Page 1
1
CHEN64372: Distillation System Design
HYSYS Training
February 2013
1 – Getting Started with HYSYS
Open the HYSYS Getting Started Guide.pdf document and start HYSYS.
You can start HYSYS by doing one of the following:
1. From the Start > All Programs menu, select AspenTech > Process Modeling V7.3 > Aspen HYSYS >
Aspen HYSYS command.
2. Follow the path: C:\Program Files (x86)\AspenTech\Aspen Hysys V7.3\hysys.exe.
Work through the Getting Started Guide to start getting familiar with the concept of [steady state] process
simulation.
Your aim is to:
• familiarise yourself with HYSYS interfaces
• successfully open and save (in your own directory!) a HYSYS file
• learn how to interrogate a pre-prepared simulation case
• learn how to make changes to a pre-prepared simulation case
• start to become familiar with the Workbook feature of HYSYS
Note that AspenTech packages can only be run from University PCs (for licensing reasons). AspenTech
Process Modeling is available in B12, C32 of the Mill and the Barnes Wallis Cluster.
2 – Creating a process flowsheet in HYSYS
Intended learning outcomes:
• use HYSYS to set up a process flowsheet simulation
• view simulation inputs and check outputs using the Workbook function
Refrigerated Gas Plant – Workshop example kindly provided by AspenTech
Start HYSYS by doing one of the following:
1. From the Start > All Programs menu, select AspenTech > Process Modeling V7.3 > Aspen HYSYS >
Aspen HYSYS command.
2. Follow the path: C:\Program Files (x86)\AspenTech\Aspen Hysys V7.3\hysys.exe.
Page 2
2
Background
Model description
In this HYSYS example we will build the above flowsheet by following the ste-by-step instructions below.
The feed (To Refrig) is a natural gas stream which may possibly contain a small amount of liquid (removed
in Inlet Separator if present). Before the gas can be sent to the export pipeline it must be chilled to knock
out any heavy hydrocarbons (which are removed in a second 2-phase separator). The gas is cooled by a
refrigerated chiller (called Chiller). In this model the refrigerant side of the exchanger is not simulated so a
Cooler unit operation is used. The feed gas is pre-chilled in a Heat Exchanger unit operation (Interchanger)
using the cold gas leaving the Low Temperature Separator.
The specification for the exported gas is that the dew point temperature at a pressure of 60 bar must not
be higher than -15 C. To simulate this a copy of the product stream is created called HC Dewpoint. A
Balance block (BAL-1) is used to copy the composition of the Sales Gas into this new stream. The other
conditions of the HC Dewpoint stream are set to 60 bar and vapour fraction of 1 (i.e. to be at its dew point
at 60 bar). Finally an Adjust block (ADJ-1) is used to automatically adjust the chiller exit until the 60 bar dew
point is at the specification of -15 C.
Creating a Fluid Package
The first step in HYSYS is to create a Fluid Package which is a set of components and your choice of a
physical property calculation method.
1 Start HYSYS and use menu option File > New > Case to create a new simulation (alternatively click on the
New Case icon or press Ctrl-N)
2 The simulation basis manager appears. This is where you choose components and physical property
methods. To add a component list, click on the Add button.
Page 3
3
3 The add component form appears:
Add the following components: Methane, Ethane, Propane, i-Butane, n-Butane, i-Pentane, n-Pentane,
n-Hexane, Nitrogen, H2S, CO2.
You will see some of these components displayed at the top of the list of available components. Click on
the component to Select it and then click on the Add Pure button. For some of the other components
e.g. Nitrogen you will need to start typing the name in the Match field before you can select it.
When you have finished adding components, close the components window.
4 Switch to the Fluid Pkgs tab and click on the Add button:
Page 4
4
5 Scroll down through the list of available property packages and select the Peng Robinson equation of
state. (This is a good general purpose package for hydrocarbons.) Rename the fluid package "GasPlant"
and close the Fluid Package window.
Creating a Process Flowsheet
6 Click on Enter Simulation Environment – see Step 4. The PFD
(Process Flow Diagram) window will open.
