12 INDIVIDUAL CATALOG H.V. VACUUM CIRCUIT BREAKERS MAGNETIC CONTACTORS PROTECTIVE RELAYS Vacuum circuit breakers HS series Protective relays DUT series Vacuum circuit breakers Auto. V Protective relays QH series Vacuum circuit breakers New-Auto.V Vacuum Magnetic Contactors HN series HIGH VOLTAGE EQUIPMENT Up to 36kV Vacuum circuit breakers Multi VCB from D&C CATALOG 19th Edition Revised
91
Embed
H.V. Vacuum circuit breakers HS series Protective relays ...
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
12INDIVIDUALCATALOG
H.V.VACUUMCIRCUITBREAKERS
MAGNETICCONTACTORS
PROTECTIVERELAYS
Vacuum circuit breakersHS series
Protective relaysDUT series
Vacuum circuit breakersAuto. V
Protective relaysQH series
Vacuum circuit breakersNew-Auto.V
Vacuum Magnetic ContactorsHN series
HIGHVOLTAGE
EQUIPMENTUp to 36kV
Vacuum circuit breakersMulti VCB
from D&C CATALOG 19th Edition
Revised
LOW VOLTAGE PRODUCTS Up to 600 VoltsIndividualcatalog No.
01 Magnetic Contactors and StartersThermal Overload Relays, Solid-state Contactors
02
Industrial Relays, Industrial Control RelaysAnnunciator Relay Unit, Time Delay RelaysElectronic Counters
DUO seriesManual Motor Starters and Contactors Combination Starters
AC Power RegulatorsNoise Suppression FiltersControl Power Transformers
Vacuum Circuit Breakers, Vacuum Magnetic Contactors12 Protective Relays
Vacuum Circuit Breakers General information ....................................................................................... 12/1Advantages .................................................................................................... 12/2HS series
General information.................................................................................... 12/4Specifications ............................................................................................. 12/5Types and ratings ....................................................................................... 12/11Installation and accessories ....................................................................... 12/14Dimensions ................................................................................................. 12/15Wiring diagrams ......................................................................................... 12/24Application guide ........................................................................................ 12/25
Auto. VSpecifications ............................................................................................. 12/26Design features .......................................................................................... 12/27Types and ratings ....................................................................................... 12/29New-Auto. V ............................................................................................... 12/30Installation and accessories ....................................................................... 12/35Dimensions ................................................................................................. 12/38Wiring diagrams ......................................................................................... 12/42
Multi VCBSpecifications ............................................................................................. 12/45Types and ratings ....................................................................................... 12/47Installation and accessories ....................................................................... 12/48Dimensions ................................................................................................. 12/50Wiring diagrams ......................................................................................... 12/54
HN series ....................................................................................................... 12/57
12 H.V. Vacuum circuit breakersVacuum magnetic contactors
Protective relays
Vacuum Magnetic Contactors
Protective Relays
MINIMUM ORDERS
Orders amounting to less than ¥10,000 net per order willbe charged as ¥10,000 net per order plus freight andother charges.
WEIGHTS AND DIMENSIONS
Weights and dimensions appearing in this catalog are thebest information available at the time of going to press.FUJI ELECTRIC FA has a policy of continuous productimprovement, and design changes may make thisinformation out of date.Please confirm such details before planning actualconstruction.
INFORMATION IN THIS CATALOG IS SUBJECT TO
CHANGE WITHOUT NOTICE.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/1
12
Breaking Rated Rated Closing Typecurrent current voltage system : Installation
FUJI vacuum circuit breakersVacuum circuit breakers are compactcircuit breakers designed for safeoperation, high reliability and easymaintenance, and are widely used forvarious types of high voltage circuits.FUJI V-circuit breakers (VCB) havebeen developed through the use of ourmany years of successful experienceand advanced technology. They arecompact and light-weight, and areavailable in a number of current ratings.
HS seriesThese types are available in all ratingsfrom 3.6 to 36kV, and can be applied toa variety of H.V. switchgear. The motor-spring stored-energy types feature auto-reclosing. The HS types arecomparatively high in breaking currentwith ratings of over 7.2kV, 20kA.• Breaking currents: 12.5kA to 50kA• Rated voltage: 3.6kV to 36kV• Standards: JEC, IECSee page 12/4.
H.V. Distribution EquipmentVacuum circuit breakers
General information
Auto. VAuto. Vs are provided with a built-inelectronic overcurrent relay and toroidal-type CT.They require little space for installationand also facilitate the system wideprotective coordination.The inverse-time operating andinstantaneous trip currents can beset by means of the dial.• Breaking currents: 8kA, 12.5kA• Rated voltage: 3.6/7.2kV• Standards: JIS C4603See page 12/26.
HS series Multi VCBAF92-31 KK03-058
Auto. V
Quick selection table
Multi VCBThe Multi VCBs are general purposeVCBs which are small in size and simplein construction thus allowing them to beapplied to many types of switchgear.• Breaking currents: 8kA, 12.5kA• Rated voltage: 3.6/7.2kV• Standards: JIS C4603See page 12/45.
Note: Installation : See pages 12/4 for HS series, 12/26 forAuto. V and 12/45 for Multi VCB.
Breaking Rated Rated Closing Typecurrent current voltage system : Installation
8.0 400 3.6/7.2 Motor-spring HA08 -A12.5 600 Fixed HA12 -A
8.0 400 3.6/7.2 Motor-spring HA08A -A12.5 600 Draw-out HA12A -A
Discontinued Mar. 2007
Discontinued Mar. 2007
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/2
Description3.6kV to 36kV, 600 to 4000A, 12.5 to 50kA
The revolutionary arc extinguishingsystem
RotaryFUJI VCBs have employeda unique designprinciple in which thecontacts are providedwith a succession of slitshaving toroidal-type CrCu contactsmounted on them.The arc is driven round the circularcontact surface as it is beingextinguished. Since the arc is notlocalized at one point there is no fear ofoverheating.This results in much improved inter-electrode dielectric strength so ensuringexcellent breaking capability. More-over, uneven contact wear is minimized.
GetterFUJI vacuum interruptersmake use of the getteringeffect. The toroidal-typecontacts are made of aspecial chromium-copper(CrCu) alloy specially developed byFUJI so as to ensure a large “getter”quality.The metallic gases thus produced atinterruption and left in the vacuum arequickly absorbed by the getter. Thegases are neutralized so maintainingthe high degree of vacuum.The interrupters require a minimum ofattention over their long service life.
SurgeSwitching surges can begenerated at smallcurrent breakingdue to the VCB inherentchopping current.FUJI has paid much attention to thisproblem, and after much effort ondesign and materials research it hasbeen possible to reduce the choppingcurrent to 3.5 Amps. This very smallchopping current means that thecorresponding surge voltage will bereduced and cost efficient surgeprotection can be carried out for motors,transformers and other load equipment.
H.V. Distribution EquipmentVacuum circuit breakersAdvantages
The revolutionary arc extinguishingsystem
Stationarycontact
Slits
Toroidal-typeCrCu contacts
Arc flow
Moving contact
Cover
Stainless steelbellows
Stationarycontact
Ceramic tube
Moving contactBellows
Shield
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/3
12
H.V. Distribution EquipmentVacuum circuit breakers
Advantages
Progress of arc extinctionArcs generated by VCBs have inherentcharacteristics that change whenapproximately 10kA is reached. Lessthan 10kA a dispersed arc occurs, overthis value the arc is concentrated. Thephotos were taken consecutively andillustrate an interruption in the 25kArange (concentrated arc). About 41/2rotations occurred (10ms at 50Hz).This time is typical, but variesaccording to breaking current andarcing times.
Explanation1. The contacts begin to open and the
arc moves from the center to the lefthand side.
2. 3. The arc is driven round the toroidal-type contact surface.
4. The contacts are in the full openposition just before interruption iscompleted.
Definitions What is the action of the “getter”?Sometimes called a “degasser” the“getter” uses a special material such aszirconium alloy that has the property ofabsorbing metallic gases in a vacuum.This allows the high degree of vacuumto be maintained.
Switching surges and VCBs?Switching surges can be generatedwhen breaking currents within severalhundreds range.VCB inherent switching surges aregenerated under certain specificconditions which mainly comprisecurrent chopping surges and multiplecurrent reignition surges. No problem isposed by switching surges whenbreaking current exceeds severalhundred amperes.
Surge voltagesThe value of the surge voltage due toswitching surges varies according to the
load circuit conditions.This can be expressed in the followingsimple formula:Surge voltage = Surge impedance Chopping currentTherefore, it is necessary to keep thechopping current low in order to reducethe surge voltage to the minimum. Thepeak transient voltage is obtained byadding to the above calculation thevoltage on the load side at the time ofcurrent chopping.
Chopping surgeThe chopping surge occurs when a lowcurrent is interrupted, the arc is unstablebefore current becomes zero and thecurrent is forcedly chopped. At this timea surge is generated by the energyremaining in the load inductance.Example:When the no-load interruption of atransformer is carried out the excitingcurrent only is interrupted.
Chopping surge
Multiple reignition surgeThe multiple reignition surges can occurwhen breaking currents range from tensto hundreds of amperes. Although noproblem is normally posed even whenbreaking these currents,
1* Chopping surge suppresed by reignition 2* Chopping surge not accompanied with reignition
Chopping current HIGH
IC : Chopping currentVl : Voltage at load sideVS : Surge transient voltageVP : Peak transient voltage
VP= Vl + VsVS= Surge impedance × IC
Surge impedance:
Chopping current LOW
VCB
Natural current zero
FUJIVCB
OthersVp
Vp
Ic
Vs
Vs
Vl Vl
Vl
I
R C L
Z=LC
Switching surge
1
2
3
4
a high surge voltage can be generatedwhen breaking an inrush current onstarting the motors.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/4
DescriptionHS type 3.6kV to 36kV up to 50kA. FUJIHS series vacuum circuit breakers aredesigned to meet the many specialneeds of industry. The vacuuminterrupter system employed reflects thelatest technology. The circuit breakerhas a very stable and constant breakingperformance over a wide range ofcurrents up to the rated short circuitcurrent value.The motor spring type (M) closingsystem can perform high speedreclosing.The contacts are made of a special alloyand require no maintenance over theirlong life time.The interrupter is provided with acontact-wear indicator which givesnotice when replacement is required.The open and close positioningindicator, operating counter, pushbuttonfor manual interruption and manualclosing device are conveniently installedon the control section of the dead-frontoperating panel, and are isolated fromthe high-voltage breaking section forsafety reasons and to facilitate operationand inspection. FUJI VCBs comprisethe fixed mounted (P) type and cradle (Xand Y) types. Since the cradle version isprovided with a draw-out systemswitchgear assembly is easily carriedout.
Ordering informationSpecify the following:1. Type number2. Rated voltage, current and frequency3. Rated breaking capacity4. Installation system5. Operating voltage and frequency (M)
of closing system6. Voltage and current of tripping system7. Optional accessories, if required
H.V. Distribution EquipmentVacuum circuit breakersHS series/General information
InstallationP : Fixed typeX : Draw-out type with cradle for JEM1425 Class CWU : Draw-out type with cradle for JEM1425 Class CWY : Draw-out type with cradle and shutter for JEM1425 MW,
Installation P, Y P, Y P, YX, U (600, 1200A only) X, U (600, 1200A only) X (1200, 2000A only)
Mass (draw-out type without cradle)[kg] 62 (X, U, Y: 600A) 66 (X, U, Y: 600A) 122 (X, Y: 1200A) 66 (Y: 1200A) 70 (Y: 1200A) 130 (X, Y: 2000A)117 (Y: 2000A) 117 (Y: 2000A) 220 (Y: 3000A)
H.V. Distribution EquipmentVacuum circuit breakers
HS series
Specifications
Notes: *1 Contact FUJI for the information concerning the 3 sec. rating of IEC.*2 If capacitor tripping system is required, connect a capacitor trip device VCB-T1A or VCB-T2A (optional accessory) to AC power supply.*3 2A for 2000A rating.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/6
Type HS4006 HS4006 HS5006 HS5006 HS6306-Mf-E -40Mf-N -Mf-NA -30Mf-N -Mf-NB
Installation P, Y P, X, Y P, Y P, Y YX (1200, 2000A only)
Mass (draw-out type without cradle) [kg] 122 (X, Y: 1200A) 400 240 320 350130 (X, Y: 2000A)220 (Y: 3000A)
H.V. Distribution EquipmentVacuum circuit breakersHS series
Specifications
Notes: *1 Contact FUJI for the information concerning the 3 sec. rating of IEC.*2 If capacitor tripping system is required, connect a capacitor trip device VCB-T1A or VCB-T2A (optional accessory) to AC power supply.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/7
12
Specifications
Type HS1210 HS1610 HS2010 HS2510 HS3110-Mf-E -Mf-E -Mf-E -Mf-E -Mf-E
Closing time at no load [sec.] 0.04 0.04 0.04 0.04 0.04
Rated operating sequence JEC O-1min-CO-3min-CO, CO-15s-CO or O-0.35s-CO-1min-COIEC O-3min-CO-3min-CO, CO-15s-CO or O-0.3s-CO-3min-CO
Opening time [sec.] JEC 0.03 0.03 0.03 0.03 0.03
IEC 0.03 0.03 0.03 0.03 0.03
Closing system Motor-spring stored energy (High speed reclosing) (M)
Operating voltage and current for closing 100V AC/DC, 1.7A (600, 1200A), 2.5A (2000A) 100V AC/DC, 2.5A200V AC/DC, 1A (600, 1200A), 1.7A (2000A) 200V AC/DC, 1.7A
Control voltage and current for closing 100V AC/DC, 4A (600, 1200A), 5A (2000A) 100V AC/DC, 5A200V AC/DC, 2A (600, 1200A), 2.5A (2000A) 200V AC/DC, 2.5A
Tripping system*2 Shunt trip (f)
Operating voltage and current for tripping 100V DC, 4A 100V DC, 4A200V DC, 2A 200V DC, 2A
Notes: *1 Contact FUJI for the information concening the 3 sec. rating of IEC.*2 If capacitor tripping system is required, connect a capacitor trip device VCB-T1A or VCB-T2A (optional accessory) to an AC power supply.
H.V. Distribution EquipmentVacuum circuit breakers
HS series
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/8
Type HS3110 HS4010 HS4010 HS5010 HS5010-30Mf-N -Mf-NA -Mf-N -Mf-NA -30Mf-N
Installation P, Y P, Y P, Y(3000A) P, Y P, YX(4000A)
Mass (draw-out type without cradle) [kg] 320 240 320 (3000A) 240 320400 (4000A)
H.V. Distribution EquipmentVacuum circuit breakersHS series
Specifications
Notes: *1 Contact FUJI for the information concerning the 3 sec. rating of IEC.*2 If capacitor tripping system is required, connect a capacitor trip device VCB-T1A or VCB-T2A (optional accessory) to AC power supply.*3 0.07s for 4000A rating.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/9
Notes: *1 Contact FUJI for the information concerning the 3 sec. rating of IEC.*2 If capacitor tripping system is required, connect a capacitor trip device VCB-T1A or VCB-T2A (optional accessory) to AC power supply.
