Model IE36CT4 IEC Indoor Current Transformer Design Characteristics Construction - epoxy • Base Plate - electro galvanized steel • Primary Terminals - copper or brass • Tested per IEC 61869-2 • Ambient Temperature - design suitable from • -25°C thru 40°C Altitude - design suitable up to 1000m above • sea level Other technical specifications may be available • upon request. Required Technical Specifications Product Data Service conditions • Insulation level • Frequency • Number of secondaries • Current ratio • Please refer to our website www.gedigitalEnergy.com/iti for complete product offering 1 of 2 Subject to change without notice Type (Model) Symbol UOM IE36CT4 Highest Voltage for Equipment (r.m.s.) U m (kV) 36 Test Voltages (kV) 70/170 Rated Frequency f R (Hz) 50 or 60 Maximum Rated Primary Current I n (A) 1500 Secondary Rated Current (A) 1 or 2 or 5 Rated Short-Time Thermal Current (1s) I th (kA) 1250 x I n ; Max. 50 Rated Dynamic Current I dyn (kA) 2.5 I th ; Max. 125 Weight ± (10%) (kg) 21 Rated burden for each secondary • Accuracy class for each secondary • Standards • Continuous primary current • Short time thermal current •