Top Banner
HVAC Systems – Understanding the basis Table of Contents 1. Introduction to HVAC Systems 2. HVAC System Types 3. HVAC Piping System 4. HVAC Air Distribution Equipments 5. Fans and Pumps 6. HVAC Instrumentation and Control 7. HVAC System Commissioning 1 www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com
119
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: HVAC Inputs by Team ABS Air Tech Gurgaon

HVAC Systems – Understanding the basis

Table of Contents

1. Introduction to HVAC Systems2. HVAC System Types3. HVAC Piping System4. HVAC Air Distribution Equipments5. Fans and Pumps6. HVAC Instrumentation and Control7. HVAC System Commissioning

1www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 2: HVAC Inputs by Team ABS Air Tech Gurgaon

Introduction to HVAC Systems• This article introduces the heating, ventilating and air-conditioning (HVAC)

systems. The primary function of HVAC systems is to provide healthy and comfortable interior conditions for occupants; well-designed, efficient systems do this with minimal non-renewable energy and air, and water pollutant emissions.

2www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 3: HVAC Inputs by Team ABS Air Tech Gurgaon

Introduction to HVAC Systems• The purpose of HVAC design is both high indoor air quality and energy efficiency.

These dual considerations require an integrated design

approach. Rigs heating, ventilation, and air conditioning system (HVAC) creates a climate that allows for maximum comfort by

compensating for changing climatic conditions.

• Though more costly to install and more complicated to operate, a chiller plant offers a number of benefits over a large number of individual packaged cooling units, including greater energy efficiency, better controllability, cheaper overall maintenance, and longer life. Using a comprehensive approach to building design, designers around the world have succeeded at creating highly efficient air-conditioning systems that provide excellent comfort at significant savings.

3www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 4: HVAC Inputs by Team ABS Air Tech Gurgaon

Introduction to HVAC Systems• Heating, ventilating and air- conditioning (HVAC) systems reduce the environmental impact of rigs/buildings in several key ways. The most important function of a HVAC systems is to provide the rig/buildings occupants with healthy and comfortable interior conditions. A carefully designed, efficient system can do this with minimal non- renewable energy and air and water pollutant emissions to minimize the

environmental impact. Cooling equipment that avoids chlorofluorocarbons and hydro- chlorofluorocarbons (CFCs and HCFCs) eliminates a major cause of damage to the ozone layer.

4www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 5: HVAC Inputs by Team ABS Air Tech Gurgaon

Introduction to HVAC Systems• Even the best HVAC equipment and systems cannot compensate for a faulty rig

design. Problems of this type cause inherently high cooling and heating needs and consume unnecessary resources and should be corrected if possible. Conservation of non-renewable energy through an intelligent architectural design offers the greatest opportunity for savings. The most important factors in these designs are careful control of solar gain, while taking advantage of passive heating, day lighting, natural ventilation and cooling. The critical factors in mechanical systems' energy consumption - and capital cost - are reducing the cooling and heating loads they must handle.

5www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 6: HVAC Inputs by Team ABS Air Tech Gurgaon

HVAC System Types• Types of System Designs - There are several major heating, ventilating, and air conditioning

system types in wide spread use today. These are air systems, hedonic and steam systems, and unitary type systems. Most systems in use today fall into one of these categories, or are a combination or variation of them. Each type of system has advantages and disadvantages.

