HUNTER-PRO 896 System ver. 2.0 9-96 ZONES INTRUDER ALARM SYSTEM INSTALLATION GUIDE The new telephone number of PIMA technical support team: +972-3-6506444
HUNTER-PRO 896 System ver. 2.0
9-96 ZONES INTRUDER ALARM SYSTEM
INSTALLATION GUIDE
The new telephone number of PIMA technical support team: +972-3-6506444
2 HUNTER-PRO 896 Installation Guide
PIMA Electronic Systems Ltd. does not represent that its Product may not be compromised
and/or circumvented, or that the Product will prevent any death, personal and/or bodily injury
and/or damage to property resulting from burglary, robbery, fire or otherwise, or that the
Product will in all cases provide adequate warning or protection. The User understands that a
properly installed and maintained equipment may only reduce the risk of events such as
burglary, robbery, and fire without warning, but it is not insurance or a guarantee that such will
not occur or that there will be no death, personal damage and/or damage to property as a result.
PIMA Electronic Systems Ltd. shall have no liability for any death, personal and/or bodily
injury and/or damage to property or other loss whether direct, indirect, incidental, consequential
or otherwise, based on a claim that the Product failed to function.
Please refer to a separate warranty statement found on PIMA website at:
http://www.pima.co.il/site/Content/t1.asp?pid=472&sid=57
Warning: The user should follow the installation and operation instructions and among other
things test the Product and the whole system at least once a week. For various reasons,
including, but not limited to, changes in environment conditions, electric or electronic
disruptions and tampering, the Product may not perform as expected. The user is advised to
take all necessary precautions for his/her safety and the protection of his/her property.
This document may not be duplicated, circulated, altered, modified, translated, reduced to any
form or otherwise changed; unless PIMA’s prior written consent is granted.
All efforts have been made to ensure that the content of this manual is accurate. Pima retains
the right to modify this manual or any part thereof, from time to time, without serving any prior
notice of such modification.
Please read this manual in its entirety before attempting to program or operate your system.
Should you misunderstand any part of this manual, please contact the supplier or installer of
this system.
Copyright © 2007 by PIMA Electronic Systems Ltd. All rights reserved. You can contact us at
PIMA Electronic Systems Ltd., 5 Hatzoref Street, Holon 58856, Israel.
Contact Us:
PIMA Electronic Systems Ltd.
5 Hatzoref Street, Holon 58856, Israel
Tel: +972-3-6506444
Fax: +972-3-5500442
Email: [email protected]
Web: http://www.pima.com
HUNTER-PRO 896 Installation Guide 3
Table of Contents
1 Introduction ...........................................................................5
1.1 HUNTER-PRO 896 Main Features ...................................................6
1.2 Signs and Abbreviations....................................................................7
1.3 The Control Panel’s PCB...................................................................8
1.4 Outputs and Output Types ..............................................................12
2 Partitioning..........................................................................13
2.1 Introduction......................................................................................13
2.2 Examples.........................................................................................13
3 Connecting Zones & Accessories .......................................16
3.1 Connecting Zones ...........................................................................16
3.2 Connecting Zone Expanders...........................................................19
3.3 Connecting Expansion Cards..........................................................20
3.4 Key & Key fob..................................................................................25
3.5 TMPR1, TMPR2: Tamper Switches ................................................25
3.6 Sirens...............................................................................................25
3.7 Relay Output....................................................................................28
3.8 OUT-1000: Outputs Expansion Card ..............................................28
3.9 Keypads...........................................................................................28
3.10 Telephone Line and Devices...........................................................30
3.11 VKD-1: Virtual Keypad.....................................................................30
3.12 TRV/TRU-100: Long Range Radio Transmitters ............................31
3.13 GSM-200: Cellular Transmitter........................................................32
3.14 MIC-200: Microphone Unit ..............................................................33
3.1 VU-20: Voice Unit ............................................................................33
3.1 Battery .............................................................................................33
3.2 Mains ...............................................................................................34
3.3 Initializing the System......................................................................34
3.4 Faults Display ..................................................................................35
4 Programming Basics...........................................................37
4.1 General ............................................................................................37
4.2 Methods...........................................................................................37
4.3 Default Codes..................................................................................39
4.4 User Menu .......................................................................................39
4.5 Technician Menu .............................................................................40
4.6 Express Programming Menu...........................................................40
4.7 The Keypad Keys ............................................................................41
4.8 Entering Names, Numbers and Characters ....................................41
4 HUNTER-PRO 896 Installation Guide
5 Programming ......................................................................42
5.1 Enabling Enhanced Communication Menu .....................................42
5.2 Key #1: System Installation...........................................................42
5.3 Key #2: Zone Programming ..........................................................45
5.4 Key #3: Communication Parameters ............................................48
5.5 Key #4: Timers, Counters .............................................................59
5.6 Key #5: General Parameters ........................................................62
5.7 Key #6: System Responses..........................................................63
5.8 Key #7: Outputs Configuration......................................................64
5.9 Key #8: Full Programming.............................................................68
5.10 Key #9: Installer Code...................................................................69
5.11 Asterisk Key *: Express Programming Menu ............................69
5.12 Key #0: Tests ................................................................................69
5.13 How to Locate Expanders’ Zones ...................................................73
6 Remote Control via Touch-tone Telephone ........................74
6.1 Mode A ............................................................................................74
6.2 Mode B ............................................................................................75
7 Troubleshooting ..................................................................77
7.1 Restoring Master & Installer Codes.................................................77
7.2 Faults Displayed on the LCD...........................................................77
7.3 Additional Faults ..............................................................................79
7.4 MS Report Formats & Codes ..........................................................81
HUNTER-PRO 896 Installation Guide 5
1 INTRODUCTION
This guide provides the installation, wiring and programming instructions for PIMA’s HUNTER-PRO 896 Intruder Alarm System. HUNTER-PRO 896 has many features that
fits customer’s individual needs, and yet it remains easy to install and simple to
program and use, both by the customer and the installer.
HUNTER-PRO 896 is secured against radio-frequency (RF) interferences and electro-
magnetic interferences (EMI).
SAFETY INSTRUCTIONS
Your HUNTER-PRO 896 Alarm System has been registered in accordance with
EN60950 and its rules. EN 60950 requires us to advise you the following information:
1. In this alarm system exist hazards of fire and electric shock. To reduce the risk of fire or electric shock, do not expose this alarm system to rain or moisture. Pay
attention: Telephone cords could be a good conductor for lightings energy.
2. Do not open the door of the alarm system. Dangerous high voltages are present inside of the enclosure. Refer servicing to qualified personnel only.
3. This alarm system should be used with AC 230V/110V, 50Hz, protected by anti electric shock breaker. To prevent electric shocks and fire hazards, do NOT use
any other power source.
4. Do not spill liquid of any kind onto the unit. If liquid is accidentally spilled onto the unit, immediately consult a qualified service.
5. Install this product in a protected location where no one can trip over any line or power cord. Protect cords from damage or abrasion.
6. Disconnect all sources of power supply before proceeding with the installation. Pay attention: do not install low voltage wires near by AC power wires they should be
separated.
7. Connect the AC transformer output to the terminal block on the control panel as
marked.
8. Connect the AC line cord to line power terminals as marked. (GND; N; L)
IMPORTANT! Regarding parameters such as Date and Time, User codes and
Telephone numbers, please refer to the HUNTER-PRO 896’s User Guide.
6 HUNTER-PRO 896 Installation Guide
1.1 HUNTER-PRO 896 Main Features
Hybrid system with 9 to 96 zones (32 wireless)
Easy to install and simple to program and use
Supports a wide range of partition options:
Up to 16 partitions each with it own Account ID and Users
Up to 8 subsystems, each with different keypads, IDs, etc.
Outgoing SMS over PSTN or GSM
Passive and active Automatic Arming:
Active: At a preset time (per day of the week)
Passive: When no motion is detected (“silence time”) for a preset period. Can be programmed by partition.
Codes: 96 User codes, 24 Key fobs, 96 Tags (RFID), Door code, Duress code and more
Various authorization levels for each user
Disarming time frame by User
Remote control of the system, including outputs, via any touchtone telephone
Full supervision data of wireless detectors (supervision, low battery, tamper)
Comprehensive zone tests for flawless installation: Walk Test, Soak Test, etc.
Several options for viewing system status:
“PIMA” Style: Status of first 32 zones in one screen
Detailed: Scrolling events, zones’ and system’s status
4 Subscriber dialing and SMS numbers with optional voice message and
microphone
4 (additional) Monitoring Stations telephone numbers
PIMA unique Integrated Digital Communicator through telephone, long-range radio, GSM/GPRS and TCP/IP
Supports split and double reporting to 2 Monitoring Stations with different account IDs
LCD keypad with multilingual Menu-Driven screens for easy programming and operation
Many alternatives for easy programming (Keypad, Fast Programmer, Local/Remote download software)
Various accessories (microphone, voice unit etc.)
Displaying the location of the zones in expansion units, their partitions and
their type
Memory Log of up to 500 events, 250 of which nonvolatile
HUNTER-PRO 896 Installation Guide 7
Prevention of burglary setup: limited bypass time, zone bypassing authorization, pre-alarm and more
Online battery and telephone line checks
LED keypad support
Filtering reoccurring faults: a fault (jamming, mains etc.) occurring 5 times in one hour will not be reported any more before an hour past with the fault not
occurring or the system is either armed or disarmed.
Reducing false alarms: Burglary report is delayed to the extent of entry delay.
A new protocol for a local MS: replaces the current protocol and contains much more information.
1.2 Signs and Abbreviations
Key press
Press and hold key until confirmation beep sounds
Enter and save data
In programming mode: return to previous screen/s
Enabled User Code: A code enabled (by technician) to enter the user menu
LCD Zone Numbers: The 1-16 & 17-32 numbers printed above and below the LCD
display window. Indicating the first 32 zones’ numbers.
MS: Central Monitoring Station
Default Master Code: 5555
8 HUNTER-PRO 896 Installation Guide
1.3 The Control Panel’s PCB
Figure 1 - HUNTER-PRO 896 Control Panel’s PCB (see details further)
HUNTER-PRO 896 Installation Guide 9
1.3.1 Fuses
F5 - protects the PCB from a battery short (Fast 5A/250 VAC)
F6 - protects the PCB from an AC short (Fast 3.15A/250 V
1.3.1.1 Thermal Fuses to limit current:
F1 – Detectors power supply (750mA)
F2, F3 – Siren 1 and Siren 2 (1.1A)
F4 – Keypad power supply (750mA)
F7 – Long-range radio transmitter protection (200 mA)
1.3.2 PCB’s Connections & Terminals
1 AC: Voltage Input
14VAC input supplied by a transformer
2 “+”, “-“: Connections to backup Battery
Red wire: “+” (positive) contact of the battery
Black wire: “-” (negative) contact of the battery
IMPORTANT! Inverting the battery polarity can damage the PCB.
3 Z1–Z8: Zones Inputs
8 zones inputs that can be connected to dry contact detectors. All zones can be
connected with single or double EOL resistors (refer to “Connecting Zones”, page 16)
NOTE: The number of zones can be expanded by connecting line/wireless expanders
(see section 3.3)
4 (+) - Detectors’ Power Supply
12V power supply for detectors that require DC voltage, such as infrared, ultrasonic, beam etc.
5 KEY - Key Fob or Remote Control Input
An input for momentary, on/off key or Key fob, to arm/disarm the system.
6 Ext, Int - External & Internal Sirens Outputs
Dedicated automatic thermal fuses (F2 and F3) for each siren (see section 3.6)
7 RELAY – Onboard Relay Connections
The onboard relay can be used to activate various auxiliary accessories, such as
external lighting, CCTV, external communicator, electric locks, etc. The relay can be triggered in response to alarm or via telephone or remote control
10 HUNTER-PRO 896 Installation Guide
8 SMOKE – Reset Smoke/Anti Mask Detectors
An output used to reset smoke/anti mask detectors by switching (+) to GND. When not
activated, this output is set to GND (-).
To manually reset these detectors:
9 KEYPAD – Communication & Power Connections for Keypads & Expanders
The KEYPAD terminal has for connections:
“+”’ “–“ - Voltage power connections; Up to 8 RXN-400/410 LCD keypads can be connected simultaneously, as well as the wireless receiver I/O-WN and I/O-8/8N/16N/R
expanders. IN/OUT - Data transfer to/from the keypad. Thermal fuse F4 protects the 13.8 VDC
power supply.
ALRM and ON/OFF – Auxiliary Outputs
ALRM – Is switched by default to (-) when alarm occurs;
ON/OFF – Is switched by default to (-) when the system is armed.
These terminals have two conditions: disconnection or short to ground. They can serve
as indicators to auxiliary units and to system or alarm status, or other modes (see section 5.8.1).
11 TMPR1 and TMPR2 – Tampers switches Inputs
Inputs for tampers’ switches on detectors and cases. The switches can be connected with or without EOL resistor/s. These inputs can also serve as indicators for monitoring
24 hour zones, panic buttons etc (see section 3.5). TMPR 2 input can serve as Zone #9 (see section 3.2.1).
12 LINE – Telephone Line Connector
The telephone line is used both for dialing and receiving remote programming calls. If the telephone line is used by other accessories, it is recommended that the system will
be the first to connect to the line.
13 SET – Telephone Sets Connector
2 outputs for connecting appliances, such as answering machine and fax (facsimile). All
devices will be disconnected by the system when it requires the telephone line.
14 AUD IN, AUD OUT, CONT – Microphone and Voice Unit Connectors
CONT is used for controlling voice unit (VU-20) and microphone (MIC-200). Only one device can be connected at a time.
AUD IN is used for 2 purposes: receiving information from audio resources and sending SMS messages with SMS-100.
HUNTER-PRO 896 Installation Guide 11
15 TRANSMITTER – Connection to Long-Range Radio/GSM-200 Cellular
Transmitter/SMS-100
TRANSMITTER is a connector to PIMA long-range radio transmitters TRU/TRV-100, to
the cellular transmitter GSM-200 (see section. 3.13) and to the SMS-100 - PSTN SMS card.
NOTES:
GSM-200 and SMS-100 cannot be installed simultaneously.
To connect long-range transmitters other than PIMA’s use TX-1000 adaptor.
16 KEYPAD – Keypad Connector
Connector to installer/technician keypad (using the TC-3 cable).
17 Expansion Cards Connector
Connector to OUT-1000 and EXP-PRO expansion cards (refer to sections 3.3.1 and
3.9).
18 SERIAL Connector
The SERIAL connector is used for connecting to TCP/IP communication and
GSM-200 transmitter.
19 JP5, JP10 – Siren Type Jumpers
Set the sirens type (in conjunction with JP6). See the table below.
20 JP6– Siren Power Source
Set the power source of the sirens. See section 3.6 for connecting various types of sirens and bells.
Jumpers state table:
Jumper State
Siren Type J5 J10 J6 Power
AC (unregulated) current (Speaker)
Up to 200mA
DC low current (Piazzo)
Up to 200mA
DC high current (Bell)
Up to 1A
12 HUNTER-PRO 896 Installation Guide
1.4 Outputs and Output Types
HUNTER-PRO 896 brings a new concept, with regard to triggering the outputs: instead of direct alarm-to-output single linkage, i.e., a certain alarm type can trigger only one
PCB output, new functions called “output types” will determine the response to events in the system.