You can now start adding streams and unit operations using
the Palette (use F4 to make it appear and disappear or press
button )
a) Left-click once on an item, move into the window and
left-click again to 'drop' the item there, or
b) Drag and drop an item by using the right-click button
(click, hold, drag, let go)
7 Add a stream. Double-click on the stream to open its input form.
Name: ToRefrig
Temperature: 15°C
Pressure: 6200 kPa
Molar flow: 1440 kmol h–1
Page 5
5
Click on Composition in the left pane and enter the stream composition. Close the input form for the
stream ToRefrig. As all properties of this stream are now determined, the colour of the bar at the
bottom of the input form will have changed from yellow to green. Additionally, the colour of the stream
icon will have changed from light to dark blue.
8 Next add a Separator unit operation on to the flowsheet to model the Inlet
Separator. It will be shown in Red as there are no streams connected yet.
Double click on the Separator to open its input form and select To Refrig as
the input stream. Enter the names of the product streams Inlet Sep Vap
and Inlet Sep Liq.
As soon as you have entered
the name of the second product
stream it will solve the
separator. (Note that no liquid
is produced.)
Click on the Worksheet tab to
see the results for the streams
connected to this unit
operation. (Note there is no
liquid product produced.)
Save your simulation (in your
p:\ drive).
Name To Refrig Inlet Sep Liq Inlet Sep Vap
Vapour 1 0 1
Temperature [C] 15 15 15
Pressure [kPa] 6200 6200 6200
Molar Flow [kgmole/h] 1440 0 1440
Mass Flow [kg/h] 29884.89251 0 29884.89251
Std Ideal Liq Vol Flow [m3/h] 88.29754564 0 88.29754564
Molar Enthalpy [kJ/kgmole] -81253.10473 -111185.1717 -81253.10473
Molar Entropy [kJ/kgmole-C] 149.3658883 118.6952453 149.3658883
Heat Flow [kJ/h] -117004470.8 0 -117004470.8
mole fractions
Methane 0.7576
Ethane 0.1709
Propane 0.0413
i-Butane 0.0068
n-Butane 0.0101
i-Pentane 0.0028
n-Pentane 0.0027
n-Hexane 0.0006
Nitrogen 0.0066
H2S 0.0003
CO2 0.0003
Page 6
6
9 Add streams and unit operations to complete the flowsheet shown in the diagram on page 1.
i) Interchanger: Heat Exchanger Unit Operation – Note that there are several types
of heaters and coolers. Take care about which streams you allocate to the Tube
side and Shell side of the heat exchanger! The stream Inlet Sep Vap should enter
the Tube side and the stream LTS Vap should enter the Shell side.
Tube-side Delta-P 35 kPa; Shell-side Delta-P 5 kPa (Parameters form)
Exchanger UA 2.7e5 kJ/C.h (Parameter form or Specs form)
Model (Exchanger Design(Weighted) (Parameters form)
Do you understand why the message 'Not solved' appears?
ii) Chiller: Cooler Unit Operation
Delta-P 35 kPa
Enter a starting guess for the exit temperature of -16 C. Add this in the input form for the exit stream
“Gas to LTS”
Note that you must define an Energy stream for the Chiller (to represent the cooling duty) called
“Chiller Q”
Page 7
7
ii) Low Temperature Separator – a Separator Unit Operation
The Low Temperature Separator is referred to as 'LTS' in stream names.
10 Viewing the process flow diagram
Can you tidy up the layout of the flowsheet for ease of use and clarity?
Hint: Right-click on a label for a stream or unit operation, select "Move/Size Label", click on the white
box around the label and drag the box to move the label.
11 Viewing stream data using the Workbook – icon is in the tool bar:
The Workbook presents tables of data for Material streams, Energy streams, Stream compositions and
summarises the Unit Operations present.
