter failure. The required connecting cables are already installed at the factory. For exten-sion of the backup time, additional batteries outside the BS 21U could be used.This requires the disconnection of the internal battery. For this purpose a jumper in the fuse panel must be used. The external battery is protected by a 50 A breaker, located in the fuse panel. The external back-up battery requires a copper cable connection between the WAGO-terminal block on the EMI-panel and the battery via the cable entry. The max. electrical load of the DC power line is

  • 26 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    ing of the batteries must be done inside the battery compartment. Note: The +0 V pole of the external batteries must be connected to ground !

    2.8.4 Abis-Interface - PCM Link TerminalThe Abis interface, located on RCAP, is terminated with the Overvoltage Protection (OVPT) which protects the LI inside the BS20 against overvoltage (residual voltage < 1 kV). Two types of OVPT are exist (for 75 Ohm or 120 Ohm cables). Dependend on the different cable impedances is recommended to: Use screened cable containing 8/10 shielded twisted pairs 0,25 mm2 for 120 Ohm

    PCM lines, e.g. S-09YS(ST)CY 8x2x0.6/1.2. Use coaxial cables for 75 Ohm wiring, e.g. 2YCCY 0.4/2.5.The maximum cable length depends on the attenuation of the cable, in order to fulfil the requirements of minimum voltage levels to be provided at Abis interface according to PCM standards. The cable shielding must be connected to the relevant ground pins as close as possible (in order to avoid EMC/RF interfering effects).

    2.8.4.1 Abis-Interface for 120 Ohm Cable Impedance

    Figure 13 OVPT with terminal block (120 Ohm)Connect the Abis-interface with twisted pair cable to the PCM link terminal as follows: Cut the cable to the required length and cut back the outer insulation (approx.19

    cm). Remove the wire insulation (0,8 mm). Wrap the exposed cable shield, whitch will be fixed at the stress relieving, with

    adhesive copper foil (approx. 4 cm). Fix the prepared cable close to the stress relieving by straps. Insert the wires into the terminals of the OVPT.

    !WARNINGThe AC connection of the BTS has to be disconnected before working at the PCM- terminal blocks. This can be done either by pulling out the AC plug or by releasing the mains breakers outside of the BTS.Releasing the internal AC breakers is not sufficient!

    tracing interfacesfor Abis-lines( 4 x Sub-D 9 )

    holes for cable fixing with s traps

    24pole-terminal block

    1357911131517192123

    24681012141618202224

  • A50016-G5100-A364-01-7631

    27

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Insert the additional wire (shielding potential) into one of the ground terminals (e.g. no. 24).

    Lead the additional wire and the uplink and downlink wires on the shortest way (that means without sleeves) between the stress relieving and the screw terminals.

    All unconnected PCM lines (4 wires per line) must be connected to one of the ground terminals.

    It is advantageous to protect the short part of the cable between stress relieving and terminal block with a shrink tube or adhesive tape.

    terminal number Signal name Function22 PCM 1 - ULA PCM Line 1 Up Link A20 PCM 1 - ULB PCM Line 1 Up Link B24 GND ground21 PCM 1 - DLA PCM Line 1 Down Link A19 PCM 1 - DLB PCM Line 1 Down Link B23 GND ground16 PCM 2 - ULA PCM Line 2 Up Link A14 PCM 2 - ULB PCM Line 2 Up Link B18 GND ground15 PCM 2 - DLA PCM Line 2 Down Link A13 PCM 2 - DLB PCM Line 2 Down Link B17 GND ground10 PCM 3 - ULA PCM Line 3 Up Link A8 PCM 3 - ULB PCM Line 3 Up Link B12 GND ground9 PCM 3 - DLA PCM Line 3 Down Link A7 PCM 3 - DLB PCM Line 3 Down Link B11 GND ground4 PCM 4 - ULA PCM Line 4 Up Link A2 PCM 4 - ULB PCM Line 4 Up Link B6 GND ground3 PCM 4 - DLA PCM Line 4 Down Link A1 PCM 4 - DLB PCM Line 4 Down Link B5 GND ground

    Table 3 Pinning of Abis-interface (OVPT 120 Ohm)

  • 28 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    The Overvoltage Protection carries 4 Sub-D9 female connectors for tracing the PCM lines. The following table shows the pinning of the tracing interfaces.

    2.8.4.2 Abis-Interface for 75 Ohm Cable Impedance

    Figure 14 OVPT with SMA connectors (75 Ohm)For Abis cabling with 75 Ohm impedance use coaxial cable e.g. 2YCCY 0.4/2.5. The coaxial cables will be prepared as follows: Cut back the outer insulation(length approx. 120 mm). Unbraid the main cable screen. Twist and tinn the screen wires and the additional wire. Insulate the screening with insulation sleeve. Fix the screening at the nearest ground point. Fix a SMA-female connector for each PCM-up and down line at the end to be con-

    nected to the OVPT. Connect the prepared cable to the matching connectors. Use a torque spanner for SMA connector (35 N/cm).Fig.2.14 shows the handling of the main cable shield.