• Air cooled

- Air cooled Chillers

6www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 7: HVAC Inputs by Team ABS Air Tech Gurgaon

7www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 8: HVAC Inputs by Team ABS Air Tech Gurgaon

8www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 9: HVAC Inputs by Team ABS Air Tech Gurgaon

9www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 10: HVAC Inputs by Team ABS Air Tech Gurgaon

• Air Cooled Chiller Advantages• Lower installed cost• Quicker availability• No cooling tower or condenser pump required• Less maintenance• No mechanical room required

10www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 11: HVAC Inputs by Team ABS Air Tech Gurgaon

• Water Cooled - Sea Water cooled Chillers - Fresh Water cooled Chillers

11www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 12: HVAC Inputs by Team ABS Air Tech Gurgaon

12www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 13: HVAC Inputs by Team ABS Air Tech Gurgaon

• Water-Cooled Chiller advantages

• Higher efficiency• Custom selection in larger sizes• Large tonnage capabilities• Indoor Chiller location• Longer life

13www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 14: HVAC Inputs by Team ABS Air Tech Gurgaon

•Purpose of an air handling system

Air Handling System

RoomWith

DefinedRequirements

SupplyAir

OutletAir

Air Handling Systems

14www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 15: HVAC Inputs by Team ABS Air Tech Gurgaon

Objectives

In the following slides, we will study the components of air handling systems in order to:

1. Become familiar with the components

2. Know their functions

3. Become aware of possible problems

15www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 16: HVAC Inputs by Team ABS Air Tech Gurgaon

+

Room/Cabin

Exhaust air treatment

Central air handling unit

Terminal air treatmentat production room level

Fresh air treatment (make-up air)

Main subsystems

16www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 17: HVAC Inputs by Team ABS Air Tech Gurgaon

FilterSilencer

Terminal filter

Weather louvre Control damper

FanFlow rate controller

Humidifier

Heating coil

Cooling coil

with droplet

separator

Production Room

Overview components

+

Prefilter

Exhaust Air Grille

Heater

Secondary Filter

Re-circulated air

17www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 18: HVAC Inputs by Team ABS Air Tech Gurgaon

• Weather louver

• Silencer

• Flow rate controller

• Control damper

• To prevent insects, leaves, dirt and rain from entering

• To reduce noise caused by air circulation

• Automated adjustment of volume of air (night and day, pressure control)

• Fixed adjustment of volume of air

Components (1)

18www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 19: HVAC Inputs by Team ABS Air Tech Gurgaon

• Heating unit •Cooling unit /dehumidifier

•Humidifier

•Filters

•Ducts

• To heat the air to the proper temperature

• To cool the air to the required temperature or to remove moisture from the air

• To bring the air to the proper humidity, if too low

• To eliminate particles of pre-determined dimensions and/or micro-organisms

• To transport the air

Components (2)

19www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 20: HVAC Inputs by Team ABS Air Tech Gurgaon

+

Production Room

Exhaust air

Return air(re-circulated)

Fresh air(make-up air)

Supply air

Air types

20www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 21: HVAC Inputs by Team ABS Air Tech Gurgaon

Filter classes

Dust filters

Standard Aerosol

FineCoarse ULPAHEPA

10 µ m > Dp > 1 µ mDp > 10 µ m Dp < 1 µ m

F5 - F9G1 - G4 U 14- 17H 11 - 13

EN 1822 StandardEN 779 Standard

21www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 22: HVAC Inputs by Team ABS Air Tech Gurgaon

Primary panel Primary panel filterfilter

Secondary Secondary filterfilter

HEPA or tertiaary filter

22www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 23: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct heaters Room Heters

SilensersSilensers

23www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 24: HVAC Inputs by Team ABS Air Tech Gurgaon

Volume control damper

De-humidification

Filter Pressure Gauges

AHU with fan Variable Speed

Controller

Humid room air

Air heater

Regeneration air

Humid room air Adsorber wheel Dry air

FireFire DampersDampers

24www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 25: HVAC Inputs by Team ABS Air Tech Gurgaon

Annex 1, 17.26

Regulation of room pressure – pressure differentials concept

Room pressure gauges

Room pressure indication panel

25www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 26: HVAC Inputs by Team ABS Air Tech Gurgaon

