This Drawing is printed from Engineering Digital Archive System (EDAS). Therefore signatures are not essentially required. May Thu 21 14:55 2020 HYDERABAD PRODUCT STANDARD TURBINES & COMPRESSORS TC 51275 REV 03 PAGE 1 OF 6 FORMAT: PREPARED BY: APPROVED BY: DATE: TD - 201 SG KHS 21.03.2012 REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company. REF DOC: I/H CONVERTER (Current to hydraulic Pressure converter) 1.0 APPLICATION: This specification specifies the requirements of current-to-hydraulic pressure proportional converter (I/H converter) used in steam turbine governing system along with the cables and connectors. 2.0 TECHNICAL DETAILS: 2.1 DESCRIPTION “I/H Converter with manual actuating knob”. 2.2 TYPE The I/H convertor shall be of proportional type meeting the flow requirements as mentioned below in the hydraulic data and the electrical data. The convertor shall have in-built dither and shall be of “plug and play” type independent of any other software modules for its functioning 2.3 ELECTRICAL DATA (to be mentioned on the name plate) Supply voltage : +24V DC (permissible range 20 – 30 V DC including ripple) Power consumption : Normal: (to be indicated by supplier) Max: (to be indicated by supplier) Analog Input signal : 4 – 20 mA Analog output signal : 4 – 20 mA (accuracy within ±1% of full scale) Protection class : Selected as per variant table and to be indicated accordingly 2.4 HYDRAULIC DATA (to be mentioned on name plate) Supply pressure : 8±1 bar (g) (normal) 11 bar (g) (max) Output signal pressure : 1.5 – 4.5 bar (gauge) 4 mA corresponds to 1.5 bar (adjustable between minimum 1 to 2 bar) 20 mA corresponds to 4.5 bar (adjustable between a minimum 3 to 5 bar) Outlet volumetric flow : 45 lpm (minimum) at ∆P = 1 bar
6
Embed
I/H CONVERTER (Current to hydraulic Pressure ... - bhel.com
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
This Drawing is printed from Engineering Digital Archive System (EDAS).Therefore signatures are not essentially required.
May Thu 21 14:55 2020
HYDERABAD
PRODUCT STANDARD TURBINES & COMPRESSORS
TC 51275
REV 03
PAGE 1 OF 6
FORMAT: PREPARED BY: APPROVED BY: DATE:
TD - 201 SG KHS 21.03.2012
REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company.
REF DOC:
I/H CONVERTER (Current to hydraulic Pressure converter)
1.0 APPLICATION:
This specification specifies the requirements of current-to-hydraulic pressure proportional converter (I/H converter) used in steam turbine governing system along with the cables and connectors.
2.0 TECHNICAL DETAILS:
2.1 DESCRIPTION
“I/H Converter with manual actuating knob”.
2.2 TYPE
The I/H convertor shall be of proportional type meeting the flow requirements as mentioned below in the hydraulic data and the electrical data. The convertor shall have in-built dither and shall be of “plug and play” type independent of any other software modules for its functioning
2.3 ELECTRICAL DATA (to be mentioned on the name plate)
Supply voltage : +24V DC (permissible range 20 – 30 V DC including ripple)
Power consumption : Normal: (to be indicated by supplier) Max: (to be indicated by supplier)
Analog Input signal : 4 – 20 mA
Analog output signal : 4 – 20 mA (accuracy within ±1% of full scale) Protection class : Selected as per variant table and to be indicated
accordingly
2.4 HYDRAULIC DATA (to be mentioned on name plate)
Supply pressure : 8±1 bar (g) (normal) 11 bar (g) (max)
Output signal pressure : 1.5 – 4.5 bar (gauge) 4 mA corresponds to 1.5 bar (adjustable between minimum 1 to 2 bar) 20 mA corresponds to 4.5 bar (adjustable between a minimum 3 to 5 bar)
Outlet volumetric flow : 45 lpm (minimum) at ∆P = 1 bar
This Drawing is printed from Engineering Digital Archive System (EDAS).Therefore signatures are not essentially required.
