HV/MV Transformers Services Range Make the most of your energy Medium Power Transformers - Oil Distribution Transformers - Cast Resin Transformers MULTIBRAND service catalogue Optimize every transformer’s performance! Schneider Electric helps you get the most of your equipment and installations Installation & Commissioning Technical Training Installation Assessment On-Demand Maintenance Modernization Services Maintenance contract End-of-life PE90586 PE90586 PE90586 PE90586 References all over the world! As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Publishing: SYNTHESE ECA, Schneider Electric. Photos: Schneider Electric 03/2013 SERED111097EN Schneider Electric Industries SAS Head Office 35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison www.schneider-electric.com ECOFIT centres Factories and Workshops dedicated to transformer services
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
HV/MV TransformersServices Range
Make the most of your energy
Medium Power Transformers - Oil Distribution Transformers - Cast Resin TransformersMULTIBRAND service catalogue
Optimize every transformer’s performance!
Schneider Electric helps you get the most of your equipment and installations
Installation &Commissioning
Technical Training
InstallationAssessment
On-DemandMaintenance
Modernization
ServicesMaintenancecontract
End-of-life
PE
9058
6
PE
9058
6
PE
9058
6
PE
9058
6
References all over the world!
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Publishing: SYNTHESE ECA, Schneider Electric.Photos: Schneider Electric
03/2013SERED111097EN
Schneider Electric Industries SASHead Office35, rue Joseph MonierCS 3032392506 Rueil-Malmaisonwww.schneider-electric.com
ECOFIT centres Factories and Workshops dedicated to transformer services
A real opportunity
The differentiating factors
• Peace of mind for every transformer installation.• Periodic actions focused on maintenance operations to maximize equipment’s service life.• Schneider Electric gives added value to high- and medium-voltage transformer services (including
non Schneider Electric transformers).• Ability to include transformers in global electrical distribution service maintenance contracts.
• The experience of a world leader in Low- & Medium-Voltage electrical distribution installations
Schneider Electric has been manufacturing LV and MV products for more than 50 years and its installed base comprises thousands of millions of products and devices.The Schneider Electric brand is known worldwide and recognized by the most demanding customers.
• True capability for handling every transformer of whatever brand
► COFRAC oil analysis labsCOFRAC accreditation, obtained in 2004, is an assurance given to a customer that the Schneider Electric analysis laboratory has the necessary human and technical resources to provide reliable and reproducible results. The accreditation reflects impartiality and competence.
• High-end capabilities for transformer services
► The "Pro Relay Box" especially designed to combine efficiency and reliability
A perfect mobile "test bench", the "Pro Relay Box" can be used to check the smooth running of 3 functions (gaseous release - pressure - temperature) of the protection relay (DGPT2, DMCR and RIS) of any oil distribution transformer. It is the only box which has been specifically designed with the designers of thoses relays. It therefore has no equivalent anywhere.
• Reactivity: Local support all over the world.There are always Schneider Electric people close to you: 6200 Services people in more than 88 countries!
• Quality certified ISO 9001
• Compliance with international standards such as IEC 60076 and IEC 60422
• Reproducibility and traceabilityAll Schneider Electric operations on every site and all equipment worldwide are systematically carried out according to the same processes, systematically classified and always available online whenever needed.
Service continuity Lifetime optimizationSafety Immediate return on investment
Note: After each analysis, all the collected information is safely recorded to improve the knowledge of every installation and carry out the necessary predictive maintenance actions "just in time".
... And many other analyses available, such as passivator content, interfacial tension, metal assays, etc.
4 "Packs*" available...• Pack 1Objective: To know the dielectric quality level. To characterize the level of quality of the liquid dielectric influencing the transformer’s efficiency (breakdown voltage, water content, acidity, colour index and appearance).
• Pack 2+ (Pack 1 and measurement of dissolved gases)Objective: To characterize internal fault properties (dissolved gases) for enhanced prevention of electrical or thermal problems.