Pressure cascade injectables Protection from micro-organisms and particles

N ote : D irection of door opening relative to room pressure

15 Pa

0 PaA ir

Lock30 Pa PassageD

C

A

B

D LF

A ir LockA ir Lock

45 Pa

Room 3 Room 2 Room 1

45 Pa60 Pa30 Pa

26www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 27: HVAC Inputs by Team ABS Air Tech Gurgaon

Pressure cascade solidsProtection from cross-contamination

N o te : D ire c t io n o f d o o r o p e n in g re la t iv e t o ro o m p re s s u re 1 5 P a1 5 P a1 5 P aE3 0 P a Pa s s a g e 0 P aA irLo ck R o o m 3 R o o m 2 R o o m 11 5 P a A ir Lo ckA ir Lo ck

N ote : D irection of door opening relative to room pressure

15 Pa

15 Pa15 Pa

E30 Pa

Passage0 Pa

A irLock

Room 3 Room 2 Room 1

15 Pa

A ir LockA ir Lock

27www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 28: HVAC Inputs by Team ABS Air Tech Gurgaon

28www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 29: HVAC Inputs by Team ABS Air Tech Gurgaon

29www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 30: HVAC Inputs by Team ABS Air Tech Gurgaon

30www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 31: HVAC Inputs by Team ABS Air Tech Gurgaon

31www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 32: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan Coil Unit

32www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 33: HVAC Inputs by Team ABS Air Tech Gurgaon

Self Contain Unit

33www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 34: HVAC Inputs by Team ABS Air Tech Gurgaon

HVAC Air Distribution Equipments• Diffusers

4 Way Diffusers Two Way Diffusers One Way Diffuser

Round Diffusers34www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 35: HVAC Inputs by Team ABS Air Tech Gurgaon

Cabin Units

35www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 36: HVAC Inputs by Team ABS Air Tech Gurgaon

• Return / Exhaust Grilles

36www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 37: HVAC Inputs by Team ABS Air Tech Gurgaon

Contents

• Fan Design• Fan Performance• Fan-duct Systems• Duct Construction• Air Duct Design

Fans and Pumps

37www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 38: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan Design

• Common types of fans– Centrifugal fans: radial, forward curved, air foil

(backward curved), backward inclined, tubular, roof ventilator

– Axial fans: propeller, tube-axial, vane-axial• Fan arrangements

– Motor location, air discharge orientation, drive train type (direct drive or pulley drive)

– Centrifugal: single width single inlet (SWSI), double width double inlet (DWDI)

38www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 39: HVAC Inputs by Team ABS Air Tech Gurgaon

Centrifugal and axial fan components

AXIAL FANSCENTRIFUGAL FANS

39www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 40: HVAC Inputs by Team ABS Air Tech Gurgaon

Propeller Tube-axial

Tube-vane

AXIAL FANS

40www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 41: HVAC Inputs by Team ABS Air Tech Gurgaon

Tubular centrifugal fan Centrifugal roof ventilator

CENTRIFUGAL FANS

(* Note the airflow paths and impeller design.)41www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 42: HVAC Inputs by Team ABS Air Tech Gurgaon

Drive arrangements and motor positions42www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 43: HVAC Inputs by Team ABS Air Tech Gurgaon

Single- and double-width centrifugal fans43www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 44: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan Performance• Major parameters

– Fan volume flow rate (m3/s or l/s), Vf

– Fan total pressure Δptf, fan velocity pressure pvf & fan static pressure Δpsf (Pa)

– Fan power & efficiency• Fan power or air power (W) = Δptf x Vf

• Fan power input on the fan shaft (brake horsepower), Pf

• Fan total efficiency: ηt = Δptf x Vf / Pf

– Combined aerodynamic, volumetric & mechanical efficiencies

• Fan static efficiency: ηs = Δpsf x Vf / Pf

• Air temp. increase through fan, ΔTf = Δptf /(ρcpaηt)44www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 45: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan performance curves