May Thu 21 14:55 2020
HYDERABAD
PRODUCT STANDARD TURBINES & COMPRESSORS
TC 51275
REV 03
PAGE 2 OF 6
FORMAT: PREPARED BY: APPROVED BY: DATE:
TD - 201 SG KHS 21.03.2012
REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company.
REF DOC:
Degree of filtration : ≤50 microns (admissible contamination level – NAS 1638 Class 7)
Leakage : < 4 lpm
Oil type : Mineral oil (synthetic based)
Viscosity range : 20 -100 cSt
Seals material : Viton-A (compatible to oil type mentioned above)
2.5 PERFORMANCE CHARACTERISTICS
Hysteresis : <0.2% of total range
Repeatability : <0.1% of total range
Accuracy : <0.1% of output value
Conversion time : < 35 msec
Fail safe operation : Control oil output to drain on loss of input signal or power failure
2.6 ENVIRONMENTAL DATA
Surrounding temperature : -40 °C to +85 °C
Humidity : 100% condensing
Shock : 10 g peak for 0.011 seconds
Vibration : 18 to 500 Hz at 4.2g
Working temperature of fluid : +30 °C to +70 °C
2.7 HYDRAULIC CONNECTIONS
i) All the hydraulic connections shall be on one side of the manifold block, which shall be part of the supply of the converter.
ii) Supply, drain and output signal connections shall be of suitable NPT female threaded type and shall be indicated by the supplier.
iii) The supply shall also include hydraulic blocks (if applicable) and suitable flushing plates and mounting connecting parts and fasteners as may be necessary.
2.8 ELECTRICAL CONNECTIONS
Electrical connection : Cable with connectors (in-line with the actuator variant model)
Cable length : 5 meters
This Drawing is printed from Engineering Digital Archive System (EDAS).Therefore signatures are not essentially required.
May Thu 21 14:55 2020
HYDERABAD
PRODUCT STANDARD TURBINES & COMPRESSORS
TC 51275
REV 03
PAGE 3 OF 6
FORMAT: PREPARED BY: APPROVED BY: DATE:
TD - 201 SG KHS 21.03.2012
REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company.
REF DOC:
2.9 ADDITIONAL SCOPE (to be supplied with actuator)
i) 1 set of soft seals of all types used in the convertor.
ii) Connecting plates / Adapter plates
iii) Flushing plates
iv) Brackets for mounting
v) Fasteners as required and all special tools required for the manual operation as well as any maintenance shall be necessarily part of supplies without exception.
vi) All accessories for configuring viz. Tablets / Laptops, their connecting cables and software shall be part of the supplies.
3.0 DESCRIPTION (NAME) PLATE
Language : English
Data as per clause 2.3 & 2.4 shall be included in the description plate.
4.0 DOCUMENTS
The description catalogues giving full sectional details and mounting details of the convertor shall be furnished along with the offer and also with the consignment. 5 copies of Operation, Maintenance & Trouble shooting manuals in English language shall be supplied within 4 weeks of placement of order.
5.0 TEST CERTIFICATE
Three (3) copies of test certificate and adjustment protocol shall be furnished for each converter assembly quoting BHEL standard number, Purchase order number and serial number of the equipment.
6.0 GUARANTEE CERTIFICATE
A guarantee certificate for 24 months of trouble free performance from the data of shipment or 12 months from the date of commissioning whichever is later shall be furnished.
7.0 PACKING
The material shall be properly packed to ensure it is capable of withstanding transit risks without damage. Hydraulic port openings shall be plugged or closed with a locking plate. The packing shall be sea-worthy.
8.0 ACCEPTANCE CRITERION
8.1 Vendor shall provide a reference list of the offered product in steam turbine applications and supplied to OEMs.
8.2 The offer is liable to be rejected if the reference list does not have at least ten different references of I/H convertors (of all types mentioned in variant table) in similar application for steam turbines from OEMs’ and under successful trouble free operation
This Drawing is printed from Engineering Digital Archive System (EDAS).Therefore signatures are not essentially required.
May Thu 21 14:55 2020
HYDERABAD
PRODUCT STANDARD TURBINES & COMPRESSORS
TC 51275
REV 03
PAGE 4 OF 6
FORMAT: PREPARED BY: APPROVED BY: DATE:
TD - 201 SG KHS 21.03.2012
REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company.
