-
UNDERWATER SOUND PRESSURES ASSOCIATED WITH THE RESTRIKE OF THE
PILE IINSTALLATION DEMONSTRATION PROJECT PILES
Measurements Results for the PIDP Restrike - East Span Seismic
Safety Project on the SFOBB
Prepared by
James A. Reyff Illingworth & Rodkin, Inc.
Prepared for
State of California Department of Transportation, District 4
Division of Toll Bridge Program 111 Grand Avenue - P.O Box
23660
Oakland, CA 94623-0660
Final Report: July 23, 2003
EXECUTIVE SUMMARY The effectiveness of a two-ring bubble curtain
system in reducing underwater sound pressures during marine pile
driving was assessed through underwater sound pressure
measurements. This was conducted when the three 108m long, 2.4m
diameter cast in steel shell piles driven in 2000 as part of the
PIDP, were restruck in December of 2002. During the measurements,
the bubble curtain system was turned ON and OFF. The restrike
involved driving the piles at refusal with the hammer at maximum
energy (1,600 to 1,740 kilojoules). This condition is not
anticipated during the east span SFOBB new east span
construction.
The reduction in sound pressures provided by the bubble curtain
system ranged considerably. The direct reduction in sound
pressures, which is evaluated by comparing bubble curtain ON and
OFF measurements, for Piles 1 and 2 was 6 to 17 dB for peak
pressures and 3 to 10 dB for RMS sound pressure levels. Piles 1 and
2 were located next to each other. Reductions at Pile 3, which was
in shallower water, were over 20 dB for both peak pressures and RMS
sound pressure levels on the north side. However, the reductions on
the south side for Pile 3 were much less. Close to Pile 3 on the
south side, the reductions were on the order of 5 to 7 dB. Further
away at about 450m south, the reductions were only about 2 dB.
Uneven bottom topography around Pile 3, which could have
compromised the bubble curtain performance near the bay bottom, is
suspected to have resulted in the lower reductions to the south. It
is important to note that overall sound pressures associated with
Pile 3 were lower than those with Piles 1 and 2.
Analysis of individual pile strike impulses indicates that the
bubble curtain reduced sound pressures at all measurement positions
at frequencies above 1000 Hz. There was a reduction in sound
pressures below 500 Hz where the bubble curtain worked particularly
well (e.g., 100m north position for Pile 3).
Measurements of peak pressures made at about 100m were
consistent with the measurements made during the PIDP in 2000.
Those measurements were the basis for predictions of the maximum
peak pressures during SFOBB east span construction. With the
exception of the 450m south position, predicted peak pressures used
in the Biological Opinion were lower than those measured. At 450m
south, measured peak pressures were 5 to 8 dB higher than
predicted. Conversely, peak pressures at 450m to 500m north were 0
to 6 dB lower than predicted.
RMS sound pressure levels, which are used to define the marine
mammal safety zone, did not exceed 190 dB at any of the measurement
positions (between 65 and 500m) when the bubble curtain system was
operating. Levels of 180 dB RMS did extend out to 450m south for
Pile 1, but did not exceed 172 dB at 450m north. With the bubble
curtain OFF, the 190 dB RMS sound pressure levels extended out to
somewhere between 200m to 300m for Piles 1 and 2 and less than 100m
for Pile 3.
-
2
TABLE OF CONTENTS
Executive Summary
..........................................................................................................................................1
Introduction......................................................................................................................................................3
Project
description.............................................................................................................................................3
Descriptors used to Describe Underwater Acoustical
TRAITs..............................................................................4
Previous Investigations
......................................................................................................................................5
SFOBB PIDP 2000
.......................................................................................................................................5
Hong Kong Aviation Fuel Transfer Facility
....................................................................................................6
Canada Place Cruise Ship
Terminal................................................................................................................6
SFOBB Bubble Curtain Design
..........................................................................................................................6
Approach..........................................................................................................................................................7
Measurement Results and Discussion
.................................................................................................................8
Peak Sound Pressures and RMS Sound Pressure
Levels...................................................................................8
Impulse
Analysis.........................................................................................................................................13
Bubble Curtain
Performance........................................................................................................................14
Comparison with PIDP Results and Predictions made in the
Biological Opinion
.............................................15
Marine Mammal Safety
Zone.......................................................................................................................17
Conclusions
....................................................................................................................................................17
Table 1 Sound Pressures Measured for Pile 1, reported as
dB..............................................................................9
Table 2 Sound Pressures Measured for Pile 2, reported as
dB............................................................................11
Table 3 Sound Pressures Measured for Pile 3, reported as
dB............................................................................12
Table 4 Comparison of Predicted and Measured Sound Pressures
Pile
1..........................................................15
Table 5 Comparison of Predicted and Measured Sound Pressures
Pile
2..........................................................16
Table 6 Comparison of Predicted and Measured Sound Pressures
Pile
3..........................................................16
Figure 1 Project
Location.............................................................................................................................
3 Figure 2 Location of PIDP
Piles...................................................................................................................
4 Figure 3 Menke MHU1700T
Hammer..............................................................................................................
5 Figure 4 Sound Attenuation Devices Used for the 2000 PIDP
............................................................................
6 Figure 5 PIDP Restrike Bubble Curtain
............................................................................................................
7
-
3
INTRODUCTION
This report presents results of underwater sound pressure
measurements conducted during the restrike of test piles in the San
Francisco Bay. These test piles were previously driven in order to
develop design information for the replacement of the east span of
the San Francisco-Oakland Bay Bridge (SFOBB) and was known as the
Pile Installation Demonstration Project or PIDP. The PIDP occurred
from late September 2000 through mid-December 2000. These piles
were restruck on December 9 and 10, 2002 as part of the PIDP
Restrike. Figure 1 is a map showing the location of the new SFOBB
East Span and the accompanying project construction limits.. At the
request of the Caltrans, underwater sound pressure measurements
were conducted to both reaffirm levels measured during the PIDP and
measure the sound attenuation provided by a bubble curtain design
that will be used for production pile driving on the SFOBB East
Span construction project.
Figure 1 Project Location
PROJECT DESCRIPTION The 2000 PIDP involved the installation of
three piles into the floor of the San Francisco Bay. The plan sheet
shown in Figure 2 shows the location of each pile. The objective of
the PIDP was to test and evaluate technical, engineering and
environmental factors associated with driving large hollow steel
piles approximately 100 meters long (Caltrans 2001). The PIDP
involved utilization of two sizes of hammers, three different pile
alignment configuration, and two different types of hydroacoustic
attenuation systems.
The piles were 108 m (356 ft) long and had an inside diameter of
2.4 meters (8 feet), and an outside diameter of 2.57 m (8.5 ft).
The piles were driven in three sections, each approximately 30
meters (108 ft) long. Pile 1 was a vertical pile that had no
hydroacoustic attenuation. Pile 2 was a battered pile (driven at an
angle) that was angled to the east and included an single ring air
bubble curtain. Pile 3 was inserted at a different location and was
also battered, but angled to the west. A proprietary fabric barrier
system (Gunderboom) was used for Pile 3.
-
4
Figure 2 Location of PIDP Piles
The objectives of the PIDP Pile Restrike Project were to conduct
a geotechnical evaluation of pile stability and to demonstrate the
effectiveness of a bubble curtain system that was designed to
provide protection to fisheries resources in San Francisco Bay. For
the Restrike, a Menke hydraulic hammer, MHU1700T, with a capacity
of 1,700 kilo joules or kJ was used at or near full capacity
(Figure 3). The geotechnical evaluation was intended to demonstrate
the limits of pile "takeup" over time verify that the pile elements
of the foundation would be strong enough to support the
construction loadings that are anticipated while the footing is
still relatively young (Woods personal communications). The
criteria for stability are 670 strikes or 250 millimeters
(approximately 1 ft). A secondary objective was to evaluate a
bubble curtain system that was improved over the single-ring system
used during the 2000 PIDP. This two-ring bubble curtain discharged
considerably more air than the 2000 PIDP bubble curtain system and
was fitted much more tightly around the pile than either the
single-ring bubble curtain or the fabric barrier system.