Total pressure

Static pressure

Fan total efficiency

Fan static efficiency

Fan power input

Velocity pressure

Volume flow rate

45www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 46: HVAC Inputs by Team ABS Air Tech Gurgaon

Typical fan performance curve

46www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 47: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan Performance• Fan Laws

– Speed (n)– Volume flow (V)– Total pressure loss (Δp )– Air density (ρ)– For air systems that are

geometrically & dynamically similar: (D = impeller diameter)

• c.f.: pump laws

47www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 48: HVAC Inputs by Team ABS Air Tech Gurgaon

Velocity triangle at the blade inlet and outlet of a centrifugal fan

CENTRIFUGAL FANS

48www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 49: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan Performance

• Major issues causing energy losses to a centrifugal fan:– Circulatory flow between the blades– Air leakage at the inlet– Friction between fluid particles and the blade– Energy loss at the entrance– Partially filled passage

49www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 50: HVAC Inputs by Team ABS Air Tech Gurgaon

Operating characteristics for a backward-curved centrifugal fan50www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 51: HVAC Inputs by Team ABS Air Tech Gurgaon

Total efficiency curves for

centrifugal fans

51www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 52: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan power curves for centrifugal fans with same impeller diameter52www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 53: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan pressure curves for centrifugal fans with same impeller diameter53www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 54: HVAC Inputs by Team ABS Air Tech Gurgaon

Velocity triangles for a vane-axial fan

AXIAL FANS

54www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 55: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan pressure curves for axial fans with same impeller diameter55www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 56: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan efficiency curves for axial fans with same impeller diameter56www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 57: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan power curves for axial fans with same impeller diameter57www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 58: HVAC Inputs by Team ABS Air Tech Gurgaon

Performance curves for

controllable-pitch vane-axial

fans

58www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 59: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems

• Duct pressure changes (c.f. atm pressure)– Static pressure (SP)– Velocity pressure (VP) = ρV2 / 2 g– Total pressure (TP) = SP + VP

• Fan: a pumping device– Fan (total) pressure = pressure difference between

fan inlet and fan discharge– At fan suction/inlet, SP = negative (c.f.

atmospheric); at discharge, SP = positive

59www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 60: HVAC Inputs by Team ABS Air Tech Gurgaon

60www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 61: HVAC Inputs by Team ABS Air Tech Gurgaon

61www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 62: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems• Pressure characteristics

– SP and VP are mutually convertible (↑or↓)– TP always decreases in the direction of airflow– For constant-area straight duct sections

• Velocity and VP are constant• TP change = SP change

– When duct cross-sectional areas are reduced• Velocity and VP increase• Absolute value of both TP and SP decrease• Dynamic losses from elbow, dampers, etc.

62www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 63: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems

• Fan-duct systems– Flow resistance R, pressure drop Δp and volume flow

rate V

– Duct sections in series:– Duct sections in parallel:

ns RRRR 21

2VRp o

np RRRR

1111

21

63www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 64: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems

• Fan-duct systems– Terminology

• Primary air (conditioned air or makeup air)• Secondary air (induced space air, plenum air, or

recirculating air)• Transfer air (indoor air that moves from an adjacent

area)

– System curve: volume flow vs pressure loss– System operating point

64www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 65: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems• System effect Δpts

– Its additional total pressure loss caused by uneven or non-uniform velocity profile at the fan inlet, or at duct fittings after fan outlet

– Due to the actual inlet and outlet connections as compared with the total pressure loss of the fan test unit during laboratory ratings

Inlet Outlet65www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 66: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan system operating point & system effect

66www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 67: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems

• Modulation of air systems– Constant volume system

• Volume flow rate remains constant• Supply temperature is raised during part load

– Variable-air-volume (VAV) system• Volume flow rate is reduced to match part load

operation• Modulation curve

67www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 68: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan modulation curve68www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 69: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems• Fan modulation methods

– Damper (vary the opening of the air flow passage)• Waste energy

– Inlet vanes (opening & angle of inlet vanes)• Low cost; less efficient than following types