H.V. Distribution EquipmentVacuum circuit breakers
HS series
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/10
H.V. Distribution EquipmentVacuum circuit breakersHS series
Type HS1220 HS1620 HS2520 HS4020 HS2530-Mf-K -Mf-E -Mf-E -Mf-N -Mf-N
Notes: *1 Contact FUJI for the information concerning the 3 sec. rating of IEC.*2 If capacitor tripping system is required, connect a capacitor trip device VCB-T1A or VCB-T2A (optional accessory) to AC power supply.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/11
12
HS2006 -06Mf-E
HS2006 -12Mf-E
HS2006 -20Mf-E
HS2506 -06Mf-E
HS2506 -12Mf-E
HS2506 -20Mf-E
HS3106 -12Mf-E
HS3106 -20Mf-E
HS3106 -30Mf-E
HS4006 -12Mf-E
HS4006 -20Mf-E
HS4006 -30Mf-E
HS4006 -40Mf-N
HS5006 -12Mf-NA
HS5006 -20Mf-NA
HS5006 -30Mf-N
HS6306 -12Mf-NB
HS6306 -20Mf-NB
Types and ratings, 3.6/7.2kV
Rating
Volts Breaking Currentcurrent
(kV) (kA) (A)
Closing system Tripping
Closing Operating voltage
system voltage Shunt-trip(f)*2
Type
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
3.6/7.2 20 600
1200
2000
25 600
1200
2000
31.5 1200
2000
3000
40 1200
2000
3000
4000
50 1200
2000
3000
63 1200
2000
Notes: *1 Installation system P: Fixed typeX: Draw-out type with cradle for JEM 1425 Class CWU: Draw-out type with cradle for JEM 1425 Class CWY: Draw-out type with cradle and shutter for JEM 1425 Class MW, PW
*2 Closing system M: Motor-spring stored-energy (High speed reclosing)
: Avaiable installation system *1
Ordering code
P, X, U, Y
P, X, U, Y
P, X, Y
P, X, Y
P, X
P, Y
Y
H.V. Distribution EquipmentVacuum circuit breakers
HS series
HS1210 -06Mf-E
HS1210 -12Mf-E
HS1210 -20Mf-E
HS1610 -06Mf-E
HS1610 -12Mf-E
HS1610 -20Mf-E
HS2010 -06Mf-E
HS2010 -12Mf-E
HS2010 -20Mf-E
Types and ratings, 12kV
Rating
Volts Breaking Currentcurrent
(kV) (kA) (A)
Closing system Tripping
Closing Operating voltage
system voltage Shunt-trip(f)*2
Type
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
12 12.5 600
1200
2000
16 600
1200
2000
20 600
1200
2000
: Avaiableinstallationsystem *1
Ordering code
P, X, Y
P, X, Y
P, X, Y
Notes: *1 Installation system P: Fixed typeX: Draw-out type with cradle for JEM 1425 Class CWY: Draw-out type with cradle and shutter for JEM 1425 Class MW, PW
*2 Closing system M: Motor-spring stored-energy (High speed reclosing)
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/12
Discontinued
Mar. 2007
H.V. Distribution EquipmentVacuum circuit breakersHS series
Notes: *1 Installation system P: Fixed typeX: Draw-out type with cradle for JEM 1425 Class CWY: Draw-out type with cradle and shutter for JEM 1425 Class MW, PW
*2 Closing system M: Motor-spring stored-energy (High speed reclosing)
HS2510 -06Mf-E
HS2510 -12Mf-E
HS2510 -20Mf-E
HS3110 -12Mf-E
HS3110 -20Mf-E
HS3110 -30Mf-N
HS4010 -12Mf-NA
HS4010 -20Mf-NA
HS4010 -30Mf-N
HS4010 -40Mf-N
HS5010 -12Mf-NA
HS5010 -20Mf-NA
HS5010 -30Mf-N
Types and ratings, 12kV
Rating
Volts Breaking Currentcurrent
(kV) (kA) (A)
Closing system Tripping
Closing Operating voltage
system voltage Shunt-trip(f)*2
Type
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
12 25 600
1200
2000
31.5 1200
2000
3000
40 1200
2000
3000
4000
50 1200
2000
3000
: Avaiableinstallationsystem *1
Ordering code
P, X, Y
P, X, Y
P, Y
P, Y
P, Y
X
P, Y
Notes: *1 Installation system P: Fixed typeX: Draw-out type with cradle for JEM 1425 Class CWY: Draw-out type with cradle and shutter for JEM 1425 Class MW, PW
*2 Closing system M: Motor-spring stored-energy (High speed reclosing)
HS1215 -06Mf-N
HS1215 -12Mf-N
HS1215 -20Mf-N
HS1615 -06Mf-N
HS1615 -12Mf-N
HS1615 -20Mf-N
HS2015 -06Mf-N
HS2015 -12Mf-N
HS2015 -20Mf-N
HS2515 -06Mf-N
HS2515 -12Mf-N
HS2515 -20Mf-N
HS3115 -12Mf-N
HS3115 -20Mf-N
HS3115 -30Mf-N
HS4015 -12Mf-N
HS4015 -20Mf-N
HS4015 -30Mf-N
Types and ratings, 15kV
Rating
Volts Breaking Currentcurrent
(kV) (kA) (A)
Closing system Tripping
Closing Operating voltage
system voltage Shunt-trip(f)*2
Type
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
15 12.5 600
1200
2000
16 600
1200
2000
20 600
1200
2000
25 600
1200
2000
31.5 1200
2000
3000
40 1200
2000
3000
: Avaiableinstallationsystem *1
Ordering code
P, X, Y
P, X, Y
P, X, Y
P, X, Y
P, Y
P, Y
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/13
12
HS1220 -06Mf-K
HS1220 -12Mf-K
HS1620 -06Mf-E
HS1620 -12Mf-E
HS2520 -06Mf-E
HS2520 -12Mf-E
HS2520 -20Mf-E
HS4020 -12Mf-N
HS4020 -20Mf-N
HS4020 -30Mf-N
HS2530 -06Mf-N
HS2530 -12Mf-N
HS2530 -20Mf-N
Types and ratings, 24kV and 36kV
Rating
Volts Breaking Currentcurrent
(kV) (kA) (A)
Closing system Tripping
Closing Operating voltage
system voltage Shunt-trip(f)*2
Type
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
M 100/110V DC 100/110V DC
24 12.5 600
1200
16 600
1200
25 600
1200
2000
40 1200
2000
3000
36 25 600
1200
2000
: Avaiableinstallationsystem *1
Ordering code
P, X, Y
P, X, Y
P, X, Y
P, Y
P, M, X
Notes: *1 Installation system P: Fixed typeX: Draw-out type with cradle for JEM 1425 Class CWY: Draw-out type with cradle and shutter for JEM 1425 Class MW, PWM: Draw-out type for HS2530
*2 Closing system M: Motor-spring stored-energy (High speed reclosing)
H.V. Distribution EquipmentVacuum circuit breakers
HS series
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/14
H.V. Distribution EquipmentVacuum circuit breakersHS series
Installation and supplied accessories
Vacuum circuit breaker Cradle Construction Accessories
P-fixed mounting type
X-draw-out type
Y-draw-out type
AF93-312
AF93-314
AF93-313
The VCB shall be fixed to the switchgear by means of 4bolts. No draw-out system is provided. Wheels areprovided to facilitate movement or transport.
Open type cubicle
• Clamp bolts(4 ea. for one unit)
• Closing handle• Plug-in connector for
control circuit• On-off counter
A cradle is provided with a draw-out system.This cradle makes unnecessary the provision of rails ormain circuit connector for the switchgear.No mechanical adjustment is required.
JEM 1425Class CW type metal enclosure
• On-off counter• Cradle with draw-out
system (Main circuitconnector, earthingshoe, rail, etc.)
A cradle is provided with a draw-out system to accept themetal-clad switchgear, which is provided with a shutter.All the necessary parts are provided for this type ofbreaker. The switchgear is very easy to assemble.
JEM 1425Class PW or MW type metal-clad switchgear
• On-off counter• Cradle with draw-out
system (Main circuitconnector, earthingshoe, rail, shutter, etc.)
This is used when thetrip circuit is connectedto an AC power supply,and as well as thecapacitor,semiconductors are alsobuilt in. It provides a DCoutput and the trip coil isDC rated.
Minimum distance to grounded metal Draw-out stroke
Grounded metal View from P
Mounting hole
180
18075404-ø14
40 20
Terminal
Terminal
711726
582
15
370
2040
786 180
38200 556
55
180
1236
924
582
0
180
1807540
688
1082
0
35400 500
4-ø12Mounting hole
4-ø14
Draw-out stroke
P
View from P
App
rox.
38°
Approx 275
Minimum distance to grounded metal Grounded metal
Terminal
HS1220X-06Mf-K, HS1620X-06Mf-E
970638619
230230
800 20
Draw-out stroke
250 55240
927 35
641
58
8
1064
230
230
30
2040
400 370 170832
Appro
x 20
°
6-ø14Mounting hole
P
2-ø14
View from P
Terminal
12/18Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
H.V. Distribution EquipmentVacuum circuit breakersHS series
Dimensions, mmDraw-out/X type
HS2520X-06Mf-E
Draw-out/Y type
HS2006Y-06Mf-E, HS2506Y-06Mf-E
514
35 35
187
187
300
425
528
481
408
162
500
649 130
22
4
197
220
533
558
15 m
in.
35
1047
3
350
20°
533
4–ø12
184
5815 min.
450150
40
40
35
53
116
2–ø11
4–ø11
(75)
(150
)
175
Note: To connect the conductors to the main circuit disconnecting-switch section (stationary side), use the four positions (4-ø11) indicated with the black dots. If two positions are to be used for fixing due to the nature of the conductors to be connected, use the two positions (2-ø11) indicated with the white circles
(Mounting holes for disconnecting-switch section)
(Mounting holes for disconnecting-switch section)
Mounting hole
PAppr
ox.
Approx.
130 130
220
TerminalGrounded metal
Draw-out stroke
Minimum distance to grounded metalDetail Q
Q
Terminal
HS2006Y-12Mf-E, HS2506Y-12Mf-E
549
35 35
187
187
300
425
563
516
408
162
500
649 130
22
4
196
220
533
558
15m
in
35
1047
3
350
20°
533
4–ø12
184
5815min
450150
40 40
35
53
116
2–ø11
4–ø11
(75)
(150
)
175
Note: To connect the conductors to the main circuit disconnecting-switch section (stationary side), use the four positions (4-ø11) indicated with the black dots. If two positions are to be used for fixing due to the nature of the conductors to be connected, use the two positions (2-ø11) indicated with the white circles
(Mounting holes for disconnecting-switch section)
(Mounting holes for disconnecting-switch section)
Mounting hole
PAppr
ox.
Approx.
145 145
220
Terminal
Grounded metal
Draw-out stroke
Minimum distance to grounded metalDetail Q
Q
Terminal
230660
230
39
40 20
1011
935 196
56
250 629
425
692
1265
1127
10
577
838
8
1255
230
40
230
865100 350350
2-ø14
Draw-out stroke
P
View from P
Minimum distance to grounded metal
Grounded metal
7 7
App
rox
38°
Approx 275
6-ø14Mounting hole
Terminal
12
12/19Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice
H.V. Distribution EquipmentVacuum circuit breakers
HS series
550
121 35
185
185
243
240
630
673
695
300
478
563
514
457
164
43318040
500
660 130
2335
10
473
Approx. 507
20°
625
4–ø12
199
P
Mounting hole
Appr
ox.
Draw-out stroke
Grounded metal
120°
120°
120°
140
M12 (Depth 20)
3-M12 Depth 20)
ø55
164
ø36
145 145
240
Terminal
Note: To connect the conductors to the main circuit disconnecting-switch section (stationary side), use the three positions
(3-M12) indicated with the black dots. If two positions are to be used for fixing due to the nature of the conductors to be connected, use the two positions indicated with a white circle and a black dot of upper side.
View from P
HS2006Y-20Mf-E, HS2506Y-20Mf-E
HS3106Y-12Mf-E, HS4006Y-12Mf-E
HS3106Y-20Mf-E, HS4006Y-20Mf-E
400
582
666 15681
4-ø12
Mounting hole
35 500
220679 115
81024
536
3
180
P
1068
8
Minimum distance to grounded metal
499150
3855 Grounded metal
Terminal
Draw-out stroke
180 180
20
27.527.5
3-M10(Depth 20)
80Grounded
terminalView from P
App
rox.
38°
Approx.275
400
582
666 15681
35 500
320679 115
81024
535
9
180
P
1068
8
Minimum distance to grounded metal
499150
3855 Grounded metal
Draw-out stroke
180 180
20
27.527.5
3-M10 80
Terminal
(Depth 20)
View from P
4-ø12
Mounting hole
Grounded terminal
App
rox.
38°
Approx.275
12/20Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
H.V. Distribution EquipmentVacuum circuit breakersHS series
Type Rated Max. operating Frequencyvoltage voltage
AF3320R3TXG0542 3.3kV 3 115% of
AF6620R3TXG0543 6.6kV rated voltage 3
For 11kV : Contact FUJI.
Application guide of surge absorberWhen VCBs are interrupted especially under specificoverlapping conditions, chopping surges or surges due tomultiple restrikes will cause an escalating effect.It is therefore recommended that surge absorbers and arrestersare fitted to protect motors or transformers.
Vacuum condition tester/VC-1AIt is recommended that a withstand voltage tester (type VC-1A,sold separately) is used to check the state of the vacuum withinthe vacuum interrupter. The method of testing is very simple.First, withdraw the VCB from its enclosure set at the OFFposition and switch the control circuit to the isolation position.Then earth the VCB together with the VC-1A tester and apply atest voltage. In this case apply 22kV (if the VCB's rated voltageis 7.2kV) between the poles of the vacuum interrupter for oneminute. Under these conditions if the vacuum is normal acontinuous buzzer signal will be given during the period the testvoltage is applied.On the other hand an intermittent buzzer sound will be given ifthe vacuum is unserviceable. Replace with a new interrupter ifnecessary.
