Top Banner
Mark Adamiak GE Grid Automation Ethernet ISO/IEC 8802-3 Ethertype SV R-SV UDP/IP Multicast t GOOS E R- GOOS E UDP/IP Multicast t 1588 MMS TCP/I P SNTP UDP/I P IEC 61850 Solutions via R-GOOSE and R-SV Profiles
14

IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

Feb 15, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

Mark AdamiakGE Grid Automation

Ethernet – ISO/IEC 8802-3 Ethertype

SV R-SV

UDP/IP

Multicast

t

GOOS

E

R-

GOOS

E

UDP/IP

Multicast

t

1588 MMS

TCP/I

P

SNTP

UDP/I

P

IEC 61850 Solutions viaR-GOOSE and R-SV Profiles

Page 2: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

2GE Title or job number

3/31/2017

Indoor GOOSE….

Page 3: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

3GE Title or job number

3/31/2017

61850 GOOSE at a Router:

GOOSE/SV

message

GOOSE• No IP Address

• No Transport

o No UDP

o No TCPBit

Bucket GOOSE after router

Requires Router

Configuration –

Vendor Specific &

NOT Interoperable

L2 to L3 Mapping

Routed

GOOSE/SVw/ UDP/IP

Router

Page 4: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

4GE Title or job number

3/31/2017

Communication NEEDS:Networked Publish/Subscribe Message

• Should be routable

– Multicast to reach multiple subscribers

• The Integrity of the Publisher/Subscriber should be validated

• Message should be authenticated

• Message should be able to be encrypted

• Should accommodate large message size

• Should manage the Authentication and Encryption key

Page 5: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

5GE Title or job number

3/31/2017

Committee Approved Technical Report:

IEC 61850:

COMMUNICATION NETWORKS AND

SYSTEMS FOR

POWER UTILITY AUTOMATION –

Part 90-5: Use of IEC 61850 to transmit

synchrophasor information according to

IEEE C37.118

Now - Written into 61850 Ed.

2.1….TBR

Page 6: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

6GE Title or job number

3/31/2017

Mark’s Proposed name for the Networked GOOSE:

Networked Object Oriented Substation

Event

The NOOSE !

Page 7: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

7GE Title or job number

3/31/2017

Name Rejected….So we have:

• R-GOOSE (for Routed GOOSE)

• For routing of Event Data

And

• R-SV (for Routed Sample Values)

• For routing periodic data

Page 8: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

8GE Title or job number

3/31/2017

IEC 61850 Profiles

Ethernet – ISO/IEC 8802-3 Ethertype

SV R-SV

UDP/IP

Multicast

GOOSER-

GOOSE

UDP/IP

Multicast

IEEE

1588

9-3 - PTP

MMS

TCP/IP

SNTP

UDP/IP

SimpleNetworkTimeProtocol

PrecisionTimeProtocol

GenericObjectOrientedSubstationEvent

ManufacturingMessagingSpecification

SampleValues

RoutedSV

RoutedGOOSE

Page 9: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

9GE Title or job number

3/31/2017

IEC 90-5 Data Model

Total Max Size:

65535 bytes

SPDU:

Session

Protocol

Data

Unit

Payload can be

Encrypted

Keyed Hash

Page 10: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

10GE Title or job number

3/31/2017

Multicast Path Establishment viaInternet Gateway Management Protocol – IGMP Ver. 3

Synchrophasor

Publisher

Synchrophas

or Subscriber

L2

Switch

Potential Firewall Issues

w/ IGMPv3

Page 11: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

11GE Title or job number

3/31/2017

Application:Substation to Substation

Substation

1

Substation

2

Substation

n

The

Clou

d - Transfer trip

- Block

- Permission

- Echo

The Cloud:

- Routers

- Firewalls

- Multi-media

Page 12: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

12GE Title or job number

3/31/2017

New Requirements: Wide Area RAS

Page 13: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

13GE Title or job number

3/31/2017

MicroGrid Control Reference Architecture

Page 14: IEC 61850 Solutions via R-GOOSE and R-SV Profiles of R-GOOSE and R...IEC 61850 Solutions via R-GOOSE and R-SV Profiles. 2 GE Title or job number 3/31/2017 Indoor GOOSE…. 3 GE Title

14GE Title or job number

3/31/2017

Synchrophasor Use Case