– Inlet cone (peripheral area of fan impeller)• Inexpensive; for backward curved centrifugal fan

– Blade pitch (blade angle of axial fan)– Fan speed (using adjustable frequency drives)

• Most energy-efficient; but usually cost more

69www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 70: HVAC Inputs by Team ABS Air Tech Gurgaon

Damper, inlet vanes & fan speed modulation70www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 71: HVAC Inputs by Team ABS Air Tech Gurgaon

Inlet vane modulation

71www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 72: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan speed modulation using

AC inverter

72www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 73: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems• Fan surge (in centrifugal fan)

– Occurs when air volume flow is not sufficient to sustain the static pressure difference between discharge & suction

• Discharge pressure is reduced momentarily• Volume flow & pressure fluctuations• Create noise & vibration

– Surge region: shall avoid operation in it• Fan stall (in axial fans)

– When smooth air flow suddenly breaks & pressure difference across the blades decreases

– The fan loses pressure capability drastically

73www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 74: HVAC Inputs by Team ABS Air Tech Gurgaon

Stall and stall region of an axial fan74www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 75: HVAC Inputs by Team ABS Air Tech Gurgaon

Fan-duct Systems

• Fan selection– Select fan type + determine fan size– Important factors:

• Pressure-volume flow operating characteristics• Fan capacity modulation• Fan efficiency• Sound power level• Airflow direction• Initial cost

75www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 76: HVAC Inputs by Team ABS Air Tech Gurgaon

76www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 77: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Types of air duct– Supply air duct– Return air duct– Outdoor air duct– Exhaust air

• Duct sections– Header or main duct (trunk)– Branch duct or runout

77www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 78: HVAC Inputs by Team ABS Air Tech Gurgaon

78www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 79: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Duct systems– Max. pressure difference (between air inside the

duct and the ambient air)• 125, 250, 500, 750, 1000, 1500, 2500 Pa

– Commercial buildings• Low-pressure duct system: ≤ 500 Pa, max 12 m/s• Medium-pressure system: 500-1500 Pa, max 17.5 m/s

– Residential buildings: 125 Pa or 250 Pa– Industrial duct system: ΔP can be higher

79www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 80: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Duct material: e.g. UL (Underwriters’ Laboratory) standard– Class 0: zero flame spread, zero smoke developed

• Iron, galvanized steel, aluminum, concrete, masonry, clay tile

– Class 1: flame spread ≤ 25, smoke developed ≤ 50

• Fiberglass, many flexible ducts

– Class 2: flame spread ≤ 50, smoke developed ≤ 100

80www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 81: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction• Shapes of air duct

– Rectangular• More easily fabricated on site, air leakage

– Round• Less fluid resistance, better rigidity/strength

– Flat oval– Flexible

• Multiple-ply polyester film w/ metal wire or strips

• SMACNA (Sheet Metal and Air Conditioning Contractors’ National Association) standards

81www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 82: HVAC Inputs by Team ABS Air Tech Gurgaon

Rectangular duct Round duct w/ spiral seam

Flat oval duct

Flexible duct

(Source: Wang, S. K., 2001. Handbook of Air Conditioning and Refrigeration)

82www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 83: HVAC Inputs by Team ABS Air Tech Gurgaon

Transverse joint reinforcement

(Source: Wang, S. K., 2001. Handbook of Air Conditioning and Refrigeration)

83www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 84: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Duct specification– Sheet gauge and thickness of duct material– Traverse joints & longitudinal seam

reinforcements– Duct hangers & their spacing– Tapes & adhesive closures– Fire spread and smoke developed– Site-fabricated or factory-/pre-fabricated

84www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 85: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Duct heat gain or loss– Temperature rise or drop– Duct insulation (mounted or inner-lined)