DESCRIPTORS USED TO DESCRIBE UNDERWATER ACOUSTICAL TRAITS
Several descriptors are used to characterize underwater noise. Two
common descriptors are the instantaneous peak sound pressure and
the root-mean-square sound pressure level averaged over the
impulse, which is sometimes referred to as the sound pressure level
(SPL) or root-mean-square (RMS) level. The peak pressure is the
instantaneous absolute maximum pressure observed during each pulse
and can be presented as a pressure (e.g., Pa) or decibel (dB)
referred to some standard pressure like 1 Pa. The majority of
literature uses peak sound pressures to evaluate injuries to fish.
The SPL or RMS level is the square root of the energy divided by
the duration of an individual acoustical disturbance (e.g., pile
strike). This level, presented in dB re 1 Pa, is equivalent to the
mean square pressure level of the pulse. It has been used by NOAA
Fisheries (formerly National Marine Fisheries Service) in criteria
for judging impacts to marine mammals from underwater impulse-type
sounds1. Except where otherwise noted, sound levels reported in
this discussion are expressed in dB re 1 Pa. In this report, peak
sound pressures are referred to as peak levels and the SPL or RMS
pressure level during the impulse is referred to as the RMS
level.
1 The RMS (impulse) level is the criterion used by NOAA
Fisheries. Underwater sound measurements from the San
Francisco-Oakland Bay Bridge Pile Driving Demonstration Project
(PIDP) indicated that 90 percent of the acoustic energy for most
pile-driving impulses occurred over a 50 to 100msec period with the
energy concentrated in the first 30 to 50msec. Analysis of
underwater data gathered during the PIDP demonstrated that the
acoustic signal measured using the standard impulse
exponential-time-weighting correlated well with the RMS level
measured over the duration of the pulse.
Pile 1
Pile 2
Pile 3
-
5
It is important to note that sound pressures measured in air are
typically described as decibels referenced to a pressure of 20 Pa,
rather than 1 Pa, which is used to describe underwater sounds. The
use of 20 Pa in air is a matter of convenience, since 1 dB re 20Pa
is the human threshold of hearing in carefully controlled
laboratory conditions. Because the acoustical impedance is much
greater in water, sound intensity and propagation are very
different. Underwater and airborne sound pressures are not
comparable.
Figure 3 Menke MHU1700T Hammer
PREVIOUS INVESTIGATIONS
SFOBB PIDP 2000
To assess the environmental and technical factors involved in
driving the very large piles proposed for the San Francisco-Oakland
Bay Bridge East Span Project, a Pile Installation Demonstration
Project (PIDP) was undertaken in late 2000 in which three
eight-foot diameter steel pipe pilings were driven into the San
Francisco Bay (Illingworth and Rodkin 2001). The underwater sound
measurements were not comprehensive, but important data came from
measurements at hydrophone depths of 1 and 6 m, without a sound
attenuation system in place. Using a pile -driver energy of 900 kJ,
peak pressures of 207 dB re: 1 Pa at a distance of 103 m and 191 dB
at distance of 358 m were measured. Levels were always lowest near
the surface (1-meter depth). A spreading loss formula was derived,
which corrected for hammer size and measured excess attenuation and
yielded approximately 30 dB loss per tenfold increase in distance
(Greene 2001). Applying the spreading-loss model for received
levels and accounting for an almost doubling of hammer energy (from
900 to 1,700 kj), the corresponding equation for 1,700 kJ is:
RLpeak = 238.9 - 29.6 log(R/10) (adapted from Greene 2001)
Where RL is the peak received level in dB re 1 Pa and R is the
distance from the pile in meters for values of R between 100 and
360 meters.
During the PIDP project, measurements were taken at Pile 2 which
had a simple unconfined air bubble curtain system (see Figure 4).
There was no bubble curtain ON/OFF test, so the effectiveness of
the system could not be directly measured. Comparison of
measurements between Pile 1 and Pile 2 indicated about 0 to 2 dB
attenuation from the system. Fairly strong currents that swept the
bubbles away from the pile were suspected to limit the ABC system
performance. A Gunderboom System was used for Pile 3 (see Figure
4). This system, which is able to confine bubbles close to the
pile, was found to reduce sound pressures by about 5 to 10 dB.
-
6
Figure 4 Sound Attenuation Devices Used for the 2000 PIDP
Air bubble ring used for Pile 2 Proprietary fabric air bubble
curtain (Gunderboom) used for Pile 3
Hong Kong Aviation Fuel Transfer Facility Underwater sound
measurements were conducted for the Hong Kong Airport Fuel Transfer
Facility project to evaluate the performance of an underwater
bubble curtain (Wursig 1999). An air bubble ring with a diameter of
50 m was placed around the pile-driving operation. With the
bubbles, the RMS sound pressure level was reduced by 3 to 5dB. The
greatest sound reduction provided by the bubble curtain was from
400 to 6400 Hz. The contractor did not measure peak pressures.
Canada Place Cruise Ship Terminal At the Canada Place Cruise
Ship Terminal in Vancouver, B.C., open-ended steel pipe piles 36
inches in diameter with 0.75-inch wall thickness were driven, as
were 24-inch diameter closed-ended steel pipe piles with 0.75-inch
wall thickness (Longmuir and Lively 2001). An air bubble curtain
was developed to protect fish. It was kept as close to the pile as
practical, allowing for battered (slanted) piles to be driven. The
authors stated that a proper bubble curtain can reduce underwater
sound overpressures from pile driving by at least 85 percent (16.5
dB) and that their bubble curtain in Vancouver reduced underwater
overpressures during pile driving from more than 22 psi to less
than 3 psi (a reduction of more than 17 dB). They referred to the
Canada Department of Fisheries and Oceans criterion for fish safety
of not exceeding an explosion blast peak pressure of 14.5 psi (220
dB re: 1 Pa). The Canada Department of Fisheries and Oceans
standard for fish safety is based on mortalities immediately after
the explosion. The Vancouver study found that, perhaps due to the
repetitive nature of pile driving, the peak pressure should be less
than 4.5 psi (210 dB re: 1 Pa) to protect small fish.
SFOBB BUBBLE CURTAIN DESIGN Following the PIDP, Caltrans
consulted with experts on bubble curtains and effects of underwater
sound pressures on Fish (Greene 2001, Hastings 2001). A review of
literature and consultation with experts indicated that a properly
designed bubble curtain could provide about 10 dB of sound
attenuation. As a result, Caltrans included a two-stage bubble
curtain in the specifications for the construction project and so a
version of this bubble curtain was used for the PIDP restrike. The
bubble curtain was designed and constructed by the contractor KFM,
Joint Venture (Woods personal communications). The bubble curtain
frame supported two rings of perforated pipes that encircled the
pile. One ring of perforated pipes ran along the bottom of the
frame. The second ring of pipes was 5 meters above the bottom ring.
Air was supplied by six 45,326 liter-per-minute (1,600
cubic-foot-per-minute) compressors. During a demonstration on
December 4th, the bubbles raised the water level about a foot above
sea level, and rendered the entire area above the bubble curtain
frame a froth of white foam. A matrix of pressure sensor hoses was
linked to the air delivery pipes, manifolds and perforated pipes to
determine the pressure at various points in the system. The
objectives were to produce a bubble flux density of at least 3
cubic meters per minute per linear meters of pipeline in each
concentric ring (32 cubic feet per minute per linear foot) and
-
7
to completely surround the pile at all times and in all current
conditions with bubbles (NMFS 2002). The bubble curtain system is
shown in Figure 5.
