Green Star – Office Interiors v1.1 Page 1 of 1 Indoor Environment Quality IEQ-4 Daylight Glare Control Points Available Points Claimed CIR Submitted 2 1 N Credit Criteria Up to two points are awarded where it is demonstrated that glare is reduced, as follows: • 1 point is awarded where automated blinds/screens with a Visual Light Transmittance (VLT) of less than 10% and a manual override function are installed by either the tenant or the base building owner to reduce glare associated with natural lighting and eliminate all direct sun penetration; • 1 point is awarded where all workstation monitors provided as part of the tenancy fitout are flat-screen and are mounted on an adjustable arm that enables the monitor to be pivoted and adjusted horizontally and vertically. Documents Provided 9 As-built architectural drawings that show the location of blinds/screens included in the tenancy fitout and marked up to show how all direct sunlight penetration is controlled; 9 A copy of the data sheet that shows the VLT properties for the installed blinds/screens; 9 Information confirming the installed blinds/screens are connected to an automated control system with a manual override function that enables occupant control; and 9 Information from the supplier/installer that quantifies all products supplied and installed in fitout. Discussion • Verosol blinds have been installed in all perimeter windows to control daylight glare. They are connected to the Dynalite touch screen and are automated with manual override. • An as-built architectural plan has been provided to show that blinds have been installed on all windows. An elevation as-built drawing has been provided to show how blinds prevent direct sunlight penetration. An electrical as-built drawings has been provided to demonstrate that all blinds are connected to a relay controller for automation and manual override function. • The VLT data sheet demonstrates that blinds used have a VLT of 5%. • The letter from Dynalite demonstrates that blinds have been automated to raise and lower on a preset schedule with manual override from the Dynalite touch screen. • Finally, supplier/installer invoices from Verosol demonstrate that the 68 roller blinds have been supplied and installed.
26
Embed
IEQ-4 Daylight Glare Control · IEQ-4 Daylight Glare Control . Points Available . Points Claimed . CIR Submitted . 2 . 1 . N . Credit Criteria . ... tel 02 8907 0900 fax 02 9957 4127
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Green Star – Office Interiors v1.1
Page 1 of 1
Indoor Environment Quality IEQ-4 Daylight Glare Control Points Available Points Claimed CIR Submitted
2 1 N
Credit Criteria Up to two points are awarded where it is demonstrated that glare is reduced, as follows: • 1 point is awarded where automated blinds/screens with a Visual Light Transmittance (VLT) of less than 10% and a manual override function are installed by either the tenant or the base building owner to reduce glare associated with natural lighting and eliminate all direct sun penetration; • 1 point is awarded where all workstation monitors provided as part of the tenancy fitout are flat-screen and are mounted on an adjustable arm that enables the monitor to be pivoted and adjusted horizontally and vertically. Documents Provided
As-built architectural drawings that show the location of blinds/screens included in the tenancy fitout and marked up to show how all direct sunlight penetration is controlled;
A copy of the data sheet that shows the VLT properties for the installed blinds/screens;
Information confirming the installed blinds/screens are connected to an automated control system with a manual override function that enables occupant control; and
Information from the supplier/installer that quantifies all products supplied and installed in fitout.
Discussion
• Verosol blinds have been installed in all perimeter windows to control daylight glare. They are connected to the Dynalite touch screen and are automated with manual override.
• An as-built architectural plan has been provided to show that blinds have been installed on all windows. An elevation as-built drawing has been provided to show how blinds prevent direct sunlight penetration. An electrical as-built drawings has been provided to demonstrate that all blinds are connected to a relay controller for automation and manual override function.
• The VLT data sheet demonstrates that blinds used have a VLT of 5%. • The letter from Dynalite demonstrates that blinds have been automated to raise and lower on
a preset schedule with manual override from the Dynalite touch screen. • Finally, supplier/installer invoices from Verosol demonstrate that the 68 roller blinds have been
Joe Karten Green Building Council of Australia Level 15, 179 Elizabeth St Sydney, NSW 2000
Dear Joe,
Following the final programming and commissioning of all lighting and blinds in the GBCA Sydney Office fitout at 179 Elizabeth Street, I confirm the following:
• Board Room default lighting levels are at a 320-400 LUX average – and lighting controls reset to these levels (or off) when video conferencing equipment is not in operation.
• The lighting has been grouped into the zones called out on the E001 Lighting plan produced by KLM and no zone exceeds 100m2.
• Switching for task based lighting at workstations is controlled via staff computers at the location. Switching for general lighting is controlled via the touch screen near reception. Switching for circulation lighting controlled via PIR and photo-electric sensors. Switching for meeting room lighting is controlled via PIR and through a manual override switch in each meeting room.
• Window blinds have been programmed for full automation with manual override function controllable from the touch screen near reception and from within the Board Room for Board Room window blinds.
The lighting has been fully programmed and commissioned in accordance with the GBCA Fitout Lighting Control document produced by Vision Design.
Feel free to contact me with any further queries you may have.
Kind regards, Joseph Gebaily Technical Leader NSW Commissioning
Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia t +61 2 8338 9899 d +61 2 9019 8845 m +61 419 748 847 f +61 2 9019 8899 [email protected] dynalite-online.com