Some output types have names that resemble the zone type that generates them, like Fire, Burglary & Anti-mask. Some have event driven names such as Zone opened,
Tamper (opened) & Buzzer. The advantage is in the fact that responding is fully programmed, i.e., you determine which PCB output will be triggered.
Each PCB output can be programmed to be triggered by a certain output type. It can
only be triggered by one output type, yet, as many as all the PCB outputs can be triggered by the same output type. Since that, all the PCB outputs triggered by the
same output type will be tripped when that output type is triggered, regardless the zone it came from. So, for example, if you program the RELAY, ON/OFF and ALRM
outputs to be triggered by the Fire output type, when this output type is triggered, all the 3 outputs will be tripped.
Example for the use of output type:
If the PCB relay output is linked to ‘Panic’ output type, than triggering the ‘Panic’
output type will trip the relay output. If zone 5 is programmed as panic zone type, than alarm generated by zone 5 will trip the relay (that applies to a keypad panic alarm
[pressing simultaneously and ] too).
HUNTER-PRO 896 Installation Guide 13
2 PARTITIONING
2.1 Introduction
A partition is a sub-division of the system, made of several zones. By using partitions
you can control user access authorizations. Each partition can be controlled by one or more keypads and a user can be given a code that will allow him to control only a
specific partition in a specified time frame.
HUNTER-PRO 896 can have up to 16 partitions and up to 8 keypads (i.e. monitored
keypads).
2.2 Examples
2.2.1 Example A
Figure 2 - Using partitions (example A)
In example A, Keypad 1 controls all 3 partitions and is used by all 3 Users.
2.2.1.1 Common Application for Example A
Offices/
Partitions
Entrance
11
76
15
5
10 12
432
14139
1 8
16
A floor in an office building has 16
rooms. Each room is programmed as a partition and can have different
User Codes/Remote Controls/TAGs
for arming/disarming the system. A single keypad is installed at the
entrance of the hallway.
In this case, the keypad will display the entire system’s status.
A detector located next to the entrance and allocated to all partitions protects the entrance, as soon as all partitions are armed. This zone will be unarmed as soon as the
first partition is disarmed.
Partition 1Partition 2
Partition 3
Keypad 1
Users 1, 2, 3
14 HUNTER-PRO 896 Installation Guide
2.2.2 Example B
......
.....
.....
Figure 3 - implementing partitions - examples B
The system is divided into X partitions, each partition is controlled by its keypad/s
(defined in “System Installation/Keypads Setup/Partitions for RKD”). A User Code has access authorizations based on partition/s (defined in User Menu/Code/User
Codes/Partitioning), e.g. User 1 can only activate Partition 1 & 5. That implies for arming/disarming too.
A keypad displays the status of its authorized partition’s only.
2.2.2.1 Common Application for Example B
An office building is divided into 4 departments with different entrances and different working hours:
Each department has its keypad: Keypad 1 controls partition 1 (store/storage floor), Keypad 2 controls partition 2 (production floor), Keypad 3 controls partition 3
(management floor), Keypad 4 controls partition 4 (storage/store floor)
Employees (i.e. users) can have access only to their partition, or to several partitions.
Control Panels (up to 8 monitored)
Partitions (up to 16)
Users (up to 96)
Control Panel 1
Partition 1
User 1
Control Panel 2 Control Panel 3
User 2 User 3
Partition 2 Partition 3
Keypad 3:
Management
floor
Keypad 2:
Production
floor
Keypad 1:
Storage (part of
1st floor)
Keypad 4: Store
(part of 1st floor)
Part. 3
Part. 2
Part. 1Part. 4
HUNTER-PRO 896 Installation Guide 15
2.2.3 Example C
......
......
.....
Figure 4 - implementing partitions - example C
A private home has 3 floors: the first floor is defined as Partition 1, the second floor is partition 2, and the third floor is partition 3.
Keypad 1 controls all 3 partitions (& displays their status)
Keypad 2 controls partition 2 only (& displays its status only)
Keypad 3 controls partition 3 only (& displays its status only)
User 1 can control partitions 1, 2, 3 using keypad 1
User 2 can activate partition 2 with keypads 1, 2
User 3 can activate partition 3 with keypads 1, 3
2.2.3.1 Common Application for Example C
Note: A user can control several partitions using a single code
Control panel 3 Control panel 2Control panel 1
Partition 3Partition 2Partition 1
User 1 User 2 User 3
3rd floor: part. 1
2nd floor: part. 2
1st floor: part. 1
Users can be given different access authorization levels with regard to keypad/floor/partition
16 HUNTER-PRO 896 Installation Guide
3 CONNECTING ZONES & ACCESSORIES
Connect the accessories according to the following diagram and instructions:
TMPR
2
TMPR
1
ON/
OFF
ALARM
KEYPAD
EX
PA
NS
ION
CA
RD
SER
IAL
KEYPAD
TR
AN
SM
IT
U3
Z1
Z2
Z3
Z4
-+
Z5
Z6
Z7
Z8
-+
KEY
-Ext
Int
CN.O
N.C
-SIREN
RELAY
SMOKE
-+
INOUT
F 5A 250VAC
AC
T1
JP
1JP
2JP
4LINESETAUDCONT
INOUT
F6
HUNTER-PRO RSA
1
JP
6
F1
F2
F3
F4
JP5
1JP10
1
F7
(-)
(+)
IN
OUT
10K
¼W
10K
¼W
(-)
(+)
Smoke
Detector
SecuBUS™
Keypads: RXN-400, RXN-410,
RXN-416, RXN-9, or
RXN-200
Expanders: I/O-8, I/O-W
TAMPER or Zone 9
SMOKE
NO
10K ¼W
Tel setMIC orVoice Unit
PSTN(LINE)
U2
10K
¼W
TAMPER
10K ¼W
NC
KEY
KEY Switch
NO
Figure 5 - Connecting Accessories to the Control Panel
3.1 Connecting Zones
IMPORTANT! Disconnect all power supply prior to installation!
3.1.1 Zones Inputs
The system’s default zone protection is without EOL (End Of Line) resistor/s. A Zone
protection can have either one or two EOLs. The detectors’ type and whether they are connected with or without EOL resistors are
set in “Zone Characteristics” (see section 5.3.1). The number of EOL resistors is set to all EOL zones and is programmed in “General Parameters” (section 5.6). For zone
programming refer to sections 5.3 & 5.6.
HUNTER-PRO 896 Installation Guide 17
3.1.2 Connecting a Detector (without EOL resistor)
Connecting NC detector with no EOL resistor is done according to the following diagram. The tamper can be connected in one of two ways:
A. To the TMPR input on the system’s PCB.
B. As a “24 hours” separate zone.
Zone
Com
mon
Com
mon
Tam
per
Zone
+ -
TMPR NC RELAY NC
12V
(+)
for
dete
cto
r’s
voltage
(-)
GN
D
Figure 6 - Connecting DEFENDER PIR without EOL resistor
3.1.3 Connecting a Detector using One EOL Resistor
Connecting NC detector with one EOL resistor is done according to the next diagrams. The tamper needs be connected to the TMPR input on the control panel’s PCB or as a
“24 hours” separate
Note: When connecting NO detector, configure the zone input accordingly (see section
5.3.1).
Connecting EOL resistor to NC DEFENDER PIR Detector
PIR (NC)
10K
¼
W
Zone (-)
+ -TMPR NC RELAY NC
Zone Common
10K ¼W
ZoneCommonCommonTamper
Zone10K
¼
W
10K
¼
W
+ -TMPR NC RELAY NC
One EOL resistor
connected to NC detector
One EOL resistor in serial to
the relay and the tamper
Separate connections for
the relay and the tamper, each with its EOL resistor
18 HUNTER-PRO 896 Installation Guide
Connecting EOL resistor to NO DEFENDER PIR Detector PIR (NO)
10K ¼W
Zone (-)
TA
MP
ER
(N
C)
Zone Common
+ -TMPR NC RELAY NO
10K ¼W
One EOL resistor connected
to NO detector
One EOL resistor in serial to the
relay and the tamper
3.1.4 Connecting a Detector using 2 EOL resistors
Apart from the tamper connection there is no difference whether the detector is NO or NC one. Connecting a detector with two EOL resistors is done according to the next
diagrams.
2 EOL Resistors with DEFENDER PIR (NC or NO) & Tamper (NC)
PIR (NC)
10K ¼W
Zone (-)
TAMPER
(NC)
10K
¼W
+ -
JP 2
JP 1
P IR 1
TAMPER NC RELAY NC
Zone
Common
10K
¼
W
10K
¼
W
2 EOL resistors with an NC
detector and tamper (NC)
2 EOL resistors connected to tamper
(NC) in serial to the relay output
HUNTER-PRO 896 Installation Guide 19
3.2 Connecting Zone Expanders
The HUNTER-PRO 896 has a basic 8 zones configuration. This can be expanded to have more zones and outputs by using different expansion cards and add-on devices.
The following is a brief scan of the zone and outputs expansion options. A detailed installation description is found further on.
EXP-PRO Local expansion card with 8 line zones. These zones will always be
numbered 9-16. See further on page 20.
I/O-8N 8 zones and a relay. It connects to the KEYPAD connections of the
control panel’s PCB. Up to 11 I/O-8N cards can be installed in HUNTER-
PRO 896.
I/O-16N Expansion card with 16 zones and a relay. It connects to the KEYPAD connections of the control panel’s PCB. Up to 5 I/O-16N cards can be
installed in HUNTER-PRO 896.
I/O-WN Wireless expansion card with wireless receiver. The receiver supports 32 wireless zones as well as 24 Key fobs for arming/disarming, send duress
code and control an output.
OUT-1000 Expansion card with 8 outputs for triggering external units. See page 28
for connecting instructions.
I/O-R Expansion card with 8 relays for operating CCTV and spotlights. The
relays can be triggered directly or as a respond to alarm. See more on
page 28.
IMPORTANT! When connecting both line and wireless expanders, the system first numbers the line zones and only than the wireless zones. Within the line expanders, the system first numbers the EXP-PRO expander, if installed.
Only afterwards the other expanders are numbered. The expanders connected through the BUS are numbered in ascending order
according to their ID.
Examples of zone numbering:
One I/O-8N/R card:
If EXP-PRO is installed: is numbered 17-24.
If EXP-PRO is not installed: is numbered 9-16 (when installed, EXP-PRO is
always numbered 9-16).
Two I/O-8N/R cards (16 zones):
If EXP-PRO is installed: are numbered 17-32.
If EXP-PRO is not installed: are numbered 9-24.
11 I/O-8N cards (88 zones):
No EXP-PRO card can be installed! (zone number cannot exceed 96)
Zones will be numbered 9-96: 8 zones onboard and 11 times 8 zones (88) on
each I/O-8N card.
20 HUNTER-PRO 896 Installation Guide
Two I/O-16N cards (32 zones)
Zones are numbered as if two I/O-8N cards are installed, therefore, the zones are
numbered 17-32 if EXP-Pro card is installed, and 9-24 if not.
One I/O-WN card (32 wireless zones):
If any other expansion card is installed, EXP-PRO or I/O-8/16, the I/O-WN zones will
be numbered after all the other zones. For example, If EXP-PRO and 2 I/O-8N cards are installed (24 zones in all, and 32 with the 8 onboard), the I/O-WN zones will be
numbered 33-64.
3.2.1 Tamper #2 Input – Optional zone #9
Tamper #2 input can serve as Zone #9, giving no expander is attached to the system and tamper #2 is disabled in “General Parameters” (see parameter “2”, in General
Parameters First Screen, page 73).
3.3 Connecting Expansion Cards
3.3.1 EXP-PRO
1. Connect the card to the system case, using the 2 supplied screws.
2. Use the supplied flat cable to connect the card to PCB’s JP3 (see the following
drawing)
3. To configure the EXP-PRO, refer to section 5.2.2.1.
R
EXPANSION CARD SERIALKEYBOARDTRANSMIT
U3
U2
C
F5
JP1 JP2 JP4JP3
J1
+V
GND
Z16
Z15
Z14
Z13
+V
GND
Z9
Z10
Z11
Z12
EXP-PROU3A
Control Panel
Figure 7 - Connecting EXP-PRO to the PCB
3.3.2 I/O-8N, I/O-16N, I/O-R
Each card must have an individual ID determined by a dip-switch on it.
No. 1 2 3 4 5 6 7 8 9 10 11
Dip-
switch
Dip-switch table
HUNTER-PRO 896 Installation Guide 21
Notes: Two cards cannot have the same ID.
The cards must be given successive IDs.
The card’s ID determines the numbering of zones connected to it (see next sub-
section).
3.3.2.1 Expanders’ Numbering
Under the HUNTER-PRO 896 configuration system, every 8 zones must have a unique ID, therefore, I/O-16N takes 2 IDs. Here’s an example for numbering few expansion
cards:
Card #1 Card #2 Card #3 Card #4
I/O-8N I/O-16N I/O-8N I/O-16N
ID=1 ID=2 (+3) ID=4 ID=5 (+6)
Note: It is recommended to connect all the accessories (-) to the system’s PCB. That
includes power suppliers, if there are any.
Follow figures 8-11 (in the next pages) for connecting expansion cards. To program the
number of expansion cards refer to section 5.3.