Figure 5 PIDP Restrike Bubble Curtain
Air bubble curtain system with compressors in background. Air
bubble curtain system in operation during the PIDP Restrike
APPROACH The measurement program was designed to quantify the
effectiveness of the bubble curtain system in reducing underwater
sound pressure levels and characterize both attenuated and
unattenuated sound pressures for each of the three PIDP piles. This
required sound measurements with the system working (ON) and when
it was not operational (OFF).
Prior to measurements, plans were developed to measure at 5
different positions. One position was made at about 60m from the
pile on the barge, and four positions were both 100m and about 450m
north and south of the pile. At the four distant positions (100m
and ~450m), measurements were made 2m below the water surface and
about 2m above the bottom. A depth of about 8m was made from the
barge (60m distance position). Buoys were set at the approximate
100m and 450m positions; however, exact positions varied due to the
influence of tidal currents.
Measurements at the fixed ~100m and ~450m positions were made
using G.R.A.S. CT10 hydrophones with PCB in-line charge amplifiers
(Model 422E13) and PCB Multi Gain Signal Conditioners (Model
480M122). The signals were fed into Larson Davis Model 820
Integrating Sound Level Meters (Type 1) and Sony Model TCD-D100
Digital Audio Data Recorders (DAT).
At the ~60-meter position from the barge, a PCB Type ICP
Pressure Transducer was used to acquire the acoustic signals. The
transducer was connected to both a Larson Davis Model 820
Integrating Sound Level Meter (Type 1) and a Sony Model TCD-D100
DAT through the PCB multi gain signal conditioner. The pressure
transducer was used at this position, instead of a hydrophone
system, since peak pressure signals from the unattenuated piles
were predicted to exceed the hydrophone system limitations. The
multi-gain signal conditioner provides the ability to add gain or
boost the signal so that measurements are made within the dynamic
range of the instruments used to analyze the signals.
The peak pressures and SPLs or RMS levels were measured, either
live or subsequently from DAT recordings using the SLM. The RMS
sound pressure levels were measured with the SLM using the standard
impulse exponential-time -weighting (35 msec rise time) function of
the Larson Davis Model 820 SLM. Additional subsequent analyses of
the acoustical impulses were performed using a Larson Davis Model
2900 Real Time Analyzer. The real time analyzer provides
narrow-band frequency and waveform analysis.
-
8
The measurement systems were calibrated prior to use in the
field with a G.R.A.S. Type 42AA Pistonphone and hydrophone coupler.
The systems calibration status was checked during post calibrations
at the end of the measurement event. All systems were found to be
within 0.5 dB of the calibration levels. Pre- and post-measurement
recordings of calibration tones were made on all DAT tapes.
MEASUREMENT RESULTS AND DISCUSSION Underwater sound measurements
were made on December 9, when two PIDP piles (Piles 1 and 2) and on
December 10, 2003 when one PIDP pile (Pile 3) were driven as part
of the SFOBB PIDP Restrike. The Menke 1700 kj hammer was used at
nearly full energy. Data summaries and graphical representations of
measured data are provided in Appendix A. Hammer and bubble curtain
data are provided in Appendix B.
Much of the data collected at the deeper sensor 450 to 500m
north of the piles could not be used due to contamination. These
measurements were made from a motorized boat that was holding
position near a buoy. The boat movement caused noise on the deeper
hydrophone, and therefore, that data was discarded. Measurements
made at the shallow level (2m deep) from the barge had to also be
discarded. Unattenuated levels were quite low at this position,
indicating that there were obstructions from the barge affecting
the sound attenuation.
Peak Sound Pressures and RMS Sound Pressure Levels Pile 1 The
pile was driven by the Menke 1,700 kJ hammer in single blow mode
instead of stroke sequence mode because of technical concerns for
safe hammer operation. Hammering was in the more regular stroke
mode for the other piles. Hammering started at 10:36 with the
bubble curtain in operation at full capacity. Hammering stopped 21
minutes later at 10:57. At 11:03 hammering started again but with
the bubble curtain off and continued for about 18 minutes with a
number of brief interruptions in driving activity. Hammer energy
was mostly above 1,600 kj and the blow count was about 30 blows per
minute. Tidal currents were almost non-existent, but observations
of floating buoys at the measurements positions indicated a light
north to south current (flood). This pile driving operation was
carried out in a driving rain storm. A history of pile strikes
measured from the DB General (65m from the pile) is shown in Figure
6.
PILE 1, from Barge at 65m History of Pile Stikes at the Deeper
Sensor
160
170
180
190
200
210
220
10:3
0
10:3
4
10:3
8
10:4
2
10:4
6
10:5
0
10:5
4
10:5
8
11:0
2
11:0
6
11:1
0
11:1
4
11:1
8
11:2
2
11:2
6
11:3
0
Time
Sou
nd P
ress
ure
(dB
)
Peak
RMS
Figure 6 Time History - Pile 1
-
9
The time history of the strikes shown in Figure 6 shows a large
variation in the amplitude of sound pressures, particularly peak
pressures from strike to strike. This is possibly due to the large
variation of hammer energy used since the hammer was operating in
manual mode. Information provided on the bubble curtain operation
is inconclusive to identify any operational problems that the
bubble curtain may have experienced. There were flow meters that
failed during the bubble curtain operation, but this does not mean
that the curtain did not operate as designed. The pile was
completely surrounded by bubbles at the surface during bubble
curtain operation. Table 1 shows the sound pressure levels in terms
of peak pressure and RMS sound pressure levels for both the Bubbles
ON and Bubbles OFF condition. Time periods that best represent a
particular condition for the pile and each bubble curtain operation
mode were selected.
Peak pressures varied considerably based on direction. Peak
pressures measured at 65m were similar to those measured at 100m
north. At 450m north, pressures were about 10 dB lower than 450m
south with or without the bubble curtain (the bubble curtain
reduced pressures by 8-10 dB at both positions). Peak pressures
with the bubble curtain ON were about 5 dB lower 100m south than at
100m north. Without the bubble curtain, peak pressures were similar
at both positions.
At 65m, the shallow water measurement appeared to be shielded by
the barge or some other underwater obstruction; therefore, those
data were discarded. While peak pressures differed by only 1 dB
with and without the bubble curtain, tape recordings indicated that
the impulses with the bubbles sounded different than without the
bubbles.
In summary, RMS sound pressure levels were about 3 to 7 dB lower
with the bubble curtain ON, while peak pressures were reduced by 6
to 12 dB. Changes in waveforms and frequency spectra are discussed
later in this report.
Table 1 Sound Pressures Measured for Pile 1, reported as dB
Peak Pressures Positions Measured Distance and General Direction
from the Pile
Time Period
Bubble Curtain
Condition South ~460m
South 100m
North 65m
North 100m
North 195m
North ~450m
Water Depth = 10m 10m 9m 10m 10m 8m 10:46:30 10:52:29 am
ON Up = 194 Dn = 196
Dn = 199
Up = 201 Dn = 201
10:56:00 10:57:29 am
ON Up = 185 Dn = 189
Dn = 194
Up = 175 Dn = --
11:04:00 11:07:59 am
OFF Up = 205 Dn = 206
Dn = 204
Up = 209 Dn = 207
Up = 182 Dn = --
11:20:00 11:20:59 am
OFF Up = 194 Dn = 198
Dn = 208
Up = 194 Dn = --
Estimated Reduction Up = 9 Dn = 9
Up = 11 Dn = 10
Dn = ~9
Up = 8 Dn = 6
Up = 7 Dn = --
RMS Sound Pressure Levels
Positions Measured Distance and General Direction from the
Pile
Time Period
Bubble Curtain
Condition South ~460m
South 100m
North 65m
North 100m
North 195m
North ~450m
10:46:30 10:52:29 am
ON Up = 183 Dn = 185
Dn = 186
Up = 188 Dn = 189
10:56:00 10:57:29 am
ON Up = 175 Dn = 178
Dn = 182
Up = 162 Dn = --
11:04:00 11:07:59 am
OFF Up = 190 Dn = 192
Dn = 189
Up = 192 Dn = 194
Up = 168 Dn = --
11:20:00 11:20:59 am
OFF Up = 183 Dn = 185
Dn = 193
Up = 181 Dn = --
Up = 171 Dn = --
Estimated Reduction Up = 7 Dn = 7
Dn = ~7
Up = 4 Dn = 5
Up = 8 Dn = --
Note: Up = upper portion of water column or about 2m below the
water surface Dn = lower portion of water column or about 2-3m
above bottom.