Page 8
8
12 The model should completely solve with the above data. Click on the Workbook icon to see a summary
of the stream results, which should match these:
Adding Balance and Adjust blocks
13 Drop a Balance block on to the flowsheet (near to the Sales Gas stream). A Balance block is at the
bottom left of the Palette. Double click on it to open the input form:
Select Sales Gas as the Inlet Stream and enter “HC Dewpoint” as the name of the Outlet Stream. Switch
to the Parameters tab and select the Component Mole Flow option for the type of Balance. This simply
copies the molar flows of each component from the inlet stream to the outlet stream but leave the
other data undefined. Close the Balance input form.
Name To Refrig Inlet Sep Vap Inlet Sep Liq Gas to Chiller
Vapour Fraction 1 1 0 0.96721349
Temperature [C] 15 15 15 -4.618347677
Pressure [kPa] 6200 6200 6200 6165
Molar Flow [kgmole/h] 1440 1440 0 1440
Mass Flow [kg/h] 29884.89251 29884.89251 0 29884.89251
Liquid Volume Flow [m3/h] 88.29754564 88.29754564 0 88.29754564
Heat Flow [kJ/h] -117004470.8 -117004470.8 0 -119033606.8
Name LTS Vap Sales Gas Gas to LTS LTS Liq
Vapour Fraction 1 1 0.904129152 0
Temperature [C] -16 9.680660011 -16 -16
Pressure [kPa] 6130 6125 6130 6130
Molar Flow [kgmole/h] 1301.945978 1301.945978 1440 138.0540217
Mass Flow [kg/h] 25597.02898 25597.02898 29884.89251 4287.863526
Liquid Volume Flow [m3/h] 77.92694944 77.92694944 88.29754564 10.3705962
Heat Flow [kJ/h] -106166138.9 -104137002.9 -120569162.7 -14403023.74
Page 9
9
14 Double click on the HC Dewpoint stream to open its input form. You can see the flow is shown in black
(i.e. a result not a model input) as 1302 kmol/h. Enter the pressure as 6000kPa (60 bar) and set the
Vapour Fraction to 1 (i.e. at its dew point). The stream should now calculate and the dew point
temperature should be displayed as -15.82°C.
15 You can change the temperature of the Gas to LTS stream manually and see how the dewpoint
temperature of the Sales Gas changes. It is convenient to use the Workbook:
16 We want the dew point to be exactly -15°C. Instead of manually changing the temperature of the
Chiller exit stream, we will use an Adjust block to automatically do this. Click on the Adjust block icon
, drop it onto the flowsheet and open its input form.
Page 10
10
The Adjusted Variable will be the temperature of stream Gas to LTS. Click on the Select Var... button to
specify this.
In the same way specify the Temperature of stream HC Dewpoint as the Target variable. Specify -15°C
as the value of the Target Variable.
There is a warning about Unknown Maximum. Switch to the Parameters tab: Enter -30°C as the
minimum value for the adjusted variable and -5°C as the maximum. The Adjust block should solve as
soon as you have entered these limits.
Page 11
11
Check the temperature of stream HC Dewpoint – it should be -15°C (plus or minus the tolerance of
0.1°C). Check the temperature of stream Gas to LTS – it should be close to -15.17°C.
17 Open the workbook and check your results.
18 Save your simulation (in your p:\ drive).
3 – Binary Distillation Modelling in HYSYS
Intended learning outcomes:
• use HYSYS to predict binary vapour-liquid equilibrium
• use the shortcut distillation model in HYSYS for a binary separation
• use the rigorous distillation model in HYSYS for a binary distillation
• use the databook and case study tools in HYSYS
A binary mixture of benzene (1) and toluene (2) is to be separated by distillation at atmospheric pressure,
101.325 kPa. The feed and products are all saturated liquids at atmospheric pressure. You may assume that
the Peng-Robinson equation of state is suitable for representing this mixture.