• Reduce heat gain/loss, prevent condensation, sound attentuation

• Minimum & recommended thickness– See ASHRAE standard or local codes

– Temperature rise curves• Depends on air velocity, duct dimensions & insulation

85www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 86: HVAC Inputs by Team ABS Air Tech Gurgaon

Temperature rise from duct heat gain(Source: Wang, S. K., 2001. Handbook of Air Conditioning and Refrigeration)

86www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 87: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Frictional losses– Darcey-Weisbach Equation

• Hf = friction head loss, or Δpf = pressure loss

• f = friction factor (dimensionless)• L = length of duct or pipe (m)• D = diameter of duct or pipe (m)• v = mean air velocity in duct (m/s)

87www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 88: HVAC Inputs by Team ABS Air Tech Gurgaon

Mode of airflow when air passes over and aroundsurface protuberances of the duct wall

δ >ε

δ <ε

88www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 89: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Duct friction chart– Colebrook formula

• Roughness & temperature corrections– Δpf = Ksr KT KelΔpf,c

• Ksr = correction factor for surface roughness

• KT = correction factor for air temperature

• Kel = correction factor for elevation

89www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 90: HVAC Inputs by Team ABS Air Tech Gurgaon

Friction chart for round duct

90www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 91: HVAC Inputs by Team ABS Air Tech Gurgaon

91www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 92: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction

• Circular equivalent– Hydraulic diameter, Dh = 4 A / P

• A = area (mm2); P = perimeter (mm)

– Rectangular duct:

– Flat oval duct:

92www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 93: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction• Dynamic losses

– Result from flow disturbances caused by duct-mounted equipment and fittings

• Change airflow path’s direction and/or area• Flow separation & eddies/disturbances

– In dynamic similarity (same Reynolds number & geometrically similar duct fittings), dynamic loss is proportional to their velocity pressure

93www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 94: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction• Local or dynamic loss coefficient

– Ratio of total pressure loss to velocity pressure

94www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 95: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction• Duct fittings

– Elbows– Converging or diverging tees and wyes– Entrances and exits– Enlargements and contractions

• Means to reduce dynamic losses– Turning angle, splitter vanes

• ASHRAE duct fitting database– Fitting loss coefficients

95www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 96: HVAC Inputs by Team ABS Air Tech Gurgaon

96www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 97: HVAC Inputs by Team ABS Air Tech Gurgaon

Region of eddies andturbulences in a round elbow 5-piece 90o round elbow

97www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 98: HVAC Inputs by Team ABS Air Tech Gurgaon

Rectangular elbow, smooth radius, 2 splitter vanes

Mitered elbow and its secondary flow

98www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 99: HVAC Inputs by Team ABS Air Tech Gurgaon

Airflow through arectangular converging

or diverging wye

99www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 100: HVAC Inputs by Team ABS Air Tech Gurgaon

Entrance Exit

100www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 101: HVAC Inputs by Team ABS Air Tech Gurgaon

Abrupt enlargement Sudden contraction

101www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 102: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct Construction• Flow resistance, R

– Total pressure loss Δpt at a specific volume flow rate V

– Flow resistance in series:

– Flow resistance in parallel:

ns RRRR 21

2VRpt

np RRRR

1111

21

102www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 103: HVAC Inputs by Team ABS Air Tech Gurgaon

Total pressure loss and flow resistance of a round duct section

103www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 104: HVAC Inputs by Team ABS Air Tech Gurgaon

Flow resistance in series

Flow resistance in parallel

104www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 105: HVAC Inputs by Team ABS Air Tech Gurgaon

Flow resistance for a Y connection

105www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 106: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design• Optimal air duct design

– Optimal duct system layout, space available– Satisfactory system balance– Acceptable sound level– Optimum energy loss and initial cost– Install only necessary balancing devices (dampers)– Fire codes, duct construction & insulation

• Require comprehensive analysis & care for different transport functions

106www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 107: HVAC Inputs by Team ABS Air Tech Gurgaon