-
10
Pile 2
The DB General barge was moved into position north of Pile 2 and
stabilized with spud piles and anchor lines. The bubble curtain
frame was lowered into the water around the pile and secured in
place on the bottom. The hammer was placed on the pile about 13:18.
Pile driving started at 13:55 with the bubble curtain on and
continued for 14 minutes stopping at 14:09. Hammering started again
at 14:20 and continued for 7 minutes without the bubble curtain
OFF. The Menke hammer was in automatic mode for most of the drive.
After about 13:53, the hammer energy was consistently above 1,500
kj and the blow count was about 30 blows per minute. Due to the
shorter driving period with the bubble curtain OFF, all
measurements could not be completed (i.e., at distances of 450m
south and 200m north). Heavy rain occurred during most of the
driving period. A history of pile strikes measured from the DB
General (60m from the pile) is shown in Figure 7.
The history plot of sound pressures shown in Figure 7 indicates
that sound pressures were more consistent than Pile 1. Table 2
presents sound pressures in terms of peak pressure and RMS sound
pressure levels for both the Bubbles ON and Bubbles OFF condition.
Time periods that best represent a particular condition for the
pile and each bubble curtain operation mode were selected. There
was a light north to south current.
Peak pressures were more consistent during the driving of Pile 2
than they were for Pile 1. All measurement positions indicated at
least 10 dB reduction in peak pressures with the bubble curtain ON,
except for the 100m north station at 2m below the water surface. An
explanation for this anomaly cannot be made, except that the tape
recording for that position sounds much louder with the bubbles
OFF. In summary, peak pressures were reduced by 9 to 17 dB and RMS
sound pressure levels were reduced by about 6 to 10 dB. At the 450m
north position, the reduction was 11-15 dB for peak pressures and
7-10 dB for RMS sound pressure levels.
PILE 2, from Barge at 60m History of Pile Stikes at the Deeper
Sensor
160
170
180
190
200
210
220
13:4
8
13:5
2
13:5
6
14:0
0
14:0
4
14:0
8
14:1
2
14:1
6
14:2
0
14:2
4
14:2
8Time
So
un
d P
ress
ure
(dB
)
Peak
RMS
Figure 7 Time History - Pile 2
-
11
Table 2 Sound Pressures Measured for Pile 2, reported as dB
Peak Pressures Positions Measured Distance and General Direction
from the Pile
Time Period
Bubble Curtain
Condition South ~460m
South 100m
North 60m
North 100m
North 195m
North ~450m
Water Depth = 10m 11m 10m 11m 11m 9m 13:54:00 13:57:29
ON Up = 194 Dn = 197
Dn = 197
Up = 200 Dn = 196
Up = 175 Dn = 179
14:02:00 14:06:59
ON Up = 190 Dn = 191
Dn = 198
Up = 180 Dn = 184
Up = 176 Dn = 180
14:20:00 14:23:59
OFF Up = 211 Dn = 208
Dn = 208
Up = 201 Dn = 205
Up = 190 Dn = 190
Estimated Reduction Up = -- Dn = --
Up = 17 Dn = 11
Dn = 11
Up = 1* Dn = 9
Up = -- Dn = --
Up = 15 Dn = 11
RMS Sound Pressure Levels Positions Measured Distance and
General Direction from the Pile
Time Period
Bubble Curtain
Condition South ~460m
South 100m
North 60m
North 100m
North 195m
North ~450m
Water Depth = 10m 11m 10m 11m 11m 9m 13:54:00 13:57:29
ON Up = 183 Dn = 185
Dn = 186
Up = 187 Dn = 184
Up = 164 Dn = 170
14:02:00 14:06:59
ON Up = 180 Dn = 180
Dn = 187
Up = Dn = 172
Up = 166 Dn = 171
14:20:00 14:23:59
OFF Up = 194 Dn = 195
Dn = 192
Up = 189 Dn = 193
Up = 174 Dn = 177
Estimated Reduction Up = -- Dn = --
Up = 11 Dn = 10
Dn = 6
Up = 2* Dn = 9
Up = -- Dn = --
Up = 10 Dn = 7
* The levels measured at 100m north at the UP position (2m below
the surface) are suspect.
Pile 3 The DB General barge was moved into position north of
pile No. 3 and was ready for driving on the morning of December 10,
2002. Hammering started at 10:02 and continued for 37 minutes with
stops to adjust the air delivery system and strain gages. Hammering
restarted at 10:52 and continued until 11:07 without the bubble
curtain in operation. Hammer energy was consistently above 1,600 kj
and the blow count was about 30 blows per minute. A history of pile
strikes measured from the DB General (60m from the pile) is shown
in Figure 8. Three different conditions were tested with this pile:
(1) bubble curtain system ON with manifold pressure of 70 to 80
pounds per square inch (psi), (2) bubble curtain system ON with
manifold pressure reduced to 50 psi, and (3) bubble curtain system
OFF. These three periods are indicated as ON+, ON-, and OFF. Time
periods that best represent a particular condition for the pile and
each bubble curtain operation mode were selected. Pile driving was
suspended between each measurement period. There was a light south
to north or ebb current observed, although the predictions
indicated a light flood current. A history of pile strikes measured
from the DB General (60m from the pile) is shown in Figure 8.
The history plot of sound pressures shown in Figure 8 indicates
that sound pressures were consistent, much like Pile 2. The Menke
hammer was in automatic mode for most of the drive. Table 3
presents the sound pressure levels in terms of peak pressure and
RMS sound pressure levels for both the bubble curtain ON and OFF.
Time periods that best represent a particular condition for the
pile and each bubble curtain operation mode were selected. There
was a light north to south current..
-
12
Sound pressures associated with this pile were lower than either
Pile 1 or Pile 2, probably due to the shallower water. Some large
reductions in peak pressure still occurred on the north side.
Reductions were over 20 dB close to the pile on the north side. On
the south side, reductions were about 5 to 7 dB. Although there was
little measured reduction at the 450m south location, levels were
185 dB or lower with the bubble curtain system ON. At ~470m north,
levels with the bubble curtain system ON were too low to measure
accurately. It is estimated that peak pressures were less than 170
dB with the bubble curtain ON and less than 180 dB with the system
OFF.
Sound pressures were measured with the bubble curtain air
delivery pressure at two settings, as indicated by ON+ and ON-.
Results indicate that there was little difference between the
settings. In fact all measurements were within 2 dB of each setting
and some levels were even lower with the reduced delivery
pressure.