3.3.2.2 I/O-8N
I/O-8N has three LEDs described in the following table:
LED STATUS DESCRIPTION
ON: Card works OK RUN
(Green) OFF: Fault with supplying voltage to card, or with card
BLINKS: Normal operating mode. LED blinks while data transferred
from control panel to card
ON: Communication fault (disconnection)
MASTER
DATA
(Red)
OFF: Communication fault (short)
BLINKS once a
second:
Data fault (expander does not receive communication from
control panel)
FAIL (Red)
BLINKS twice
a second:
Communication fault (check display)
22 HUNTER-PRO 896 Installation Guide
I/O-8N
RELAY RUN
MASTER
DATA
FAIL
1 COM2 3COM4 5 COM6 7 COM 8 +
Dip-switch to set
expanders’ ID
V 1
+V 2 +
3 IN
4 OUT
Control I/O-8
Expander’s
Tamper
1 2
3 4
ON
DIP
NC
C N
O
+
8 zones connection
Power supply
Technician
keypad
Additional
expanders
connections
Parallel
connection
to control
panel
TM
P (-) (+
) (OU
T) (IN
)(-)
(+)
INO
UT
1
2
3
4
1
2
3
4
To external
Tamper
Relay
output
Parallel
connection
Figure 8 - I/O-8N Expansion card
1 V
-
2 V
+
3 4
KEYPAD
-V +V IN OUT
Control panel
BUS
KEYPAD
ID=2
1 V-
2 V+
3
4
I/O8N/16N
or I/OW
RXN-410
ID=1
Figure 9 - Connecting external expansion cards on control panel BUS
KEYPAD
ID=1
BUS
External power
supplier
PS2
EXPANDER
ID=1
-
+
Connecting minus
line () of all units
1 -
V
2 +
V
3 4
KEYPAD
-V +V IN OUT
CONTROL PANEL
Figure 11 - Connecting external expansion cards to control
panel BUS with external power supplier PS-2
HUNTER-PRO 896 Installation Guide 23
I/O-16N
RELAY RUN
MASTER
DATA
FAIL
1 COM 2 3 COM 4 5 COM 6 7 COM 8 +
V 1
+V 2 +
3 IN
4 OUT
הרקב IO8
1 2
3 4
ON
DIP
NC
C N
O
+
16 zones connections
9 COM 10 11 COM12 13 COM14 15 COM 16
TM
P (-) (+
) (OU
T) (IN
)(-)
(+)
INO
UT
1
2
3
4
1
2
3
4
Dip-switch to set
expanders’ ID
Expander’s
Tamper
Power supplier
Technician
keypad
Additional
expanders
connections
Parallel
connection
to control
panel
To external
Tamper
Relay
output
Parallel
connection
I/O-R
RELAYRUN
MASTER
DATA
FAIL
NC C1 O +
V 1
+V 2 +
3 IN
4 OUT
הרקב IO8
1 2
3 4
ON
DIP
+
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
TM
P (-) (+
) (OU
T) (IN
)(-)
(+)
INO
UT
1
2
3
4
1
2
3
4
NCC2 O NCC3 O NC C4 O NC C5 O NC C6 O NC C7 O NCC8 O
Dip-switch to set
expanders’ IDExpander’s
Tamper
Power supplier
Technician
keypad
Additional
expanders
connections
Parallel
connection
to control
panel
To external
Tamper
Dry contact relay outputs
Parallel
connection
3.3.3 I/O-WN
I/O-WN is a wireless receiver integrated with
HUNTER-PRO 896. It enables the connection of
wireless detectors (such as PIR, Reed Switch etc).
See section 3.2 for more details.
I/O-WN connects to the PCB’s KEYPAD connections. See the next drawing and the table that follows:
Red
Red
Red
Green
Green
24 HUNTER-PRO 896 Installation Guide
I/O-WN Control Panel
1 -V -
2 +V +
3 OUT IN
+-
+
HU
NT
ER
-PR
O 8
96
zones
T AMPER
I/O -W
3 41-V 2+V
BUS
OUT
IN
KEYPAD
Figure 12 - Connecting I/O-WN
Note: For further information regarding I/O-WN, refer its guide
3.3.3.1 I/O-WN LEDs
The I/O-WN has 5 LEDs, described in the following table:
Status Description LED
ON: I/O-WN operating and connected to voltage
BLINK: I/O-WN voltage fault
OFF: Fault in I/O-WN device/connection to
voltage
I/O-WN processor operation and
connection to voltage
RUN (Green)
BLINK: Connection OK
ON: Communication failure
OFF: Short in communication wiring
I/O-WN
connection to control panel
DATA
(Red)
BLINK ONCE: Transmission from wireless device
received by I/O-WN
OFF: No transmission received from wireless device
Receiving
transmissions
RX
(Red)
BLINK ONCE: Wireless device identified
OFF: Wireless device not identified (no
reception from wireless device)
Identifying I/O-WN's additional
wireless devices
VALID (Green)
OFF: No failures
ONE LONG BLINK: I/O-WN did not receive a valid
frame from HUNTER-PRO 32
TWO LONG BLINKS: I/O-WN did not receive ACK
from HUNTER-PRO 32
THREE LONG BLINKS: I/O-WN is not programmed
FOUR LONG BLINKS: General/Fatal error. For one
minute no communication from I/O-WN.
Communication failures between
I/O-WN and HUNTER-PRO 32
control panel
FAIL (Red)
HUNTER-PRO 896 Installation Guide 25
3.4 Key & Key fob
Connect a key or Key fob according to the next diagram, with a 10kΩ EOL resistor on the PCB terminal input. The key can be set as momentary or ON/OFF switch. The
default is momentary.
Z8-
+KEY
-S1
SSIR
EN
Co
ntr
ol
Pa
nel
Key
(-)N.O
Figure 13 - Connecting key
3.5 TMPR1, TMPR2: Tamper Switches
In addition to cases and boxes protection, the tampers can be used for panic buttons, sensors (temperature, pressure etc.) with dry contact outputs and more.
Connect the tamper switch between the TMPR1/TMPR2 connections and ground (–). TMPR1 input is connected to the tamper switch onboard the PCB.
A 10kΩ resistor at the terminal input on the PCB provides a short/disconnect indication, since the tamper switches are NC type.
Notes:
1. By default, TMPR1 & TMPR2 inputs are enabled and without EOL (see section 5.6).
2. To use tamper #2 as zone #9, see section 3.2.1.
TMPR
2
TMPR
1
ON/
OFF
ALRM
KEYPAD
-
SMOKE- + OUT
JP5
Z5 Z6 Z7 Z8 - + KEY -
S1 S2
F3
Tamper
switch
Control Panel
IN
F2
Figure 14 - Connecting tamper switch
3.6 Sirens
Three siren types can be connected to the HUNTER-PRO 896 control panel:
1. AC Siren: This is usually a horn or 8Ω speaker that is driven by the control panel’s built-in oscillator.
Note: The AC siren can produce two different tones (frequencies). The tones are
predetermined. To set zone tone see section 5.3.
26 HUNTER-PRO 896 Installation Guide
2. Low current DC Siren: This is usually 200mA piazzo siren. The control panel supplies current only for activation.
3. High current DC Siren: This can be a bell or any other high current device
with internal oscillator. The control panel supplies 3A for activation only.
The sirens outputs are split: JP5 is associated with “Ext.” (external) output; JP10 is
associated with “Int.” (internal) output.
IMPORTANT!
1. Different siren types cannot be connected simultaneously.
2. Activating solely the external siren is disabled.
3.6.1 AC Siren
The siren is connected between the terminal block outputs (Ext. or Int.) and GND (-).
Make sure the siren is not set as DC (see section 5.6.1). Set Jumpers JP5, JP6 & JP10 to short legs 2 and 3 (see Figure 15).
The siren’s sound is produced by a built-in oscillator and programmed in “Zone Responses” menu. When zone type
is programmed, a different siren tone to different zone
types can be set (see section 5.3.2).
S R K O A 1 2 3 H T B L M
+ - - - + - - - + _ - - -
Setting a different
siren tone
In “General Parameters”, set “-“ under “D”. This will set the siren as AC (see section 5.6).
KD1E2EKAB2SMPZTF
-_+-+--------+--
Setting siren type
Siren 1
Siren 2
(-)
Figure 15 - Connecting AC Siren
3.6.2 Low Current DC Siren
The siren is connected between terminal block outputs (Ext. or Int.) and (+).
KD1E2EKAB2SMPZTF
-_+-+--------+--
Set “+“ under “D” in “General Parameters” (see section 5.6.1This will set the siren as DC.
Short JP5 legs 1 & 2 and JP6 2 & 3 (see Figure 16).
HUNTER-PRO 896 Installation Guide 27
SIR
ENS
-+
KEY
-ExtInt
CN.O
N.C
-RELAY
SMOKE DC
Siren 1
(+)
DC
Siren 2
Figure 16 - Connecting low current DC Siren
3.6.3 High Current DC Siren
The siren is connected between terminal block outputs (Ext. or Int.) and (+).
KD1E2EKAB2SMPZTF
-_+-+--------+--
Set “+“ under “D” in “General Parameters” screen (see section 5.6.1) This will set the siren as DC.
Set JP5 & JP10 to short legs 2 & 3 and JP6 to short legs 1 & 2.
SIR
EN
KEYBOARD
-+
KEY
-Ext.
Int.
CN.O
N.C
-RELAY
SMOKE
-+
IN
F4
SIREN 1
SIREN 2
(+)
Bell
Figure 17 - Connecting a high current DC Siren
The following table describes the various siren installation possibilities:
Opt. Siren Type Conditions JP5,
JP10
JP6 Programming
1 Speaker Panel generates
tone. Uses unregulated
voltage.
2-3 2-3 In “General Parameters”
menu, mark “-“ under ‘D’.
2 Low current self-activating bell (up
to 200 ma)
Uses the panel’s regulated voltage
(+V)
1-2 2-3 In “General Parameters” menu, mark “+”under ‘D’.
3 High current self-
activating bell
Uses The panel’s
battery
1-2 1-2 In “General Parameters”
menu, mark “+”under ‘D’.
28 HUNTER-PRO 896 Installation Guide
3.7 Relay Output
The relay can be used for activating external devices (light, CCTV etc.) and is activated response to alarm/fault, when entering relay code in the keypad and via telephone.
To program Relay Code refer to “HUNTER-PRO 896 User Manual”. To program relay trip time see section 5.5.2.
Note: If the relay timer is programmed to zero, the relay is constantly tripped until
relay code is entered or the system is disarmed.
3.8 OUT-1000: Outputs Expansion Card
OUT-1000 is an 8 TTL outputs card, used to activate peripheral devices such as CCTV,
alarm triggered lights, etc. Use the cable to connect the control panel’s JP3 connector to OUT-1000’s JP1 connector. Follow next figure in order to connect the card to the
control panel:
R
EXPANSION CARD SERIALKEYBOARDTRANSMIT
U3
U2
C
F5
JP1 JP2 JP4
GND
GND O
UT8
76
54
32
112V
JP1
JP3
Figure 18 - Connecting OUT-1000 to control panel
Note: OUT-1000 can be connected simultaneously with EXP-PRO by connecting
OUT-1000’s JP2 to EXP-PRO’s JP1 (see OUT-1000 guide for instructions).
3.9 Keypads
Reminder: Up to 8 monitored keypads can be connected simultaneously
Connect the keypad’s wires to the PCB KEYPAD terminals.
IMPORATNT!
The 4 wires used to connect the keypad must totally be separated.
The panel’s power source (-/+) for keypads cannot be used for detectors.
HUNTER-PRO 896 Installation Guide 29
3.9.1 RXN-400 & RXN-410 LCD Keypads
Keypads Control Panel
1 - -
2 + +
3 OUT IN
4 IN OUT
Figure 19 - Connecting 8 LCD keypads to control panel
To set the keypad’s ID:
1) Short JP1 legs 1 & 2 on the keypad (see figure below).
JP1
PROGRAMMING
U1
1
TAMPER
TMPR
TMPR
4
3
2+V
1-V
BUS
TAMPER
(Optional)
Terminal
block
connection
to control
panel
RJ11- Connecting to
the fast programmer
(PRG-22) and local
programming
adaptor LCL-11A
JP1:
Programming
Keypad’s ID
+
-
OUT
IN
Figure 20 - LCD keypad without back cover
2) In the following screen, enter new ID number (1 to 8):
Enter new ID: 1
3) Short JP1 legs 2 & 3 (back to the jumper’s primary state).
4) Repeat the process above for the remaining keypads. Note that each keypad must have a unique ID number and that numbering must be consecutive.
Notes:
1. If keypad supervision is not needed, the number of keypads connected to the
system (see section 5.2.4) and all keypads’ IDs should be set to zero.
2. Up to 8 keypads can be connected to the system, whether they are supervised or
not.
30 HUNTER-PRO 896 Installation Guide
3.10 Telephone Line and Devices
The system should be the first device connected to the telephone line (through the LINE terminals). Other devices (telephone set, answering machine, etc.) need to be
connected to the SET terminals to enable “line snapping”. When alarm occurs, these devices will be disconnected so the system can dial and
receive calls. When calls are over the line will be reconnected to the SET terminals.
TMPR
2
TMPR
1
ON/
OFFALARMOUT
F4
T1
TELEPHONE OUTLET
Co
ntr
ol
Pa
ne
l
LIN
ESET
AUD
CONT
INOUT
Figure 18 - Connecting telephone line to control panel
3.11 VKD-1: Virtual Keypad
VKD-1 is PIMA’s software for creating a virtual LCD keypad and connecting it to any PIMA control panel, locally (via cable) or remotely, via the internet. With VKD-1 you
can view and control the system just as if you use a real LCD keypad connected to the system.
The VKD-1 can operate any PIMA control panel directly from your PC, is easy to install (does not require any special panel settings), and suitable for new and existing PIMA
panels.
Computer
Internet
ROUTER
FIREWALL
Ethernet
ROUTER
FIREWALL
Ethernet
Intruder
Alarm
Panel
VKD-1
SecuBUS
Figure 21 – VKD-1 connections
to PC and control panel
Figure 22 – VKD-1 on desktop
VKD-1 installation guide can be downloaded from our website at: www.pima-alarms.com.
HUNTER-PRO 896 Installation Guide 31
3.12 TRV/TRU-100: Long Range Radio Transmitters
3.12.1 Mounting Guidelines
Following these guidelines will minimize RF interference:
Do not mount the Panel close to a metal wall or ceiling
Make sure you leave enough space for the antenna between the metal box and the
ceiling
Install the antenna at a distance from the Control Panel’s wiring
Mount the antenna after you complete all other installations
Make sure the antenna is not folded and is vertical
Close the HUNTER-PRO 32 metal box when performing transmission tests
3.12.2 Connecting the Transmitter
Note: The TRV/TRU-100 can transmit in 2 frequencies
1. Mount the HUNTER-PRO 896 metal box on the wall
2. Screw the transmitter to the system box. Make sure the screws are tightened; else, the transmitter’s range can be reduced.
3. Connect the antenna to the transmitter. Make sure the antenna is straight.
4. Make sure the 5-pin cable is connected to the transmitter’s Molex (named: “To
the system” on the transmitter’s sticker.)
5. Connect the other end of the 5-pin cable to the male Molex, placed on the
Control Panel’s upper left side (named “Transmitter” on the Control Panel.)
To use the second frequency only:
1. Follow the pervious 1 to 5 instructions, and then:
2. Connect the 2-pin cable to the transmitter’s F2 Molex (named F2 on the transmitter’s
sticker.)
3. Connect the other end of the 2-pin cable to the control panel depends on the
desired transmitter operation:
To constantly work with the second frequency:
Connect it to (-) output on the Control Panel.
To work with 2 frequencies according to event type:
1. Connect it to one of the system’s outputs, such as ALARM or ON/OFF to one of the
PGM outputs: AL/ON/OFF/RELAY.
2. Program these outputs in “Outputs” menu (see section 5.8). The related parameters
need to be programmed in “Communication Configuration” menu (see section 5.4).
32 HUNTER-PRO 896 Installation Guide
4 screws (at the base of the antenna)
Molex for connecting 5-pin cable to
control panel
Molex for connecting 2-pin cable to
activated the second frequency
Connection to program connector
using COMAX
Antenna connector
TRV/TRU-100
Control PanelPC
comax
DPR-44
To
th
e
Syste
mF 2
Pro
gra
m
TRANSMITTER
Figure 23 - Connecting TRV/TRU-100 to control panel
3.13 GSM-200: Cellular Transmitter
Indication LED
Power Connector
Connection toTRANSMITTERconnector on thecontrol panel
Antena
SIM Card socket
Connection toAUDIO IN/OUTterminals on thecontrol panel
IMPORTANT!