Arrester/GLI
Type GLI-3G GLI-6G
Rated voltage 4.2kV 8.4kVNominal discharge current 2.5kA 2.5kAMax. clamping voltage 15kV or less 30kV or lessDischarge current withstand 30kA, 2 times 30kA, 2 timescapacity
Type VC-1A (Portable type)
Input voltage 100V 50/60HzOutput voltage 22/11kV ACOperation Continuous (or 10 min. if the output is short-
circuited)Detecting current When 1.0A current flows in the L.V. input circuit
the detector relay operates and interrupts.Timer 1-minute timer is built into the tester.Accessories Input cord: 3 meters. Cord for test use (with
clips): 1.5 meters (2 leads)Mass 20kg
Notes: : Suppression device required – : Suppression device not required*1 The withstand voltages (impulse) of transformer must exceed the values
listed above.*2 When breaking a magnetizing inrush current , it is recommended that a
suppression device will be used.*3 Semiconductor device must be provided with suitable suppression
devices when a semiconductor is installed on the load side oftransformer.
C-R type surge absorber
50/60Hz
50/60Hz
Dimensions, mm/Surge absorber SH-27
Dimensions, mm
Vacuum condition testerVC-1A
R
C
4-12×16Ellipse
400455490
70 100
max
.120
390
140 140
Liftinglug
Groundingterminal(ø7)
Terminal
Cable for14~38mm2
ER:100 ΩC:0.1µF
Internal circuit
ø30
18
T T T
113350180
240
25
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/26
H.V. Distribution EquipmentVacuum circuit breakersAuto. V
Auto.V Description7.2/3.6kV, 400A, 600A, 8kA, 12.5kAFUJI Auto. Vs are vacuum circuitbreakers which incorporate a built-insolid-state OCR and CT.As they do not require to have a CTinstalled inside the switchgear cubicle oran OCR fixed to the front panel, space issaved in the cubicle and wiring andinstallation are simplified.A system protection is easily arrangedusing Auto. Vs with primary circuitbreaker and also a protectivecoordination with low voltage MCCBs.The CT is a compactly built toroidal typeand it is fitted to the upper part of theVCB. Its overcurrent withstanding valueis as large as 12.5kA, 1 sec.
Features Built-in solid-state OCR and CT are
provided System protective coordination is
easily arranged using the VCBs. Compactly assembled, so saving
space With a CT having a large overcurrent
withstand value of 12.5kA The setting range of the rated current
Rated breaking capacity (kA) 8 12.5 8 12.5 50MVA at 3.6kV 80MVA at 3.6kV 50MVA at 3.6kV 80MVA at 3.6kV100MVA at 7.2kV 160MVA at 7.2kV 100MVA at 7.2kV 160MVA at 7.2kV
Rated making current, peak value (kA) 20 31.5 20 31.5
Rated closing time (s) — 0.03
Rated short-time current, 1 second (kA) 8 12.5 8 12.5
Auxiliary contact 2NO + 2NC (5NO + 5NC available on request)
Alarm contact 1NO 100/110V AC 2.0A, 200/220V AC 1.0A, 100/110V DC 0.3A
Mass (kg) Fixed 25 28 27 30
Standard H.V. circuit breaker: JIS C 4603 (1990) AC circuit breaker: JEC2300 (1998)Overcurrent relays for H. V. power receiving: JIS C 4602 (1986)
Note: *1 Operating current setting value 8 to 80A is also available.*2 Maximum values when the VCB is used with a 6% reactor connected in a 6.6kV AC circuit.
Halve these values for a 3.3kV AC circuit.
AF92-35
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/27
12
H.V. Distribution EquipmentVacuum circuit breakers
Auto. V
Design featuresThe four dials facilitate the setting of theovercurrent protection as follows:
Rated operating currentRated current range: 24 to 320A(8 to 80A)No. of steps: 15Steps from 24A to 320A can be set bythe two dials—CT’s primary current dialand multiplying factor dial of primarycurrent. These breakers are mostsuitable for receiving and distributingfacilities with capacities from 6kV, 170 to2000kVA. Since the rating for theprimary current can be freely changedexpenses for changing the CT ratio canbe saved when expanding electricalfacilities.
Operating timeNo. of steps: 16 (T=50 to T=0.5)The operating time setting dial of thesolid-state OCR’s corresponds with thetime lever of the induction type OCR’s. Ithas 16 steps, fromT = 50 to T = 0.5.
Instantaneous trip currentTrip current: 5 to 15 times the operatingcurrent.This device is designed toinstantaneously trip when a large currentflows due to a short-circuit fault. It canbe set so it does not operate in the faceof inrush currents due to eithertransformers or capacitors and acoordination can be arranged withprimary circuit breakers. It can be set tooperate at between 5 and 15 times itsoperating current.
Operating current and time settingrange for Auto. V
➃ Operating time setting dialThis corresponds to the time lever for theinduction type relay and can be set at 16steps, from T = 50 to T = 0.5.
➄ Self diagnostic functionContinuously monitors operation of theinternal microcomputer and lights alarmLEDs on detection of abnormal conditions.
Rated operating current setting dialsThe combination of these two dialspermits the setting of 15 possiblecombinations.
➀ Rated operating current value (A)
Multiplying factor dial
0.8 1.0 1.2 1.4 1.6
Standard 30A 24 30 36 42 48
75A 60 75 90 105 120
200A 160 200 240 280 320
TEST Set at this point whencarrying out the operatingtest of OCR’s
➁ Terminals for operating testsWhen carrying out the operating test, setthe rated operating current setting dial atthe TEST position and apply the testcurrent between the C1-com and C2-comterminals.
➂ Instantaneous tripping current setting dial
This can be set to 5 to 15 times the ratedoperating current value. When set at theLOCK position the instantaneous functionstops.
Primary currentsetting dial
➅ Elapsed operating time indicators (LEDs)
• Start: This LED lights whenever maincircuit current exceeds the operatingcurrent setting for overcurrentinterruption.
• Elapsed operating time: These fourLEDs indicate the breaker’s overcurrentactivation status in 20, 40, 60, or 80% ofthe maximum overcurrent durationbefore interruption occurs.
➆ Reset leverResets the OCR and its operationindicators.
AF92-42
Rated operating current
Operatingtime
In = Rated currentItr = Instantaneous tripping current
Instantaneoustrip current
CurrentItrIn
Tim
e
➀ ➄
➁ ➂ ➃
➅
➆
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/28
H.V. Distribution EquipmentVacuum circuit breakersAuto. V
500
100
10
2
1.0
0.1100 300 1000 10000%
100 1000%
New typeAuto. V
Ordinary typeAuto. V
T = 50
T = 10
T = 10
Induction type
Tim
e (s
ec)
Current
Current
Operating characteristics
Tim
e
Non-operatingcharacterstics(Solid-state type)
Non-operatingcharacteristics(Induction type)
MCCB 60%
90%
100%
CT 50.5Atap 5A
OC
Inst tap 30A
1.2sec.
1.0
0.1
0.01105 20 30 100A
105 20 30 100A50
100
200
300
500
1000A
n>5 n>10 n>20
OC
R o
per
atio
n t
ime
(sec
.)C
T p
rim
ary
curr
ent
(A)
OCR Input current50
50
0.02
Design features Auto. V improves system
dependabilityFUJI solid-state type OCR’s are providedwith the ideal inverse time characteristicsinstead of the conventional electronic typelinear characteristics.In the case of the conventional inductiontype OCR’s their long inverse time zone incharacteristic curves do not extendsmoothly, and so they do not meet therequirements of the operatingcharacteristics of L. V. breakers thusmaking it difficult to arrange acoordination. The operating time of Auto.V’s at 300% current has been greatlyimproved to 10 sec. as against 2 to 3 sec.for conventional OCR’s. The function toextend the operating time by five times, anoption of the previous Auto. V is includedin the new Auto. V as a standard feature.
Inertia characteristics exceed 90%The inertia characteristics correspond withthe “non-operating characteristics(permissible)”.When carrying out the coordination withthe low voltage MCCB’s, it is necessary toconsider the “non-operatingcharacteristics” and “coordination” inwhich the inertia characteristics are takeninto consideration.In the case of the induction type OCR’sthe inertia characteristics normaly exceed60%, thus make it difficult to establishcoordination with low voltage MCCB’s.On the other hand in the electronic typeOCR’s their inertia characteristics exceed90%, giving them ideal operatingcharacteristics.
The overcurrent withstanding valueof the CT is 12.5kA
The CT built in the Auto. V is extremelysmall in size but its toroidal design permitsit to withstand overcurrents having valuesas large as 12.5kA for1 sec.
CT with large overcurrent constantThe internal CT’s overcurrent constant of20 or more was achieved by combining aCT with a very low activation power OCR.When using a CT in combination with aprotective relay, the CT’s overcurrentconstant must be large enough for theovercurrent. To determine compatibility,overall OCR operation must be checkedfrom the combined CT and OCRcharacteristics as shown in the figure atright.
The operating characteristics of Auto. Vand induction type OCR (FUJI CH1-53 type)
The inertia characteristics of Auto. V andinduction type OCR
CT overcurrent constant and OCRoperation characteristics
Operating characteristics ofovercurrent relays
The curves indicate the time-currentcharacteristics of OCR’s. Thesecharacteristics meet the requirements ofJIS C4602 “Overcurrent Relays forH. V. Power Receiving”Note: For practical dial setting method or the test
method of solid state OCR’s please contactFUJI.
Note:* Overcurrent constantIn CT the secondary current increases proportionallyto the increase of the primary current.When the value exceeds a certain value a saturationtakes place due to magnetic saturation. Theovercurrent constant(n) indicates the value obtainedby dividing, the current value at the point where theerror reaches 10%, by the rated current.
Current at the point wherethe error reach 10%
n = —————————————Rated current
JEC190 (1977) instrument transformer for protectiverelay is stipulated as “n>5, n>10 and n>20”. It isnecessary that they have an adequately largeovercurrent constant when incorporated withprotective relays.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/29
12
H.V. Distribution EquipmentVacuum circuit breakers
Auto. V
Types and ratingsRatings Installation Closing system Shunt trip
System Operating 100/110V AC 100/110V DCtype voltage Type Ordering code Type Ordering code
Fixed: B Manual-spring HA08B-H6F HA31BH6-400F HA08B-H7F HA31BH7-400FSwitchboard use Motor-spring 100/110V AC/DC HA08B-A6F HA31BA6-400F HA08B-A7F HA31BA7-400F
Instantaneous 200/220V AC/DC HA08B-B6F HA31BB6-400F HA08B-B7F HA31BB7-400F48V DC HA08B-C6F HA31BC6-400F HA08B-C7F HA31BC7-400F21/24V DC HA08B-D6F HA31BD6-400F HA08B-D7F HA31BD7-400F
Fixed: C Manual-spring HA08C-H6F HA31CH6-400F HA08C-H7F HA31CH7-400FCubicle use Motor-spring 100/110V AC/DC HA08C-A6F HA31CA6-400F HA08C-A7F HA31CA7-400F
Instantaneous 200/220V AC/DC HA08C-B6F HA31CB6-400F HA08C-B7F HA31CB7-400F48V DC HA08C-C6F HA31CC6-400F HA08C-C7F HA31CC7-400F21/24V DC HA08C-D6F HA31CD6-400F HA08C-D7F HA31CD7-400F
Fixed: P Manual-spring HA08P-H6F HA31PH6-400F HA08P-H7F HA31PH7-400FPortable type Motor-spring 100/110V AC/DC HA08P-A6F HA31PA6-400F HA08P-A7F HA31PA7-400F
Instantaneous 200/220V AC/DC HA08P-B6F HA31PB6-400F HA08P-B7F HA31PB7-400F48V DC HA08P-C6F HA31PC6-400F HA08P-C7F HA31PC7-400F21/24V DC HA08P-D6F HA31PD6-400F HA08P-D7F HA31PD7-400F
Fixed: B Manual-spring HA12B-H6F HA32BH6-600F HA12B-H7F HA32BH7-600FSwitchboard use Motor-spring 100/110V AC/DC HA12B-A6F HA32BA6-600F HA12B-A7F HA32BA7-600F
Instantaneous 200/220V AC/DC HA12B-B6F HA32BB6-600F HA12B-B7F HA32BB7-600F48V DC HA12B-C6F HA32BC6-600F HA12B-C7F HA32BC7-600F21/24V DC HA12B-D6F HA32BD6-600F HA12B-D7F HA32BD7-600F
Fixed: C Manual-spring HA12C-H6F HA32CH6-600F HA12C-H7F HA32CH7-600FCubicle use Motor-spring 100/110V AC/DC HA12C-A6F HA32CA6-600F HA12C-A7F HA32CA7-600F
Instantaneous 200/220V AC/DC HA12C-B6F HA32CB6-600F HA12C-B7F HA32CB7-600F48V DC HA12C-C6F HA32CC6-600F HA12C-C7F HA32CC7-600F21/24V DC HA12C-D6F HA32CD6-600F HA12C-D7F HA32CD7-600F
Fixed: P Manual-spring HA12P-H6F HA32PH6-600F HA12P-H7F HA32PH7-600FPortable type Motor-spring 100/110V AC/DC HA12P-A6F HA32PA6-600F HA12P-A7F HA32PA7-600F
Instantaneous 200/220V AC/DC HA12P-B6F HA32PB6-600F HA12P-B7F HA32PB7-600F48V DC HA12P-C6F HA32PC6-600F HA12P-C7F HA32PC7-600F21/24V DC HA12P-D6F HA32PD6-600F HA12P-D7F HA32PD7-600F
Voltage3.6/7.2kV
Breakingcurrent8.0kA
Rated current400A
Voltage3.6/7.2kV
Breakingcurrent12.5kA
Rated current600A
12/30Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
H.V. Distribution EquipmentVacuum circuit breakersNew-Auto. V
New-Auto.V DescriptionThe New-Auto.V is a circuit breaker that consists of astandard MULTI.VCB provided with a CT (currenttransformer), and incorporates a multiple function protectorsand controllers to prevent equipment from overcurrent andother factors, thus saving energy and reducing installationman-hour.• Multiple function protectors and controllers offers versatile
features such as ground-fault directional, ground-faultovervoltage, undervoltage, and overvoltage protectivefunctions in addition to overcurrent protection. It alsoincludes measurement functions for a variety of items, suchas current, voltage, power, power-factor, frequency, andzero-phase voltage values.
Highly reliable overcurrent protection• Withstand overcurrent of CT: 12.5kA• Overcurrent constant of CT: n>20
SpecificationsType HA08A –A8 HA12A –A8Closing system Motor-springInstallation Draw-out: X, Y, URated voltage (kV) 3.6/7.2Rated current (A) 400 600Rated frequency (Hz) 50/60Rated breaking capacity (kA) 8 12.5
50MVA at 3.6kV 80MVA at 3.6kV100MVA at 7.2kV 160MVA at 7.2kV
Rated making current, peak value (kA) 20 31.5Rated closing time (s) 0.03Rated short-time current, 1 second (kA) 8 12.5Insulation level Dielectric: 22kV, 1 minute Impulse (1.2 × 50µs): 60kVRated breaking time 3-cycleOpening time (s) 0.03Operating duty 0 — 1 min. — CO — 3 min. — CO or CO — 15 sec. — COLife expectancy Mechanical (operations) 10,000
Cradle for X type 11 11Standard H.V. circuit breaker: JIS C 4603 (1990), AC circuit breaker: JEC 2300 (1998)
Note: * 1Maximum values when the VCB is used with a 6% reactor connected in a 6.6kV AC circuit.Halve these values for a 3.3kV AC circuit.