    Pin No. Signal (x=1,2,3,4) Pin No. Signal (x=1,2,3,4)1 PCMx-ULB 2 GND/G3 GND/G 4 GND/G5 PCMx-DLB 6 PCMx-ULA7 GND/G 8 GND/G9 PCMx-DLA

    Table 4 Pinning of PCM line monitoring interface (SUB-D9,female)

    PCM1-UL

    PCM2-UL

    PCM3-UL

    PCM4-UL

    PCM1-DL

    PCM2-DL

    PCM3-DL

    PCM4-DL

    PCM1-UL-MON

    PCM2-UL-MON

    PCM3-UL-MON

    PCM4-UL-MON

    PCM1-DL-MON

    PCM2-DL-MON

    PCM3-DL-MON

    PCM4-DL-MON

    Monitoring Interfaces for PCM lines SMA-male connectors for PCM lines fixing screws

  • A50016-G5100-A364-01-7631

    29

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Figure 15 Preparation of 75 Ohm coaxial cable

    2.8.4.3 Abis-Interface without OVPTWithout OVPT (the lightning protection for 4 PCM channels), if this function is not needed, a SUB-D25 female connector is the direct interface for the PCM links.

    approx. 120 mm75 Ohm coaxial cable

    cable shield

    coaxial lines

    main cable screen

    twisted, tinned main cable screen and addition wire

    additional wire

    screening with insulation sleeve

    Pin no. SubD 25 Signal name Function1 PCM 1 - ULA PCM Line 1 Up Link A14 PCM 1 - ULB PCM Line 1 Up Link B3 GND/G shield pair 12 PCM 1 - DLA PCM Line 1 Down Link A15 PCM 1 - DLB PCM Line 1 Down Link B16 GND/G shield pair 24 PCM 2 - ULA PCM Line 2 Up Link A17 PCM 2 - ULB PCM Line 2 Up Link B6 GND/G shield pair 35 PCM 2 - DLA PCM Line 2 Down Link A

    Table 5 Pinning of the Abis-interface cable without OVPT (SubD 25 connector)

  • 30 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2.8.5 Serial Interface - Signalling Link TerminalThe Serial Interface(SI) is connected to the signaling link terminal on site as follows: Refer to the site documentation for the required information about the location of the

    signaling link terminal and the type of cable and connector which have to be used. Determine the distance between rack and link terminal. Cut the cable to the required length. Fix the SubD 9 male connector at the end to be connected at the serial interface of

    the rack. Follow the connector assembly instructions and the handling instructions of the

    cable. Put up the connector on the Serial Interface. Tighten the fastening screws. Lead the cable through cable entry forward to the link terminal, fix matching wires at

    the required pins. Refer to the site documentation for the pinning.

    18 PCM 2 - DLB PCM Line 2 Down Link B19 GND/G shield pair 47 PCM 3 - ULA PCM Line 3 Up Link A20 PCM 3 - ULB PCM Line 3 Up Link B9 GND/G shield pair 58 PCM 3 - DLA PCM Line 3 Down Link A21 PCM 3 - DLB PCM Line 3 Down Link B22 GND/G shield pair 610 PCM 4 - ULA PCM Line 4 Up Link A23 PCM 4 - ULB PCM Line 4 Up Link B12 GND/G shield pair 711 PCM 4 - DLA PCM Line 4 Down Link A24 PCM 4 - DLB PCM Line 4 Down Link B25 GND/G shield pair 813 GND/G main cable shield

    Pin no. SubD 25 Signal name Function

    Table 5 Pinning of the Abis-interface cable without OVPT (SubD 25 connector)

    Pin no.SubD 9 Signal name Pin no.SubD 9 Signal name1 OPSERCD 6 OPSERDSR2 OPSERRXD 7 OPSERRTS3 OPSERTXD 8 OPSERCTS4 OPSERDTR 9 OPSERRI5 OPSERGND --

    Table 6 Pinning of the Serial Interface

  • A50016-G5100-A364-01-7631

    31

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.8.6 Shelter Alarm Interface - Signalling Link TerminalFor the (optional, currently not used) connection between the signalling link terminal on site and the shelter alarm interface (SAL) at RCAP proceed in following steps: Locate the SubD 37 connector at the rack cabling access panel. Refer to the site-specific documentation for the required information about the

    location of the signalling link terminal, the type of shielded cable and type of connec-tor, which has to be used.

    Determine the real distance between rack and signalling link terminal and cut the cable for the required length.

    Fix the SubD 37 male connector at the end, which has to be connected at the serial alarm interface. The pin assignment you will find in the site-specific documentation.

    Pay attention to the assembly instructions of the connector and the handling instruc-tions of the cable which are used.