PILE 2, from Barge at 60m History of Pile Stikes at the Deeper
Sensor
160
170
180
190
200
210
220
10:0
2
10:0
6
10:1
0
10:1
4
10:1
8
10:2
2
10:2
6
10:3
0
10:3
4
10:3
8
10:4
2
10:4
6
10:4
9
10:5
3
10:5
7
11:0
1
11:0
5
Time
So
un
d P
ress
ure
(d
B)
Peak
RMS
Data from 1st part of drive not collected at barge
Figure 8 Time History - Pile 3
-
13
Table 3 Sound Pressures Measured for Pile 3, reported as dB
Peak Pressures Positions Measured Distance and General Direction
from the Pile
Time Period
Bubble Curtain
Condition South ~450m
South 100m
North 60m
North 100m
North 200m
North ~470m
Water Depth = 5m 5m 6m 4m 4m 4+m 10:04:30 10:55:59
ON+ Up = 193 Dn = 192
Up = 179 Dn = 179
Up =
-
14
conditions between the location of Pile 1 and 2 and the location
of Pile3. At Pile 3, sound pressures were much lower even without
the bubble curtain ON. In fact, the bubble curtain OFF condition
resulted in similar, but slightly higher, peak pressures as the
bubble curtain ON conditions at Piles 1 and 2. However, the shape
of the waveform is much different in terms of rapid pressure
rise/fall t imes.
Pile 1 The pressure time traces show similar patterns of rapid
rise and fall of pressures during the first 0 to 15 msec of the
acoustical event when the bubbles were OFF. With bubbles ON, much
of that fluctuation was reduced. Frequency spectra for the bubbles
OFF condition are similar at 100m north and south, where most
energy is contained below 1000 Hz. With bubbles ON, sound pressures
were reduced from 500 Hz and above with the greatest reductions
above 1000 Hz. The bubble curtain was more effective at reducing
sound pressures at 100m south. The bubble curtain provided about 11
dB of reduction at the south position and about 6 dB at the north
position.
Pile 2 While the magnitude of sound pressure was greater for
100m south, there were more substantial fluctuations at the 100m
north position with the bubble curtain OFF. This appears to be
evident in the low frequency spectrum (i.e., below 500Hz).With
bubbles ON, acoustic energy above 1000 Hz was attenuated by 10 to
30 dB, especially at the 100m north position. At the 100m north
position, bubbles ON appeared to reduce sound pressures by 5 dB at
the lower frequencies. The resultant frequency spectra at 100m
north and south were similar with the bubbles ON, while showing
some considerable differences at the lower frequencies without the
bubbles. Overall, the bubble curtain provided about 10 dB of
attenuation at these positions for this pile.
Pile 3 The unattenuated piles at 100m north and south for Pile 3
showed some similar characteristics as the attenuated conditions
for Piles 1 and 2. As a result, the bubbles OFF sound pressures for
this pile were similar to those of Piles 1 and 2 when the bubbles
were ON. When bubbles were OFF at Pile 3, sound pressures were
reduced further by 5 to 7 dB at 100m south and 15 to 20 dB at 100m
north. At 100m south, most reductions occurred above 1000 Hz. At
100m north, reductions of 5 to 10 dB occurred around 200 Hz and
reductions of 30 dB occurred between 1000 and 1500 Hz. This was in
addition to the 20 to over 30 dB reduction above 1500 Hz. The sound
pressure amplitude was reduced to a fraction of the amplitude when
the bubbles were OFF.
Bubble Curtain Performance The bubble curtain performance was
directly measured by making sound pressure measurements with the
system ON and with it OFF. The system performance varied
considerably from location to location as a result of differences
in measurement positions and pile conditions. All piles were driven
at refusal using full or nearly full hammer energy.
When evaluating ON/OFF conditions for Pile 1, the reductions
between ON and OFF conditions were 6 to 10 dB for deep sensor
positions and 6 to 12 dB lower for the shallow sensor positions,
excluding the measurements from the barge, where the shallow sensor
was suspected to be shielded by underwater obstructions. The
reductions in RMS sound pressure levels was generally 2 to 4 dB
less than peak pressures (i.e., 2 to 7 dB reduction). At 100m,
reductions were 4 to 7 dB greater to the south. Reductions at 450m
were similar between north and south, except that levels with the
bubble curtain ON or OFF were 10 dB lower to the north than to the
south. This indicates that there is excess attenuation of about 10
dB at 450m north.
The location of Pile 2 was next to Pile 1 so measurement
positions changed very little. Reductions measured for Pile 2 were
on the order of 9 to 17 dB for peak pressures and 6 to 11 dB in RMS
sound pressure levels. The one exception was the shallow sensor at
100m north where the measured reduction was only 1 to 2 dB. Again,
the bubble curtain appeared to be more effective 100m south than at
100m north. While OFF measurements could not be made for 450m
south, the ON measurements indicate that reductions were greater at
450m north. The ON pressures at 450m north were 15 dB lower than
they were at 450m meters south.
Pile 3 was at a different location than Piles 1 and 2. Overall
sound pressures with the bubble curtain OFF were about 5 to 12 dB
lower than they were for Piles 1 or 2. The bottom topography at
this pile was rough, where it is likely that there was a gap of
about 5 to 7 feet in the southwest and west directions. This would
limit the effectiveness of the bubble curtain due to flanking of
sound underneath in the southwest and westerly directions. Towards
the north, the measured reductions were 11 to 25 dB in peak
pressures and 14 to 21 dB in RMS pressures (RMS levels could not be
measured at 450m north). In the southerly direction, the reductions
were 2 to 8 dB in peak pressures and 1 to 5 dB in RMS sound
pressure levels. The
-
15
differences in attenuation from the bubble curtain in these
directions is indicative of a leak in the south side, probably due
to the uneven bottom terrain. It should be noted that the sound
pressures in the south with the bubble curtain ON were 10 to 15 dB
lower than OFF conditions for Piles 1 and 2.
Comparison with PIDP Results and Predictions made in the
Biological Opinion The restrike involved driving a pile at refusal
with the hammer at maximum energy (1,600 to 1,740 kilojoules). This
condition was not encountered during acoustical measurements
associated with the PIDP in 2000 and is not anticipated during
construction. For these reasons, the results obtained during the
restrike are not directly comparable to results that were obtained
during the PIDP in 2000 or upcoming construction. In addition to
the differences discussed above, measurement positions were
slightly different.
Pile 1 During the PIDP, a peak pressure of 207 dB was measured
about 100m west of the pile when the hammer energy was about 1,000
kilojoules. During the restrike with the bubble curtain OFF, the
highest peak pressures were 206 dB southeast and 209 dB northwest.
With the bubble curtain ON, peak pressures were 194-201 dB (6 to 14
dB lower). The PIDP measurements for Pile 1 (Illingworth &
Rodkin, 2001) were used as a basis for predicting impacts to
biological resources (Greene 2001, NOAA 2001). The PIDP Restrike
results were lower than predicted for all position except 450m
south. At that position, unattenuated pressures were 8 dB higher
than predicted. The basis for these predictions was measurements
for Pile 1 at 103m west and 358m northwest. At distances of 450m,
the predictions were 6 dB to high for 450m north and 8 dB to low
for 450m south with unattenuated conditions. Predicted and measured
sound pressures for Pile 1 are summarized in Table 4.
Table 4 Comparison of Predicted and Measured Sound Pressures
Pile 1
Predicted Sound Pressures with NO Sound Attenuation*
Measured with Bubble Curtain OFF
Measured with Bubble Curtain ON
Position RMS Peak RMS Peak RMS Peak
65m 203 215 193 208 186 199
100m South 197 209 192 206 185 196
100m North 197 209 194 207 189 201
450m South 178 190 185 198 178 189
450m North 178 190 171 184 162 175
* The Biological Opinion (Caltrans 2001) assumed about 10 dB of
sound attenuation.