KK03-052
Draw-out type MW or PW(Y type)
Multiple function protectorsand controllers
12/31Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice
12
H.V. Distribution EquipmentVacuum circuit breakers
New-Auto. V
Specifications (Multiple function protectors and controllers)Item SpecificationGeneral Control power supply [V] 100/110DC (80 to 143DC) or 100AC (85 to 132AC)specification Power consumption (main unit) [W] 15W max.
Rated frequency [Hz] 50/60 (settings selectable)Rated current CT primary side [A] 30/100/300 AC (selectable)
CT secondary side [A] 0.1 ACRated zero-phase current ZCT [mA] 200/0.2 AC *1
Insulation resistance 10M between all electric circuits and groundVibration resistance 1.96m/s2, 16.7Hz, 0.4mm double amplitude in three directions for 10
minutes eachShock resistance 300m/s2 three times each in three directionsDielectric strength 2kV AC between all charged parts and ground excluding MN signal line,
RS-485 signal line, and transducer output terminal.*2
Noise immunity Damped vibration waveform at 1 to 1.5MHz with peak voltage of 2.5 to3kV continuously applied for 2 secondsImpulse noise in rectangular waveform (1ns/1U) at peak voltage of1.5kV applied for 10 minutesRadiowave freguency band: 10V/m on 140MHz, 430MHz, and 900MHzbandsCellular phone (800MHz/1.5GHz at 0.8W) or PHS (1.9GHz 10mW) inclose contact
Static electric noise In contact with metal part: ±6kVPanel surface (not in contact with no metal parts): ±8kV
Lightning impulse Between all electric circuits and ground (excluding MN signal line, RS-485 signal line, and transducer output terminal)4.5kV, 1.2x50U, three times each on positive and negative sides
Ambient humidity 10˚C to 60˚C (with no condensation or icing)Storage temperature -20˚C to +70˚C (with no condensation or icing)Humidity 20% to 90% (on daily average with no condensation)Operating atmosphere Free from corrosive gas and excessive dustGrounding Ground at a resistance of 100 or lessMass 1.4kgPermissible momentary power interruption time 20ms (continuous operation) with display turned off
The protective relay is, however, operable for 200ms after the power isinterrupted.*3
(Display turns off, communication stops, and fault output turns on)Protective Overcurrent Rated operation current (51) 15 to 390Afunction protection setting range
Instantaneous Rated trip Setting range (1 to 20) × rated current (in 0.2 increments), LOCKovercurrent current Operating value ±15% max. of each setting currentprotection 50 Operating Operating value 0.05s max. at 200% of setting current (INST) timeShort-time Rated trip Setting range (1 to 20) × rated current (in 0.2 increments), LOCKovercurrent current Operating value ±10% max. of each setting currentprotection Operating Setting range 0 to 5s (at 0.05 increments)51DT time Operating value ±17% max. of 300% of setting value,
±12% max. of 700% of setting value (Lower limit: ±50ms)Time-lag Rated trip Setting range 50 to 130% of rated current (at 10% increments), LOCKovercurrent current Operating value ±10% max. of each setting currentprotection 51 Operating Time-magnification (0.5 to 20) × (in 0.1 increments), (20 to 100) × (in 1 increments)
time (lever) setting rangeOperating value ±17% max. of 300% of setting value,
±12% max. of 700% of setting value (Lower limit: ±100ms)Ground fault Zero-phase Setting range 0.1 to 1.0A (at 0.05A increments), LOCKprotection current Operating value ±10% max. of setting value67DG and 51G Zero-phase Setting range 2.5% to 15% of rated voltage (at 2.5% increments)
voltage Operating value ±25% max. of setting valuePhase Max. sensitivity 30, 45, 60˚
Operating angle range Max. sensitivity phase: ±80˚Operating angle tolerance ±15%
Operating time Setting range 0.1 to 3s (at 0.05s increments), 3 to 120s (at 1s increments)Operating value ±5% max. of setting value (Lower limit: ±50ms)
12/32Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
H.V. Distribution EquipmentVacuum circuit breakersNew-Auto. V
Protective Overvoltage Voltage Setting range 110 to 150V (at 5V increments), LOCKfunction protection Operating value ±5% max. of setting value
59(OV) Operating time Setting range 0.1, 0.2 to 2s (at 0.2s increments), 2 to 10s (at 1s increments)Operating value ±5% max. of setting value (Lower limit: ±50ms)
Undervoltage Voltage Setting range 20 to 100V (at 5V increments), LOCKprotection Operating value Setting value of 90V min.: ±5%27 (UV) Setting value of 85V max.: ±[2.3 +(110V/voltage setting value)x 0.16x 2]%
Operating time Setting range 0.1, 0.2 to 2s (at 0.2s increments), 2 to 10s (at 1s increments)Operating value ±5% max. of setting value (Lower limit: ±50ms)
Prealarm Overcurrent Voltage Setting range 10% to 100% of rated current (at 5% increments), LOCKOCA Operating value ±10% max. of setting value
Operating time Setting range 10 to 200s (at 10s increments)Operating value ±5% max. of setting value
Leakage Voltage Setting range 50%, 60%, 70%, and 80% of 67DG or 51G operating current setting value, Lockcurrent Operating value ±10% max. of setting value (Lower limit: ±20mA)OCGA Operating time Setting range 10 to 200s (at 10s intervals)
Operating value ±5% max. of setting valueExternal Input circuit Fixed, 5 points CT primary rated current 100V DC (143V max.)/100V ACI/O (30A/100A/300A): 3 points, (132V max.) common usespecifications CT test position: 1 point, DC ON voltage: 40V min,
trip output lock: 1 point 70V max.General-purpose, 3 points External making, external breaking and AC ON voltage: 40V min,
external reset of each one point is 70V max.default.
Others, 2 points Trip coil (TC) disconnection monitoring,52a contact: each one contact
Output circuit Input, 1 point Making earrent: 15 A (110V DC )Off and trip, 1 point Permissible continuous current: 4AAlarm output, 8 points Current made or broken: 0.2 A (110V DC inductive load, L/R=15ms)Device failure, 1 point Permissible continuous current: 1A
Metering Current, demand current and demand max. current 0, 0.4% to CT rating and to CT rating x 1.3and display Fault current of 2000% max. can be displayedspecifications Zero-phase current and zero-phase 200/0.2mA ZCT primary current: 0.05 to 1.0A *1
current history max. value Fault current of 4A max. can be displayedZero-phase voltage and zero-phase voltage history 1.5% to 50% *4
max. valueVoltage 5 to 150V on VT secondary sideFrequency 45 to 55Hz (50Hz) and 55 to 65Hz (60Hz)Power-factor Lead 0 to 1.0 to Lag 0Active power, reactive power, demand power and 0, 0.4% to ( 3 x rated voltage x 1.3In x power-factor 1.0) %max. demand power (In: CT primary rated current)Active energy and reactive energy JIS C 1216 (meter with transformer), equivalent to table 4 normal classHistory data Number of protective operation times: 0 to 9999
Operating hours: 0 to 9999 x 100 hrNumber of switching times: 0 to 9999 x 10 times
Notes *1 When using ZCT, FUJI's dedicated product ZCT- is recommended. For details, please contact FUJI.*2 Do not apply 2kV between lines.*3 When you use AC power as control power supply, and 27 (UV) function, and you require that the operating time setting at power failure
be operated more than 2s, the use of a UPS or AC power supply UM2P-A1 is recommended (sold separately).*4 When you use zero-phase potential input device, use FUJI's dedicated ZPD-1.
12/33Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice
12
H.V. Distribution EquipmentVacuum circuit breakers
Types and ratingsRatings Installation Closing system Trip system Type
Closing system Operatingvoltage
Voltage Draw-out with Motor-spring 100/110V AC/DC Shunt trip HA08AX-A83.6/7.2kV cradle: X Instantaneous (Operated by signalBreaking Draw-out with communication with HA08AY-A8current cradle and shutter: Y multiple function8.0kA Draw-out with protections andRated current cradle: U controllers) AH08AU-A8400A 100/110V DC
Voltage Draw-out with Motor-spring 100/110V AC/DC Shunt trip HA12AX-A83.6/7.2kV cradle: X Instantaneous (Operated by signalBreaking Draw-out with communication with HA12AY-A8current cradle and shutter: Y multiple function12.5kA Draw-out with protections andRated current cradle: U controllers) AH12AU-A8600A 100/110V DC
KK03-061
KK03-051
Multiple function protectors and controllers offersversatile features.
A host of protective functions• Provided with ground-fault directional, ground-fault
overvoltage, undervoltage, and overvoltage protectivefunctions in addition to overcurrent protection.
New- Shunt trip 8 100/110V DC, 3.4AAuto.V *2 Operated by signal communication
with multiple function protectors andcontroller
Note: *1 To use AC to trip the Auto. V, use a capacitor trip device in combination with the trip system.*2 In the case of shunt tripping with AC power supply, use the capacitor shunt trip power supply in combination. For details, refer to the
• Use a VT with a capacity of at least 50VA.• Use a 3A fuse to protect the control circuit• Spring charging time is 5 seconds.
New-Auto.V
HA 08 A X - A 8 L S1 KPanel lead wireBlank: With panel lead wireK: Plug onlyPosition switchBlank: With no position switchS1: With run position and test position,
both with SPDT contactsVacuum interrupter usedBlank: Standard level vacuum interrupterL: Low-level-surge vacuum interrupterTripping system8: Multiple function protectors and controllers provided
Supplied accessories Insulation tube for mainterminal
Installationtypes: B and C
Wiring diagram
Optional accessories SupporterSupporter kit for stabilizing the back offixed type B, C Auto. V on the floor.
AF92-493
SH-27
Vacuum condition testerVC-1A
For further information see page 12/25.
Position indicating switch (HZ2AD)Switch for indicating the service positionsand test positions of draw-out (X, Y, U).Used for interlocking to other devicesattached to the cradle for draw-out type.
SG 1075
Manual handle for motor-spring typeAll types
KK03-073
KK03-075
Draw-out extension rail (HZ2AE)Used with draw-out type (X, Y, U).Use of an extension rail makes dailychecking easier because the VCB can bepulled out of the panel.Double stack types do not require lifters orchain blocks.
KK03-079
KK03-076 K03K-077
Draw-out handleInstallation types: X, Y, and U
KK03-074
KK03-080
LifterL-2HNB
• Connector with external lead wireInstallation types: X, Y and U
• Lead wire for multiplefunctionprotectors and controllersNew-Auto.V type
• Jumper wire for digital multi-functionrelay testNew-Auto.V type
Type: C
Type: B
Namer1: Charging resistorr2: Discharge resistorr3: Series resistorSi: Silicon rectifier diodePL: Pilot lamp
12/37Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice
12
H.V. Distribution EquipmentVacuum circuit breakers
Auto. V/New-Auto.V
Specifications of AC meter (for Auto.V)
Note: *1. Specify that the meter is to be used for the Auto.V when ordering themeter alone.
*2. Set the full scale (A) to a value twice as large as the primary currentsetting (A) in the built-in OCR. For example, if the primary current ofthe OCR is 75A, read the full scale of the AC meter as 150A.
DS100V AC
CB52
52aT.C
Trip output Control powersupply
UM2P-A1
Multiple functions protectors andcontrollers
B- B- B- B-B-
Outline of devices used in combination
OWP101
AF00-416
Optional accessories AC power supply unit (for New-Auto.V)Type UM2P-A1Rated input voltage 100/110V AC (Allowable variation: 85 to 132V)Rated output Control power of multiple 100/110V DC 0.15A
functions protectors andcontrollersPower supply of capacitor Rated charge voltage: 140V DC (C=1500 µ F)trip device
Power failure Control power of multiple 1scompensation time functions protectors and
controllersPower supply of capacitor When power failure occurs at 60V AC, the charge voltage is 75DCtrip device or higher after the elapse of 30s.
Operating temperature range -10 to +60˚C (no icing or no condensation)Insulation resistance Between all electrical circuits and ground: 10M
(500V DC megger)Withstand voltage Between all electrical circuits and ground: 2000V AC for 1minLightning impulse Between all electrical circuits and ground: 4500V 1.2/50µsMass 1.5kgNotes: The power failure compensation time of this AC power supply unit is 1s. If you use the UV (undervoltage) function with the operation time at 1.2s or longer,
connect an external capacitor (not supplied) together between this unit's terminals 5 and 6, by referring to the table below.
Operating time of protection External capacitor capacitance Example of capacitor 27 (UV)1.2 to 2s (at 0.2s increments) 1500 µ F (Withstand voltage: 200V DC min.) Nichicon-made LNT2D152MSM3 to 5s (at 1s increments) 6800 µ F (Withstand voltage: 200V DC min.) Nichicon-made LNT2D682MSM6 to 10s (at 1s increments) 1600 × t ( µ F)
t = Operating time (setting value) of protection 27 (UV)
1. : Interior of VCB.2. : External draw-out terminals of VCB.3. : Interior of multiple functions protectors and controllers (Mounted separately)4. Control circuit lead wire (provided) Wiring on panel side5. The wiring settings of the multiple functions protectors and controllers are initial ones with B5 turned on and B6 turned off.6. The internal wiring of the multiple functions protectors and controllers is shown with function codes.7. The external wiring of the muliple functions protectors and controllers is the wiring only used for overcurrent protective function.
Multiple functions protectorsand controllers
Local
Test terminals
OFF OFFTC disconnectionmonitoring Remote
Local
Remote
Auxiliary switch circuit
Auxiliary circuit plug (front view)
Trip lock
Operation
Trip lock
Operation
Trip lock
Operation
ONON
52C: Making coil52T: Breaking coil52X: Magnetic contactor for closing circuit52Z: Pumping prevention relayM: Control motorRF: RectifierCT1 and CT2: Current transformers
LS1: Limit switch (Draw-out interlock use)LS2: Limit switch (Motor stopping use)LS3: Limit switch (Motor startup use)LS4: Limit switchLS5: Limit switch (LS4 and LS5 are both turned ononly when the circuit is ready to be turned on.)