    Put up the connector on the shelter alarm interface and tight the fastening screws.For connecting the wires at the signalling link terminal refer to the site documentation for the pin assignment. Type and pinning of the terminal on site are subject to change and depending on the customer.The following table gives information about the pinning of the SubD 37 connector:

    Pin no. SubD 37

    signal name Pin no. SubD 37

    signal name

    1 no.1 positive, undefined 20 no.1 minus, undefined2 no.2 positive, undefined 21 no.2 minus, undefined3 no.3 positive, undefined 22 no.3 minus, undefined4 no.4 positive, undefined 23 no.4 minus, undefined5 no.5 positive, undefined 24 no.5 minus, undefined6 no.6 positive, undefined 25 no.6 minus, undefined7 no.7 positive, undefined 26 no.7 minus, undefined8 no.8 positive, undefined 27 no.8 minus, undefined9 no.9 positive, undefined 28 no.9 minus, undefined10 no.10 positive, undefined 29 no.10 minus, undefined11 no.11 positive, undefined 30 no.11 minus, undefined12 no.12 positive, undefined 31 no.12 minus, undefined13 no.13 positive, undefined 32 no.13 minus, undefined14 no.14 positive, undefined 33 no.14 minus, undefined15 no.15 positive, undefined 34 no.15 minus, undefined16 no.16 positive, undefined 35 no.16 minus, undefined17 no.17 positive, undefined 36 no.17 minus, undefined18 37

    19 -

    Table 7 Pinning of the shelter alarm interface

  • 32 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2.8.7 Operator Alarm Interface - Signaling Link TerminalA SubD 37 connector located at the EMI-panel is the interface for external alarms (stan-dard TTL)and commands(max. +4,7 V, min. 10mA driver capability).The Alarm Connection KIt (ACK) on the SUB-D37, equipped with terminal block, allows simple connection of wires. The OAL Interface provides 14 Alarm Line inputs and 4 Command Line outputs, processed by the ALCO module.

    The connection is as follows: Put up the Alarm Connection Kit on the Operator Alarm Interface. Tighten the fastening screws. Lead the cable through the cable entry forward to the ACK terminal block, fix

    matching wires at the required pins. Refer to the site documentation for the actual pinning.

    Pin Signal name

    Alarm expected Pin Signal name

    Alarm expected

    1 OPCMD1P undefined 2 OPCMD1M undefined3 OPCMD2P undefined 4 OPCMD2M undefined5 OPCMD3P undefined 6 OPCMD3M undefined7 OPCMD4P undefined 8 OPCMD4M undefined9 ENVA0P Smoke (not BS21U) 10 ENVA0M Smoke (not BS21U)11 ENVA1P Water detection*** 12 ENVA1M Water detection***13 ENVA2P Humidity detect.*** 14 ENVA2M Humidity detect.***15 ENVA3P AC Lightning Prot. 16 ENVA3M AC Lightning Prot.17 ENVA4P AC-warning *** 18 ENVA4M AC-warning ***19 ENVA5P undefined 20 ENVA5M undefined21 ENVA6P STOT/ROT ** 22 ENVA6M STOT/ROT **23 ENVA7P 48VOT/48OTB** 24 ENVA7M 48VOT/48OTB**25 ENVA8P SDO/KVz 26 ENVA8M SDO/KVz27 ENVA9P ACSF**/ACR*** 28 ENVA9M ACSF**/ACR***29 ENVA10P room***/heat*** 30 ENVA10M room***/heat***31 ENVA11P MBB**/BBR** 32 ENVA11M MBB**/BBR**33 ENVA12P BCHF** 34 ENVA12M BCHF**35 ENVA13P AC l.-prot. 36 ENVA13M AC l.-prot.* only if equipped with AVV or microwave, ** from SSC, *** only if sensor is installed

    Table 8 Pinning of the Alarm Connection Kit

  • A50016-G5100-A364-01-7631

    33

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Without ACK, the SUB-D37 female connector at the EMI-panel is the direct interface of external alarm- and command lines.

    Pin no. SubD 37

    Signal name (new)

    Signal name (old)

    Pin no. SubD 37

    Signal name (new)

    Signal name (old)

    1 OPCMD1P OPCMD1P 20 ENVA5M OPALM6M2 OPCMD1M OPCMD1M 21 ENVA6P OPALM7P3 OPCMD2P OPCMD2P 22 ENVA6M OPALM7M4 OPCMD2M OPCMD2M 23 ENVA7P OPALM8P5 OPCMD3P OPCMD3P 24 ENVA7M OPALM8M6 OPCMD3M OPCMD3M 25 ENVA8P OPALM9P7 OPCMD4P OPCMD4P 26 ENVA8M OPALM9M8 OPCMD4M OPCMD4M 27 ENVA9P OPALM10P9 ENVA0P OPALM1P 28 ENVA9M OPALM10M10 ENVA0M OPALM1M 29 ENVA10P OPALM11P11 ENVA1P OPALM2P 30 ENVA10M OPALM11M12 ENVA1M OPALM2M 31 ENVA11P OPALM12P13 ENVA2P OPALM3P 32 ENVA11M OPALM12M14 ENVA2M OPALM3M 33 ENVA12P OPALM13P15 ENVA3P OPALM4P 34 ENVA12M OPALM13M16 ENVA3M OPALM4M 35 ENVA13P OPALM14P17 ENVA4P OPALM5P 36 ENVA13M OPALM14M18 ENVA4M OPALM5M 37 --19 ENVA5P OPALM6P -- --

    Table 9 Pinning of the operator alarm interface (OAL)

    signal name signal meaningOPCMD_P Operator command no. _, positiveOPCMD_M Operator command no. _, minusENVA_P Enviromental alarm no. _, positiveENVA_M Enviromental alarm no. _, minus

    Table 10 Signal meaning, operator alarm interface

  • 34 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2.8.8 Local Maintenance Terminal (LMT) InterfaceThe LMT interface is a HDLC link interface for the CCTRL . A SubD 15 female connec-tor, located at the fuse panel front plate allows the connecting of a Local Maintenance Terminal (LMT) for commissioning and service purposes.