To prevent RF interference:
Do not mount the system close to a metal roof or wall Check that there is enough space for the antenna between the system
and ceiling Keep wiring as distant as possible from antenna
Install the antenna only after system installation is done
Make sure the antenna is not folded
HUNTER-PRO 896 Installation Guide 33
3.14 MIC-200: Microphone Unit
1. Connect Mic-200’s Con. output to the control panel’s CONT terminal.
2. Connect Mic-200’s OUT output to the control panel’s AUD IN terminal.
3. Connect MIC-200’s (-) and (+) to the detectors’ power source.
Note: MIC-200 is supplied without wires
JP5
Z5 Z6 Z7 Z8 KEY -S1 S2
F3
F2
TMPR
2
TMPR
1
ON/
OFFALARMOUT
F4
T1
Control
Panel
LINE
SET
AUD
CONT
INOUT
TAMPER to prevent
cover removal
Trimmer
Do Not Touch!
MIC-200- +
Drawing 2- Connecting MIC-200 to control panel
3.1 VU-20: Voice Unit
1. Connect the TR input to the control panel’s CONTROL output.
2. Connect the AUDIO output to the control panel’s AUD IN input (blue wire).
3. Connect the (-) and (+) to the detectors’ power source.
Voice
Unit
VU-20
TR(+)
JP5
Z5 Z6 Z7 Z8 - + KEY -S1 S2
SIREN
F3
F2
TMPR
2
TMPR
1
ON/
OFF
ALARMOUT
F4
T1
yellow
blue
GND(-)
V(+)
red
black
AUDIO
Control Panel
LINE
SET
AUD
CONT
INOUT
Drawing 3 - connecting VU-20 to control panel
3.1 Battery
The HUNTER-PRO 896 has a rechargeable 16V battery. The charging voltage for the
battery is 13.8 V.
3.1.1 Battery Tests
The system performs battery tests Every 5 minutes and when applying power to the system.
Note: If a test fails, the system displays battery fault and responds as programmed in
the faults responses (activating sirens, dialing the Monitoring Station, etc.).
34 HUNTER-PRO 896 Installation Guide
3.1.2 Manual Battery Test
To test the battery and the phone line:
Master code .
If the battery is ok a “Battery OK” message displays. If not, the message is “Low
Battery” and the battery should be replaced.
3.2 Mains
IMPORTANT! Before connecting the power cord to the system, verify that the cord is
disconnected from the mains socket.
Connect the transformer to the AC terminals on the PCB and then to mains.
With an Ohm meter, check for continuity between the grounding point on the control panel, PCB and GND terminal, to the electrical outlet grounding point. The resistance
must be less than 1 Ohm.
Notes:
1. A current limit device, such as circuit breaker, fuse, must be connected in serial to the power cord.
2. Electrical grounding must be connected!
3.3 Initializing the System
Make sure the connections to the system are as described in previous sections.
Connect AC mains power supply.
Connect the backup battery to the fast connection terminals, red wire to (+)
and black wire to (-).
Close the control panel case and verify that the screws do not touch the battery.
Note: If you connect the battery before mains , an AC FAULT will be displayed until
you connect the AC. The AC FAULT will be logged in memory.
Keypad Ver. 1.15
Keypad ID:0
When connecting to mains, the keypad will sound a long beep and display the screen shown on the left.
Starting
Please wait...
Few seconds afterwards the “Please wait” screen
displays.
1 JAN 07 00:00
Clock not set
Drawing 6 - HUNTER-PRO 896 System Display
Then, the fault LED blinks, and a message that the clock is not set is displayed. If faults exist, they will be
displayed one by one.
HUNTER-PRO 896 Installation Guide 35
Note: To turn off the buzzer, press long . In case a new fault occur the buzz returns. Only after all faults are handled, the red LED ceases to blink and the default
display appears.
3.3.1 Setting Time & Date
USER MENU
Choose 1,2...8
Master/User
Code
9
Enter time (HH:MM format) and
Enter Date and then
Notes:
Use and to move the cursor to the left and right.
The user code must be enabled by the installer to set the time.
Another way to access the User Menu: Installer Code
3.4 Faults Display
Faults are displayed according to the various displaying types in the system (see the
user guide for details).
3.4.1 In PIMA Fast Display
The I/O-WN wireless receiver faults:
Indi. Fault
L Low battery of detector
V No signal received from detector on a preset time
F Detector’s tamper is opened
L---------------
-----F------V---
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 2223 24 25 26 27 28 29 30 31 32
Faults display for example: low battery on zone 17, no signal received from zone (detector) 7, zone
#14’s tamper has been opened.
Note: When the display is set to “Fast Display” and a battery/tamper/supervision fault
occurs, the display will automatically be set to “Open Zones Scan”. When faults are all
handled the fast display returns.
36 HUNTER-PRO 896 Installation Guide
3.4.2 In Scan Open Zones Display
The following are example wireless receiver faults:
Display Screen Fault
2 JUL 07 13:10
Wireless Unit
No communication between I/O-WN and the system
1 JUL 07 03:00
W/L Unit Tamper
Wireless unit is opened
5 JUN 07 14:20
FL: Zone 14
Zone (detector) 14’s tamper is opened
5 JUN 07 14:25
LB: Zone 19
Low Battery in zone 19
7 OCT 07 16:32
SV: Zone 35
No supervision on zone 35
W/L Recvr. fail
ENTER/NEXT/END
This fault appears when trying to program the I/O-WN
receiver although the receiver is not installed
3.4.3 Memory Log of Faults
Show:
All Events-09
User Menu
Select 1,2...
MASTER/USER
CODE2 NEXT
Show:
Defaults Only-1NEXT
Show:
Zone Alarms-2NEXT
Show:
Arming/Dis.-3
The memory log has 3 viewing options: 1 - all events, 2- alarms, 3 - arming/disarming.
The top line displays the memory event number (top left) and the time and date in
which the event was registered. The event name is displayed in the bottom line.
3.4.3.1 Examples for wireless faults as displayed in memory log:
Memory Log Fault
1) 5 JUN 07 14:20
W/L Recvr. fail
Wireless receiver or connection to the receiver is faulty
2) 5 JUN 07 14:20
Wireless Z Fault
Detector’s tamper of reed switch are opened. The zone’s name and number will be displayed intermittently
3) 5 JUN 07 14:20
Low Battery - 15
Low battery on zone 15 wireless detector
4) 5 JUN 07 14:20
Supervision - 28
Zone 28 sent no signal for a preset time. The zone’s
name and number will be displayed intermittently
5) 5 JUN 07 14:20
W/L Unit Tamper
Wireless receiver unit is opened
6) 5 JUN 07 14:20
Receiver Jamm.
Wireless receiver channel is jammed
HUNTER-PRO 896 Installation Guide 37
4 PROGRAMMING BASICS
4.1 General
The HUNTER-PRO 896 is supplied with factory default parameters. In most installations
you will have none or few parameters to program, except for user-specific parameters, such as telephone numbers, zone names etc.
4.2 Methods
There are few ways to program the HUNTER-PRO 896:
1. Locally with the PIMA Fast Programmer PRG–896. The PRG-896 can have 7
different programs, each with a preset of parameters. It connects to any LCD keypad.
2. Locally or remotely (via telephone or GSM) with COMAX, PIMA control & communicate software.
3. Directly with the keypad.
4.2.1 Fast Programming with PRG-896
PRG-896 is based on ROM chip. It holds parameters that have been uploaded with
COMAX and then downloaded to a system at a site. PRG-896 can only be programmed with an RXN LCD Keypads. It connects to RJ-11 connector on the keypad PCB. See the
fast programming procedures on section. 5.9.3.
-V
+V
IN
OUT
TMPR
2
TMPR
1
ON/
OFF
ALARM
-S1
S2
CN.O
N.C
-
SIR
EN
RELAY
SMOKE
-+
INOUT
F4
F3
Fast LoadENTER/NEXT/END
RXN-410
KEYBOARD
Control
Panel
KEY
PRG-896
Figure 24 - Connecting LCD Keypad to Control Panel and PRG-896
4.2.2 Local Programming with COMAX
COMAX gives a quick and easy way to upload sets of parameters in the service station
and download them later on at a customer site. Connecting the PC with the COMAX to the control panel is done using LCL-11A adaptor.
38 HUNTER-PRO 896 Installation Guide
COMAX
To PC Serial (RS-232) Port
e.g., COM1, or USB
D-type
9 pin
-V
+V
IN
OUT
TMPR
2
TMPR
1
ON/
OFF
ALARM
JP5
KEY
-S1
S2
CN.O
N.C
-SIR
EN
RELAY
SMOKE
F4
F3
KEYBOARDOUT
IN+
-
Local UploadENTER/NEXT/END
LCL-
11A
RXN-400
A serial-to-USB
adaptor is avialable
Figure 25 - Connecting Keypad to Control Panel and PC with COMAX
4.2.3 Remote Programming with COMAX
You can program the HUNTER-PRO 896 over a telephone line with a PC, PIMA modem (PSTN) and the COMAX software. In addition to programming, you also have access to
the memory log. Please refer to the COMAX User Manual for detailed information.
4.2.4 Programming with a Keypad
HUNTER-PRO 896 has two basic menus: User menu, made of single-press key
commands (the commands are printed above the keypad’s keys), and Installer menu.
SRK12123HTBL
+---_++++---
Drawing 4- Example
for a Zone Status Bar
This is a parameters set display.
(+): The parameter is enabled.
(-): The parameter is disabled.
_ : The current programmed parameter
When the blinking sign _ reaches a letter, the display changes for 3 seconds and
shows the function’s full name and a brief description.
For example:
Parameters screen
Parameter’s description automatically appears for few seconds when curser moved upon parameter
HUNTER-PRO 896 Installation Guide 39
4.2.5 Menu Navigation
Backward/Forward keys. Press these keys to navigate between screens/ options/parameters.
Selection/Conformation keys.
Exit key. Pressing this key exits a current menu without saving/changing it.
Reset/Erase/Change status key (“-” to “+” and vice-versa).
4.3 Default Codes
The system default codes are:
Master Code 5555
Technician Code 1234
4.4 User Menu
There are 3 ways to enter the user menu, where parameters like time, dialer numbers
and codes are programmed:
1. Using Master code: User Menu
Choose 1,2..
MASTER
CODE
9
2. Using enabled (see notes
below) User code: User Menu
Choose 1,2..
USER
CODE
9
3. Using Technician code
(see notes below) TECHNICIAN
CODE0
9
User Menu
Choose 1,2..
Notes:
1. Only enabled user code can access the user menu. Once enabled, entering it will display the User menu. To enable, mark “+” under “M” (User Code>Menu) in
“General Parameters” menu (see section 5.6). As a result, actions such as arming and disarming cannot be activated directly by the user code, but by entering the
user code first and then pushing the desired key. 2. User Code has no authorization to change Master Code.
3. When accessing User menu from within Installer menu, changing codes is disabled.
40 HUNTER-PRO 896 Installation Guide
4.5 Technician Menu
To enter Technician Menu:
MASTER CODE NEXTUser Menu
Choose 1,2..TECHNICIAN CODE
Technician Menu
Choose 1,2..
-OR-
TECHNICIAN CODE
Technician Menu
Choose 1,2..
4.6 Express Programming Menu
To make programming as easy and quick as possible, the HUNTER-PRO 896 has a
special menu, made of a sequence of screens with all the necessary parameters to
initialize the system. This menu is accessed by pressing in technician menu.
Following is a table with the express programming screens and their details
consecutively. Press to save and continue to the next parameter.
Sub-menu Details
Set up time
Set up date
…..
Set up the 4 private dialer numbers. Use the asterisk key for ‘+’, ‘-‘, ‘#’, ‘P’ (one second pause)
Set up entry/exit delay
Set up expanders, local and wireless
Set up number of remote expanders
Set up account #1 phone and radio codes
Set up monitoring station #1 protocol
…..
Set up 4 MS phone numbers. Use the asterisk key for ‘+’, ‘-‘, ‘#’, ‘P’ (one second pause)
Set up the MS1 reports
Set up test time and interval
Set up radio test interval
Set up 4-6 digits installer code (a code must be
entered or an error message will appear)
HUNTER-PRO 896 Installation Guide 41
4.7 The Keypad Keys
Key Functions Page
System installation: expanders, keypads etc. 42
Zones: types, responses, names, partitions etc. 45
Communication: MS1 options, subscribers numbers, communication options, radio report codes etc.
48
Timers: entry/exit delay, outputs times, reports delays, soak test
days etc.
59
General Parameters 62
System Responses: mains fault, battery fault etc. 63
Outputs Configurations 64
Full programming (reset), local and fast download 68
Installer Code change 69
Fast programming 69
Tests 69
4.8 Entering Names, Numbers and Characters
Enter letters and any other character like in a cellular phone.
. , ? ! 1 A B C 2 D E F 3 Cancel
G H I 4 J K L 5 M N O 6 Next char.
P Q R S 7 T U V 8 W X Y Z 9 Prev. char.
( ) / * : - + # Space, 0 Enable/Disable Save
42 HUNTER-PRO 896 Installation Guide
5 PROGRAMMING
5.1 Enabling Enhanced Communication Menu
HUNTER-PRO 896 has an enhanced menu with various communication parameters. By
default, this menu is not enabled. This is because most installations do not require programming these parameters. If you do not have the knowledge required please do
not change the default parameters. To enable access to the enhanced menu, either mark “+” under parameter ‘P’ in the
first “General Parameters” screen (see section 5.6.1) or press long in the first
Communication menu (key #3).
5.2 Key #1: System Installation
Note: From here onwards, though not appeared in drawings, Technician code (default
1234) must first be entered for accessing all technician menus.
Sys Installation
ENTER/NEXT/ENDENTR1
System Installation menu contains parameters such as service provider, expanders,
wireless setup and keypads.
5.2.1 Service Provider and End of Service Date
ENTR1Service Provider
ENTER/NEXT/END9
Sys Installation
ENTER/NEXT/ENDENTR
Service Provider
PIMA El. Systems
Enter the system’s service provider’s details, like name and telephone number. To
display this screen, press long , when the system is disarmed.
Press and set the date in which the service ends. In that date the following 2
messages appears onscreen1 intermittently:
14 MAR 08 12:00
Call Service
14 MAR 08 12:00
Service Provider... .
The messages ceases to appear in next arming or when entering technician code.
5.2.2 Expanders
ENTR1Expanders
ENTER/NEXT/ENDENTRNEXT
Sys Installation
ENTER/NEXT/END
Set the details for the expanders installed in the system.
1 This message appears only if the default service provider has been changed and the
end of service date is set.
HUNTER-PRO 896 Installation Guide 43
5.2.2.1 Local Expanders
XMW
_--
Par. Name Marking “+” means
X Local Expander Local expander EXP-PRO with 8 additional zones is installed
M Not Used -
W Wireless Expand I/O-WN wireless receiver is installed
to save and proceed to next screen.