Pile 2 During the PIDP, measurements were only made at about
200m west with a bubble curtain in operation for Pile 2. Peak
pressures with the PIDP at 200m were 201 dB and 200 dB with hammer
energies of 550 and 1000 kilojoules. During the restrike, peak
pressures at 100m were 201, 206, 206, 208, and 211dB. A measurement
made with only the bubble curtain ON at almost 200m during the
restrike had peak pressures of 180 to 184 dB. For the restrike,
Pile 2 appeared to be slightly louder than Pile 1 when comparing
sound pressures for the bubble curtain OFF conditions. With the
bubble curtain ON during the restrike, peak pressures were 194 to
200 dB at 100m. With the bubble curtain OFF measurements were equal
or less than predicted (by 0 to 7 dB). Measurements with the bubble
curtain OFF could not be made at 450m south, but would probably
have been higher than predicted. With the bubble curtain ON, sound
pressures were 1 dB higher than unattenuated predictions at 450m
south and 6 dB lower at 450m north. Closer in, pressures were 12 to
17 dB lower than unattenuated predictions (see Table 5).
-
16
Table 5 Comparison of Predicted and Measured Sound Pressures
Pile 2
Predicted Sound Pressures with NO Sound Attenuation*
Measured with Bubble Curtain OFF
Measured with Bubble Curtain ON
Position RMS Peak RMS Peak RMS Peak
65m 203 215 192 208 187 198
100m South 197 209 195 208 185 197
100m North 197 209 193 205 184 196
450m South 178 190 NA NA 180 191
450m North 178 190 177 190 172 184
* The Biological Opinion (Caltrans 2001) assumed about 10 dB of
sound attenuation.
Pile 3 Measurements from the PIDP in 2000 and the restrike
indicate that Pile 3 resulted in lower sound pressures than Piles 1
or 2. This was likely caused by the shallow water conditions at
Pile 3. At many of the measurement locations, the water was about
50% shallower (e.g., 5m for Pile 3 vs 11m for Piles 1 and 2).
Measurements made during the PIDP at about 100m were 193 to 197 dB
(with the Gunderboom system not operating) and 189 dB when the
Gunderboom was operating and hammer energies were 1600 kilojoules
(comparable to the restrike). Measurements during the PIDP restrike
at about 100m were 197 to 199 dB with the bubble curtain OFF and
179 to 192 dB with the bubble curtain ON (the south side was 192 dB
and the north side was about 179 dB). At 500m north during the PIDP
with the Gunderboom ON, peak pressures were about 170 dB. At about
470m north with the bubble curtain ON, peak pressures were less
than 170 dB and about 184 dB with the bubble curtain OFF.
At all measurements positions, bubble curtain OFF pressures were
less than predicted unattenuated pressures, even at 450m south. At
most locations, OFF pressures were about 10 dB lower than
predicted. At 450m south, the OFF conditions were only 3 dB less
than predicted. When the bubble curtain was ON, sound pressures
were 5 to 35 dB lower than unattenuated predictions. With the
exception of the 450m south position, all bubble curtain ON sound
pressures were 20 to 30 dB lower than unattenuated predictions (see
Table 6).
Table 6 Comparison of Predicted and Measured Sound Pressures
Pile 3
Predicted Sound Pressures with NO Sound Attenuation*
Measured with Bubble Curtain OFF
Measured with Bubble Curtain ON
Position RMS Peak RMS Peak RMS Peak
65m 203 215 191 204 170 180
100m South 197 209 186 199 181 192
100m North 197 209 184 198 169 179
200m North 187 199 180 195 168 178
450m South 178 190 175 187 174 185
500m North 176 189 172 184
-
17
Marine Mammal Safety Zone The marine mammal monitoring safety
zone is defined as the area where RMS sound pressure levels are
less than 190 dB. Based on the PIDP restrike measurements with the
bubble curtain ON, the safety zone extended out to about 100m north
for Pile 1 and was less than 100m for Piles 2 and 3. In fact, RMS
sound pressures levels of 190 dB or greater were not measured at
any of the measurements positions for Piles 2 and 3 when the UABC
system was ON. When the bubble curtain was OFF, the limit of the
safety zone extended beyond 100m to somewhere between 200 and 300m
for piles 1 and 2. For Pile 3 with the bubble curtain OFF, the
safety zone did not appear to extend beyond 100m.
CONCLUSIONS The effectiveness of a two-ring bubble curtain
system in reducing underwater sound pressures during marine pile
driving was assessed through underwater sound pressure
measurements. This was conducted when the three 108m long, 2.4m
diameter cast in steel shell piles driven in 2000 as part of the
PIDP, were restruck in December of 2002. During the measurements,
the bubble curtain system was turned ON and OFF. The restrike
involved driving the piles at refusal with the hammer at maximum
energy (1,600 to 1,740 kilojoules). This condition is not
anticipated during the east span SFOBB new east span
construction.
The reduction in sound pressures provided by the bubble curtain
system ranged considerably. The direct reduction in sound
pressures, which is evaluated by comparing bubble curtain ON and
OFF measurements, for Piles 1 and 2 was 6 to 17 dB for peak
pressures and 3 to 10 dB for RMS sound pressure levels. Piles 1 and
2 were located next to each other. Reductions at Pile 3, which was
in shallower water, were over 20 dB for both peak pressures and RMS
sound pressure levels on the north side. However, the reductions on
the south side for Pile 3 were much less. Close to Pile 3 on the
south side, the reductions were on the order of 5 to 7 dB. Further
away at about 450m south, the reductions were only about 2 dB.
Uneven bottom topography around Pile 3, which could have
compromised the bubble curtain performance near the bay bottom, is
suspected to have resulted in the lower reductions to the south. It
is important to note that overall sound pressures associated with
Pile 3 were lower than those with Piles 1 and 2.
Analysis of individual pile strike impulses indicates that the
bubble curtain reduced sound pressures at all measurement positions
at frequencies above 1000 Hz. There was a reduction in sound
pressures below 500 Hz where the bubble curtain worked particularly
well (e.g., 100m north position for Pile 3).
Measurements of peak pressures made at about 100m were
consistent with the measurements made during the PIDP in 2000.
Those measurements were the basis for predictions of the maximum
peak pressures during SFOBB east span construction. With the
exception of the 450m south position, predicted peak pressures used
in the Biological Opinion were lower than those measured. At 450m
south, measured peak pressures were 5 to 8 dB higher than
predicted. Conversely, peak pressures at 450m to 500m north were 0
to 6 dB lower than predicted.
RMS sound pressure levels, which are used to define the marine
mammal safety zone, did not exceed 190 dB at any of the measurement
positions (between 65 and 500m) when the bubble curtain system was
operating. Levels of 180 dB RMS did extend out to 450m south for
Pile 1, but did not exceed 172 dB at 450m north. With the bubble
curtain OFF, the 190 dB RMS sound pressure levels extended out to
somewhere between 200m to 300m for Piles 1 and 2 and less than 100m
for Pile 3.
-
18
REFERENCES
Greene, C.R., Jr. 2001. Proposed Construction Impact Avoidance
and Minimization Measures, Regarding the
interaction between fish and sounds from pile driving while
building the new San Francisco-Oakland Bay Bridge. Produced by
Greeneridge Sciences and Illingworth & Rodkin, Inc. under
contract to the California Department of Transportation, Task Order
No. 2, Contract No. 43A0063. September.
Illingworth and Rodkin, Inc. 2001. Noise and Vibration
Measurements Associated with the Pile Installation
Demonstration Project for the San Francisco-Oakland Bay Bridge
East Span, Final Data Report. Produced by Illingworth & Rodkin,
Inc. under contract to the California Department of Transportation,
Task Order No. 2, Contract No. 43A0063. June.
Longmuir, C. and T. Lively. 2001. Bubble Curtain Systems for Use
During Marine Pile Driving. Produced by
Fraser River Pile & Dredge, Ltd. National Marine Fisheries
Service, Southwest Region. Biological Opinion San Francisco-Oakland
Bay Bridge
East Span Seismic Safety Project. Ref: 151422-SWR99-SR-190
Reyff, J., P. Donavan, C. R. Greene Jr. 2002. Underwater Sound
Levels Associated with Construction of the
Benicia-Martinez Bridge. Produced by Illingworth & Rodkin,
Inc. and Greeneridge Sciences under contract to the California
Department of Transportation, Task Order No. 18, Contract No.