Flow characteristics of a supply duct system

107www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 108: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design

• Design velocity– Constraints: space available, beam depth– Typical guidelines:

• Main ducts: air flow usually ≤ 15 m/s; air flow noise must be checked

• With more demanding noise criteria (e.g. hotels), max. air velocity: main duct ≤ 10-12.5 m/s, return main duct ≤ 8 m/s, branch ducts ≤ 6 m/s

– Face velocities for air-handling system components

108www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 109: HVAC Inputs by Team ABS Air Tech Gurgaon

109www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 110: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design• Reduce dynamic losses of the critical path

– Maintain optimum air velocity through duct fittings– Emphasize reduction of dynamic losses nearer to

the fan outlet or inlet (high air velocity)– Proper use of splitter vanes– Set 2 duct fittings as far apart as possible

• Air duct leakage– Duct leakage classification

• AISI, SMACNA, ASHRAE standards

110www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 111: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design

• Fire protection– Duct material selection– Vertical ducts (using masonry, concrete or clay)– When ducts pass through floors & walls– Use of fire dampers– Filling the gaps between ducts & bldg structure– Duct systems for industrial applications

• Any other fire precautions?

111www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 112: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design• Design procedure (computer-aided or manual)

– Verify local codes & material availability– Preliminary duct layout– Divide into consecutive duct sections– Minimise local loss coefficients of duct fittings– Select duct sizing methods– Critical total pressure loss of tentative critical path– Size branch ducts & balance total pressure at junctions– Adjust supply flow rates according to duct heat gain– Resize duct sections, recalculate & balance parallel paths– Check sound level & add necessary attenuation

112www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 113: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design• Duct layout

– Symmetric layout is easier to balance• Smaller main duct & shorter design path

– For VAV systems, duct looping allows feed from opposite direction

• Optimize transporting capacity (balance points often follow the sun’s position)

• Result in smaller main duct

– Compare alternative layouts & reduce fittings– For exposed ducts, appearance & integration with

the structure is important113www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 114: HVAC Inputs by Team ABS Air Tech Gurgaon

Typical supply duct system with symmetric layout & looping

114www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 115: HVAC Inputs by Team ABS Air Tech Gurgaon

Air Duct Design• Duct liner

– Lined internally on inner surface of duct wall– Mainly used for noise attenuation & insulation– Fiberglass blanket or boards

• Duct cleaning– Prevent accumulation of dirt & debris– Agitation device to loosen the dirt & debris– Duct vacuum to extract loosened debris– Sealing of access openings

115www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 116: HVAC Inputs by Team ABS Air Tech Gurgaon

Duct breakout noise

116www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 117: HVAC Inputs by Team ABS Air Tech Gurgaon

HVAC Piping System

117www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 118: HVAC Inputs by Team ABS Air Tech Gurgaon

HVAC Instrumentation and Control

118www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com

Page 119: HVAC Inputs by Team ABS Air Tech Gurgaon

HVAC System Commissioning• The key elements of commissioning include:

• Installation checks. Check installed equipment to ensure that all associated components and accessories are in place.

• Operational checks. Verify and document that systems are performing as expected, and that all sensors and other system control devices are properly calibrated.

• Documentation. Confirm that all required documentation has been provided, such as a statement of the design intent and operating protocols for all building systems.

• O&M manuals and training. Prepare comprehensive operation and maintenance (O&M) manuals, and provide training for rig operations staff.

• Ongoing monitoring. Conduct periodic monitoring after the school is occupied to ensure that equipment and systems continue to perform according to design intent.

• Correctly implemented, commissioning is extremely cost-effective, and should improve the delivery process, increase systems reliability, improve energy performance, ensure good indoor environmental quality, and improve operation and maintenance of the facility.

119www.absairtech.in || www.abscleanroom.com || www.absventilation.com || www.abscoldroom.com