5.2.2.2 Remote Expanders
Remote Expanders
0 Set the number of remote expanders installed to the system.
Notes:
1. Entering a number bigger than 11 will result in an error message.
2. If an EXP-PRO expander is already installed, only 10 I/O-8N expanders can be
installed.
5.2.3 Wireless Expander
Programming the wireless expander menu is subjunctive to marking “+” under “W” in
the expanders menu (see section 5.2.2.1). If not, an error message appears.
ENTR1Wireless Setup
ENTER/NEXT/ENDENTRNEXT
Sys Installation
ENTER/NEXT/ENDX29
Add Zone?
ENTER/NEXT/ENDENTR
Add Zone? 9
ENTER/NEXT/END.
The first available zone appears. (zone #9 is first, if no expander is installed)
.
Add Zone?
Activate Device. Activate the wireless device and wait for confirmation message:
Device added
Press END. . Up to 32 wireless zones, 24 Key fobs and 24 wireless
keyboards can be handled by the I/O-WN receiver.
IMPORTANT! The wireless zones are numbered only after all other zones, including line
expanders.
44 HUNTER-PRO 896 Installation Guide
5.2.3.1 Deleting a Wireless Zone
ENTR1Wireless Setup
ENTER/NEXT/ENDENTRNEXT
Sys Installation
ENTER/NEXT/ENDX29
Add Zone?
ENTER/NEXT/ENDNEXT
Delete Zone?
ENTER/NEXT/END and enter zone number
Device Deleted
Press END
Delete Zone?
Please Wait...….
5.2.3.2 Supervision Interval
ENTR1Wireless Setup
ENTER/NEXT/ENDENTRNEXT
Sys Installation
ENTER/NEXT/ENDX29
Add Zone?
ENTER/NEXT/ENDBACK
Supervision:
ENTER/NEXT/ENDENTR
Supervision:
Hrs:0 Min.s:0
Set the wireless zones’ interval supervision.
5.2.4 Keypads
ENTR1Keypads Setup
ENTER/NEXT/ENDENTRNEXT X3
Keypads Setup
0
Sys Installation
ENTER/NEXT/END
ENTREnter the number of
installed keypadsPart. For RKD
++++++++++++++++
9
Set the number of keypads connected to the system (8 max.). Giving a different ID to each will indicate the system to supervise them, i.e. monitor their tampers. The IDs
should be given consecutively from #1 to #8.
Note: If monitoring the keypads is not required, the number of keypads should be set
to “0” (Zero)
5.2.5 Keypads’ Partitions
Set which partitions will be controlled by which keypad. Enter a keypad number or
scroll with and and mark “+” to allocate a partition. to save and go
on to next keypad.
For example: if keypad #2 should only control partition
#2, a “+” is to be marked above #2. Part. for RKD 2
-+--------------
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Note: Keypad partitions are available only in partitioned system.
HUNTER-PRO 896 Installation Guide 45
5.2.6 I/O-R Expander Settings
ENTR1IO-R Exp.Setting
ENTER/NEXT/ENDENTRBACK
Sys Installation
ENTER/NEXT/END
Enter the number of
installed I/O-R
expanders
IO-R Exp.Setting
0
Set the number of installed I/O-R (relays) expanders.
5.3 Key #2: Zone Programming
Configure the system’s zones: line, wireless and expansions’ zones.
5.3.1 Zones’ Configurations
2 ENTRZone Configur.
ENTER/NEXT/ENDENTR
Zones
ENTER/NEXT/END
ENTRBurglary
Zone 1 1
BOFHHIDTEPDESS
---+++-----+++ 1
Zone characteristicsZone type
Zone name Programmed
zone no.
Zone number
Enter zone
number
Set the zones’ type (i.e. Burglary, Panic, Fire).
5.3.1.1 Zone Type
These are the HUNTER-PRO 896’s zone types:
BURGLARY (called Alarm in other PIMA systems), PANIC, FIRE, DURESS/HOLD-UP, MEDICAL, ANTI-MASK, SPECIAL BURGLARY 1, SPECIAL BURGLARY 2, SILENT PANIC,
SPECIAL FIRE.
Press a number or to go to a zone. Use to change zone type.
The next table describes the zone characteristics:
Par. Para. Full
Name
Enabling (marking “+”) this parameter means
B Bypassed
Permanently
The zone is permanently bypassed
0 Normally Open An NO detector is connected in this zone
F 24 Hour Zone Zone is armed around the clock, regardless if the system is
armed or not.
H Active in Home 1 Zone is armed in Home 1 mode
H Active in Home 2 Zone is armed in Home 2 mode
I Entry Delay Exit/Entry delayed zone. It’s possible to select one of two pre-programmed delay
times using the “T” parameter in this menu.
Zones ENTER/NEXT/END
ENTR29
46 HUNTER-PRO 896 Installation Guide
Par. Para. Full Name
Enabling (marking “+”) this parameter means
D Zone Follower This zone will not trigger the alarm if opened during the Entry/Exit delay.
T Second Delay
Time
If marked “+” in addition to the “I” parameter in this menu,
then entry delay time will be set according to “Time 2” (refer to section 5.5)
E EOL Resistores Zone is protected by EOL resistor/s. For determining if system uses one EOL or two, refer to “General Parameters”
in section 5.6.
P Conditioned Zone This zone will trigger the alarm only when other “conditioned” zone is opened within the “Cond. Zone Time.”
It is possible to select more than 2 zones.
D Double Knock Zone activates alarm only after two successive pulses occur
in the duration of time set in Timers Menu (possible for more than two zones.)
E User Bypass Zone can be bypassed by user (this is to restrict users from
bypassing crucial zones like panic)
5.3.2 Zone Responses
2 ENTR ENTRNEXTZones
ENTER/NEXT/END
Zone Response
ENTER/NEXT/END
Burglary
ENTER/NEXT/ENDENTR
SSLTBM
ENTER/NEXT/END
Zone Responses
The six parameters defining the zone responses are:
Par. Description Enabling (marking “+”) this parameter means…
S Activate Siren Alarm from a zone will activate the sirens
S Ext. SRN in OFF Alarm from a zone will activate external siren when the
system is disarmed (OFF)
L No Daytime MS No alarm report is sent to the MS when the system is
disarmed
T Dif. Siren Tone Different siren tone (not applicable with DC siren)
B Automatic Bypass A zone will automatically be bypassed if 3 alarms occur in it
consecutively
M Activate Audio Alarm from a zone will activate the audio device2 (VU-20 or MIC-200)
2 Together with enabling “V” in Communication menu (section 5.4.4), for VU-20 only
HUNTER-PRO 896 Installation Guide 47
5.3.2.1 Zone Sensitivity
Sensitiv.(X50mS)
8
Set the zones’ sensitivity in milliseconds. Sensitivity means, the time a zone has to be opened to trigger an alarm. The number entered is multiplied
by 50. In the example screen, entering 8 means a sensitivity of 8 times 50, i.e. 400 ms.
The sensitivity menu appears after pressing in zone responses menu.
5.3.3 Zone Name
2 ENTR ENTRNEXTZones
ENTER/NEXT/END
Zone Name
ENTER/NEXT/END
Zone Number: 1
X2
Set the zones’ names. A name can have up to 13 characters.
5.3.4 Partitioning
2 ENTR ENTRNEXT x3Zones
ENTER/NEXT/END
Partitioning
ENTER/NEXT/END
Set the partitions to which the zones are allocated.
Setting the partitions along with setting the keypads’ partitions determines the nature of the system (i.e. Split
System/ Partitioned System). Marking “+” allocates a zone to a corresponding partition.
Part. For Zone1
+---_-----------
Drawing 6 - Allocating
zones to a partition
For more details on partitions, refer to chapter 2.
5.3.5 Partitions Names
2 ENTR ENTRNEXT x4Zones
ENTER/NEXT/END
Partition Name
ENTER/NEXT/END
Partition1 Name
Partition 1
The partition’s name will appear on every allocated keypad. To enable the displaying of partitions:
5 ENTRDisplay Type:
Show Part NameBACK
Enter
Master
Code
Note: Partitions names can only be displayed in partitioned keypads
48 HUNTER-PRO 896 Installation Guide
5.3.6 Copy Zone
2 ENTR ENTRBACKZones
ENTER/NEXT/END
Copy Zone
ENTER/NEXT/END
Source Zone: 7
Target: 9 To 32Example TCP
+++ENTR
Copy zone is a very useful installation feature, in which some or all features of one
zone can be copied to other zone/s. Once you finish programming this “Source” zone, you can choose “Target” (consecutive) one or more zones and copy its type,
characteristics and partitions (see table next sub-section). This enables you to finish installation much faster, by not having to configure each zone separately.
To copy to a single target zone, the target “from” & “to” zone numbers should be the same.
5.3.6.1 Copying Options
Par. Marking “+” means…
T Copy the zone type
C Copy the zone characteristics
P Copy the zone allocated partitions
To copy, . If ok, a 5 seconds countdown is performed and the next screen is
displayed:
Finish Coping!
Press END.
5.4 Key #3: Communication Parameters
Communication menu contains the parameters for the Monitoring Station.
5.4.1 Monitoring Station 1 Options
5.4.1.1 MS1 Protocol
3 ENTR ENTRCommunication
ENTER/NEXT/END
MS 1 Options
ENTER/NEXT/END
MS 1 Protocol
0 230 T=0A
B
Set the MS1 PSTN protocol. A & B determine the PSTN protocol (see the matching columns in code table, section 7.4) and T determines the radio station number (which
is given by the MS).
Notes:
1. MS 1 is programmed to ContactID format by default.
2. If no Radio receiver is not installed, do not change the default T=0 parameter.
HUNTER-PRO 896 Installation Guide 49
5.4.1.2 MS1 Report Parameters
A A 1 2 P F D M O L T W I R
+ + + + + + + + + + + + + + 1
Set the type of events to be reported to MS1.
Par. Alarm\Event
A Alarms
A Anti-Mask
1 Special Burglary 1
2 Special Burglary 2
P Panic
F Fire
D Duress/Hold-up
M Medical
O Open/Close by Phone (PSTN)
L Failures
T Periodic Tests
W Smart Remote Test: When the system is armed, 2 rings and hang
up triggers the system to dial to the MS and send a TEST event
I Technician Code Entered: a report sent to MS when technician
code is entered
R Send Open/Close events by radio
To save, .
5.4.1.3 Test Time and Interval
Test Time:00:00
Interval:24 Hrs
Set time and interval to send test events to the MS. When leaving the test time 00:00,
the system will ignore it and act according to the interval time only. When changing it
to any other time, the system will act according to both test time and the interval (e.g. if you set Test time to 23:00 and Interval to 3 Hrs, then test reports will be sent every
3 hours and everyday at 23:00. If you leave the time 00:00 and set the interval to 168, then the reports will be sent once a week).
The interval time starts when connecting the system to power.
.
5.4.1.4 Radio Test Interval
Radio Tst. Inter
Hrs:24 Min.s:0
Set the radio test interval. See the previous sub-section for how-to. .
50 HUNTER-PRO 896 Installation Guide
5.4.1.5 ID Account Addition
If the account number is made of 6 digits, the first two should be set in this screen.
5.4.2 Account Numbers
3 ENTR ENTRCommunication
ENTER/NEXT/END
Account No.
ENTER/NEXT/END NEXT
Set the PSTN and Radio account numbers. There can only be 16 accounts, one for each partition.
ENTRAcouont.No 1
Ph:0000 Rd:0000
Acouont.No 16
Ph:0000 Rd:0000
RadioTelephone
If all the accounts are the same, program only one account. (open/close events
will be sent without the account number)
If the account number is set to 0000 no reports will be sent to the MS.
An un-partitioned system will send reports from account #1 only.
5.4.3 Phone Numbers
ENTR NEXT
ENTR ENTR
Communication
ENTER/NEXT/END
Phone Numbers
ENTER/NEXT/END
MS Phone 1<Del=# Phone 4<Delete=#
X23
….
Set MS1 telephone numbers (4 max.). If the system is set to Double Report, then
telephone numbers #1 & #2 are allocated to MS1, and telephone numbers #3 & #4 to
MS2. To save, .
Note: If the MS answers a call from #1, the system will not dial the others. If not, the
system will call #2 etc. The number of call attempts is 8.
5.4.4 Communication Options
3 ENTR ENTRNEXT X3Communication
ENTER/NEXT/END
Commun. Options
ENTER/NEXT/END
P T L L T A V D R P O S D
+ - - - + - - - + - + - -
Set the Communication Options such as telephone line, line test, answering machine and split account numbers. To enable a feature: mark “+”;
To disable: mark “-“.
HUNTER-PRO 896 Installation Guide 51
Par. Description Enabling this parameter means…
P Connected T.Line A telephone line is connected to the system
T No Dia. tone chck The system dials without checking for a dial tone (in
case the system connected via switch-board or the line is not clear)
L Line Test in ON The system tests the phone line (once a minute) when it is armed
L Line Test in OFF The system tests the phone line (once a minute) when
it is disarmed
T Tone Dial “+” For DTMF
“-“ For Pulse
A Answer. Machine If answering or fax machine are attached to the
phone line, the system snaps incoming call following a sequence of two rings, hang-up, 10 seconds pause
and a ring.
Note: Set the answering machine to pick calls after more than 2 rings.
V Voice Unit VU-20 voice unit is connected to the system.
D Download Disable Downloading parameters from COMAX via modem is
disabled. To temporarily allow it, enter Master code
and X2 (only valid for two minutes.)
R Rem. Disarm Disab The option of remotely disarming the system by the telephone is disabled.
P Pre Alarm Report The system sends a report when Entry Delay starts.
O Tst Rprt in OFF Test reports are sent when the system is disarmed.
S Split Account No. When reporting to 2 MSs (with different account
numbers), account #1 will be reported to MS1 and #2 to MS2. Assigning account number per partition is
disabled.
D Disarm after Al. The system will report an open event occurring immediately after alarm, even when the open/close
parameter is disabled (in MS1 options menu).
5.4.4.1 Number of Rings
No. of Rings 10
Set the number of rings before the system picks up an incoming call. To manually
answer, Master code X2
52 HUNTER-PRO 896 Installation Guide
5.4.4.2 ACK Waiting Time
Ack Wait Time:
PSTN:20 GSM:30
Set ACK time (the time in seconds which the panel waits for MS handshake signal). If no ACK received a communication error appears. HUNTER-PRO 896 allows different
ACK waiting times for PSTN and GSM max. waiting time: 60 sec.
5.4.4.3 External Line
External Line
_
Set a pre-number (up to two digits) if the system is connected to a switch-board.
5.4.4.4 Number of Transmissions
No. of Trans.: 5
Set the number of transmissions of the long-range radio channel for any event that is
not reported via PSTN. .
Note: The duration between the transmissions is 10 seconds and cannot be changed.
5.4.5 Selecting Main Monitoring Station
Set which of the following will be the main monitoring station (channel) – PSTN, GSM (cellular) or IP network. If the system cannot communicate through the main channel,
it will try to send reports through the other two, while keep trying to call the first.