REF DOC:
for more than 2 years.
8.3 End user feedback from the above references shall be furnished along with the offer for consideration of the offer.
8.4 OFFER STAGE
Vendor shall submit following test certificates:
1) Input signal versus pressure
2) Flow versus differential pressure
3) Dynamic response test (Pressure versus time)
4) Hysteresis 5) Hazardous area certification as per clause 10.0
6) Check list as per clause 13.0
9.0 MARKING
9.1 A tag bearing 12 digit material code shall be attached to each converter.
9.2 The following details shall be marked on packing case
1) Manufacturer’s name
2) Manufacturer’s model number
3) BHEL order number
4) BHEL standard number, TC51275.
10.0 HAZARDOUS AREA CERTIFICATION
The IH converter proposed to be used in hazardous area shall be flameproof Ex-d certified for using in hazardous area IEC Zone-1, Gas gr. IIA, B & C, T4. Statutory certificates shall be furnished as follows:
10.1 For all explosion protected equipments / instruments / systems or equipments with any other type of protection allowable as per this specification which are manufactured abroad and certified by any statutory authority like BASEEFA, FM, UL, PTB, LCIE etc. should also have the approval of Petroleum And Explosives Safety Organisation (PESO) / Chief Controller of Explosives (CCE), Nagpur. PESO certification is a statuatory requirement for use of explosion protected items / instruments in India.
10.2 For all flame proof equipments manufactured locally (indigenously), the testing shall be carried out by any of the test house like CMRI / ERTL etc. The equipment shall in addition bear the valid approval from Petroleum and Explosives Safety Organisation (PESO) / Chief Controller of Explosives, Nagpur and a valid BIS license.
This Drawing is printed from Engineering Digital Archive System (EDAS).Therefore signatures are not essentially required.
May Thu 21 14:55 2020
HYDERABAD
PRODUCT STANDARD TURBINES & COMPRESSORS
TC 51275
REV 03
PAGE 5 OF 6
FORMAT: PREPARED BY: APPROVED BY: DATE:
TD - 201 SG KHS 21.03.2012
REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company.
REF DOC:
11. VARIANT TABLE
VARIANT NO. DESCRIPTION MATERIAL CODE
01 Explosion proof IH converter:
This shall be Flame proof Ex-d certified as per IEC 60079 for using in hazardous area IEC zone 1, Gas group II A, B & C.
TC9751275016
02 Weather proof IH converter: This shall be complying to Protection Class IP65
TC9751275024
03 Connector with cable for Weather proof I/H Converter
TC9751275032
12. RECORD OF REVISIONS
REV.
DATE REVISION DETAILS REVISED APPROVED
02 03.12.15 Variant 03 added. AT SG/KHS
03 19.05.20 Sl.No. 2.9 (Additional scope) revised. Sl.No. 10 (Hazardous area certification) added. Generally revised
AT SG/KHS
This Drawing is printed from Engineering Digital Archive System (EDAS).Therefore signatures are not essentially required.
May Thu 21 14:55 2020
HYDERABAD
PRODUCT STANDARD TURBINES & COMPRESSORS
TC 51275
REV 03
PAGE 6 OF 6
FORMAT: PREPARED BY: APPROVED BY: DATE:
TD - 201 SG KHS 21.03.2012
REV - 00 COPY RIGHT AND CONFIDENTIAL The information on this document is the property of BHEL. It must not be used directly or indirectly in any way detrimental to the interest of the company.
REF DOC:
13. CHECK LIST (to be duly filled and certified by supplier)
S.No. Description Yes / No Document No.
1.0 Company name
2.0 Model No. of IH converter offered
3.0 Detailed catalogue enclosed
4.0 Additional literature enclosed
5.0 General arrangement drawing enclosed
6.0 Cross section drawing enclosed
7.0 Oil connection details and mounting details enclosed
8.0 Supply oil cleanliness requirement
9.0 Filter requirement in oil supply line
10.0 Recommendation of filter type and size
11.0 Power consumption Normal: Maximum:
12.0 Electrical connection diagram enclosed
13.0 Electrical connector details
13.0 Deviation to specification
14.0 Details of deviation to be specification enclosed