Name To Refrig Inlet Sep Vap Inlet Sep Liq
Vapour Fraction 1 1 0
Temperature [C] 15 15 15
Pressure [kPa] 6200 6200 6200
Molar Flow [kgmole/h] 1440 1440 0
Mass Flow [kg/h] 29884.89251 29884.89251 0
Liquid Volume Flow [m3/h] 88.29754564 88.29754564 0
Heat Flow [kJ/h] -117004470.8 -117004470.8 0
Name Gas to Chiller LTS Vap Sales Gas
Vapour Fraction 0.968893565 1 1
Temperature [C] -4.231353288 -15.17291076 9.701386445
Pressure [kPa] 6165 6130 6125
Molar Flow [kgmole/h] 1440 1310.029538 1310.029538
Mass Flow [kg/h] 29884.89251 25818.23339 25818.23339
Liquid Volume Flow [m3/h] 88.29754564 78.50266912 78.50266912
Heat Flow [kJ/h] -118983714.8 -106845197.8 -104865953.8
Name Gas to LTS LTS Liq HC Dewpoint
Vapour Fraction 0.909742734 0 1
Temperature [C] -15.17291076 -15.17291076 -15.00034875
Pressure [kPa] 6130 6130 6000
Molar Flow [kgmole/h] 1440 129.9704623 1310.029538
Mass Flow [kg/h] 29884.89251 4066.659125 25818.23339
Liquid Volume Flow [m3/h] 88.29754564 9.794876523 78.50266912
Heat Flow [kJ/h] -120449656.4 -13604458.55 -106744583
Page 12
12
1 Start HYSYS and Open a New Case.
2 Create a Fluid Package
Add Components Benzene and Toluene by typing in to Match Full name/synonym. In the Fluid Pkgs
tab, Add the fluid package Peng-Robinson. Enter the Simulation Environment.
3 Add a stream to the flowsheet using the Palette. Use HYSYS to generate vapour-liquid equilibrium
data at atmospheric pressure. Plot the equilibrium data – i.e. mole fraction of benzene in the vapour
phase (y-axis) vs. mole fraction of benzene in the liquid phase (x-axis). Equilibrium information may
be obtained from Feed stream property table (K value).
4 Add a Feed stream with the following flow rate, composition and condition and product purities:
Composition (mole fraction of benzene)
Flow rate
(kg/h)
Feed thermal
condition, q
Feed,
z1
Distillate,
xD,1
Bottom
product, xB,1
30,000 1 0.44 0.975 0.035
Add a Short Cut Distillation unit to the process flow diagram.
Double-click on the unit to open the dialogue box. In the Design tab, on the Connections page,
provide names for the product streams and the reboiler and condenser duties.
`
In the Design tab, enter the design Parameters (including key components, their purities and the
actual reflux ratio once the minimum reflux ratio has been calculated). Note the minimum reflux
ratio.
You may assume that the column pressure is uniform and equal to atmospheric pressure. Select an
External Reflux Ratio that is 10% greater than the minimum reflux ratio to determine the number of
stages required for the separation.
Page 13
13
The light key component is that which is mainly recovered in the Distillate and the heavy key
component is that recovered to the Bottom product.
View the results in the Performance tab – note the minimum reflux ratio, Rmin, actual reflux ratio, R,
and minimum number of stages, Nmin, for the required separation, as well as the duty of the
condenser and reboiler.
5 Apply the shortcut distillation model repeatedly for R/Rmin ratios of 1.02, 1.05, 1.1, 1.2, 1.5 and 2.
Record the results of:
External reflux ratio
Actual number of trays
Condenser duty
Reboiler duty
You may wish to plot the number of stages required (y-axis) vs. the reflux ratio (x-axis).
6 Use Databook to record multiple ‘states’. Select Databook from the Tools menu.
In the Databook form that appears, click Insert and then find the Object (the shortcut column) and
Variable (e.g. External reflux ratio) that you wish to select. Click Add. Repeat for the other variables
you wish to Add (Actual trays, condenser duty, reboiler duty). Close the Variable Navigator.
In the Data Recorder tab of the Databook, Add an Available Scenario and give it a name (e.g. Reflux
ratio). Check the Include boxes for all the variables.
Page 14
14
Allow both the Column form (on the Design Parameters page) and the Databook form to be visible.
Enter the actual reflux ratio for the column (e.g. the value 1.02@Rmin) and click on Record in the
Databook form. Give the new solved state a name (e.g. “1.02Rmin”) then click OK. You can View your
results – select to view as a Table.