43A0063. August.
Reyff, J. 2003. Underwater Sound Levels Associated with Seismic
Retrofit Construction of the Richmond-San
Rafael Bridge. Produced by Illingworth & Rodkin, Inc under
contract to the California Department of Transportation, Task Order
No20, Contract No. 43A0063. January.
Wursig, B., C. R. Greene, Jr., T. A. Jefferson. 1999.
Development of an Air Bubble Curtain to Reduce
Underwater Noise of Percussive Piling. Marine Mammal Research 49
(2000) 79-93.
-
19
Appendix A
Data Summary and
Time History of Sound Pressures
-
20
-
21
-
22
Pile 1
Pile 1
Pile 3
-
23
Pile1 12-09-2002
160
170
180
190
200
210
220
10:30 10:34 10:38 10:42 10:46 10:50 10:54 10:58 11:02 11:06
11:10 11:14 11:18
450mdn450up100mSdn100mSup60mdn100mNdn100mNup200mNup450mNup
ON OFF
Pile2 12-09-2002
160
170
180
190
200
210
220
13:54 13:55 13:56 14:02 14:03 14:04 14:05 14:06 14:20 14:21
14:22 14:23
450mdn450up100mSdn100mSup60mdn100mNdn100mNup200mNdn450mNdn450mNup
ON
OFF
ON
Pile3 12-10-2002
160
170
180
190
200
210
220
10:04:30 10:30:57 10:32:57 10:38:24 10:45:36 10:52:48 10:54:48
10:56:48 10:58:48 11:06:15
450mdn450up100mSdn100mSup
60mdn100mNdn100mNup200mNdn200mNup450mNup
ON
OFF
ON ON ON
OFF
-
25
Appendix B
Summary of Hammer Performance Data and Bubble Curtain
Operation
Pile 1
Time: hh:mm:ss
Blow No.
Blows/min Stroke cm
Energy kNm
Activity
10:35:52 Stop key in cabin pushed
11:37:15 Start: single blow mode 11:17:34 Start : stroke
sequence mode
11:17:59 19 23.9 86 1623 11:18:22 29 28.2 86 1699 11:18:42 39
29.9 86 1730 11:19:03 49 30.5 86 1730 11:19:23 59 29.7 86 1724
11:19:43 69 28.9 86 1696
C2 reported hammer not on pile
Pile 2
Time: hh:mm:ss
Blow No.
Blows/min Stroke cm
Energy kNm
Activity
13:51:37 Start
13:51:52 12 75.9 38 620 13:52:03 22 67.9 56 903 13:52:04 Stop
13:52:37 Start 13:53:11 32 22.3 86 1545 14:07:37 472 31.1 86 1622
14:07:36 Stop 14:18:42 Start 14:18:59 482 30.6 86 1684 14:25:13 672
29.9 86 1676 14:25:20 Stop 14:26:05 C2 Hammer not on pile
-
26
Pile 3
Time: hh:mm:ss
Blow No.
Blows/min Stroke
cm
Energy kNm
Activity
10:01:50 Start in stroke sequence mode 10:02:03 14 42.1 40 746
10:02:21 24 28.8 62 1201 10:04:41 93 31 88 1733 10:05:01 103 30.8
88 1736 Stop 10:29:15 116 30.5 86 1746 Start 10:31:29 186 31 86
1713 10:31:48 196 31.1 86 1703 Stop 10:35:07 215 31.1 86 1712 Start
10:38:06 305 30.6 86 1688 Stop 10:43:07 315 30.6 86 1693 Start
10:46:02 405 31.3 86 1698 Stop 10:51:22 416 30.3 86 1703 Start
10:59:05 648 29.3 86 1691 Stop 11:04:20 659 30.2 88 1725 Start
11:05:40 699 29.7 88 1735 Stop
11:07:09 C2 reported hammer not on the pile
-
27
BUBBLE CURTAIN REPORT
December 9, 2002
PDIP Restrike Data The Bubble Curtain was used as a noise
attenuation device during the re-strike of the PDIP piles. During
the re-strike the following observations were noted: Pile 1: Two of
the four flow meters at the aeration pipe failed during the
re-strike. One on meter the top ring and one on the bottom ring.
The two remaining meters at times had significant fluctuations in
their readouts. The flow meters at the compressors were inaccurate
because of wide fluctuations in their readouts. This could have
been attributed to the flow characteristics of the distribution
manifold. This problem continued throughout the entire project.
Pile 2: The flow meters at the aeration pipe were repaired and
reliable readings were obtained at pile 2. Reliable readings were
also obtained at all but one of the pressure gauges. No readings
were taken from the flow meters at the compressor due to the
constant fluctuation of the meters. The manifold pressure was held
constant at 70 psi. Pile 3: Accurate readings were obtained from
the flow meters at the aeration pipe during the pile driving
operation. One of the pressure gauges on the bottom ring failed and
no readings were obtained from this gauge. No readings were taken
from the flow meters at the compressor due to the constant
fluctuation of the meters. On this particular pile the manifold
pressure was kept at constant intervals of 80, 70 and 50 psi in
order to change the flow of air through the system. A higher
manifold pressure decreases the flow rate at the aeration pipe and
decreasing the manifold pressure increases the flow rate at the
aeration pipe. With decreased flow at the aeration pipe the inlet
pressure should also be reduced. An increase in flow by decreasing
the manifold pressure increases the inlet pressure. The size of the
bubble can be determined from the pressure and flow rate. The goal
was to determine if bubble size had an influence on attenuating the
sound pressure levels.
-
28
LOCATION START TIME PIPE SECTION Pile 1 1030 hrs Top Ring INLET
FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 1500 3100
Reading # 2 2600 0 Reading # 3 2740 0 Reading # 4 2100 0 MANIFOLD
PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 60 10 0 20 12
Reading # 2 60 20 20 25 25 Reading # 3 68 20 20 25 25 Reading # 4
70 22 22 25 25 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm)
Reading # 1 Reading not reliable due to constant fluctuation of
meters Reading # 2 Reading not reliable due to constant fluctuation
of meters Reading # 3 Reading not reliable due to constant
fluctuation of meters Reading # 4 Reading not reliable due to
constant fluctuation of meters
NOTES:
1. Bubble curtain on for first 400 blows. 2. Bubble curtain off
for remaining 270 blows.
LOCATION START TIME PIPE SECTION Pile 1 1030 hrs Bottom Ring
INLET FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 3500 3100
Reading # 2 3600 1700 Reading # 3 3470 0 Reading # 4 3390 0
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 60 0 0 25
25 Reading # 2 60 0 0 20 20 Reading # 3 68 0 0 22 22 Reading # 4 70
0 0 20 20 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm) Reading # 1
Reading not reliable due to constant fluctuation of meters Reading
# 2 Reading not reliable due to constant fluctuation of meters
Reading # 3 Reading not reliable due to constant fluctuation of
meters Reading # 4 Reading not reliable due to constant fluctuation
of meters
NOTES:
1. Bubble curtain on for first 400 blows. 2. Bubble curtain off
for remaining 270 blows.
-
29
LOCATION START TIME PIPE SECTION Pile 2 1400 hrs Top Ring INLET
FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 2600 2900
Reading # 2 2480 3100 Reading # 3 2670 3100 Reading # 4 2600 3080
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 60 10 10
15 10 Reading # 2 55 15 15 15 10 Reading # 3 55 15 15 15 10 Reading
# 4 55 10 15 15 10 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm)
Reading # 1 Reading not reliable due to constant fluctuation of
meters Reading # 2 Reading not reliable due to constant fluctuation
of meters Reading # 3 Reading not reliable due to constant
fluctuation of meters Reading # 4 Reading not reliable due to
constant fluctuation of meters
NOTES:
1. Bubble curtain on for first 350 blows. 2. Bubble curtain off
for remaining 320 blows.