    2.9 Board Insert ProceduresThe BS21 will be delivered fully equipped with all modules necessary for proper function. If the rack was shipped unequipped, the following equipment is designed for completion on site: Power Amplifiers Transceive Processor Units Antenna Combiner Backup Batterie Generic Power Supplies AC/DC Converter Fan unit HYCOM or DUKITThe required transmission equipment will be delivered and installed by the customer personnel (exept turnkey contracts).Unequipped mounting positions must be covered by cover plates.

    SUB-D15 Pin No. Signal Name SUB-D15 Pin No. Signal name1 - 2 LRXDA

    3 LCTSA 4 LTXDA5 LRTSA 6 LTXCLKA7 LRXCLKA 8 GND/G9 LRXDB 10 LCTSB11 LTXDB 12 LRTSB13 LTXCLKB 14 LRXCLKB15 -

    Table 11 Pinning of the LMT interface

    dimension (H x W) used for unequipped mounting positions of:

    291 mm x 29.5 mm MCLK, CCTRL, LI291 mm x 34.5 mm BBSIG141 mm x 29.5 mm RXAMCO141 mm x 119.7 mm GPSU141 mm x 74.5 mm DCTPU/DCPA291 mm x 89.5mm TPU/PA

    Table 12 Cover plate dimensions

  • A50016-G5100-A364-01-7631

    35

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Code keys are fitted on core and RF-modules connected to the back plane in order to avoid installation at incorrect mounting positions. The jack bushing fitted with the code keys also provide connection of the earth/mass to the module before contacting the signal socket when the board is being plugged-in.

    Figure 16 Location of the code keys

    2.9.1 Mounting Position of Boards and ModulesThe subrack of the BS 21 houses all boards of the radio equipment:Core Modules: Alarm Controller (ALCO); Master Clock (MCLK), Link Interface (LI); Core Controller (CCTRL); Generic Power Supply (GPSU)TX/RX Modules: Transceiver and Processor Units (TPU); Power Amplifiers (PA) DC Converters for TPU and PA ;Baseband Controllers (BBSIG); RXAMCO

    code key

    code key

    levers

    2

    code key no.

    Module name long name code keyBBSIG baseband and signalprocessing unit 2MCLK master clock 1CCTRL core controller 4RXAMCO receiver antenna module and multicoupler 1LI link interface 5ALCO alarm and control board 3GPSU generic power supply unit 4PA power amplifier 2DCPA direct current converter for PA 4TPU transceiver and processor unit 1DCTPU direct current converter for TPU 3

    Table 13 Code keys of RF and core modules

  • 36 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    The subrack is equal forD900/D1800 and D1900 equipment. The types and numbers of boards are subject to modification. For the required information refer to the site-specific documentation.The subrack of the BS 21 shelter also contains all supplementary equipment, required for operation of the base station: AC/DC converters Transmission equipment2 AC/DC converters provide the -48 V nominal voltage and battery charging. The AC/DC converter no.0 (master) controls the battery charging.NTPM (BS21E), CSU (BS21U) or Microwave could be used for connecting the BS 21 to the Base Station Controller (BSC). This transmission equipment could be installed in field no. 03 C of the subrack or outside the shelter. The subrack must be equipped with a NTPM-kit for installation of NTPMs. This frame houses the NTPMs and is needed for the connections with the power supply and the other BTS equipment. If microwave equipment or Channel Servise Unit should be used for transmission, a comparable installation kit is necessary. Install the transmission equipment by means of their mounting instructions. The required connectors for the cables between microwave outdoor unit and the microwave indoor unit must be mounted on the stripes for exten-sion cabling. EMI-panel.g Caution: The installer has to guarantee the protection of the microwave equipment

    and the external DC lines (if not lead in metal, grounded conduit) against lightning surges ! The required lightning protections must be located outside the EMI-shield (EMI-panel). The shield of the microwave cable must be grounded on the EMI-panel.