7 Using a Case study to generate multiple ‘states’. Choose the Case Study tab in the Databook form.
Add a case study and give it a name (e.g. Reflux ratio case study). As we have already defined
variables for the Databook, these are available for selection. For a case study, we need to select at
least one Independent variable, and select one or more Dependent variables. Here we select the
External reflux ratio as the independent variable and all the others as dependent variables.
Click on View to see the Case Studies Setup form; input the upper and lower bounds for the variable
(Low Bound, High Bound) and the step size. Choose a lower bound close to Rmin and an upper bound
of close to twice that value, with a relatively small step size (e.g 0.03 so that results close to Rmin can
be seen). Click Start and then click on Results (in a Table).
8 To carry out of rigorous simulation of a distillation column, create a new feed stream identical to the
first (apart from the name); add a rigorous distillation column.
Double-click on the column to open the Distillation Column Input Expert window and follow it to set
up the simulation. You will need to enter names for material and energy streams.
Page 15
15
Use the result of the shortcut simulation to provide initial values for the number of stages and feed
stage location:
Column with 22 trays, and feed on the 13th
stage (from the top)
Condenser type: Total Condenser (i.e. liquid product and liquid reflux)
Reflux ratio of 1.73
Distillate flow of 150 kmol h–1
Condenser temperature 81°C
In the Input Expert on page 1 enter the number of stages, feed stage location, type of condenser and
names of material and energy streams. When these variables have all been specified, the Next>
button will become active. On page 2, leave the Reboiler Configuration with the default settings.
Click Next> to continue.
On page 3 of the Input Wizard, enter the condenser and reboiler pressure values as 101.325 kPa and
the pressure drop in the condenser as 0. Click Next>.
Click on Next> and continue to page 4 of the input expert. Temperature Estimates are not usually
needed; click on Next> to skip this step and to go to the final page of the Input Expert. Enter the
estimated values for distillate flow rate and reflux ratio (on a molar basis).
Click on Done once the Inputs are entered. The Column dialogue box will appear. As this is a new
column it will not automatically solve.
Page 16
16
Switch to the Monitor page in the Design tab. This window is a good place from which to run the
column. Note there are four specifications: the two created by the Input Expert are Active (i.e. the
Active box is checked). To create an initial solution, click Run the column simulation. Use the
Worksheet tab on the column input form to check your results. The flow rates of distillate and
bottom product should be 150 and 199 kmol h–1
respectively.
9 At this stage, you have created two basic specifications (which can be changed later) for the
overhead product flow rate and the reflux ratio. To set the column specifications to describe the
required separation, it is convenient to use the Monitor page in the Design tab. To ensure that the
required separation is achieved, you can add alternative specifications. Whenever you set column
specifications, you need to ensure that the number of Degrees of Freedom is zero, or the column will
not run. If you set too few, or too many, specifications, this criterion will not be met. The number of
degrees of freedom is shown on the Monitor page of the Design tab. Click on Add Spec… in the
Design tab to add specifications. Select Column Component Fraction and complete the component
fraction form for both the distillate stream and bottom product. Rename the specification to
something specifically meaningful.
Be sure to check the “Active” flag for the new specifications (and uncheck it for the specifications you
will no longer be using) so that the number of degrees of freedom remains zero.
10 The results of the simulation can be seen in the Performance tab. Various Column profiles can be
generated, e.g. to show molar flows, and the Plots tab allows other results, such as K values, to be
tabulated or plotted.
Page 17
17
Compare the reflux ratio required to meet the product specifications with that predicted by the
shortcut model. What are the main assumptions of the shortcut model? Consider the rigorous
simulation results to decide whether the assumptions are valid in this case.
11 Use the rigorous model to explore the relationship between number of stages and reflux ratio. Be
sure to set the specifications in terms of the separation performance. Repeat the rigorous simulation
of the column when it has fewer stages (starting from close to Nmin calculated by the shortcut model)
and more stages (up to around four or five times Nmin).
Plot your results and i) assess how the reflux ratio changes with the number of stages; ii) compare
the rigorous calculated value of Rmin to the minimum reflux ratio calculated using the shortcut model.