PGN
+--
Par. Main
P PSTN
G GSM
N IP network (MS1 only)
5.4.6 Report Codes Formats
5.4.6.1 PSTN Report Codes
The system’s default report codes are in ContactID format (which includes PAF &
NPAF). If the FF codes are not changed, reports are Contact ID standards: Burglary,
Fire, etc. To send other codes do as follows: subtract 100 from the event number (in ContactID) and Convert the result to hexadecimal number.
For example: to send “High Temperature” event, no. 158: 158 less 100 is 58. 58 converted to Hex. is 3A. So, by sending the code 3A you report on high temperature (in Contact ID).
The restore code must match the alarm code.
HUNTER-PRO 896 Installation Guide 53
3 ENTR ENTRNEXT X4Communication
ENTER/NEXT/END
Report Codes 4X2
ENTER/NEXT/END
Zones
ENTER/NEXT/ENDENTR
Z1: FF Z2: FF
Z3: FF Z4: FF
The PSTN report codes (4x2) menu and the following Radio menu have 3 sub-menus:
Zones, Zones’ restore and General Reports. A code is a hexadecimal number (and can therefore be made from the digits “0” to “9”
and the letters “A” to “F”). The system’s default code is FF for all zones.
To set a report code:
Use and to go to the event you want to change and key to move
to next screen.
Place the cursor on the event’s code (see code table further)
Push a key to enter a digit and then , as many times as needed, to choose a letter.
5.4.6.2 PSTN & Radio Report Codes Table
Event Code Details
Z1 ,Z2 , ... Z96 Alarm from zone #1, #2 etc.
R1 ,R2 , ... R96 Restore Code from the according zone/s. The report comes after siren time ends or when disarming occurs immediately
after alarm.
ZFL + RESTR Zone fault in EOL zone + Restore code
BYP Zone Bypassed
TM1, TM2 + RESTR TAMPER 1 and/or TAMPER 2 Opened + Restore Code
AC + RESTR Mains voltage (AC) failure + Restore Code
LB + RESTR Low Battery + Restore Code
PF + RESTR Power Failure: Card voltage lower than 9 volts + Restore
Code. Low card voltage indicates AC Fall and Low Battery
PHN + RESTR Telephone Line Fail + Restore Code
PNC Panic code entered
ICODE False code entered
FUS + RESTR Fail-Unsafe State: Detectors’ Voltage Fault + Restore Code
ARM System armed
DISAR System disarmed
TST System tested (manual, automatic, or “wake-up”).
Note: The restore code displays as “RESTR” to the event’s right
54 HUNTER-PRO 896 Installation Guide
IMPORTANT!
The following menus are available only if the enhanced menu is enabled (see
section 5.1).
5.4.7 GSM-200 Transmitter
5.4.7.1 Parameters
3 ENTR ENTRNEXT X6Communication
ENTER/NEXT/END
GSM Transmitter
ENTER/NEXT/END
GSM Settings
ENTER/NEXT/ENDENTR
GRTY
----
Par. Name Mark “+” to indicate that…
G GSM TX Installed GSM-200 transmitter is installed
R Use Radio ID Account Radio Account IDs will be used for GSM reports
T Auto Test Report Reports for auto-tests will be reported via GSM in
addition to PSTN
Y GPRS Encryption The information sent via GSM will be encrypted and sent in GPRS protocol
IMPORTANT!
If a radio transmitter is not connected to the system, ‘T’ should be set to
zero in the “Comm. Format” screen (“T” stands for wireless communication
format). Otherwise, all events will be reported via radio as well!
5.4.7.2 GSM Modes
GSM Settings
ENTER/NEXT/ENDNEXT
GSM Modes
ENTER/NEXT/ENDENTR
GSM-200 Mode 1
Voice Channel
NEXTGSM-200 Mode 1
Data ChannelNEXT
GSM-200 Mode 1
GPRS ChannelNEXT
GSM-200 Mode 1
SMS Channel
Set the GSM-200 transmitter operating modes. The transmitter has 2 modes: Mode 1
for MS1 and mode 2 for MS2 (double report).
Each mode can be set to one of four channels: Voice, Data, GPRS or SMS3.
When setting a mode to data channel, for example, the transmitter waits for data format information and not other.
The Data channel can be used by COMAX for uploading and downloading. To do that, the GSM-200 SIM must have a second phone number.
If both MSs are connected using GPRS, the second channel will be used to report to MS2.
3 GSM-200 and SMS-100 cannot be installed in the same system.
HUNTER-PRO 896 Installation Guide 55
5.4.7.3 GSM Phones
GSM Settings
ENTER/NEXT/ENDNEXT
GSM Phones
ENTER/NEXT/ENDENTR
MS Phone 1<Del=#X2
Set GSM-200 MS1 phone numbers 1 to 4. .
5.4.7.4 GPRS Settings
GSM Settings
ENTER/NEXT/ENDNEXT
GPRS Settings
ENTER/NEXT/ENDENTR
Station IP
0. 0. 0. 0.X3
ENTRStation Port
10001ENTR
Tst intrvl(GPRS)
Min:5 Secnd:0
Set the GPRS mode parameters. These include the MS IP number (should be given by
the MS), the station port (to which the GPRS information is launched) and the GPRS test interval.
Notes:
1. If no specific instruction given by the MS, do not change the port number.
2. To see the transmitter’s version, press long in main screen. The display will
show both the transmitter and the system version4.
5.4.8 SMS Settings
3 ENTR ENTRNEXT X7Communication
ENTER/NEXT/END
SMS Settings
ENTER/NEXT/END
System Name-SMS
Alarm System
Set a name to identify the system in SMS reports. A name can be the customer’s name
or any other. “Alarm System” is the default name.
A demo cell phone SMS message
Notes: The text for the SMS messages is taken from the system’s memory log
For further SMS definitions, refer to section 5.4.13.3
4 If SMS-100 and not GSM-200 is installed, its version will be displayed.
System SMS name
Zone name
Time of alarm/event, as
registered in memory log
Event type and zone no.
Date of alarm/event, as
registered in memory log
56 HUNTER-PRO 896 Installation Guide
5.4.9 Serial Output
3 ENTR ENTRNEXT X8Communication
ENTER/NEXT/END
Serial Output
ENTER/NEXT/END
LNRG
____
Set the serial output use:
Par. Name Marking “+” means the device is…
L Local Monitoring Connected locally using PIMA new local protocol
N Net4pro Connected to PIMA’s PIMAnet server
R Radio Protocol Available only in some panel versions
G GSM-200 Serial Consult your distributer/PIMA
5.4.10 Modem Call Back
3 ENTR ENTRNEXT X9Communication
ENTER/NEXT/END
Modem Call Back
ENTER/NEXT/END
Call Back1<Del=#
Set the modem callback phone numbers. Up to 3 numbers can be programmed.
Note: If callback telephone #1 is set, in any attempt to contact the system over the telephone line, the panel will hang up and call the PC back. This is yet another safety
step to protect the system from unauthorized access
5.4.11 Private Dialer Options
3 ENTR ENTRNEXT X10Communication
ENTER/NEXT/END
Private Dialer
ENTER/NEXT/END
AA12PFDMOL
++++++++-+
Set the private dialer report parameters. Mark “+” under any alarm/event to be sent to
the private dialer. Open/Close events are relevant to SMS only. See next table for details.
Par. Name Par. Name
A Alarms F Fire
A Anti-mask Alarm D Duress
1 Special Burglary 1 M Medical
2 Special Burglary 2 O Open/Close (SMS only)
P Panic L Failures
HUNTER-PRO 896 Installation Guide 57
5.4.12 MS2 Options
3 ENTR ENTRNEXT X11Communication
ENTER/NEXT/END
MS2 Options
ENTER/NEXT/END
AA12PFDMOLTWIR
++++++++++++++.2
MS 2 Protocol
0 0ENTR
Set Monitoring Station #2 options.
5.4.12.1 MS2 Protocol
Set MS2 PSTN protocol. Setting this protocol will indicate the system to report to 2 monitoring stations.
Note: In order to report to two Monitoring Stations with two different account ID numbers, in addition to setting the protocol, mark “+” under parameter “S” (Split Subscriber) in “Communication Options” menu (section 5.4). In this case, Account 1
numbers will be sent to MS1 while Account 2 numbers to MS2.
To disable reporting to MS2, set its protocol to 0, 0.
5.4.12.2 MS2 Report Parameters
Set the parameters the system will report to Monitoring Station 2. All parameters are similar to those of Monitoring Station 1 as described in section 5.4.1 but the radio
option: you cannot report to MS2 via radio.
5.4.13 Advanced Programming
Note: Advanced programming may require professional knowledge in communication protocols. Beware not to change parameters unless you checked it with the cellular
provider first.
3 ENTR ENTRBACKCommunication
ENTER/NEXT/END
Advanced Prog.
ENTER/NEXT/END
Choose Provider
ENTER/NEXT/ENDENTR
Cell. Providers
GSM PROVIDER 1
5.4.13.1 Choose Provider
Set the cellular provider for the GSM SMS service. The system is pre-programmed with
unique parameters to every provider and these should usually not be changed. Up to 5
providers can be programmed. to save.
5.4.13.2 Cellular Provider’s Details
Choose Provider
ENTER/NEXT/ENDNEXT
Cell. Providers
ENTER/NEXT/END
Cell. Providers1
ENTER/NEXT/ENDENTR
...
In the following screens the details needed for the system to contact the cellular
provider’s SMS center are entered. This information should be provided by the cellular
provider. The next screens are:
58 HUNTER-PRO 896 Installation Guide
Screen Information to enter
Provider’s Name 1 Provider’s name according to the previous
menu (sec. 5.3.10)
SMS center phone 1 First provider SMS center phone no.
Provider APN…1 First provider APN no.
Provider APN…1 APN number
User… 1 Username
User 1 Enter User #1 name
Password… 1 Password
Password 1 Enter User #1 password
To program another provider in “Cell. Providers1” screen.
5.4.13.3 PSTN SMS Phones
3 ENTR ENTRBACKCommunication
ENTER/NEXT/END
Advanced Prog.
ENTER/NEXT/END NEXT
PSTN SMS Phone
ENTER/NEXT/END
X2
ENTRSMS Center OUT
ENTRSMS Center IN
Set the details for the SMS-100 card to contact the PSTN provider’s SMS center. The IN
& OUT phone numbers are to be provided by the PSTN provider.
The OUT no. is the SMS center incoming phone no.
The IN no. is the SMS center outgoing phone no.
5.4.13.4 Network Settings
3 ENTR ENTRBACKCommunication
ENTER/NEXT/END
Advanced Prog.
ENTER/NEXT/ENDBACK
Network Settings
ENTER/NEXT/ENDENTR
9
The next screens are:
Screen Information to enter
Station IP The MS computer’s IP no.
Test Interval Enter time in minutes and seconds
Attempts to Fail No. of attempts to contact the MS before “comm. error” appears
HUNTER-PRO 896 Installation Guide 59
5.5 Key #4: Timers, Counters
Set the system’s entry/entry delay times, outputs trip times, faults response times and more.
5.5.1 Entry/Exit Delay
Entry 1 2 Exit
20 20 60
Set the system’s all-zones entry delay 1 and 2 (See section 5.3.1 for determining an entry delay for a zone) and the exit delay. Default entry time is 20 seconds and exit, 60
seconds.
5.5.2 Outputs Trip Times
4 ENTR ENTRNEXT
Timers, Counters
ENTER/NEXT/END
Output Times
ENTER/NEXT/END
Ext. Siren Time
ENTER/NEXT/END
Ext. Siren Time
240 secondsENTR
Set the outputs trip times. The output trip time is the time in which an output remains
triggered.
HUNTER-PRO 896 has three types of output trip times:
1. Output trip time ‘0’: the output is tripped until next system disarming.
2. Output trip time 1-9998: the output trip time in seconds.
3. Output trip time 9999: the output is tripped for as long as an output type (see further) is triggered. For example, one may want to trigger a relay output when
and for long as a fault occurs, e.g. mains fault. As soon as the fault is resolved the output is switched off.
5.5.2.1 Output types and their default times
Following is a table of all output types (see section 1.4) with their default triggering
time. The key presses are with regard to the drawing in section 5.5.2.
Output type Trip time (sec)
- Ext. Siren 240
X1 Int. Siren 240
X2 Burglary 240
X3 Anti-mask 240
X4 Special Burglary 1 240
X5 Special Burglary 2 240
X6 Smoke 240
4 ENTR ENTR Timers , Counters
ENTER / NEXT/ ENDEntry/Exit Delay
ENTER/NEXT/END
9
60 HUNTER-PRO 896 Installation Guide
Output type Trip time (sec)
X7 Fire 240
X8 Special Fire 240
X9 Panic 240
X10 Silent Panic 240
X11 Hold Up 240
X12 Medical 240
X13 Tamper 240
X14 Mains Fault 9999
X15 Low Battery 9999
X16 Phone Fault 9999
X17 Trouble 9999
X18 Zone Bypassed 9999
X19 GSM Fault 9999
X20 Comm. Fault 9999
X21 TAG Activation 240
X22 Door code 5
X23 W/L Remote 5
X24 Test 5
X25 Audio Device 60
X26 Remote control* 60
X27 Zone Open Hold** 0 (min)
* Remote Control time defines the time an output under remote control remains
opened.
** Zone Open Hold time is an energy saving feature: use it to turn off air conditions or
lights at the end of the day. It is a timer that works in conjunction with the ‘Zone Opened’ output type: normally,
a PCB output that is triggered by ‘Zone Opened’ output type is closed as soon as the final zone of the output partitions is closed. But when setting the ‘Zone Open Hold’
time it will remain opened for that time, and only if no movement had been detected by the motion detectors, the PCB output will be closed.
5.5.3 AC Report Delay
4 ENTR
ENTR
NEXT X2Timers, Counters
ENTER/NEXT/END
AC Report Delay
ENTER/NEXT/END
AC Report Delay
240 Minutes
Set the mains (AC) failure report delay time (in minutes). When mains resume the
timer resets. Time range: 0 - 250 minutes. to save.
5.5.4 Phone Report Delay
. Set the phone failure report delay time (in minutes).
HUNTER-PRO 896 Installation Guide 61
5.5.5 Burglary Report Delay
. Report on burglary alarm occurring within entry delay will be delayed for the
period set in this menu. If the system is disarmed during this period, the report will not be sent at all. If the burglary delay or entry delay is over and the system is armed, a
burglary report is sent. This reduces unnecessary reports.
5.5.6 Soak Test Days
. Set the number of days a zone (mostly, a zone that causes false alarms) will
be tested. During this period of time, any events initiated by the zone will neither be reported to MS nor trigger the alarm/private dialer, etc, but will be displayed in the
“Fast display”. The events will only be recorded in the memory log.
Max time is 7 days. After this period of time, the zone will automatically return to
normal operation. If set to “0” the zone returns to normal operation at midnight of the same day.
Note: In PIMA display, the letter “T” indicates a zone undergoing a test.
5.5.7 Double Knock
. Set the Double Knock time (in seconds). Double Knock is a feature used for
reducing false alarms in specified zones. In order for a zone configured as “double knock” to trigger am alarm, it must detect two violations in a predetermined time set in
this screen (see “Zone Programming” section 5.3).