    Figure 17 BS 21, full equipped with mounting unit numbering

    mounting unit

    00

    01*)

    02

    03

    B

    C

    D

    E

    F

    C

    FUSE PANEL DUKIT

    RXAMCO

    0 1 2 3

    FAN UNIT

    air outlet

    air inlet

    AC/D

    C 0

    AC/D

    C 1

    ALCO

    BBSI

    G 0

    BBSI

    G 1

    LI MCL

    KCC

    TRL

    PA 0

    PA 1

    TPU

    0

    TPU

    1

    backupbattery

    GPS

    U 0

    DCP

    A 0

    DCP

    A 1

    DCT

    PU 0

    DCT

    PU 0

    heat

    exc

    han

    ger

    aco

    ust

    ic a

    ttenu

    atio

    n

    EMI-PANEL

    transmission equipment

    or HYBRIDin case of rack extension

  • A50016-G5100-A364-01-7631

    37

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.9.2 Transmission Equipment located outside the BS21If the transmission equipment is located outside adjacent to the BS21 and connected with the OVPT on the EMI-panel, the connection of the bottom plugs of cable no. 135 and 136 is required for the direct connection between OVPT and LI via back plane. The plugs are visible and accessible in the unequipped field for transmission equipment (C 03).

    Figure 18 Abis connection with external transmission equipment

    2.9.3 Transmission Equipment inside the BS21

    2.9.3.1 Installation of Microwave EquipmentIf microwave will be installed inside the shelter, the disconnection of the shelter bottom plugs of Abis interface cable and LI interface cable is required. The Li interface cable has to be extended with microwave adapter cable. The transmission equipment must be connected to the - 48 V DC power supply with the double FASTON 6,3 mm of power supply cables, labelled MW0 (for microwave 0) and MW1 (microwave 1). The output cable of the microwave equipment have to be routed through the stripes at the lefthand side of the EMI panel.

    Shelter Bottom Plugs back plane

    Link Interface

    LI interface cable OVPT

    EMI-panel

    Abis

    terminal block

    toexternaltransmission equipment D25

    female male

    interface cable

    femalemale

  • 38 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    Figure 19 Abis connection with internal microwave

    2.9.3.2 Installation of NTPM or CSUIf NTPM (BS21E) or CSU (BS21U) will be installed inside the enclosure, the shelter bottom plugs of the Abis interface cable and the LI interface cable have to be discon-nected. The Abis interface cable have to be extended with NTPM cable. The D25 female connector of the NTPM cable has to be plugged in NTPM back plane. The D25 male connector of link interface cable has to be plugged in NTPM back plane. The transmis-sion equipment must be connected to the - 48 V DC power supply with the double FASTON 6,3 mm of power supply cables, labelled NTPM 0 (for NTPM/CSU 0) and NTPM 1 (for NTPM/CSU 1).Note, that in case of other NTPM/CSU equipment than Siemens is used special cabling or additional adaption might be necessary.

    Figure 20 Abis connection with internal NTPM or CSU

    back plane

    Link Interface

    OVPT

    EMI-panel

    terminal block

    toexternaltransmission equipment

    -48 V DC-48 V DC

    Abisinterface cable

    Link interfacecable

    malefemale

    (disconnected)

    microwaveadapter cable

    microwavemicrowave01

    leaded throug stripesexternal cables

    back plane

    Link Interface

    OVPT

    EMI-panel

    terminal block

    toexternaltransmission equipment

    NTPM0CSU0

    NTPM1CSU1

    -48 V DC-48 V DC

    NTPM back plane

    Abisinterface cable

    NTPMadapter cable

    Link interfacecable

    femalemale

    D25

    D25 D25

    malefemale

  • A50016-G5100-A364-01-7631

    39

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.10 System CablingThe system cabling consists of connections which must be installed between the front connectors of the RF modules. It depends on the different equipping variants and the cell configuration of the site. The prefabricated semi-rigid cables are shipped separately in their own carton to avoid twisting and damage.Before starting the installation procedure, refer to the site documentation and determine types and numbers of cables required for the complete cabling.The following section gives an overview of the required cable connections.

    Figure 21 System cabling BS 21, overview

    2.10.1 Duplex Combiner Kit (DUKIT) - RXAMCOThe following figure shows the cable routes for connections between the DUKIT and the RXAMCOs. For installation of the cables proceed as follows: Refer to the site specific documentation for information about the variant numbers

    of the required connections between DUKIT and the RXAMCOs. Route the cables from the RX/RXdiv connectors at DUKIT to the RXin connectors. To avoid load of the connectors during the bending procedure, bend the cables to

    the correct form before you fixing the cable at the front-connectors of the modules. Pay attention to the minimum bending radius of 5.0 mm. Terminate all unused RF connectors of the RXAMCO by 50 Ohm load resistors !

    shelter access panel (EMI panel)

    DUKIT PA TPU BUS 1LI

    RXAMCO

    RXAMCOdiv.