0
10
20
30
40
50
0 1 2 3 4 5
No
. st
ag
es
Reflux ratio
Page 18
18
4 – Distillation Simulation in HYSYS
Intended learning outcomes:
• use HYSYS to set simulate multicomponent distillation columns
• use the simulation to obtain simulation results
• change simulation inputs
Vinyl chloride separation – Workshop example kindly provided by AspenTech
Model Description
In this HYSYS example we will build the above flowsheet to separate a mixed stream of Vinyl Chloride, 1-2
Dichloroethane and HCl by following the step-by-step instructions below. The first distillation column (HCl
Column) removes HCl from the mixture as a vapour top product (HCl Out). The bottom product of this
column (HCl Col Residue) flows into the second column which separates the Vinyl Chloride top product
from the 1,2-Dichloroethane.
1 Open a new Case in HYSYS. C:\Program Files\AspenTech\Aspen HYSYS 2006.5\hysys.exe
2 Setting Preferences
Check your preferences – which Unit Sets are you using; in what format will results be reported, etc.
Open the Tools menu, select Preferences and click on the Variables tab.
3 Creating a Fluid Package
In the Simulation Basis Manager, add Components by typing in to Match Formula or Full
name/synonym. Then close the Components List View window.
Vinyl Chloride C2H3Cl or VinylChloride
1,2-Dichloroethane C2H4Cl2 or 12DiChloroEthane
HCl
In the Fluid Pkgs tab, Add the fluid package SRK (Soave-Redlich-Kwong). Change the Name of the
Fluid Package to SRK. Close the Fluid Package form and then Enter Simulation Environment.
Page 19
19
4 Simulating a Column
Add unit operations or streams on to the flowsheet using the Palette. Add the feed stream and name
it HCl Column Feed. Enter the stream data:
Temperature 50°C
Pressure 2500 kPa
Define the stream Composition. Set the Composition Basis to Mass Flows (and then close Basis box).
Vinyl Chloride 60000 kg/h
1,2 Dichloroethane 80000 kg/h
Hydrogen Chloride 35000 kg/h
Close the Input Composition form. The green status bar
indicates that the stream is fully defined –in the Conditions you
should see the stream properties have been determined.
Add a distillation Column unit operation to the flowsheet using the Distillation Column
Icon in the Palette of unit operations. Place it to the right of the feed stream.
Double click on the Column to open its input form. In Input Expert on page 1 enter:
Condenser Type: Full Reflux (i.e. vapour product and liquid reflux)
Number of stages: 15; Feed stream is HCl Column Feed; Inlet stream is on 8_Main (Stage 8
from the top)
Condenser Energy Stream: Q Cond1
Page 20
20
Reboiler Energy Stream: Q Reb1
Ovhd Vapour Outlet: HCl Out
Bottoms Liquid Outlet: HCl Col Residue
When all of the above specifications have been given, go to page 2 of the Input Expert, which lets you
choose the type of reboiler. Leave the default settings which are equivalent to a simple kettle
reboiler model.
Click on Next>. One the third page enter these pressure values:
Condenser pressure: 2400 kPa
Condenser pressure drop: 20 kPa
Reboiler pressure: 2430 kPa
Click Next> on page 3 of the input expert. Temperature Estimates are not usually needed. On the
final page of the Input Expert, enter estimated values for distillate flow rate and reflux ratio (on a
mass basis):
Vapour Rate: 35200 kg h–1
Note that HCl is to be recovered; its feed is 35000 kg h–1
.
Reflux ratio: 1.4
Click on Done once the Inputs are entered. As this is a new column it will not automatically solve.
Page 21
21
Click on Monitor (Design page) and review the specifications: there are four specifications – the two
created by the Input Expert are Active (i.e. the Active box is checked). To create an initial solution,
Run the column simulation.