LOCATION START TIME PIPE SECTION Pile 2 1400 hrs Bottom Ring
INLET FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 3400 3100
Reading # 2 3580 3170 Reading # 3 3580 1700 Reading # 4 3520 0
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 70 20 0 25
25 Reading # 2 70 20 0 20 25 Reading # 3 70 22 0 22 27 Reading # 4
70 22 0 22 25 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm) Reading
# 1 Reading not reliable due to constant fluctuation of meters
Reading # 2 Reading not reliable due to constant fluctuation of
meters Reading # 3 Reading not reliable due to constant fluctuation
of meters Reading # 4 Reading not reliable due to constant
fluctuation of meters
NOTES:
1. Bubble curtain on for first 350 blows. 2. Bubble curtain off
for remaining 320 blows.
-
30
LOCATION START TIME PIPE SECTION Pile 3 1000 hrs Top Ring INLET
FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 1780 1900
Reading # 2 1750 1890 Reading # 3 1760 1890 Reading # 4 1790 1910
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 80 10 10
10 10 Reading # 2 80 10 10 10 10 Reading # 3 80 10 10 10 10 Reading
# 4 80 10 10 10 10 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm)
Reading # 1 Reading not reliable due to constant fluctuation of
meters Reading # 2 Reading not reliable due to constant fluctuation
of meters Reading # 3 Reading not reliable due to constant
fluctuation of meters Reading # 4 Reading not reliable due to
constant fluctuation of meters
NOTES: Manifold Pressure: Pressure regulated at valve on exit
side of the manifold. Flow and pressure at aeration pipe are
reduced as a result. 1. Bubble curtain on for blows 0 100. LOCATION
START TIME PIPE SECTION Pile 3 1000 hrs Bottom Ring INLET FLOW
METER READING @ ARETION PIPE (cfm) Reading # 1 2700 2100 Reading #
2 2640 2120 Reading # 3 2640 2110 Reading # 4 2670 2120 MANIFOLD
PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 80 13 0 15 15
Reading # 2 80 12 0 14 15 Reading # 3 80 12 0 15 15 Reading # 4 80
12 0 13 12 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm) Reading #
1 Reading not reliable due to constant fluctuation of meters
Reading # 2 Reading not reliable due to constant fluctuation of
meters Reading # 3 Reading not reliable due to constant fluctuation
of meters Reading # 4 Reading not reliable due to constant
fluctuation of meters
NOTES: Manifold Pressure: Pressure regulated at valve on exit
side of the manifold to maintain a constant pressure of 80 psi.
Flow and pressure at aeration pipe are reduced as a result. 1.
Bubble curtain on for blows 0 100.
-
31
LOCATION START TIME PIPE SECTION Pile 3 1030 hrs Top Ring INLET
FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 2980 2700
Reading # 2 3100 2710 Reading # 3 3060 2740 Reading # 4 3070 2660
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 70 15 15
15 15 Reading # 2 70 15 15 15 15 Reading # 3 70 15 15 15 15 Reading
# 4 70 15 15 15 15 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm)
Reading # 1 Reading not reliable due to constant fluctuation of
meters Reading # 2 Reading not reliable due to constant fluctuation
of meters Reading # 3 Reading not reliable due to constant
fluctuation of meters Reading # 4 Reading not reliable due to
constant fluctuation of meters
NOTES: Manifold Pressure: Pressure regulated at valve on exit
side of the manifold to maintain a constant pressure of 70 psi.
Flow and pressure at aeration pipe show constant readindgs. 1.
Bubble curtain on for blows 101 200. LOCATION START TIME PIPE
SECTION Pile 3 1030 hrs Bottom Ring INLET FLOW METER READING @
ARETION PIPE (cfm) Reading # 1 3200 2990 Reading # 2 3210 3080
Reading # 3 3180 3060 Reading # 4 3240 3020 MANIFOLD PRESSURE (psi)
INLET PRESSURE (psi) Reading # 1 70 18 0 18 20 Reading # 2 70 17 0
17 20 Reading # 3 70 16 0 17 18 Reading # 4 70 18 0 18 20
COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm) Reading # 1 Reading
not reliable due to constant fluctuation of meters Reading # 2
Reading not reliable due to constant fluctuation of meters Reading
# 3 Reading not reliable due to constant fluctuation of meters
Reading # 4 Reading not reliable due to constant fluctuation of
meters
NOTES: Manifold Pressure: Pressure regulated at valve on exit
side of the manifold to maintain a constant pressure of 70 psi.
Flow and pressure at aeration pipe show constant readindgs. 1.
Bubble curtain on for blows 101 200.
-
32
LOCATION START TIME PIPE SECTION Pile 3 1035 hrs Top Ring INLET
FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 3280 3250
Reading # 2 3220 3210 Reading # 3 3360 3205 Reading # 4 3280 3215
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 50 17 19
20 20 Reading # 2 50 18 18 20 20 Reading # 3 50 17 18 20 20 Reading
# 4 50 18 19 20 20 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm)
Reading # 1 Reading not reliable due to constant fluctuation of
meters Reading # 2 Reading not reliable due to constant fluctuation
of meters Reading # 3 Reading not reliable due to constant
fluctuation of meters Reading # 4 Reading not reliable due to
constant fluctuation of meters
NOTES:
Manifold Pressure: Pressure regulated at valve on exit side of
the manifold to maintain a constant pressure of 50 psi. Flow and
pressure at aeration pipe show constant readings. Flow and pressure
at the aeration pipes are increased as a result. 1. Bubble curtain
on for blows 201 350.
LOCATION START TIME PIPE SECTION Pile 3 1035 hrs Bottom Ring
INLET FLOW METER READING @ ARETION PIPE (cfm) Reading # 1 3585 3350
Reading # 2 3605 3410 Reading # 3 3590 3405 Reading # 4 3580 3415
MANIFOLD PRESSURE (psi) INLET PRESSURE (psi) Reading # 1 50 22 0 25
25 Reading # 2 50 23 0 25 25 Reading # 3 50 23 0 25 25 Reading # 4
50 25 0 25 25 COMPRESSOR FLOW @ DISTRIBUTION MANIFOLD (cfm) Reading
# 1 Reading not reliable due to constant fluctuation of meters
Reading # 2 Reading not reliable due to constant fluctuation of
meters Reading # 3 Reading not reliable due to constant fluctuation
of meters Reading # 4 Reading not reliable due to constant
fluctuation of meters
NOTES:
Manifold Pressure: Pressure regulated at valve on exit side of
the manifold to maintain a constant pressure of 50 psi. Flow and
pressure at aeration pipe show constant readings. Flow and pressure
at the aeration pipes are increased as a result. 1. Bubble curtain
on for blows 201 350.
-
33
Depths around PIDP Piles
PIDP Pile Nos. 1 and 2
8 foot radius 20 - 30 foot radius
North 31' North 31'Northwest 33' Northwest 33'West 34' West
35'SouthWest 31' SouthWest 32'South 31' South 32'SouthEast 31'
SouthEast 20'East 31' East 30'NorthEast 31' NorthEast 32'
PIDP Pile No. 3
8 foot radius 20 - 30 foot radius
North 24' North 23'Northwest 24' Northwest 27'West 25' West
29'SouthWest 30' SouthWest 26'South 25' South 22.5'SouthEast 20'
SouthEast 21'East 20' East 22'NorthEast 21' NorthEast 22'