    BUS 2BBSIG

    MCLK

    CCTRL

    ALCO

    back plane

    164,165

    162,163

    156-158

    151,152

    153-155

    159-161

    Abisor

    AbisOVPT

    LMTsite inputs

    site outputs

    system cabling with no. of variantother connections (preinstalled at factory)external connections

    shelter access panel (EMI panel)

  • 40 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    Figure 22 DUKIT - RXAMCO connections (incl. diversity)

    backupbattery

    BBSI

    G

    BBSI

    G

    ALCO

    LI MCL

    K

    PATPU

    TPU

    DCP

    A

    DCP

    AD

    CTPU

    DCT

    PU

    DC AC

    0 1

    AC/DCconverters

    0 1

    RXAMCO 0 1 32

    RXin

    TPU

    151-155

    RX 0; 1

    RXdiv 0; 1

    PA

    routing variant

    from DUKIT

    connector

    to connector required cable length

    151 RX 0 RXAMCO 0 RXIN 1150 mm152 RX 1 RXAMCO 2 RXIN 1150 mm153 RX 1 RXAMCO 1 RXIN 1150 mm154 RX div 0 RXAMCO 1 RXIN 1150 mm155 RX div 1 RXAMCO 3 RXIN 1150 mm

    Table 14 DUKIT - RXAMCO connections (incl. diversity)

  • A50016-G5100-A364-01-7631

    41

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.10.2 RXAMCO - TPUThe installation of the cable connections between the RXAMCOs and the the TPUs is as follows: Refer to the site specific documentation for information about the variant numbers

    of the required connections. Route the cables from the RXO connectors at RXAMCO to the RX or RXdiv con-

    nectors (if receive path diversity is required). To avoid load of the connectors during the bending procedure, bend the cables to

    the correct form before you fixing the cable at the front-connectors of the modules. Pay attention to the minimum bending radius of 5.0 mm. Use a bending tool for

    bending of semi rigid cables. Terminate all unused RF connectors by 50 Ohm load resistors !

    Figure 23 Cable routes for RXAMCO - TPU connections (incl. diversity)

    backupbattery

    BBSI

    G

    BBSI

    G

    ALCO

    LI MCL

    K

    PATPU

    TPU

    DCP

    A

    DCP

    AD

    CTPU

    DCT

    PU

    DC AC

    0

    0

    1

    1AC/DCconverters

    0 1

    RXAMCO 0 1 32

    RX 0123

    TPU

    RXDIV

    RX

    156-161

    routing variant

    from RXAMCO

    connector to connector required cable length

    156 0 RXO 0 TPU 0 RX 400 mm

    Table 15 Routing variants for RXAMCO - TPU connections (incl. diversity)

  • 42 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2.10.3 TPU - PA ConnectionsEach transceiver processor unit has to be connected to the power amplifier with the same relative number. One semi rigid cable ( 2.2 mm; length approx. 270 mm) is there-fore needed per installed carrier.Refer to the site specific documentation for information about the required connections.

    Figure 24 Cable routes for TPU - PA connections

    157 0 RXO 1 TPU 1 RX 400 mm158 2 RXO 0 TPU 1 RX 400 mm159 1 RXO 0 TPU 0 RX div 400 mm160 1 RXO 1 TPU 1 RX div 400 mm161 3 RXO 0 TPU 1 RX div 400 mm

    routing variant

    from RXAMCO

    connector to connector required cable length

    Table 15 Routing variants for RXAMCO - TPU connections (incl. diversity)

    backupbattery

    BBSI

    G

    BBSI

    G

    ALCO

    LI MCL

    K

    PATPU

    TPU

    DCP

    A

    DCP

    AD

    CTPU

    DCT

    PU

    DC AC

    0

    0

    1

    AC/DCconverters

    0 1

    TPU

    162, 163

    TX

    TXinPA 0 1

  • A50016-G5100-A364-01-7631

    43

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    The following tables gives information about the variant numbers of these connections.

    2.10.4 PA - DUKIT ConnectionsThe TXout connector of the power amplifier has to be connected to the TX connectors at DUKIT. Refer to the site-specific documentation for information about the required connections.

    Figure 25 Cable routes for PA - DUKIT connections

    routing variant

    from RXAMCO connector

    connector to connector required cable length

    162 TPU 0 TX PA TXIN 180 mm163 TPU 1 TX PA TXIN 180 mm

    Table 16 Routing variants for TPU - PA connections

    BBSI

    G

    BBSI

    G

    ALCO

    LI MCL

    K

    PATPU

    TPU

    DC AC

    AC/DCconverters

    0 1

    TXout

    TX 0

    TX 1

    PA 0 PA 1

    164, 164

    routing variant

    from PA

    connector to connector required cable length

    164 0 TXout DUKIT TX 0 180 mm165 1 TXout DUKIT TX 1 180 mm

    Table 17 Routing variants for PA - DUKIT connections

  • 44 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    2.11 Antenna ConnectionsThe antenna configuration and the required cabling are site-dependent. site. One trans-mit/receive path is needed per cell. If receive antenna diversity is required, an additional receive path has to be installed. For detailed information about the antenna configura-tion and the antenna cabling refer to the site-specific documentation. The following figure gives an example for the antenna connections (one cell incl. receive antenna diversity):

    Figure 26 Antenna cabling BS 21 (example)

    2.11.1 Transmit/Receive Antenna ConnectionsCoaxial jumper leads connect the antenna feeder cables to the transmit/receive antenna connectors at the shelter access panel. The EMI-panel is equipped with 2 7/16 female connectors, numbered ANT 0 and ANT 1. The required number of jumper cables must be fabricated on site. They should be as short as possible.

    transmit/receiveantenna

    receive antenna(diversity)