• Pack 3 (Pack 2+ + furan derivatives)Objective: To check the solid insulation performance in order to pre-empt damage at the coil level (furan derivatives).
• Pack 4 (Pack 3 + particle counting + tangent delta and resistivity)Objective: To perform a complete check-up on the transformer (dissolved gases, thermal emission), characterize elements in suspension and the polar compounds of the dielectric for maximum safety.
* For transformers with inhibited oil inside, measurement of the inhibitor content must be added to the pack chosen.
Pack 3 (≤ 170 kV; every 5 years> 170 kV; every 2 years)
Additional transformer services
Oil Distribution Transformers (ODT) Schneider Electric oil analysis offers
Installation and CommissioningSchneider Electric provide specialists to take care of on-site assembly operations, in full compliance with Schneider Electric procedures.
End-of-life• Recovery of regulated substances Turnkey solution for recovering toxic substances and persistent organic pollutants such as PCBs.• Maximum recycling of materials:Ferrous and non-ferrous materials (85% of the mass) are separated and cleaned and recycled.
Modernization• Factory refurbishment • Oil replenishmentwith either the original dielectric vacuum filling or with a biodegradeable alternative.
On-Demand Maintenance• Supply of spare parts Sourcing of parts guaranteed by the manufacturers. Stocking and supply of parts according to customers’ requirements.• Minor on-site repairsOn-site, Schneider Electric’s team can perform minor repairs e.g. for minor oil leaks in the tank or radiators, replacement of gaskets, replacement of protection devices, or paint work.• On-site electrical testingVerification of the equipment’s compliance with on-site standards (transformation ratios, insulation, resistance and loss values, impedance voltage, etc.).• In-house repairs and electrical testsIn Schneider Electric refurbishment facilities, complete untanking and repairs with full electrical testing range according to standards and customer requests (routine, standard and special tests).
HV/MV Transformers Services Range: a global offer adaptable locally
• In-house repairs- Gasket replacements, re-painting, replacement of protection devices, inspection and cleaning of bushings, complete electrical testing, etc.
• In-house repairs- Re-painting, replacement of protection devices, inspection and cleaning of bushings, complete electrical testing, etc.
• Fan installation
• Spare parts
• Visual inspection: - Cleanliness.- Surface coating damage.- Checks for leakage.- Checks on tightening.- Oil level.- Connections and setting of protection relays. • Accessories:- Installation of surge arresters.- Locking devices on connections and housing.- Retention tank.- Cable boxes.- Silica gel replacement, etc. • Maintenance on OLTC (On Load Tap Changer)
• Visual inspection: - Cleanliness.- Surface coating damage.- Checks on tightening.- Magnetic circuit status.- Winding status.- Connections and setting of protection relays. • Accessories:- Installation of surge arresters.- IP housing.- Locking devices on connections and housing.- Cable boxes, etc.
On-Demand Maintenance and Services Maintenance Contracts
Cast Resin Transformers
Oil Immersed Transformers
Preventive Predictive Corrective
Diagnosis• Oil sampling and analysis, interpretation of results (see "ODT- Oil sampling and testing" paragraph on left page, for more explanations if needed)
• Check on hot spots:- IR thermography.- Measurement of contact resistance.- Results interpretation.
• Dielectric measurements:- Expertise and interpretation of results.
• Accessories:- Checks on sensors and temperature protection relays (Pro Relay Box).- Online transformer monitoring.- Online DGA (Dissolved Gas Analysis).
Diagnosis• Check on hot spots:- IR thermography.- Measurement of contact resistance.- Interpretation of results.
• Dielectric measurements:- Expertise appraisal and interpretation of results.
• Accessories:- Checks on sensors and temperature protection relays.- Online transformer monitoring.
Risk assessment according to environment, conditions of use, criticality.
Risk assessment according to environment, conditions of use, criticality.