IMPORTANT!
If one of the zones set as Double Knock remains open, alarm will be
triggered in the pre-set time.
5.5.8 Conditioned Zones Time
. Set the time span (in seconds) it takes a conditioned zone to be activated. For
example, if zone 1 and 2 are conditioned together, and only zone 1 is opened, no
alarm will be generated. Only if both zones are opened within a predetermined period of time, set in this screen, an alarm will be generated (see “Zone Programming” section
5.3).
5.5.9 Bypass Limit Time
. Set the time (in minutes) in which a zone remains bypassed before it is
automatically released and becomes armed again. This protects against burglary preparation by bypassing zones before the system is armed.
5.5.10 False Code
. Set the number of allowed false code entries (max 24), before the system
reports the MS, presents “False Code” message and react according to the
configurations in System Responses menu (see “System Responses” , section 5.7).
62 HUNTER-PRO 896 Installation Guide
5.5.11 Inactivity Report
. This feature is an indication if the system has been inactive (not armed) for
the number of days set in this screen. The MS can then call the customer to check this issue.
5.6 Key #5: General Parameters
ENTR5
Gen. Parameters
ENTER/NEXT/END
General parameters are presented in 2 consecutive screens.
5.6.1 General Parameters First Screen
KD1E2EKAB2SMPZTF
--+-+--------+++
Par. Name Marking “+” means…
K State Key Switch (+) Toggle key (On/Off) (-) Momentary key
D DC Siren DC Siren is installed
1 TAMPER 1 Connec. Tamper 1 is connected
E TAMPER 1 - EOL Tamper 1 is protected with EOL
2 TAMPER 2 Connec. (+) Tamper 2 is connected (-) Tamper 2 input serves as Zone #9
E TAMPER 2 - EOL Tamper 2 is EOL protected
K Key-> Home State Arming with a key arms to HOME 1
A Automatic-> HOME Automatic arming arms to HOME 1
B Byps. Zone in Au. All opened zones are bypassed in auto-arming
2 2 EOL Resistors All EOL protected zones have 2 resistor
S Siren beep in ARM When arming the siren will beep once. When disarming with key/remote control the siren will
beep twice.
M User Code-> Menu (+) Entering User code displays User menu
(-) Entering User code arms/disarms
P Advanced Menu Enhanced communication menu is enabled
Z - Not in use
T Byps. Tmpr. in Arm Arming is enabled with faulty tamper
F Byps. Fail in ARM Arming is enabled with system fault
to save and proceed to the second parameters screen.
HUNTER-PRO 896 Installation Guide 63
5.6.2 General Parameters Second Screen
CLDSF12ZERPFCJAO
+-----+---------
Par. Name Marking “+” means…
C Light KP continu All keypad keys light (low) at all time
L Light KP in Alrm All keypads light (high) in alarm
D Light KP in Dely All keypads light (high) in (exit/entry) delay
S Buzzer In Alarm Keypad buzzer buzzes in alarm
F Enable Fast Arm to arm the system.
to arm the system to HOME 1.
to arm the system to HOME 2.
1 Cancel HOME1 Del HOME1 entry delay time is ‘0’
2 Cancel HOME2 Del HOME2 entry delay time is ‘0’
Z Disp. Alrm in ON Alarms are displayed when the system is armed
E Not in use -
R Retrigger Opn.Zn An opened zone does not stop to generate alarms and send reports to the MS until it is closed or the system
is disarmed
P Disp. Armed Part Armed partitions are displayed
F Final door Closing final delayed zone will end exit delay
C Full remote cont Full remote control (including outputs) is enabled
J Report W/L Jamm. Wireless jamming is alerted & reported
A Part. AutoArming Auto-arming by partition ia enable
O Not in use -
5.7 Key #6: System Responses
6 ENTR ENTR
System Response
ENTER/NEXT/END
Mains Fault
ENTER/NEXT/END
SSAL
----
Mutual screen to
all faults/events
Set the system’s responses to 5 faults/events. These are: Mains Fault, Low Battery, Phone Fault, False Code, and Zone Failure/Tamper.
Note: The differentiation of responses between Armed & Disarmed states, as in other
PIMA systems like HUNTER-PRO 32, does not apply to HUNTER-PRO 896.
Par. Name Mark “+” to set the response
S Activate Siren Activate sirens
S Ext. SRN in OFF Activate external siren when system is disarmed
A Act. Burgl Output Activate burglary output type
L No Daytime MS Reporting to MS when system in OFF state is disabled
64 HUNTER-PRO 896 Installation Guide
5.8 Key #7: Outputs Configuration
7 ENTR ENTROutput Configur.
ENTER/NEXT/END
External Siren
ENTER/NEXT/END
ENTR
Part. for OUT
++++++++++++++++
PD
-+ENTR
Output TypeOutput’s partitions
Output’s Polarity
External Siren
External Siren
PCB’s (physical) output
Set the system’s outputs and output type’s configuration. See section 1.4 to distinct
between the two.
The outputs can also be triggered based on the system’s partitions, i.e. be triggered
only by alarms generated in the enabled partitions.
IMPORTANT!
By default, the output types are allocated to the physical outputs, according to the printed outputs names on the PCB. It is not advisable to change these
unless specific installation requirements.
5.8.1 PCB & Expanders Outputs
There are seven outputs on the system’s PCB: Ext. & Int. SIRENS, SMOKE, RELAY,
ON/OFF, ALARM, Audio Ctrl. The expanders' outputs are also set in this menu.
7 ENTR
Output Configur.
ENTER/NEXT/END
External Siren
ENTER/NEXT/END
p
Press PCB/Expanders Output
X1 Internal Siren
X2 RELAY
X3 SMOKE (reset detectors)
X4 ON/OFF
X5 ALARM
X6 Audio Control
X7 OUT-1000 Outputs
X8 I/O-R Outputs
X9 I/O-8 Outputs
5.8.2 Output Types
Following, is a table of all output types by their order in the menu and the relation to
the PCB outputs. To clarify, the process of programming is as follows:
Pick the output to be programmed pick an output type set the
output partition/s set the output polarity (see how further)
HUNTER-PRO 896 Installation Guide 65
Output type What triggers the PCB output?
External Siren Alarms from a zone programmed to trigger the external
siren output type
Internal Siren Alarms from a zone programmed to trigger the internal siren output type
Burglary Alarms from ‘Burglary’ zone type5
Anti-Mask Alarms from ‘Anti-Mask’ zone type
Special Burglary 1 Alarms from ‘Special Burglary 1’ zone type
Special Burglary 2 Alarms from ‘Special Burglary 2’ zone type
Burglary - All Types All alarms from ‘Burglary’, ‘Special Burglary 1’ and ‘Special Burglary 2’ zone types
Fire Alarms from ‘Fire’ zone type
Special Fire 1 Alarms from ‘Special Fire 1’ zone type
Panic Alarms from ‘Panic’ zone type, or keypad panic code (
+ )
Silent Panic Alarms from ‘Silent Panic’ zone type
Hold-Up (Duress) Alarms from ‘Hold-Up (Duress)’ zone type, or keypad hold-
up code
Medical Alarms from ‘Medical’ zone type
Alarms - All Types All the alarms from all the zones
Audio Control Activating audio (MIC-200) or voice unit (VU-20)
Zone Open Opening a zone
Zone Bypassed Bypassing a zone
Smoke Detector Power
Resetting Smoke detectors
Tamper Tamper switch opened
Trouble (zone) Zone troubled
Buzzer Keypad buzzer activated
Armed Arming the system
Installer Program Entering installer code
General Fault System general fault
MAINS Fault Mains fault
Low Battery Low battery fault
Phone Fault Phone Fault
GSM Fault GSM fault
Communication Fault Failing to communicate with the MS
Not In Use -
Door Code Entering door code
Wireless Remote Pushing the button in remote control
Test Sending test report
5 All the zone types are programmed by default to activate the external siren in response to alarm. To change this, see section 5.3.2.
66 HUNTER-PRO 896 Installation Guide
Output type What triggers the PCB output?
Not In Use -
Not In Use -
Remote Control Activating an output by remote call
Not Used -
Station ACK ACK received from the MS*.
* This output type is used as indication that a report sent to the MS has been received. When an alarm from a zone programmed to trigger the “Station ACK” output type
occurs, the PCB output programmed to be triggered by this output type “waits” for the
system to receive ACK. As the ACK is received the output is tripped for 10 seconds (and can switch on bulb etc.).
5.8.3 Output Partitions
Set the outputs partitions (see drawing in section 5.8), i.e. define which partitions are
enabled to activate which output.
5.8.4 Polarity & Activating in Disarm
Set the polarity of the output and whether it will be activated when the system is disarmed (see drawing in section 5.8).
Par. Name Marking “+” means…
P Polarity
<+=Pos.
’+’ The output is disconnected in alarm
‘-‘ The output is switched to negative in alarm (GND)
D Active in Disarm
‘+’ The output is activated when the system is disarmed ‘-‘ The output is activated when the system is armed
5.8.5 ‘Ext. Siren’ and ‘Int. Siren’ Outputs
These 2 PCB outputs distinct, due to the following reasons:
1. They’re both high current outputs.
2. They can trigger any speaker siren.
3. Ext. Siren output can be triggered only when Int. Siren output is. In other words,
activating sirens in HUNTER-PRO 896 can be done in one of three ways: Both internal and External, internal only, no siren.
Note: It is advisable not to associate only ‘External Siren’ and ‘Internal Siren’ to these two outputs (this is the default programming). You can, however, associate the external and internal output types to any other PCB
output, but then the sirens must be DC sirens (i.e. contain a built-in oscillator).
HUNTER-PRO 896 Installation Guide 67
5.8.6 Expanders’ Outputs
5.8.6.1 OUT-1000
7 ENTR ENTRBACK
ENTR
Output Configur.
ENTER/NEXT/END
OUT-1000 Outputs
ENTER/NEXT/END
Output 1
X3
Output 1
Fire ENTRPart. For OUT 1
++++++++++++++++
PD
-+ 1
ENTR
Expander
Expander’s output No. Output’s output type Output’s partitions
Output’s polarity
Output’s No.
Set OUT-1000 (8 outputs expansion card) outputs. Besides the expander output number screen, all other screens match the outputs configuration screens.
5.8.6.2 I/O-R
Configure I/O-R 32 outputs. I/O-R is programmed the same as OUT-1000.
5.8.6.3 I/O-8N
Configure I/O-8N 8 outputs. I/O-8N is programmed the same as OUT-1000.
5.8.7 Examples for Output Programming
1. Programming ON/OFF output:
7 ENTR ENTRNEXT
ENTR
Output Configur.
ENTER/NEXT/END
ON/OFF Output
ENTER/NEXT/END X4
Part. For OUT 1
+++----++---+++
PD
-+ENTR
Pick an output
Set output typeEnable partitions to
activate the output typeSet output’s polarity& active in disarm
ON/OFF Output
Armed
The procedure is as follows: you first pick a physical output. Then you determine what output type will trigger it. In this case, the default output type is ‘Armed’, so when the
system is armed, this output is triggered. Then you determine from within which partition/s this output can be triggered. Then you set the rest.
2. Set ALARM output to “follow open zone” zone type. As a result, when a zone of this type is opened, the ALARM output is triggered:
7 ENTR ENTRNEXT
ENTR
Output Configur.
ENTER/NEXT/END
ALARM Output
ENTER/NEXT/ENDX5
Part. For OUT 1
+++----++---+++
PD
-+ENTR
Set output typeEnable partitions to
activate the output typeSet output’s polarity
& active in disarmON/OFF Output
Zone Open
68 HUNTER-PRO 896 Installation Guide
3. Set output 4 on OUT-1000 to trigger Internal Siren output type in alarm:
7 ENTR ENTR
NEXT ENTR
Output Configur.
ENTER/NEXT/END
OUT-1000 Outputs
ENTER/NEXT/END
Output 4
X3Output 4
Internal Siren ENTRPart. For OUT 1
++++++++++++++++
PD
-+ 1ENTR
Pick output No. 4 Set output’s output type Set output’s partitions
Set output’s polarity & active in disarm
Output’s No.
NEXT X3
5.9 Key #8: Full Programming
5.9.1 System Default
Initialize the system to factory defaults.
8 ENTR ENTR
Full Programming
ENTER/NEXT/END
System Defaults
ENTER/NEXT/END
Are You Sure?
ENTER/NEXT/END. to confirm.
When system initialization is executed:
Defaulting 25
Please Wait.... A countdown from 25 to
zero ends with this message:
Syst.Defaulted
Press END.
5.9.2 Local Download
8 ENTR ENTRNEXT
Full Programming
ENTER/NEXT/END
Local Download
ENTER/NEXT/END
Use this menu to program HUNTER-PRO 896 with the COMAX upload/download software. COMAX runs on a local computer that connects to the system using LCL-11A
adaptor and the keypad (see section 4.1 for connecting with LCL-11A and the COMAX
User Guide). Pressing enters the system to standby state, waiting to receive data.
Immediately press ‘Local’ icon in COMAX to start the process. Wait until “Connected” message is displayed on the COMAX status bar. You can now start
programming.
HUNTER-PRO 896 Installation Guide 69
5.9.3 Fast Load
8 ENTR ENTRBACKFull Programming
ENTER/NEXT/END
Fast Load
ENTER/NEXT/END
Full
Select Prog. 1-7- OR - NEXT
Communication
Select Prog. 1-71 ... 7
Set the options for the PRG-896 fast programmer. HUNTER-PRO 896 has 2 loading options: full 7 different programs or only the communication parameters.
Reminder: PRG-896 is programmed with COMAX software.
5.10 Key #9: Installer Code
ENTR9Installer Code
ENTER/NEXT/END
Installer Code
****** (4-6)
Set/change the Installer code. A code is 4 - 6 digits long.
IMPORTANT!
If the Installer code starts with zero (0) the code is locked and cannot be reset, in case of power loss. This is another precautious measure against
intruders. If this happens, please contact PIMA support team.
5.11 Asterisk Key *: Express Programming Menu
ENTR
*
Installer Code
ENTER/NEXT/END
Hour
00:00
For details, refer to section 4.6.
5.12 Key #0: Tests
Test menu has 9 sub-menus for testing the system’s line and wireless zones, the
outputs, and communication.
5.12.1 Walk-Test
0 ENTR ENTR
Tests
ENTER/NEXT/END
Walk-Test
ENTER/NEXT/END
Tested 0 of 9
Test all the line and wireless zones in the system. To perform a test, trigger detectors that need to be tested. During the test, the display shows the number of tested
detectors out of the overall number of the detectors. The memory log keeps record of the test, including the number of zones triggered.
When the tests are over, . If all zones were tested:
Untested Zones:
All Zones Tested
70 HUNTER-PRO 896 Installation Guide
If not, the system displays the names of the zones not tested, in the following order:
Untested Zones:
UT:Zone 12
Untested Zones:
UT: Living Room
Untested Zones:
++++++++++++++++
Untested Zones:
Burglary
ENTR ENTR
Zone No. Zone Name Zone’s Partitions
Zone Type This test is very useful for testing the system at the end of installation.