SW1: Rotary switch (for CT tap or test selection)SW2: Toggle switch (for operation and trip lock selection)51 and OCR: Overcurrent relayRy: Control relayBx: Fault display buzzerS: Buzzer stop switch
12/45Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice
12
H.V. Distribution EquipmentVacuum circuit breakers
Closing system Manual-spring Motor-spring Motor-springInstallation Fixed: B, C, P, Fixed: B, C, P Draw-out: X, Y, URated voltage (kV) 3.6/7.2 3.6/7.2 3.6/7.2Rated current (A) 400 600 400 600 400 600Rated frequency (Hz) 50/60 50/60 50/60Rated breaking capacity (kA) 8 12.5 8 12.5 8 12.5
50MVA at 3.6kV 80MVA at 3.6kV 50MVA at 3.6kV 80MVA at 3.6kV 50MVA at 3.6kV 80MVA at 3.6kV100MVA at 7.2kV 160MVA at 7.2kV 100MVA at 7.2kV 160MVA at 7.2kV 100MVA at 7.2kV 160MVA at 7.2kV
Rated making current, peak value (kA) 20 31.5 20 31.5 20 31.5Rated closing time — 0.03 0.03Rated short-time current, 1 second (kA) 8 12.5 8 12.5 8 12.5Insulation level Dielectric: 22kV, 1 minute Impulse (1.2 × 50µs): 60kVRated breaking time 3-cycle 3-cycle 3-cycleOpening time (s) 0.03 0.03 0.03Operating duty 0 — 1 min. — CO — 3 min. — CO or CO — 15 sec. — COLife expectancy Mechanical (operations) 10,000
Draw-out (X type) — — — — 34 35Cradle for X type — — — — 11 11
Standard H.V. circuit breaker: JIS C 4603 (1990), AC circuit breaker: JEC 2300 (1998)
Note: * Maximum values when the VCB is used with a 6% reactor connected in a 6.6kV AC circuit.Halve these values for a 3.3kV AC circuit. Trip system
• The width of the draw-out type iscompatible with a panel width of500mm.
• The depth of the draw-out type iscompatible with a panel depth of700mm.
Draw-out MW and PW type
Draw-out type for small depth switchboard.
AF92-4 AF92-3 KK03-054
B-type C-type X-type Y-type
Description7.2/3.6kV, 400A, 600A, 8kA, 12.5kAThe new Multi-VCB series of general-purpose vacuum circuit breakers arebased on the conventional HA seriesand feature improved safety and ease ofuse. With 2300mm high switchgearcubicles they can be stacked up to fourhigh with consequent saving ofinstallation space. Multi VCBs areavailable in different mounting versionsuch as the fixed type (B, C, P) anddraw-out type (X, Y, U).
Features Highly reliable and safety closing
system• Manual-spring stored energy closing
system for improved operation safety,reliability, and constant closing speed.
• Half the torque formerly required forthe manual operation and a new-turn-type handle improve operability.
2NO + 2NC 100/200V AC, 10A 5NO + 5NC contacts are available on requeststandard provided 100/200V DC, 5/3A
For an AC-trip control circuit, use also a capacitortrip device VCB-T1A (for 100/110 AC) or VCB-T2A (for 200/220V AC), sold separately.
Operating current: At least 3AThe impedance of coil is less than 8Ω.
Note: *1 To use AC to trip the Multi VCB, use a capacitor trip device in combination with the trip system.*2 Use the static-type OCR (overcurrent relay) in combination with Fuji Electric's QH-OC1 or QH-OC2, and fault display in combination with the JH11 type
Supplied accessories Insulation tube for mainterminal
Installationtypes: B and C
Wiring diagram
Optional accessories SupporterSupporter kit for stabilizing the back offixed type B, C VCB on the floor.
AF92-493
SH-27
Vacuum condition testerVC-1A
For further information see page 12/25.
Position indicating switch (HZ2AD)Switch for indicating the service positionsand test positions of draw-out (X, Y, U).Used for interlocking to other devicesattached to the cradle for draw-out type.
SG 1075
Manual handle for motor-spring type
KK03-073
KK03-075
Draw-out extension rail (HZ2AE)Used with draw-out type (X, Y, U).Use of an extension rail makes dailychecking easier because the VCB can bepulled out of the panel.Double stack types do not require lifters orchain blocks.
KK03-079
Draw-out handleInstallation types: X, Y, and U
KK03-074
KK03-080
LifterL-2HNB
• Connector with external lead wireInstallation types: X, Y and U
Type: C
Type: B
Namer1: Charging resistorr2: Discharge resistorr3: Series resistorSi: Silicon rectifier diodePL: Pilot lamp
AC operatedAuxiliary switch Control circuit terminal
(B, C, P types)
12/56Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
H.V. Distribution EquipmentVacuum circuit breakersMulti VCB
4
2
(P)(P),
OCR
(P),
OCR
r 2
95
7
RDSW
Z
Si
r1
C1
6
52
8363228 3531272324 40 39
VCB-T1Aor
VCB-T1PA
3 6
2 4 8
1
262422
252321 27
28
31
32
33
34
35
36
37
38
29
30
39
40
8
(N)(N),
4
(N),
2
LS1
LS4
LS252X
52X
52X
LS3
RF
LS5
52Z5252Z
5252
RF
3 1 343026 33296 252122 38 37
52M
r
52X
52T52C
52Z
52T
ON OFF OFF
5NO contacts 5NC contactsAuxiliary switch circuit
AC control
X, Y, or U type(Front view of VCB)
Draw-out typeMotor-spring closing/shunt trip
52C: Closing coil52T: Breaking coil52X: Magnetic contactor for closing circuit52Z: Pumping prevention relayM: Control motorRF: Rectifier
LS1: Limit switch (Draw-out interlock use)LS2: Limit switch (Motor stopping use)LS3: Limit switch (Motor startup use)LS4: Limit switchLS5: Limit switch (LS4 and LS5 are both turned on only when the the circuit is ready to be turned on.)
VCB-T1A or VCB-T1PA: Capacitor shunt trip power supply (Sold separately)OCR: Overcurrent relay
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/57
12
H.V. Distribution EquipmentVacuum magnetic contactors
HN series
Description3.3/6.6kV 200, 400 Amps
HN type vacuum magneticcontactors incorporate a SUPERMAGNET provided with a built-in IC.The IC minimizes the powerconsumption used in the closing circuit.HN types vacuum magnetic contactorsoperate on both AC and DC powersupplies. A common insulating frame forunits with a rated voltage of 3kV and6kV simplifies switchgear design.
FeaturesThe SUPER MAGNET• Holding currents are minimized
with an IC-controlled closing circuit.This is a cost-effective feature.
• Both AC and DC power supplyoperation possible.
• The SUPER MAGNET holds withoutchattering even when the linecontrol voltage drops.
• The SUPER MAGNET’s wide rangeof operating voltages allows it to beused in countries throughout theworld.
Operating coil voltage
Specifications
Type HN46A *1-2 HN46A *1-4
Rated voltage (kV) 3.3/6.6
Rated frequency (Hz) 50/60
Rated current (A) 200 400
Rated breaking current (kA) 4
Rated short-time current (kA) 4 (2 sec.)
Insulation levelDielectric strength/1 min (kV) 22 (16 between poles)Impulse 1.2X50µs (kV) 60 (45 between poles)
Making and breaking capacity (kA) 1.6 3.2
Operating frequency (sw/hour)Normal energized type 600Mechanically latched type 600
Electrical durability (Operations) 250,000
Mechanical durability (Operations)Normal energized type 2,500,000Mechanically latched type 250,000
Average operating timeOpening time (ms) 140Closing time
Normal energized type (ms) 100Mechanically latched type (ms) 20
MassFixed type (Normal energized) (kg) 19 19Draw-out type (Normal energized) (kg) 34*2 34*2
HN46AYHN46AP
AF99-131
AF99-160
Rated voltage OperatingAC (50/60Hz) DC voltage range
– 21–24V 85–110% – 48V of rated100–110V 100–110V voltage200–220V 200–220V
Shared insulating frame for 3kV and6kV contactorsHN type vacuum magnetic contactorshave a special insulating frame. Thedimensions of the frame are the samefor both 3kV and 6kV models, whichfacilitates switchgear design.
Advanced vacuum interrupterA high performance interrupterminimizes surges due to closing andbreaking, which makes special surgeprecautions unnecessary.
*1: Installation system *2:Without VT and cradleP: Fixed typeX: Draw-out typeH: Draw-out type/Bushing type connectorY: Draw-out type/Bushing type connector+shutter(X, Y, H: With fuse holder)
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/58
H.V. Distribution EquipmentVacuum magnetic contactorsHN series
Operating coil voltage and current Normal energized type
Type Rated operating Current (A)voltage (V) * Closing Holding
HN46A -2S1, 4S1 100–110 AC 3 0.05100–110 DC 3 0.05
HN46A -2S2, 4S2 200–220 AC 1.5 0.03200–220 DC 1.5 0.03
HN46A -2S4, 4S4 48 DC 8 0.1
Mechanically-latched type
Type Rated operating Current (A)voltage (V) * Closing Trip
HN46A -2L1, 4L1 100–110 AC 3 3.5100–110 DC 3 3
HN46A -2L2, 4L2 200–220 AC 1.5 2.2200–220 DC 1.5 2
HN46A -2L3, 4L3 21–24 DC 16 8.5
HN46A -2L4, 4L4 48 DC 8 4.5
Types and ordering codes/Fixed types
Installation Operating Rated Rated Appropriate Operating coil voltage (V) Type andsystem system voltage (kV) current (A) fuse type AC DC ordering code
Fixed type Normal 3.3/6.6 200 – 100–110 100–110 HN46AP-2S1(P) energized 200–220 200–220 HN46AP-2S2
* Provided fuse holder: K. See page 12/60 (Type number nomenclature)
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/59
12
H.V. Distribution EquipmentVacuum magnetic contactors
HN series
Installation Operating Rated Rated Appropriate Operating coil voltage (V) Type andsystem system voltage (kV) current (A) fuse type AC DC ordering codeDraw-out Normal 3.3/6.6 200 HF338E/3/20–100 100–110 100–110 HN46AX-2S1A(X) energized HF338E/6/20, 30 200–220 200–220 HN46AX-2S2A
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/60
H.V. Distribution EquipmentVacuum magnetic contactorsHN series
HN 46A X – 2 S 2 A /
Operating systemS: Normal energized typeL : Mechanically latched type
Rated current2: 200A4: 400A
Installation systemP: Fixed typeX: Draw-out typeH: Draw-out type/Bushing type connectorY: Draw-out type/Bushing type connector
with shutter
Type number nomenclature
Basic typeBreaking capcity 4kARated voltage 3.3/6.6kV
Supplied accessories for draw-out types Mechanical interlock1. When the contactor is closed, it is impossible to shift it
from the service position to the test position.2. Under the condition where the contactor is closed, it is
impossible to change it from the test position to the serviceposition.
3. At both the test and the service positions, the interlock pinwill engage and so lock the contactor in position. Thus thepositions are always fixed correctly. Even if a closingoperation is carried out at an intermediate position, thecontactor cannot be closed.
Electrical interlockWhen the interlock pin is locked at both the service and testpositions the limit switch will be closed, and the contactor canbe operated.
ShutterCradle with bushing type connectors can also be provided witha shutter.
On-off counter (6-digit)An on-off counter is standard with all VCB series.This easily legible counter enables quick estimation ofremaining service life.
Ratings of interlock contactContact arrangement SPDT
Operating current Res. Load Ind. Load250V AC 16A 10A125V AC 16A 10A
125V DC 0.6A 0.3A
Fuse holder type (For X, Y, H types)A: For HF338E/3/20–100 or HF338E/6/20, 30 fuseB: For HF338E/3/150, 200 or HF338E/6/40–200 fuseC: For JB-3/50–200 or JB-6/20, 50 fuseD: For JB-6/100–200 fuseJ: For JC-6/5–75 fuseK: For JC-6/100 fuse
Name plateBlank : Japanese (JEM)ZJ : English (JEM)ZC : English (IEC)ZA : English (AS)ZB : English (BS)
Operating coil voltage (Closing/Trip)1: 100–110V AC, 100–110V DC2: 200–220V AC, 200–220V DC3: 21–24V DC (Mechanically latched type only)4: 48V DC5: Closing 100-110V AC, 100–110V DC
Trip 200–220V AC, 200–220V DC6: Closing 200–220V AC, 200–220V DC
Trip 100-110V AC, 100–110V DC7: Other voltage
Specify operating voltage when ordering
Bushing CT (BCT) (Optional accessories)*For Y, H typesA to K (Specify BCT code when ordering, see page 12/61 ➁)
VT (Optional accessories)*For X, Y, H typesP1 to PA (Specify VT code when ordering, see page 12/61 ➀)
Ratings of fuse blown indicatorContact arrangement 1NO + 1NC
Operating current Res. Load Ind. Load250V AC 16A 10A
250V DC 0.3A 0.06A125V DC 0.6A 0.3A30V DC 6A 4A
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/61
12
H.V. Distribution EquipmentVacuum magnetic contactors
HN series
Codes of VTs and BCTs for draw-out types
➀ VT (For X, Y, H) ➁ BCT (For Y, H)Code Voltage No. of VTs Code Current No. of BCTs Code Current No. of BCTs
Optional accessories Position switches (Ordering code HZ1ND)SPDT position switches can be fitted to indicate the testposition and the service position. (For X, Y, H)
Capacitor trip devices
Type Ordering Tripping time after Input voltage Tripping coilcode power failure: voltage
VS-T1A HZ1NI 30 sec. 100–110V AC 100–110V DCVS-T2A HZ1NJ 200–220V AC 200–220V DCRatings of position switch
Contact arrangement Service pos. SPDT, Test pos. SPDTService pos. 2PDT, Test pos. 2PDT
Operating current Res. Load Ind. Load250V AC/DC 3A NC: 2A, NO: 1.5A125V AC/DC 10A NC: 7.5A, NO: 6A30V DC 15A 10A14V DC 15A NC: 15A, NO: 10A
Ratings of VT
For VT For control power supply *
3300V/110V, 220V 1.0 class 100VA 3300V/110V, 220V 400VA6600V/110V, 220V 1.0 class 100VA 6600V/110V, 220V 400VA
* When used as control power supply, it becomes short-time rating.
Ratings of BCTMax. Frequency Primary Secondary Burden Overcurrentvoltage (kV) (Hz) current(A) current(A) (VA) capacity
6.9 50/60 20, 30, 40, 50 5 25 40 times,
75, 100, 150 1 sec
200, 300, 400
VT and bushing CT (BCT)Draw-out types have room for fitting VTs in the space box.It is possible to fit up to 2 VTs in the space. 3 BCTs can be fitted tothe bushing type connector. The ratings are shown in the Table.