    11

    1

    3

    2

    2

    4

    4

    5

    5

    5

    1 connector 7/16 male2 coaxial jumper lead3 connector 7/16 female4 clamp5 grounding kit6 antenna feeder cable7 angle connector 7/16 male

    7

    1

    4

    BS 21

    6

    5

    3

    3

    connection to the grounding stripat the lower basket of the cable entrycover

  • A50016-G5100-A364-01-7631

    45

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    For installation of the jumper cables proceed as follows: Take the required number of stoppers ( approx. 3.0 cm) out of the cable entry.Slip

    off the sealing rings. Check the actual distance between the connectors at the SCAP and the connection

    point to the antenna feeder cables. Cut the foam dielectic cable to the required length. Slip a sealing ring onto the cable. Connect a 7/16 male connector at the end which has to be connected at the antenna

    connector at the EMI-panel. Connect a 7/16 female connector at the end which has to be connected with the

    antenna feeder cable. Fix each prepared jumper lead at the appropriate antenna connector. Lead the cables through the cable entry forward to the antenna feeder cables.

    2.11.2 Receive Antenna Connections (diversity)Coaxial jumper leads are necessary for connections between the antenna feeder cables of the diversity receive path and the receive antenna connectors ANTDIV 0; ANTDIV 1. Fabricate the jumper leads on site as described in Section 1.9.1. The installation proce-dures are identical to those for the transmit/receive antenna jumpers.

    2.11.3 Identification of Antenna Feeder CablesThere are two different ways to identify the antenna feeder cables for connecting via short jumper cables to the antenna connectors of the BS61.

    meaning colour 1.label (nearest to connector)

    colour 2. label colour 3.label

    TX/RX cable red --- ---TX/RX div. cable red --- whitesector 0 --- green ---sector 1 --- orange ---sector 2 --- blau ---

    Table 18 Label colours of antenna feeders for BS61 with DUCOM

    meaning colour 1.label (nearest to connector)

    colour 2. label colour 3.label

    TX cable red --- ---RX cable white --- ---RX cable div. white --- whitesector 0 --- green ---sector 1 --- orange ---sector 2 --- blau ---

    Table 19 Label colours of antenna feeders for BS61 with HYCOM or FICOM

  • 46 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    For instellation and service purposes it is useful to know, which hardware is connected to which cell. The numbering, seen from the top of the antenne pole, starts at an azimuth angle of 0 (north) and rotates clockwise. The first existing cell which beam center line lies at 0 or more degree is defined as cell 0 or sector 0. The next one following in the same direction cell is cell 1 etc. In case of omni cell the cell no. is 0.

    Figure 27 Cell numbering (top view to the antenna pole)

    2.11.4 Mounting of the Cabel Entry CoverAfter all external cabling works are finished and all cables fixed by the clamps of the cable entry, proceed in steps as follows: Check the correct fixing of all connectors at the EMI-panel. Bend the external cables inside the EMI-panel to the correct form. Pay attention to

    the minimum bending radius of each cable type. Make sure that all sealings are in the correct position. Close the top cover of the shelter and fix it by the fastening screws, located in the

    upper area of the door frame. Fix all cables leaving the shelter at the holders of the cable entry cover. Use adhesive sealing tape for closing the gap between shelter and cable entry

    cover. Set up the cover and tighten the 6 M6 Allen screws.The following figure will give orientation for the handling of the cable entry cover.

    sector width 120

    sector angle

    directional antenna

    pole

    sector 0sector 1

    sector 2

    N

    0

    beam center line

  • A50016-G5100-A364-01-7631

    47

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Figure 28 Mounting of the cable entry cover

    Note, that the installation of the BS21U is not allowed without cable entry cover! Before re-opening of the shelters top for EMI-panel access in case of extension- or mainte-nance works, the cable entry cover has been dismounted at first.

    2.12 Rack ExtensionRack extension is necessary to save the antenna system and provide a 4 carrier cell with two coupled BS21. Rack extension could be realized in case of new installation of two BS21 on site or a second BS21 will be added to the already installed shelter. The follow-ing figure gives information about the minimum site dimensions.

    3 x 2 Philips screws M6

    bracket

    cable entry cover

    conduittermination

    3 x 2 Allan screws M6

    cable routing in conduit

    grounding point forantenna cable shields

    cableholder

  • 48 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    Figure 29 Minimum site dimensions for BS21 rack extension

    The distances as shown in the figure are necessary for function and maintenance of the equipment on site: approx. 150 mm between back and wall for opening the top cover approx. 500 mm between sidewall and cabel entry cover or wall for securing the

    function of the air inlets and air outlets. Further the space reservation is needed for removing the cable entry cover.

    min. 870 mm for complete opening of the front doorsIn case the racks are installed without base constructions, a min. distance between floor and ceiling or other lowest construction part of 1600 mm is absolute required (for opening the top cover).

    2.12.1 Connections between the Racks1/2 jumper leads are required for connecting the racks, equipped with N-type female connectors at both ends. The laying of these cables requires a metal cable duct or metallic tubes between the shelters, which must be connected to ground for lightning protection.The rack extension consists of the jumper connections as shown in the figure and the rack-internal system cabling. Further a HYBRID module has to be installed in each BS21. The slots of RXAMCO 2 and 3 are the mounting position for the HYBRID.