Check your results in the Worksheet tab on the column input form:
Name HCl Column Feed HCl Out HCl Col Residue
Vapour Fraction 0 1 0
Temperature [C] 50 -2.173 143.5
Pressure [kPa] 2500 2400 2430
Molar Flow [kgmole/h] 2728.5 963.0 1765.5
Mass Flow [kg/h] 1.75E+05 3.52E+04 1.40E+05
Liquid Volume Flow [m3/h] 169.48 40.43 129.05
Heat Flow [kJ/h] -2.141E+08 -9.058E+07 -9.450E+07
Compositions (mole frac)
VinylCl 0.3519 0.0035 0.5419
12-ClC2 0.2963 0.0000 0.4579
HCl 0.3518 0.9965 0.0002
Save your Simulation (on the p: drive).
5 Specifying the Column Performance
The desired separation is to recover Vinyl Chloride in the bottom product – no more than 0.12@10–3
mole fraction of Vinyl Chloride is permitted in the overhead product – and to recover HCl in the top
product (with no more than 0.30@10–3
mole fraction HCl in the bottom product).
Use the Monitor page to check that the number of Degrees of Freedom is zero. If you set too few, or
too many, specifications, the column will not run.
To check the current performance of the column, Add new (inactive) specifications.
• Column Component Fraction (molar) of Vinyl Chloride in the HCl Out product = 0.12@10–3
• Column Component Fraction (molar) of HCl in the HCl Col Residue stream = 0.3@10–3
Page 22
22
Note that you can rename the specifications to something more meaningful than the default. Close
the dialogue boxes after entering the new specifications.
The new specifications have been added to the list but are not Active. You can see the current value
of the newly specified variables. Check the Active box for the first new specification. The status
changes from green to red as the number of degrees of freedom is -1. Uncheck the Ovhd Vap Rate
specification.
The column will solve using the new combination of specifications. Now activate the second new
specification and uncheck the Reflux Ratio specification.
What is the calculated Reflux Ratio? It should be 1.22.
Save your Simulation, if you have not already done so!
6 Reviewing the Column Performance
The Column dialogue box allows access to a great deal of information about the column
performance. For example, in the Performance tab:
Summary of the overall mass balance on the column and the stream compositions;
Profiles of temperatures, pressures, flow rates, as well as the reflux ratio and reboil ratio
(molar ratio of vapour leaving reboiler to bottom product flow rate);
Plots (graphical or tabulated) of Tray by Tray properties in the column.
Explore some of these facilities in order to understand better the separation that is being carried out.
7 Adding the Second Distillation Column
The second distillation column shown in the flowsheet diagram above Step 1 separates the bottom
product of Column 1 to produce Vinyl Chloride (top product) and 1,2-Dichloroethane (bottom
product). Add a second distillation column and use the input wizard to enter the following data:
10 stages with the feed entering on stage number 7;
Total condenser;
Default reboiler (equivalent to simple kettle reboiler);
Condenser pressure 900 kPa; Condenser pressure drop 20 kPa; Reboiler pressure 930 kPa;
Mole fraction of 1,2-Dichloroethane in the overhead product is 0.005;
Mole fraction of Vinyl Chloride in the bottom product is 0.001.
Check your stream results for the column and plot the column temperature profile (Performance
Tab, Plots page). They should be similar to those shown below:
Page 23
23
Name HCl Col Residue VC Product DCE Product
Vapour 0 0 0
Temperature [C] 143.3 56.5 176.6
Pressure [kPa] 2430 900 930
Molar Flow [kgmole/h] 1768.9 964.6 804.4
Mass Flow [kg/h] 140012 60439 79573
Liquid Volume Flow [m3/h] 129.3 65.6 63.7
Heat Flow [kJ/h] -94.5e6 16.64e6 -116.4e6
Mole Fractions:
VinylCl 0.5427 0.9945 0.0010
12-ClC2 0.4570 0.0050 0.9990
HCl 0.0003 0.0005 0.0000
Condenser duty: 47.5e6 kJ/h Reboiler duty: 42.2e6 kJ/h
Temperature Plot: Flow Plot:
Use your simulation to check the feed stage location on both columns.
Add a heat exchanger to check the effect on reboiler duty of preheating the feed to column 1
Check the effect of letting down the pressure of the feed to column 2 and of cooling the feed to column 2.