C-R type surge absorber
Type Ordering Max. operating Frequency Ratedcode voltage voltage
AF3320R3 HZ1AK 3.3kVTXG0542 3
AF6620R3 HZ1AL 6.6kVTXG0543 3
115%rated voltage
50/60Hz
50/60Hz
Dimensions,mm/Surge absorber
• Mounting position of CT2 CTs-Fit to U and W poles3 CTs- Fit to U, V and W poles
Example: • Two 6.6kV/110V VTs and no BCTHN46A–/P4
• No VT and two 50/5A BCTsHN46A–/D2
• Two 6.6kV/110V VTs and two 50/5A BCTsHN46A–/P4D2
R
C
4-12×16 Ellipse
400455490
70 100
max
.120
390
140 140
Liftinglug
Groundingterminal(ø7)
Terminal
Cable for14-38mm
ER:100 ΩC:0.1uF
Internal circuit
ø30
18
T T T
2
Cradle
BCT
R S T
U V W
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/62
H.V. Distribution EquipmentVacuum magnetic contactorsHN series
System Type Ratings Applicable load (max)voltage Voltage Breaking Minimum Current 3φ Motor 3φ Transformer 3φ Capacitor(kV) Refer to the Table (kV) capacity breaking (A) Squirrel-cage Wound-rotor
Optional accessories Power fuses for draw-out typesThe table indicates the appropriate current limiting fuses foruse with HN vacuum magnetic contactors.
Notes: JB fuse: The rated current value meets the requirements of JEC-2330 (1986) M (motor).HF and JC fuses: The rated current value meets the requirements of JEC-2330 (1986)G (general).Contact FUJI when the JC fuse will be used for a motor load application.
VS: Vacuum contactor52: Auxiliary contact for vacuum contactor52T: Tripping coil52C: Closing coil52Z: Anti-pumping relayIC: IC-control deviceLS1: Limit switch for interlockMCX: Auxiliary relay for closingPF: Power fuse (Optional accessories)SW: Power fuse blown indication contactVT: VTVTF: Fuse for VTBCT: Bushing type CT
r1r2
r3
PL
52T
OFF
3
52
46C(P2)
(P1)
Capacitortrip device
C
6
8 5
SiZ
+
SW
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/66
Protective RelaysDUTGeneral information
Basic typeDUT: Single function type digital relay
ConstructionU: Unit standard structure type, DC auxiliary energizing sourceA: Unit standard structure type, AC auxiliary energizing sourceR: DQ series replacement type, DC auxiliary energizing sourceB: DQ series replacement type, AC auxiliary energizing sourceT: Testing tool
(Noise immunity conforming to standard of B-402)M: Independent time-lag
(Noise immunity conforming to standard of B-402)
No. of inputA: One inputB: Two inputsC: Three inputs
Output duration and operation display hold functionS: Slow reset (1s), Display hold function: ProvidedK: Instantaneous reset (0.2s), Display hold function: ProvidedA: Instantaneous reset (0.2s), Display hold function: Not provided
Protective relays DUT
Features• The DUT series digital type protective relays have been
developed to replace the conventional induction type,rectifier type, and static type DQ series relays.
• The DUT series relay has a single protection functionincorporating with a 16-bit CPU and output circuit.
• Six kinds of protective relays such as OCR, OCGR, OVR,OVGR, UVR, and DGR are available.
• The operation of overcurrent relay can be selected from 6kinds of inverse time-lag characteristics and independenttime-lag characteristics.
• They continuously monitor the CPU and the power supply,and are activated when a defective condition is detected.
• The mass has been reduced by using molded plastic resinfor the relay-case and the front cover of the relay.
• Forced operation function can be executed by switching,which facilitates sequence checking. Forced reset functionfacilitates periodical inspection.
• They have the same mounting size as the previous DQseries relays, making replacement easy. Note, however,that the teriminal numbers and terminal locations of thedigital type relay are different from those of the previoustype relays. The digital type relay needs an auxiliaryenergizing source. DQ series replacement relays having
Rating and setting range• Overcurrent relay DUTACC: rated current 5A, inverse time-lag 1-6A, instantaneous 5-40ADD: rated current 5A, inverse time-lag 2-12A, instantaneous 10-80ACE: rated current 5A, independent time-lag 1-6ADE: rated current 5A, independent time-lag 2-12AHH: rated current 1A, inverse time-lag 0.2-1.2A, instantaneous 1-8AJJ: rated current 1A, inverse time-lag 0.4-2.4A, instantaneous 2-16AHK: rated current 1A, independent time-lag 0.2-1.2AJK: rated current 1A, independent time-lag 0.4-2.4A• Ground overcurrent relay DUTEAA: rated current 5A, inverse time-lag 0.1-0.8A, instantaneous 0.5-4ABB: rated current 5A, inverse time-lag 0.5-4A, instantaneous 2.5-20AAE: rated current 5A, independent time-lag 0.1-0.8ABE: rated current 5A, independent time-lag 0.5-4AFF: rated current 1A, inverse time-lag 0.02-1.16A, instantaneous 0.1-0.8AGG: rated current 1A, inverse time-lag 0.1-0.8A, instantaneous 0.5-4AFK: rated current 1A, independent time-lag 0.02-0.16AGK: rated current 1A, independent time-lag 0.1-0.8A• Overvoltage relay DUTVGD: rated voltage 110V, operation setting 60-150V• Ground overvoltage relay DUTGGA: rated voltage 110V, operation setting 5-50VDA: rated voltage 190V, operation setting 5-50V• Undervoltage relay DUTUJG: rated voltage 63.5V, operation setting 10-60VGH: rated voltage 110V, operation setting 15-100V• Ground directional relay DUTDAA: zero-sequence voltage (3Vo) 110V, operate current 1-10mAAB: zero-sequence voltage (3Vo) 190V, operate current 1-10mABA: zero-sequence voltage (3Vo) 110V, operate current 10-100mABB: zero-sequence voltage (3Vo) 190V, operate current 10-100mA
Rated frequency5: 50Hz6: 60Hz
Development order
the same terminal arrangeminet with DQ series relays areavailable.
• The internal element of the relays can be drawn-out fromthe relay case. At this time the CT circuit is automalicallyshort-circuited and inspection is easy, so inspection issimple.
• The setting modes can be set by operating the settingcontrol switches on the front panel while checking the valueon the setting indicator (7 segments) and the LED.
• Immunity to square wave impulse, radio frequencyinterference, and electrostatic discharge noise immunitycomply with B-402 (Digital Protective Relays and ProtectiveEquipment) (Types DUTN, DUTM only).
J: 100V AC 50HzK: 100V AC 60HzL: 110V AC 50HzM: 110V AC 60HzN: 127V AC 50HzP: 127V AC 60Hz
R: 200V AC 50HzS: 200V AC 60HzT: 220V AC 50HzU: 220V AC 60HzV: 250V AC 50HzW: 250V AC 60Hz
Example
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/67
12
Protective RelaysDUTE
Specifications, DUTE Items marked with should be specified when ordering. See page 12/66 for the 10th digit or later of type number.
Application and name Detection of ground fault (mainly resistance grounded line system), ground overcurrent relay
ElementOperate timeOperate value accuracy (%)f2 locking function (f2/f1) (%)
Instantaneous*6, *7±515 or more
Independent time-lag*6, *8*915 or more
1
DUTUETAA-2DUTAETAA-2DUTRETAA-2
DUTBETAA-2
DUTUEMAA-2
DUTAEMAA-2
DUTUETAK-2DUTAETAK-2DUTRETAK-2
DUTBETAK-2
DUTUEMAK-2
DUTAEMAK-2
0.20.2
With –With With –With
DQARA1HADQARA1HBDQAJA1HB
LED: Time lag x 1, Instantaneous x 1
LED: Time lag x 1, Instantaneous x 1Magnetic inversion: Time lag x 1, Instantaneous x 1Trip: Time-lag 1NO, Instantaneous: 1NO, Alarm: 1NC, External output: 1NO15 (at resistive load, 0.5s, 110V DC)5
10 (at inductive load, L/R=0.04, 110V DC)
LED: Time lag x 1, Instantaneous x 1
DQAJA1HA
LED: Operation x 1
LED: Operation x 1
LED: Operation x 1Magnetic inversion: Operation x 1
Trip: 1NO, Alarm: 1NCExternal output: 1NO
Holding factor (%) 52DQAJA1HH DQARA1HH
Note: *1 DQ series replacement type relay has the same terminal arrangement with DQ series relay. DQ series replacement type relay with a panel mounting adapter that has the same depth with DQ series relay, is also available. For details, contact FUJI.
*2 The value in parentheses indicates the pitch. The “L” indicates the setting is locked.*3 Zero represents instantaneous operate time (80ms max.).*4 The output duration of 1s is used in the case of the circuit breaker tripping, and that of 0.2s is used on other occasions.*5 Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.*6 See the operate time characteristics on page 12/69.*7 ±5% of max. time setting, or for min. time setting, 80ms max. when 200% input current of operate setting value.*8 ±5% of max. time setting, or for min. time setting, 80ms max. when 300% input current of operate setting value.*9 ±5% in accuracy guaranteed setting range (three times min. of min. operate setting value to max. operate setting value), ±15% for outside the accuracy guaranteed setting range.*10 If “S” or “K” is selected for the 8th digit of the code symbols, both LED and magnetic inversion operation indicators are provided with a display hold function.
If “A” is selected, the LED indicator has no display hold function.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/68
Protective RelaysDUTA
Specifications, DUT A Items marked with should be specified when ordering. See page 12/66 for the 10th digit or later of type number.
Application and name Detection of overload, short-circuit and ground fault of directly grounded line system, overcurrent relay
Display hold function *12DC auxiliary energizing source AC auxiliary energizing source
Arrangement
Limiting making capacity (A)Continuous current carrying capacity (A)Limiting breaking capacity DC (VA)
LED: Time lag x 1, Instantaneous x 1LED: Time lag x 1, Instantaneous x 1Magnetic inversion: Time lag x 1, Instantaneous x 1LED: Time lag x 1, Instantaneous x 1Magnetic inversion: Phase display x 2, Instantaneous x 1LED: Time lag x 1, Instantaneous x 1Magnetic inversion: Phase display x 3, Instantaneous x 1Trip: Time-lag 1NO, Instantaneous: 1NO, Alarm: 1NC, External output: 1NO15 (at resistive load, 0.5s, 110V DC)5
10 (at inductive load, L/R=0.04, 110V DC)
0.2 0.20.2 1
DQARA1HB, DQAWA2(C2, E2, F1, J2) HB, D
LED: Operation x 1LED: Operation x 1Magnetic inversion: Operation x 1
LED: Operation x 1Magnetic inversion: Phase display x 2
LED: Operation x 1Magnetic inversion: Phase display x 3
Trip: 1NO, Alarm: 1NCExternal output: 1NO
With With
*7*10
*7, *9*10
f2 locking function (f2/f1) (%)Holding factor (%)
1 input
—52DQAJB1, C1,D1HJDQAJB1, C1,D1HH
2 inputs, 3 inputs —
DQAJB1, C1,D1HCDQAJB1, C1,D1HB
DQAJB1HADQAJD1HA
DQARA1HH, DQAWA2(C2, E2, F1, J2) HH, GDQAWG1P
0.2
—
LED: Time lag x 1, Instantaneous x 1
—
—
—
LED: Operation x 1
—
—
With With
DQARA1HA, DQAWA2(C2, E2, F1, J2) HA, N—
Notes: *1 DQ series replacement type relay has the same terminal arrangement with DQ series relay. DQ series replacement type relay with a panel mounting adapter that has the same depth with DQ series relay, is also available. For details, contact FUJI.
*2 The value in parentheses indicates the pitch. The “L” indicates the setting is locked.*3 The output duration of 1s is used in the case of the circuit breaker tripping, and that of 0.2s is used on other occasions.*4 Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.*5 Zero represents instantaneous operate time (40ms max.).*6 Zero represents instantaneous operate time (50ms max.).*7 See the operate time characteristics on page 12/69.*8 ±5% of max. time setting, or for min. time setting, 40ms max. when 200% input current of operate setting value.*9 ±5% of max. time setting, or for min. time setting, 50ms max. when 300% input current of operate setting value.*10 ±5% in accuracy guaranteed setting range (1.5 times min. of min. operate setting value to max. operate setting value), ±10% for outside the accuracy guaranteed setting range.*11 Display by phase (R, S and T) is as follows.
DC auxiliary energizing source: Numbers 1 and 3 appear on the setting display (7 segments) when the number of inputs is 2 (“2” is not displayed for (S) phase), and 1, 2, and 3 appear when the number of inputs is 3.AC auxiliary energizing source: Numeric values that appear on the setting display (7 segments) are the same as the case of a DC auxiliary energizing source. Characters “R” and “T” appear on the magnetic inversion operation indicator when the number of inputs is 2 ((S) phase is not displayed), and “R”, “(S)” and “T” appear when the number of inputs is 3.
*12 If “S” or “K” is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.If “A” is selected, the LED indicator has no display hold function.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/69
12
Protective RelaysDUTE, DUTA
Instantaneous element Independent time-lag elementDUTH-2, DUTN-2 DUTT-2, DUTM-2
3s3
4
5[s]
2
1
0
2.1s
1.2s
0.3s
100 200 300 400
Input current (100% = Setting current)
500[%]
Op
erat
e ti
me
Op
erat
e ti
me
sett
ing
200%Input current
All current setting
Remark :Operate time in the state where operate time setting is 0s.Ground overcurrent relay : 80ms max.Overcurrent relay : 40ms max.
Setting valueoperate time setting [s]
Accuracy ε [%] (operate time range)
3.0 ±5 (2.850 to 3.150s)
±4.3 (1.971 to 2.229s)
±3.5 (1.095 to 1.305s)
±2.8 (0.216 to 0.384s)
2.1
1.2
0.3
Operate time accuracy
3s3
4
5[s]
2
1
0
2.1s
1.2s
0.3s
100 200 400 600 800
Input current (100% = Setting current)
1000[%]
Op
erat
e ti
me
Op
erat
e ti
me
sett
ing
300%Input current
All current setting
Remark : Operate time in the state where operate time setting is 0s.Ground overcurrent relay : 80ms max.Overcurrent relay : 50ms max.
Setting valueoperate time setting [s]
Accuracy ε [%] (operate time range)
3.0 ±5 (2.850 to 3.150s)
±4.3 (1.971 to 2.229s)
±3.5 (1.095 to 1.305s)
±2.8 (0.216 to 0.384s)
2.1
1.2
0.3
Operate time accuracy
Notes*1 : Operate time accuracy ε (%)
T10: Nominal operate time at referenceoperate time setting "n" = 10
Tn : Actual operate time at operate timesetting "n"
Where
*2: FAccuracy of items marked "*" (See the next page.)is ±100ms when the value "ε ·T10 " given in theabove equation "ε" is smaller than 100ms.
