Top Banner
HVAC systems cross-contamination control Presented by Gordon Farquharson August 2015
20

HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

May 19, 2018

Download

Documents

tranminh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

HVAC systemscross-contamination control

Presented by Gordon Farquharson

August 2015

Page 2: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 2 © PharmOut 2015

The GMP requirements

The HVAC system must achieve the following:

• Ensure appropriate conditions for the product or process – Temp; RH.

• Help prevent contamination and cross-contamination by:

– Room pressurisation.

– Use of filtration if recirculation of air is used. (GMPs for dosage forms and API specifically allow recirculation provided you have assessed and managed the risk of cross-contamination).

– Proving dust extract systems for points of high emissions (these systems never recirculate).

Page 3: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 3 © PharmOut 2015

Possible routes for cross-contamination via the HVAC

• Recirculation of contaminated air without sufficient air filtration.

• Passage of airborne dust via ducting system when HVAC is OFF or FAILED state.

• Estimating the quantity of dust that might cause a cross-contamination problem is very difficult ……therefore we tend to “overkill” to be sure.

Page 4: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 4 © PharmOut 2015

HVAC Systems - Security

• We can apply this to whole systems or local controlled zones (booths)

• This is the best way to save energy

• But, you must prevent unacceptable levels of cross-contamination

GMP accepts recirculation of air

• Location of filter is risk dependant

• Remember someone has to change the filter (occupational health issue)

• Specification of filter is risk dependant

Filtration in recirculation pathway

Page 5: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 5 © PharmOut 2015

OSD, API – Use of HEPA filters

• Cross-contamination control in recirculation air handling systems.

• Prevention of discharge of potent compound dust to atmosphere – security or policing filters.

• HEPA filters of H13 or H14 specification are chosen because they can be leak tested:

• Aerosol photometer method – scan or average leak test.

• Particle counter method.

Page 6: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 6 © PharmOut 2015

Let’s look at some of the position options• There are several possible locations:

• Recirculation systems –

• 1. Final filter in air supply AHU.

• 2. Terminal supply to room.

• 3. In Return air duct to AHU.

• 4. In Return at room boundary.

• Once through systems

• 5. In Exhaust air duct to atmosphere.

• 6. In Exhaust at room boundary + In Exhaust to atmosphere

Incre

asin

g P

ote

ncy/T

ox

icity

Page 7: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 7 © PharmOut 2015

Source ISPE API Baseline® Guide

Recirculation– HEPA at AHU Supply

Page 8: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 8 © PharmOut 2015

Source ISPE API Baseline® Guide

Recirculation–HEPA at Room Supply Terminal

Page 9: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 9 © PharmOut 2015

Process

Room 2Process

Room 1

F7 - + F7 Option H13

F7

H13 or 14

G4

Recirculation–In return duct to AHU

G4

Page 10: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 10 © PharmOut 2015

Process

Room 2Process

Room 1

F7 - + F7 Option H13

G4 +H13/14

Recirculation–In return at room boundary

G4 +H13/14

Page 11: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 11 © PharmOut 2015

Source ISPE API Baseline® Guide

5. Once Through – HEPA at room exhaust (Potent Compounds)

Page 12: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 12 © PharmOut 2015

Source ISPE API Baseline® Guide

6. Once Through – HEPA at room exhaust + System Exhaust

Bag-outFilter in duct

Page 13: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 13 © PharmOut 2015

Some other cross-contamination control strategies

Dust control booth (managed airflow)

Dust collectors

Vacuum Cleaning systems

Effective cleaning and housekeeping

Closed materials transfer

Contained processes

Page 14: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 14 © PharmOut 2015

Airflow Control Booth

Sampling

Dispensing

Page 15: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 15 © PharmOut 2015

Dust collectors

• Local

• Central

• Cross-contamination via duct system drops in processrooms.

Page 16: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 16 © PharmOut 2015

Vacuum Cleaning

• Convenient

• Fast

• Central vs Local Equipment

• Cleaning the tools

• Emptying the bag

Page 17: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 17 © PharmOut 2015

Floor cleaning & House-keeping

• Convenient

• Fast

• Frequent

• Avoid spreading contamination

Page 18: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 18 © PharmOut 2015

Closed Material Transfers

Avoid manual transfers (scooping)

• Gravity

• Vacuum transfer

• Dense phase conveying

• Spiral conveyor

Page 19: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 19 © PharmOut 2015

Contained Processes

• Closed process equipment

• Isolators around equipment & processes

• Rigid

• Flexible – glove bags

• Cleaning usually becomes more critical when we contain machines

Page 20: HVAC systems cross-contamination control systems cross-contamination control ... leak test. •Particle counter method. ... Vacuum Cleaning systems

Slide 20 © PharmOut 2015

Thank you for your time.Questions?

Gordon Farquharson

[email protected]