In each case, assess the reboiler duty to evaluate the effect of the change on distillation performance.
Page 24
24
5 – Physical property modelling in HYSYS
Intended learning outcomes:
• Understand the role of physical and thermodynamic property modelling in process design
• Appreciate the potential impact of inaccurate models on process design
Vapour-liquid equilibrium modelling
Example 11.2 in Sinnott and Towler (Chemical Engineering Design, 2009, p. 698) applies the McCabe-Thiele
method for distillation column design. The data of Kojima et al. (1968) are used. [Kojima et al., 1968,
Kagaku Kogaku 32, 149 – the data in Table 1 are provided in the file Acetone-water VLE data.xls.]
Table 1 Vapour-liquid equilibrium data for acetone and water at atmospheric pressure (101.3 kPa).
Temperature
(°C)
Mole fraction
acetone in
liquid
Mole fraction
acetone in
vapour
74.8 0.05 0.6381
68.53 0.1 0.7301
65.26 0.15 0.7761
63.59 0.2 0.7916
62.6 0.25 0.8034
61.87 0.3 0.8124
61.26 0.35 0.8201
60.75 0.4 0.8269
60.35 0.45 0.8376
59.95 0.5 0.8387
59.54 0.55 0.8455
59.12 0.6 0.8532
58.71 0.65 0.8615
58.29 0.7 0.8712
57.9 0.75 0.8817
57.49 0.8 0.895
57.08 0.85 0.9118
56.68 0.9 0.9335
56.3 0.95 0.9627
1 Use HYSYS to predict the vapour-liquid equilibrium behaviour of the same mixture (at 101.3 kPa) using
the following physical property models:
a. UNIQUAC using i) the fitted parameters available in HYSYS and ii) parameters estimated using
UNIFAC (VLE);
b. NRTL;
c. PRSV.
2 Once you have added the components Acetone and Water to your file, Add three property packages.
The first will be selected as your ‘default’ property package.
Page 25
25
3 Generating vapour-liquid equilibrium data in HYSYS is straightforward but it requires the stream
composition to be specified, so becomes repetitive. The Adjust function is useful for changing the
composition of a mixture.
Here I have treated the Pure Acetone stream flow rate as fixed, and select the Pure Water flow rate to
be the “Adjusted variable”, and require the flow rate of the Acetone-Water mixture (the “Target
variable”) to be constant at 100 kmol h–1
:
Together with the Databook feature, it is possible to change the “Independent variable” (in this case
the Pure Acetone flow rate) over a specified range (effectively 0 to 100 kmol h–1
) and collect the
vapour-liquid equilibrium results that are generated.
Page 26
26
Results may be viewed as a graph or table (or a ‘transposed table’ which can then be copied and pasted
conveniently into Excel).
4 Generate the x-y data for each physical property package (and for UNIQUAC with the default and
UNIFAC VLE parameters). You will need to change the Fluid Package for each feed stream and for the
mixer so that the same fluid package is used to model all streams in the process.
Alternatively, you can change the fluid package by going back to the Basis Environment (button ), on
the Fluid Pkgs tab > Flowsheet-Fluid Pkg Associations > Fluid Pkg To Use, and selecting the desired
Fluid Package from the drop-down menu.
Page 27
27
Change object by object:
Or change all objects simultaneously:
5 Compare your predicted vapour-liquid equilibrium behaviour with the experimental data. If the
experimental data are reasonably good, then they give an indication of reality – we wish to understand
which property package gives the most realistic predictions.
It is conventional to represent the experimental data as points (called ‘markers’ in Excel) without lines
between them, as no information exists between the points, and to represent the results of model
predictions as lines (without markers, as the exact values at which the model is applied is generally not
important):
6 Consider which of the three models (and which parameters) you would most trust for designing the
distillation column in this example. What might the consequences be of using a poor physical property
model?
0
10
20
30
40
50
60
70
80
90
100
0 20 40 60 80 100
Mo
l% a
ceto
ne
in
va
po
ur
Mol% acetone in liquid
Kojima experimental data
UNIQUAC