    3290

    500

    cable ductcable duct

    500 500

    150

    1700

    870

  • A50016-G5100-A364-01-7631

    49

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    Figure 30 Jumper cable connections between the BS21 racks

    DUKIT 1:2 DUKIT 1:2

    HYBRIDBG

    stripes equippedwith N-connectorin EMI-panel

    BS 21

    TX/RX antenna 1Sector 0

    RX0

    TXTX

    RXDIV TX0

    RXDIV RXDIVTPU TPU PA PATX TX TXin TXin

    RX RX

    1/2 jumpercable with N-type female connector

    DUKIT 1:2 DUKIT 1:2

    HYBRIDBG

    RXAMCOdiv

    RX 0

    TXTX

    RXDIV TX 0

    RXDIV RXDIVTPU TPU PA PATX TX TXin TXin

    RX RX

    BS 21

    TX/RX antenna 1Sector 0

    RXAMCOdiv

  • 50 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    The extension kit, which contains the 4 jumper cables, 2 HYBRID incl. SMA adapters and the extension system cabling, is necessary for the implementation of rack exten-sion. Proceed in following stages: Open the top cover and the front doors of both racks. Install in each rack one RXAMCO and the HYBRID module. Prepare the stripes at the EMI-panel for fitting of N-type male connectors. Unscrew the EMI panel and lift it up in open position. Substitute the input isolator of the TXin 0 connector by an SMA adapter. Insert the prefabricated connecting cables between EMI-panel and RXAMCO. Fix the N-type connectors at the stripes. Lift back the EMI-panel and fix it by the screws. Fix the stripes at the EMI-panel. Lead the flexible RF-connecting cable to the front connectors of RXAMCO and TPU

    and fix them in accordance with Tab.2.20.

    For completion of the rack-internal cable the following connections are necessary in both racks:

    The last step of the extension works will be the connecting of the racks to the trans-mit/receive antennas. The BS21 called 0 has to be connected via 1/2 jumper cable to TX/RX antenna 0. Rack 1 has to be connected TX/RX antenna 1. Both antennas serving the same sector (0).

    BS21, rack 0 BS21, rack 1moodule connector module connector

    TPU 0 RXDIV RXAMCO 0 RXO 3TPU 1 RXDIV RXAMCO 0 RXO 2RXAMCO 0 RXO 3 TPU 0 RXDIVRXAMCO 0 RXO 2 TPU 1 RXDIV

    Table 20 Connections between the racks

    from module connector to module connectorTPU 0 RX RXAMCO 0 RXO 1TPU 1 RX RXAMCO 0 RXO 0PA 0 TX HYBRID TX 0

    PA 1 TX HYBRID TX 1

    RXAMCO 0 RXIN DUKIT RX 0HYBRID TXOUT DUKIT TX 0

    Table 21 Connections for TX/RX path of extended BS21

  • A50016-G5100-A364-01-7631

    51

    IMN:BS 21 BS 21 Installation

    Id:0900d80580070fc3

    2.13 Spare Parts

    2.13.1 Spare parts for BS 21EFor later field maintenance are the following spare parts available:l

    description (for BS 21E, Siemens no. S30861-C22-X)

    part number

    screw cage nut kit A50016-C1-A21guides rail kit A50016-C31-A71mounting kit for module A50016-C31-A191thermal contact kit A50016-C41-A1fan kit A50016-C-41A11M:fuc kit A50016-C41-A21battery 12V kit A50016-C41-A3120A fuse kit A50016-C41-A41door kit A50016-C41-A101rear panel kit A50016-C41-A111roof kit A50016-C41-A121r.h. side panel kit A50016-C41-A131front rear IP/EMC seal kit A50016-C41-A141door alarm switch kit A50016-C41-A151roof IP seal kit A50016-C41-A161air intake/exhaust kit A50016-C41-A171door hinge kit A50016-C41-A181latch SQ drive kit A50016-C41-A191cable entry kit A50016-C41-A201cabinet door stay kit A50016-C41-A211security screw cage nut kit A50016-C41-A221roof screw kit A50016-C41-A231l.h. cowl intake/exhaust kit A50016-C41-A241paint retouch A50016-C42-A251smoke sensor kit A50016-C42-A1overvoltage protection kit A50016-C42-A21appliance socket kit A50016-C42-A31filters kit A50016-C42-A51NFI switch 25A kit A50016-C42-A61breaker kit A50016-C43-A1

  • 52 A50016-G5100-A364-01-7631

    IMN:BS 21

    Id:0900d80580070fc3

    BS 21 Installation

    thermostat 3...15 degree kit A50016-C43-A11thermostat -5...5 degree kit A50016-C43-A21temperature fuse kit A50016-C43-A31backplane A50016-C43-A41heat exchanger int/ex fan kit A50016-C43-A101heat exchanger control module kit A50016-C43-A111heatexchanger control module fuse kit A50016-C43-A121