LED: Operation x 1Magnetic inversion: Operation x 1
DQVRA1HH,DQVWA2 (F1) HH, G
DUTUGTAK-2DUTAGTAK-2DUTRGTAK-2
DUTBGTAK-2
DUTUGMAK-2
DUTAGMAK-2
0.2
With
DQVRA1HB,DQVWA2 (F1) HB, D
DUTUGHAA-2DUTAGHAA-2DUTRGHAA-2
DUTBGHAA-2
DUTUGNAA-2
DUTAGNAA-2
0.2
–
LED: Operation x 1
DQVJA1HA
DUTUGTAA-2DUTAGTAA-2DUTRGTAA-2
DUTBGTAA-2
DUTUGMAA-2
DUTAGMAA-2
0.2
–
LED: Operation x 1
DQVRA1HA,DQVWA2 (F1) HA, N
ConstructionUnit standard structure typeDQ series replacement type *1
Unit standard structure type (B-402)
Ratings
Operation indicators
Contacts
Characteristics
Mass (kg)Previous relay type
Auxiliary energizing sourceDCACDC
AC
DC
AC
Frequency (Hz)Voltage (one input) AC (V)ElementSetting range*2
Output duration *4 (s)Rated burden (VA)Continuous withstand voltageAuxiliary energizing source*5Display hold function *7Auxiliary energizing source
ArrangementLimiting making capacity (A)Continuous current carrying capacity (A)Limiting breaking capacity DC (VA)Operate timeOperate value accuracy (%)Holding factor (%)
DCACDCAC
DCAC
Notes: *1 DQ series replacement type relay has the same terminal arrangement with DQ series relay. DQ series replacement type relay with a panel mounting adapter that has the same depth with
DQ series relay, is also available. For details, contact FUJI.
*2 The value in parentheses indicates the pitch.
*3 Zero represents instantaneous operate time (70ms max.).
*4 The output duration of 1s is used in the case of the circuit breaker tripping, and that of 0.2s is used on other occasions.
*5 Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*6 ±5% in accuracy guaranteed setting range, ±15% for outside the accuracy guaranteed setting range. 10 to 50V for accuracy guaranteed setting range, 5 to 10V below for outside the
accuracy guaranteed setting range
*7 If “S” or “K” is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.If “A” is selected, the LED indicator has no display hold function.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/72
Protective RelaysDUTV
Specifications, DUT V Items marked with should be specified when ordering. See page 12/66 for the 10th digit or later of type number.
Application and name Detection of overvoltage, overvoltage relay
LED: Operation x 1Magnetic inversion: Operation x 1
DQVRA1HH,DQVWA2 (F1) HH, G
DUTUVTAK-2DUTAVTAK-2DUTRVTAK-2
DUTBVTAK-2
DUTUVMAK-2
DUTAVMAK-2
0.2
With
DQVRA1HB,DQVWA2 (F1) HB, D
DUTUVHAA-2DUTAVHAA-2DUTRVHAA-2
DUTBVHAA-2
DUTUVNAA-2
DUTAVNAA-2
0.2
–
LED: Operation x 1
DQVJC1HA
DUTUVTAA-2DUTAVTAA-2DUTRVTAA-2
DUTBVTAA-2
DUTUVMAA-2
DUTAVMAA-2
0.2
–
LED: Operation x 1
DQVRA1HA,DQVWA2 (F1) HA, N
ConstructionUnit standard structure typeDQ series replacement type *1
Unit standard structure type (B-402)
Ratings
Operation indicators
Contacts
Characteristics
Mass (kg)Previous relay type
Auxiliary energizing sourceDCACDC
AC
DC
AC
Frequency (Hz)Voltage (one input) AC (V)ElementSetting range*2
Output duration *4 (s)Rated burden (VA)Continuous withstand voltageAuxiliary energizing source*5Display hold function *6Auxiliary energizing source
ArrangementLimiting making capacity (A)Continuous current carrying capacity (A)Limiting breaking capacity DC (VA)Operate timeOperate value accuracy (%)Holding factor (%)
DCACDCAC
DCAC
Notes: *1 DQ series replacement type relay has the same terminal arrangement with DQ series relay. DQ series replacement type relay with a panel mounting adapter that has the same depth with
DQ series relay, is also available. For details, contact FUJI.
*2 The value in parentheses indicates the pitch.
*3 Zero represents instantaneous operate time (70ms max.).
*4 The output duration of 1s is used in the case of the circuit breaker tripping, and that of 0.2s is used on other occasions.
*5 Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*6 If “S” or “K” is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.If “A” is selected, the LED indicator has no display hold function.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/73
12
Specifications, DUT U Items marked with should be specified when ordering. See page 12/66 for the 10th digit or later of type number.
Protective RelaysDUTU
Application and name Detection of undervoltage, undervoltage relay
LED: Operation x 1, Magnetic inversion: Operation x 1
DQVRB1HH,DQVWB2HH, G
DUTUUHAK-2DUTAUHAK-2DUTRUHAK-2
DUTBUHAK-2
DUTUUNAK-2
DUTAUNAK-2
0.2
With
DQVJD1HB
DUTUUHAA-2DUTAUHAA-2DUTRUHAA-2
DUTBUHAA-2
DUTUUNAA-2
DUTAUNAA-2
0.2
–
LED: Operation x 1
DQVJD1HA
DUTUUTAK-2DUTAUTAK-2DUTRUTAK-2
DUTBUTAK-2
DUTUUMAK-2
DUTAUMAK-2
0.2
With
DQVRB1HB,DQVWB2HB, D
DUTUUTAA-2DUTAUTAA-2DUTRUTAA-2
DUTBUTAA-2
DUTUUMAA-2
DUTAUMAA-2
0.2
–
LED: Operation x 1
DQVRB1HA,DQVWB2HA, N
ConstructionUnit standard structure typeDQ series replacement type *1
Unit standard structure type (B-402)
Ratings
Operation indicators
Contacts
Characteristics
Mass (kg)Previous relay type
Auxiliary energizing sourceDCACDC
AC
DC
AC
Frequency (Hz)Voltage (one input) AC (V)ElementSetting range*2
Output duration *4 (s)Rated burden (VA)Continuous withstand voltageAuxiliary energizing source*5Display hold function *6Auxiliary energizing source
ArrangementLimiting making capacity (A)Continuous current carrying capacity (A)Limiting breaking capacity DC (VA)Operate timeOperate value accuracy (%)Holding factor (%)
DCACDCAC
DCAC
Notes: *1 DQ series replacement type relay has the same terminal arrangement with DQ series relay. DQ series replacement type relay with a panel mounting adapter that has the same depth with
DQ series relay, is also available. For details, contact FUJI.
*2 The value in parentheses indicates the pitch.
*3 Zero represents instantaneous operate time (70ms max.).
*4 The output duration of 1s is used in the case of the circuit breaker tripping, and that of 0.2s is used on other occasions.
*5 Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*6 If “S” or “K” is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.If “A” is selected, the LED indicator has no display hold function.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/74
0–3 (0.1), [Zero is instantaneous (0.2±0.05)]1Voltage circuit: 1VA, ratedCurrent circuit Operate current value at 1 of power-factor: 1–10mA is 2.7Ω burden. 10–100mA is 0.27Ω burden.Voltage circuit: 115, current circuit: 100
10 (at inductive load, L/R=0.04, 110V DC)Operate phase angle is (θ+80)±5° leading max., (θ+280)±5° lagging max., under 1000% of operate current setting. Max. sensitivity phase angle (θ) is ±5° max. of setting value.Operate current accuracy is ±10% max. of setting value under max. sensitivity phase angle.
±10±10±5 (under 30% of rated voltage. 1000% of operate current setting)
(operate time setting value + 0.2) ±0.35 (under operate time setting value = 0.3 to 3)1202DQWJA1HHDQWPAHHDQWPFHHDQWPAHGDQWPFHG
DUTADTBS-3DUTBDTBS-3
1
AC100, 110, 127, 200, 220, 250 50, 60Hz
AC100, 110, 127V rated : 15VAAC200, 220, 250V rated : 20VAWithLED: Operation x 1, Magnetic inversion: Operation x 1
1
DQWPAHHDQWPFHH
DUTUDTBK-3DUTRDTBK-3
0.2
With
0.2
DQWJA1HBDQWPAHBDQWPFHBDQWPAHDDQWPFHD
DUTUDTBA-3DUTRDTBA-3
0.2
–
0.2
DQWJA1HADQWPAHADQWPFHADQWPAHNDQWPFHN
DUTADTBK-3DUTBDTBK-3
0.2
With
0.2
DQWPAHBDQWPFHB
DUTADTBA-3DUTBDTBA-3
0.2
–LED: Operation x 1
0.2
DQWPAHADQWPFHA
ConstructionUnit standard structure typeDQ series replacement type *1 *7Ratings
Operation indicators
Contacts
Characteristics
Mass (kg)Previous relay type
Frequency (Hz)Zero-sequence voltage AC (V) Zero-sequence current *6 AC (A) Setting range *2
Output duration *3 (s)Burden (VA)
Continuous withstand input (% of rating)Auxiliary energizing source*4Display hold function *8Operation indicators
ArrangementLimiting making capacity (A)Continuous current carrying capacity (A)Limiting breaking capacity DC (VA)Influenced by phase angle *5(under 30% of rated voltage)Influenced by voltage-current *5(under 30% of rated voltage)Accuracy
Resetting time (s)Holding factor (%)
Notes: *1 DQ series replacement type relay has the same terminal arrangement with DQ series relay. DQ series replacement type relay with a panel mounting adapter that has the same depth with
DQ series relay, is also available. For details, contact FUJI.
*2 The value in parentheses indicates the pitch.
*3 The output duration of 1s is used in the case of the circuit breaker tripping, and that of 0.2s is used on other occasions.
*4 Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*5 See the characteristic diagrams on page 12/77
*6 Zero-sequence current (3Io) flowing into secondary side of zero-sequence current transformer (ZCT).
Use ZCT complying with L-class (200/1.5mA, Z=10Ω, pf=0.5) defined by JEC 1201.
*7 Noise immunity per B-402 (Digital Protective Relays and Protective Equipment)
*8 If “S” or “K” is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.If “A” is selected, the LED indicator has no display hold function.
Specifications, DUT D Items marked with should be specified when ordering. See page 12/66 for the 10th digit or later of type number.
Protective RelaysDUTD
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/77
12
Connection diagrams
+ –9 10 18
SO.
14 15
Alarm
AL
11 12
Trip
X
16 17
Externaloutput
X
1 2
3Vo
3 4
3Io
A5 A6
Trip
B14 B15+ –
Alarm
A9 A10 B18
SO.
ALX
A7 A8
Externaloutput
X
A1 A2
3Vo
A3 A4
3Io
DUTUDTB-3, DUTADTB-3 DUTURDTB-3, DUTBDTB-3
Characteristic diagrams
90°
60°
30°
200 400 600 800 1000 1200[%]0°
330°
300°
270°
240°
210°
180°
150°
120°
Zero-sequence voltage 3Vo=30% of rated voltageMax. sensitivity phase angle θ=60° (leading current)
Leadingcurrent
Zero-sequence current (3lo) (100%=Setting current)
Operating range
[%]1200
1000
800
600
400
200
00 20 40 60 80 100 [%]
Zero-sequence voltage (3Vo)(100%=Zero-sequence rated voltage)
Zer
o-se
que
nce
curr
ent (
3lo)
(100
%=
Set
ting
cur
rent
)
• Zero-sequence rated voltage 3Vo : 100%=110V• Max. sensitivity phase angle between zero-sequence input
voltage and current θ is constant.• Operate voltage setting : 5V (equivalent to 4.5%)• Operate current setting : 100%=1.5mA
• Characteristics influenced by phase angle • Characteristics influenced by voltage-current
Operete time characteristics
Protective RelaysDUTD
5
4
3
2
1
0100 200 300 400 500 600 700 800 900 1000 [%]
[s]
Op
erat
e tim
e
Operatetimesetting
3.0s
2.1s
1.2s
0.3s
0s
Zero-sequence current 3Io (100%=Setting current)
100% of rated voltageZero-sequence voltage 3Vo
1000% of setting currentZero-sequence current 3Io
Setting value
All voltage,currentsetting
Operate Time setting[s]
Operate time[s]
3.0 3.2
2.3
1.4
0.5
2.1
1.2
0.3
0.2
Accuracy ε [s](Operate time range)
±0.35 (2.85 to 3.55)
±0.35 (1.95 to 2.65)
±0.35 (1.05 to 1.75)
±0.35 (0.15 to 0.85)
±0.05 (0.15 to 0.25)0
Operate time accuracy
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/78
Protective RelaysDUT
Terminal arrangement(Seen from the rear)
Terminal No. (12 to 18 of M4×8)1817161514131211109
8642
7531
110
16
1313
13
1111
1111
1111
1111
11
44 4.9
Connection sheet
Dimensions, mm
Terminal arrangement(Seen from the rear) Terminal No.
(20 of M4×8)B18
A10 A8 A6 A4 A2
A9 A7 A5 A3 A1
B17B16B15B14B13B12B11B10B9
110
1111
1111
1111
1111
11
1.1
6.6
11 11 11 11
11 11 11
44 4.9
Connection sheet11
Panel
174
120 30
179
201
190
152
2 of M6bolts and nuts
Insulated terminal cover
Name plate
Panel
30
179
233
156
2 of M6 bolts and nuts
Terminal block adapterInsulated terminal cover
152
• Unit standard structure type, DUTU, DUTA
• DQ series replacement type, DUTR, DUTB
2–ø7 holes
154
174
112+2 0
Mounting hole dimensionon panel
When mounting two or more relays adjacentto each other, the minimum mounting pitch of the relays (from center to center) should be130mm horizontally and 210mm vertically.
Symbols (conforming to JIS C-0301)Explanatory diagram
Time-lagelement contact
Currentcircuit
Short-circuitingbar of paired terminals
Externalterminal No.
Polarity of relayinput
Input current(V: input voltage)
1810151413121143 9
Instantaneouselement contact
Alarm contact(continuousmonitoring)
Draw-outdevice
Auxiliaryenergizingsource andpolarity
L
H
1716
L
HAL
+ –
SO.External outputAlarmTripI
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/79
*The terminal numbers above are as same as those of output terminals of DUT series protective relays.
7.1kg
Connection diagram Dimensions, mmDUTT1 DUTT1
1
2
3
4
5
6
7
8
9
10
18
11
12
13
14
15
16
17
1
2
3
4
5
6
7
8
9
10
18
11
12
13
14
15
16
17
INPUT
INPUT
INPUT
INPUT
AC inputterminal
Relay inputsection
Relay outputsection
Auxiliary energizing sourceinput terminal
Frame ground (FG) terminal
TRIP
ALARM
OUTPUT
P (R)
N (T)
DUT protective relay case
270
300
8305
1 11
12
13
14
15
16
17
9
18
10
2
3
4
5
6
7
8
INPUT
INPUT
INPUT
INPUT
DUT protective relay case
Name plate
P (R)
N (T)
FG
CONTROLSOURCE
TRIP
ALARM
OUTPUT
DUTT1
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/80
QH series protective relays
DescriptionFUJI overcurrent relays and voltagerelays have inverse-time characteristics(induction and static types). The QHseries is compact budget priced versionand is easily installed on panels. It isdrum-shaped and ideally suited forgeneral industrial applications.The directional ground-fault relay (DG) isused, combined with zero-phase currenttransformer (ZCT) and zero-phasepotential input device (ZPD).The ground-fault relay (GR) is used,combined with zero-phase currenttransformer (ZCT).
QH-DGAF90-528
QH-OCAF90-78
Protective RelaysQH seriesGeneral information
ZCTAF91-267
Specifications
Overcurrent relays
TypeTrip systemRated currentRated frequencyInverse time-lag element
Instantaneous elementIndicationContact
Consumed VAMass
QH-OC1Shunt trip5A50/60Hz3-3.5-4-4.5-5-6A0.5-1-2-3-4-5-6-7-8-9-10-15-20-30-40-50 (16 steps)300% overcurrent: 10s ± 17% or less, 700% overcurrent: 1.67s ± 12% or less at min. operating current and time-lag setting = 10Extremely inverse time-lag 20-30-40-50-60-Lock200%, 0.05s or lessStart, time-lag elapsed, operate, power, alarmMaking capacity 10A at 100V DC, 220V DC (L/R=7ms)Breaking capacity 1A at 110V DC (L/R=7ms) 3.5A at 220V AC (cosø=0.4)2A at 24V DC (max. 30W at 125V DC) (L/R=7ms)2A at 100V AC (max. 220VA at 250V AC) (cosø=0.4)2VA (at 5A)1.1kg
QH-OC2Current trip
Breaking capacity60A at 110V AC (depending on CT burden)
2VA (at 5A)1.1kg
Setting rangeTime-lag settingOperate time
Operate characteristicSetting rangeOperate time
For tripQH-OC1: 1NOQH-OC2: 2NC
For alarm, 1NO
Voltage relays
TypeTrip systemRate voltageSetting rangeOperate time settingIndicationContact
Consumed VAMass
Overvoltage relayQH-OV1Shunt trip110V AC115-120-125-130-135-140-150V0.1-0.2-0.5-1-1.5-2-2.5-3-4-5-6-8-10sStart, operate, powerMaking capacity 5A at 250V AC (cosø = 0.4)Breaking capacity 2A at 250V AC (cosø = 0.4)2VA1kg
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/81
12
Protective RelaysQH series
General information
Description Primary Rated Dielectric Over- Type Masscurrent primary strength current
voltage constant(A) (kV) (kg)
Round-hole 100 3.3/6.6 22kV AC 40 ZCT-561A 0.5through-type 200 1 min. ZCT-562A 0.5
300 50/60Hz ZCT-653 0.8400 common ZCT-654 0.8600 use ZCT-906 3.0
Split-toroidal 100 ZCT-451D 0.9 type 400 ZCT-654D 1.2
Zero-phase current transformers
Type ZPD-1
Structure Indoor use, epoxi-resininsulator
Rated voltage 7.2kV
Electrostatic 3 250pFcapacitance
Dielectric Class 6A, 22kV ACstrength (1 minute)
Mass (kg) 3.6kg (1set = 3pcs)
Zero-phase potential input device
Specifications
Directional ground-fault relays
TypeTrip systemZero-phase voltage setting range
Zero-phase current setting rangeOperating time settingOperating characteristic
IndicationResetting methodTest buttonContact
Rated control voltageFrequencyOperate phase angle
Consumed VAMass
QH-DG3 (for receiving circuit)Shunt trip, current trip2.5-5-7.5-10-12.5% of zero-phase voltage 3810V at full ground-fault0.1-0.2-0.3-0.4-0.6A (ZCT primary side)Insnt.-0.2-0.3-0.4-0.6s±30ms at 130% current setting value-40ms to +0ms at 400% current setting value(when 150% of voltage setting value applied)Within ±10% of current setting value (when 150% of voltage setting value applied)Within ±25% of voltage setting value (when 150% of current setting value applied)Operate, zero-phase current/voltage, powerAuto-manual (selectable by a switch)ProvidedMaking capacity: 10A at 110V ACBreaking capacity: 7.5A at 110V AC (cosø= 0.4), 0.4A at 125V DC (L/R= 7ms) 7.5A at 110V AC (cosø= 0.5) Making capacity: 1.5A at 110V AC (cosø= 0.4), 0.1A at 125V DC (L/R= 7ms) 110V AC 50/60Hz50Hz-60Hz (changeable by a switch)Non grounded system: Lag 45°±20°, lead 135°±20°PC grounded system: Lag 70°±15°, lead 110°±15°7VA (at operating)1.9kg
QH-DG4 (for branching circuit)
-
6VA (at operating)1.9kg
Operating time
Zero-phase currentZero-phase voltage
For shunt trip: 1NO
For current trip: 2PDTFor alarm: 1NO
The QH-DG4 will function as branching unit for power receiving use QH-DG3.It cannot be used solely.Operating phase angle
(non grounded system)
Non-operating range
Operating range
90˚
0˚180˚
–45˚±20˚
135˚±20˚
–90˚
Accessories, sold separately
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/82
• Protective relays Zero-phase current transformers
ZCT–561A
Basic type Type of transformer (Hole-through diameter/Rated current)561A: Hole-through type Ø56/100A562A: Hole-through type Ø56/200A653: Hole-through type Ø65/300A654: Hole-through type Ø65/400A906: Hole-through type Ø90/600A451D: Split-toroidal type Ø45/100A654D: Split-toroidal type Ø65/400A
Ordering informationSpecify the following:1. Type number2. Rated control voltage and frequency3. Rated current and frequency
(Overcurrent relay)4. Setting range (Volts or Amperes)
Ground-fault relays
TypeTrip systemOperating current settingOperating time
Indication
Contact
Consumed VATest buttonMass
QH-GR3AShunt trip, current trip0.1-0.2-0.4-0.6-0.8A0.1 to 0.3s at 130% current setting value0.1 to 0.2s at 400% current setting valueMagnetic inversion (manual reset)Green LEDMaking capacity: 10A at 250V AC (cosø= 0.4), 10A at 125V DC (L/R= 7ms) Breaking capacity: 7.5A at 110V AC (max. 825VA at 250V AC) (cosø= 0.4) 1.2A at 100V DC (max. 120W at 125V DC) (L/R= 7ms) 2A at 110V AC (max. 220VA at 250V AC)2A at 24V DC (0.1A at 125V DC)5VA (at operating)Providied1.7kg
OperationPowerFor trips: 2PDT
For alarm: 1NO
• Zero-phase potential input deviceZPD–1
Zero-phase potential input device
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/83
12
ZCT-906 Zero-phase current transformersZCT-561A, 562A
ZCT-653, 654
ZCT-451D, 654D
ZPD-1
Protective RelaysQH series
100
118 44
φ 55
5068
50
φ100
30
φ19.5 85
120
59
108
2.3
kt
k
ktk
t
Separator
K
φ 56
Mounting. plate
125
64
191
91
114
94 ø89.
5
ø28.5
128
178
7 Separator
Output terminal Test terminal
L
Mounting-plate
ø90
136
140
φ 65
77
φ 64.
5
300A: φ21 400A: φ25
50
140
170
41
Mounting. hole2-φ9
Separator
NP
K
Test terminal Output terminal
(R63
)
ø45(ø65) 56.5
(66.
5)
105(
125)
150(170)
165(185) 36
33Terminalcover
19ø6
140(160)
Jumper plate K
l
k
( ) : for ZCT-654D
ø80
115
23
20 20
32
ø75
22
3-M10 Depth 17
Electrode capPre-wired bofore shipment
ZPD-1
Approx. 300 max.
Approx. 300 max.
TE
N
E
N
Y2
Y1
E
N
Dimensions, mm
Relays
QH-OC1, OC2, OV1, UV1, DG3, DG4, GR3A
Panel cutting
2-M6
124
124φ142
2-φ7
φ 137155
152 11827
ø13
8
Zero-phase potential input device
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice12/84
QH-DG3, shunt-trip QH-DG3 with QH-DG4Installation at receiving point and branchpoint (QH-DG3 at receiving point, QH-DG4at branch point)
Protective RelaysQH series
QH-GR3, shunt-trip
QH-GR3, current trip
Internal wiring diagram/QH-GR3
C.B
C.T C.T
T.C52a
DC power supply
CTT
Alarmcontact (NO)(On for 0.1S)
Alarmcontact (NO)(On for 0.1S)
C1R C2R C1T C2T T1 T2 a1 a2
AS
A
X X X
C.B
C.T
C.T
T.C T.C
CTT
C1R T1R C2T2R C1T T1T C2T2T a1 a2
A
AS
X X X
DC power supply
T.C.
VT
CB
52aP1 P2 T1 T2 a1 a2
Alarmcontact (NO)(On for 0.1S)
X XX
DS
K
ZCT
LE3
ktk
l
lt
VT
100V AC
E3
52a
Controlpowersupply
CB(52)
TC
CTOCR OCR
E3
T N N NE E E
ZPD-1E1
Y1
Y2
V0 testterminal
Z1
Z2
P1
P2
QH-DG4M
N
S0
T1
T2
O1
O2
S1
S2
a1
a2
Y1
Z2(Y2)
QH-DG3
QH-GR3A
P1
P2100V AC
Alarm contact (NO)
Alarm contact (NO)(On for 0.1s)
N
P52T
52
52
ZCT
CT CT
K
L
QH-OC1T1
T1
T2 a1
a1 a2
a2
C1R C2R C1T C2T
AS
A
Z1
Z2 S0
QH-GR3A
P1
P2100V AC
52a
Alarm contact(NO)
Alarm contact(NO)(On for 0.1s)
52
ZCT
K
L
QH-OC2
T1 T2 O1 O2
a1
a1 a2
a2
C1RT1RC2T2R T1T
C1T C2T2T
AS
A
Z1
Z2
Z1 S0 S1 S2
T2T1O2O1a2a1P2P1
Z2
ZCT
QH-GR3A
110V AC
ktk
l
lt
ktk
l
lt
CTCT
V0 testterminal
X XX
DS
K
ZCT
LE3
ktkl
lt
VT
100V AC
E3
CB(52)
TC
TC
CT OCR OCR
E3
E2
T N N NE E E
ZPD-1E1
Y1
Y2
Z1
Z2
P1
P2
QH-DG4
QH-DG3
M
NT1
T2
O1
O2
S1S2
a1
a2
Y1
Z2(Y2)
S052a
SB
Tr(500VA or more)
AC100V
QH-DG3, current trip
V0 testterminal
T N N NE E E
ZPD-1EA
Y1
Y2
DS
K
ZCT
L ED
ktkl
lt
CB(52)
ZCT
kt
k l
lt
VT
100V AC
ED
CB(52) TC
TC
To OCRTo OCR
QH-DG4
To powersupply fortripping
CT
ED
ED
Z1
Z2
P1
P2
QH-DG3
M
N
a1
a2
T1
T2
T1
T2TC
To VT
To TC
To OCR
To power supplyfor tripping
52a
O1
O2
S1S2
Y1
Z2(Y2)
P1
P2
Z1
Z2
T1
T2
O1
O2
S1
S2
M
N
P1
P2
Z1
Z2
T1
T2
O1
O2
S1
S2
M
N
S0
a1
a2
52a
CB(52)
ZCT
kt
k l
lt
QH-DG4
ED
T1
T2TC
To VT
To TC
To OCR
To power supplyfor tripping
52a
S0
a1
a2
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 12/85
12
Characteristic curvesQH overcurrent relay
Protective RelaysQH series
Dial 10
Current (%)
300
700
Time (s)
10
1.67
0.5
1
2
3
4
5678910
15
20
30
40
50
Dial
20.01
0.03
0.04
0.05
0.1
0.2
0.3
0.4
0.5
1
Ope
ratin
g tim
e (s
econ
d)
2
3
4
5
10
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
10000
5 10 50 100
Multiple of current setting (%)
500 1000 5000 10000
0.01100 1000
0.03
0.02
0.04
0.05
0.1
Multiple of current setting (%)
Instantaneous tripping characteristic
Ope
ratin
g tim
e (s
econ
d)
Catalog Disclaimer
The information contained in this catalog does not constitute an express or implied warranty of quality, any warranty of merchantability of fitness for a particular purpose is hereby disclaimed.
Since the user's product information, specific use application, and conditions of use are all outside of Fuji Electric FA Components & Systems'control, it shall be the responsibility of the user to determine the suitability of any of the
products mentioned for the user's application.
One Year Limited Warranty
The products identified in this catalog shall be sold pursuant to the terms and conditions identified in the"Conditions of Sale" issued by Fuji Electric FA with each order confirmation.
Except to the extent otherwise provided for in the Conditions of Sale issued by Fuji Electric FA, Fuji Electric FA warrants that the Fuji Electric FA products identified in this catalog shall be free from significant defects in materials and workmanship provided the product has not been: 1) repaired or altered by others than Fuji Electric FA; 2) subjected to negligence, accident, misuse, or damage by circumstances beyond Fuji Electric FA's control; 3) improperly operated, maintained or stored; or 4) used in other than normal use or service. This warranty shall apply only to defects appearing within one (1) year from the date of shipment by Fuji Electric FA, and in such case, only if such defects are reported to Fuji Electric FA within thirty (30) days of discovery by purchaser. Such notice should be submitted in writing to Fuji Electric FA at 5-7, Nihonbashi Odemma-cho, chuo-ku, Tokyo, Japan. The sole and exclusive remedy with respected to the above warranty whether such claim is based on warranty, contract, negligence, strict liability or any other theory, is limited to the repair or replacement of such product or, at Fuji Electric FA's option reimbursement by Fuji Electric FA of the purchase price paid to Fuji Electric FA for the particular product. Fuji Electric FA does not make any other
representations or warranties, whether oral or in writing, expressed or implied, including but not limited to any
warranty regarding merchantability or fitness for a particular purpose. Except as provided in the Conditions of Sale, no agent or representative of Fuji Electric FA is authorized to modify the terms of this warranty in writing or orally. In no event shall Fuji Electric FA be liable for special, indirect or consequential damages, including but not limited to, loss of use of the product, other equipment, plant and power system which is installed with the product, loss of profits or revenues, cost of capital, or claims against the purchaser or user of the product by its customers resulting from the use of information, recommendations and descriptions contained herein. The purchaser agrees to pass on to its customers and users, in writing at the time inquiries and orders are received by buyer, Fuji Electric FA's warranty as set forth above.
Caution "Safety precautions"
• Operate (keep) in the environment specified in the operating instructions and manual. High temperature, high humidity, condensation, dust, corrosive gases, oil, organic solvents, excessive vibration or shock might cause electric shock, fire, erratic operation or failure.
• Follow the regulations of industrial wastes when the product is to be discarded.• The products covered in this catalogs have not been designed or manufactured for use in equipment or systems which,
in the event of failure, can lead to loss of human life.• If you intend to use the products covered in this catalog for special applications, such as for nuclear energy control,
aerospace, medical, or transportation, please consult tour Fuji Electric FA agent.• Be sure to provide protective measures when using the product covered in these catalogs in equipment which, in the
event of failure, may lead to loss of human life or other grave results.• Follow the directions of the operating instructions when mounting the product.