5.12.2 Single Zone Test
0 ENTR ENTR
Tests
ENTER/NEXT/END
Single Zone Test
ENTER/NEXT/END
NEXT
Single Zone Te32
ZONE 32Press zone no. and ENTR
This test checks a single detector, line or wireless. To test a zone, press the designated
zone number. The first 8 zones are the outputs on the PCB and are named “on board
zone”. Pressing displays the zone’s name, partition and type.
The process of testing a wireless zone is the same. The detector’s RSSI level is
displayed in response to receiving a transmission (see next section on how to test a wireless zone). All other screens match.
5.12.3 Wireless Test
0 ENTR ENTRNEXT
Tests
ENTER/NEXT/END
Wireless Test
ENTER/NEXT/END
Wait for Trans.
Zone 19 19
RSSI=3 (3=MAX)
X2
Zone Name Zone Number
RSSI level:
1= Weak
2= Medium
3= Excellent
Trigger a wireless
detector. A series of
beeps will be produced by
the keypad buzzer, once a
transmission received RSSI: Received SignalStrength Indication
This is a wireless detector test. The purpose of the test is to check the reception level of wireless detectors installed in the system. A transmission from a detector will be
displayed on the screen, showing the detector’s RSSI, and be registered in the memory log. This test is useful for finding the best location for wireless detectors and their
optimal regularity.
5.12.4 Set Soak Zone
0 ENTR ENTRNEXT
Tests
ENTER/NEXT/END
Set Soak Zone
ENTER/NEXT/ENDX3
Zone Number: 1
Entr-Conf #-RstENTR
Soak Zone
Zone 1 -1
HUNTER-PRO 896 Installation Guide 71
Set a zone to be soaked (tested). When a zone/detector is suspected of causing false alarms, it can be configured to be in a test mode. A test can last up to 7 days (to set
the number of soak days, refer to section 5.5.6) All events from a tested zone will neither trigger the alarm, nor be reported to MS.
However, they will be registered in the memory log.
When the programmed time for the soak test is over, the zone will automatically return
to normal operation.
To turn a zone from soak to normal mode, in the zone number screen.
5.12.5 Outputs Test
0 ENTR ENTRNEXT
Tests
ENTER/NEXT/END
Outputs Test
ENTER/NEXT/ENDX4
ENTR
Outputs Test
External Siren
Exit=END
This feature lets you to test directly every output connected to the system - local and
remote. Pressing triggers the output for 10 seconds. Pressing ends the test.
Testing the outputs has a great advantage - it allows the installer to define between
connection problems and programming faults: if a device does not work properly but is
triggered by the output test, than the problem lays with programming (or the device itself) and not connection.
On the other hand, failing to trigger the external siren (for example) through the output test, indicates a connection or other-than-programming problem.
These are the outputs test screens by their order:
Output Key Presses Details
External Siren
Onboard output
Internal Siren
Onboard output
Relay X2
Onboard output
Smoke Output X3
Onboard output
On/OFF Output X4
Onboard output
ALARM Output X5
Onboard output
Audio Contrl
Out X4
Onboard output
OUT-1000 Outputs
X3 to trigger one of
OUT-1000 8 outputs
Exp IO-R
Outputs X2 to trigger one of
I/O-R 32 outputs
Exp IO-8 Outputs
to trigger one of the
I/O-8’s cards
72 HUNTER-PRO 896 Installation Guide
5.12.6 Test MS Dialer
0 ENTR ENTRBACK X4
Tests
ENTER/NEXT/END
Test MS Dialer
ENTER/NEXT/END
Test MS Dialer
Select T. No. 1-4
Test the Monitoring Station’s PSTN numbers. Pressing will dial the MS phone #1,
pressing will do so for phone #2, and so on.
Note: The MS PSTN and radio test screens have a feature to help you overcome
missing information/installation: if, while trying to perform a test, a data is missing, like
a phone number or a protocol, an error message is displayed asking you to press . After pressing the key, the required menu will automatically be displayed.
For example:
Set Ph. Connect!
Press END
. This error message occurs when trying to test the
MS radio without programming the account number first. Pressing transfers the
menu to
Commun. Options
ENTER/NEXT/END
screen in “Communication” menu.
5.12.7 Test MS GSM
0 ENTR ENTRBACK X3
Tests
ENTER/NEXT/END
Test MS GSM
ENTER/NEXT/END
Test MS GSM
Select T. No. 1-4
Test the MS GSM phone numbers. Refer to previous section for instructions. If the
GSM-200 receiver is not installed, an error message appears
Set GSM Install.
Press END
5.12.8 Test MS Radio
0 ENTR ENTRBACK X2
Tests
ENTER/NEXT/END
Test MS Radio
ENTER/NEXT/END
Please Wait..
Test the long range radio transmitter, TRV/TRU-100. Pressing will send a transmission event test to the MS. No ACK from the MS should be received in this test.
See previous note in case radio related data is missing in the system.
HUNTER-PRO 896 Installation Guide 73
5.12.9 GSM Signal Strength
0 ENTR ENTRBACK X2
Tests
ENTER/NEXT/END
GSM Sig. Strength
ENTER/NEXT/END
GSM Sig.Strength
_________..
Strong signal indicator _
The stronger the reception the more indicators appearWeak signal indicator .
_
The GSM signal strength indication is like the one in a cell phone. If reception is weak
(more dots than squares appear) you need to relocate the GSM receiver.
5.12.10 Network Statistics
L:T0 R0
G:T0 R0
This screen gives information regarding the network and GPRS connections. The top
line shows the PIMAnet network and the bottom shows the GPRS. The numbers are the packets sent and received.
When the ‘L’ and ‘R’ values in each line match or close, the connection is OK. The numbers can be reset in coordination with the MS.
5.13 How to Locate Expanders’ Zones
EN TR5
A ll Zon es : 2 7
Z ON E 27EN TR
D is pl ay Typ e
A ll Zone s
E n te r
M a s te r
C o d e
NEX T X 3
Al l Zone s: 27
Wi r el es s Exp a nd .EN TR ...
HUNTER-PRO 896’s “All Zones” display type gives details on every zone programmed in the system and allows the technician to quickly locate it.
74 HUNTER-PRO 896 Installation Guide
6 REMOTE CONTROL VIA TOUCH-TONE
TELEPHONE
HUNTER-PRO 896 can be remote-controlled via any touch-tone telephone, including
cellular. The system can be controlled in one of two options:
Mode A: Basic commands, including arming and disarming (the default mode).
Mode B: Full control, including all the outputs
Note: The entire chapter applies both when you call the system and vice verse
6.1 Mode A
1. Dial the telephone number the system is connected to.
2. Wait for confirmation tone (a long tone followed with two beeps)
3. Enter Master Code
4. Wait for status tone:
Continuous: The system is disarmed
Beeps: The system is armed
Note: The system will not respond to commands while playing the confirmation tone.
It is important to wait until the confirmation tone is over before pushing any telephone
key.
5. Push a key according to the next table. The system confirms the command with two short beeps.
The following table includes system’s commands by telephone keys:
key Function
Stop external siren and dialer. The dialer will not dial to any more numbers
Arm the system
Disarm the system
Arm the system to “Home 1” mode
Switch the (PCB) relay ON
Switch the (PCB) relay OFF
Arm the system to “Home 2” mode
Listen in for one minute (only available with MIC-200). To extend listen in time (in
one minute), push again as needed.
While the system and the remote telephone are communicating with each other, the following message will display on all connected keypads: “Other keypad in use”.
HUNTER-PRO 896 Installation Guide 75
If the system does not receive any command for a period of 60 seconds, it shall disconnect and return to normal mode. The system will remain in standby (displaying
“Other keypad in use” on all the keypads) for another 60 seconds, before returning to normal mode.
6.1.1 Example for arming the system via telephone:
Dial the system’s phone no. the system answers wait for confirmation tone to
end enter Main code wait for command confirmation tone to end
6.2 Mode B
Repeat steps 1-4 in previous section to establish communication with the system.
To activate an output: & the corresponding command from the following
tables.
To deactivate an output: & the corresponding command from the following
tables.
System PCB Outputs OUT-1000
* 01 Arm 11 External Siren 21 Output no. 1
# 01 Disarm 12 Internal Siren 22 Output no. 2
* 04 Arm to ‘Home 1’ 13 Relay 23 Output no. 3
* 07 Arm to ‘Home 2’ 14 SMOKE detector 24 Output no. 4
* 08 Listen-in 15 ON/OFF 25 Output no. 5
* 00 Telephone
16 ALARM
26 Output no. 6
17 Audio Ctrl 27 Output no. 7
28 Output no. 8
I/O-8N Expanders
31 Expander no. 1 37 Expander no. 7
32 Expander no. 2 38 Expander no. 8
33 Expander no. 3 39 Expander no. 9
34 Expander no. 4 40 Expander no. 10
35 Expander no. 5 41 Expander no. 11
36 Expander no. 6
76 HUNTER-PRO 896 Installation Guide
I/O-R expander #1 I/O-R expander #2
51 Output #1 55 Output #5 59 Output #1 63 Output #5
52 Output #2 56 Output #6 60 Output #2 64 Output #6
53 Output #3 57 Output #7 61 Output #3 65 Output #7
54 Output #4 58 Output #8 62 Output #4 66 Output #8
I/O-R expander #3 I/O-R expander #4
67 Output #1 71 Output #5 75 Output #1 79 Output #5
68 Output #2 72 Output #6 76 Output #2 80 Output #6
69 Output #3 73 Output #7 77 Output #3 81 Output #7
70 Output #4 74 Output #8 78 Output #4 82 Output #8
Send system status via SMS to private dialer
91 Phone #1 93 Phone # 3
92 Phone #2 94 Phone # 4
6.2.1 Examples for Mode B
Activate external siren output: Dial wait for confirmation tone Enter Main code Wait for command confirmation
tone to end Push *11
Switch off output #5: Dial wait for confirmation tone Enter Main code Wait for command confirmation
tone to end Push #25
HUNTER-PRO 896 Installation Guide 77
7 TROUBLESHOOTING
This chapter describes failures displayed on the keypad, various problems that may be encountered due to improper programming, and options for troubleshooting failures
that might occur due to incorrect installation and/or programming.
7.1 Restoring Master & Installer Codes
In case both codes are not available:
Disconnect mains.
Disconnect battery.
Wait 10 seconds and reconnect battery.
Wait for “Clock Not Set” to display.
Enter the default Master code (5555).
Set a new Master code (the former code is not valid anymore).
Connect mains.
Set time & date.
Note: After connecting power, the system enables access to the menu using the
default code (5555) for 30 seconds only. If access does not occur during this time, the
process needs to be repeated
The process is also useful for Installer code (Default code 1234), with the
exception of a code that starts with zero. In this case the code cannot be reset.
7.2 Faults Displayed on the LCD
In case of a fault, the red fault LED on the keypad blinks. The description of the fault
appears on the first line of the LCD Keypad at the right side. The faults are:
Fault Description & Repair
Clock Not Set Appears on first operation and when reconnecting after
power/battery failure. Set time & date
Low Battery 1. Make sure the battery fuse is intact. 2. Check battery charge voltage.
3. Wait 24 hours for recharging and recheck. 4. If the message stays on, replace battery.
Low Voltage Low PCB DC charge. Mostly occurs after long mains power failure that causes the battery to get drained. Programming is
unavailable when this fault occurs. To repair: connect to mains and replace battery if required.
Mains Fault No mains power. If other appliances around work, check the
system’s electric socket and fuse. If ok connect mains and the PCB AC fuse
78 HUNTER-PRO 896 Installation Guide
Fault Description & Repair
TAMPER 1 Tamper 1 is open
TAMPER 2 Tamper 2 is open
Zone Fault 1. In EOL protected zones: F - Cut, S - Short 2. In detectors wires: F L- Cut, S H- - Short
3. In wireless detectors: detector’s tamper is open
KEYPAD NOT
CONNECTED
No communication between the keypad and the PCB. Check the
following:
1. Disconnection between PCB’s “OUT” and keypad. 2. Keypad’s voltage supply is lower than 13v. (verify that no more
than 8 keypads are connected) 3. Keypad fault - replace it.
4. PCB fault - replace it.
Phone Line Fault No dial tone is indicated. The system checks the phone line
constantly.
Note: Disconnect any appliance connected to the phone line during checking
Keypad X Fault 1. Check keypad X ID (if possible)
2. Check keypad X wiring 3. If ID and wiring is OK, disconnect the keypad and connect it as
close as possible (50 cm max.) to the system box. If the keypad
still out-of-order, consult PIMA support
Detec. Vol. Fault Check for short in the detectors’ wires
Expander X Fault Expander’s X comm. or vol. connection fault
Expander X Tamper Expander’s X tamper is open
Keypad X Tamper Keypad’s X tamper is open
Other Keypad in use When more than one keypad is connected and one is being
programmed, the others will have this message on screen. This message appears also when the system is being programmed
from a different source such as remote programming via computer and telephone.
GSM-200 faults
GSM Unit Fault Connection problem or fault in GSM-200 receiver
GSM Comm. Fault GSM-200 to MS1 connection problem
GSM Link Fault Low reception or jamming in GSM channel
SIM Card Fault No SIM card installed in GSM-200 or SIM card fault
GSM Com. Fault 2 GSM-200 to MS2 connection problem
Note: For further information on GSM-200 refer to the GSM-200 guide
Communication faults
W/L Unit Tamper Wireless receiver’s tamper is opened or out-of-order. Check that its cover is closed
Note: For further information on I/O-WN, refer to the I/O-WN guide
HUNTER-PRO 896 Installation Guide 79
Check Keypad number
Keypad’s ID does not match programming
MS. Com. Fault Failure to communicate with the MS including in test mode. This fault appears if the HUNTER-PRO communicator cannot
transfer reports to MS. Possible reasons are incompatible protocol or phone line failure.
Check the following: The telephone line is properly connected to the LINE
terminal blocks.
In Communication menu (section. 5.4) the “P” for telephone is programmed with “+”.
At least one MS telephone number is programmed. Telephone account ID for MS is other than 0.
Comm. format is compatible with the one used in the MS. Correct telephone numbers have been entered.
If the system is connected to an extension of a private switchboard a prefix has been programmed.
SMS Com. Failure Communication failure between the system and the provider’s SMS center
Install SMS Unit SMS-100 unit is not installed
Network Fault Communication failure between the system and the PIMAnet card.
IO-R X Fault Fault in I/O-R relay expander
IO-R X Tamper I/O-R tamper is open
IO-R X Voltage Low voltage to I/O-R
Wireless Jamming Radio channel is jammed
IO-8 X Voltage Low voltage to I/O-8
Supervision: Wireless detector ceased to send reports to the system
Note: If more than one fault occurs simultaneously they will be displayed one by one
7.3 Additional Faults
7.3.1 MS Comm. Fault
The system has preset to test all aspects of communication to MS:
Technician code. All testing process will be displayed on the keypad.
7.3.2 MS Radio Fault
Make sure that:
1. The wiring between system and radio receiver is ok.
2. Radio account no. is other than ‘0’.
3. Comm. format is compatible with the one used in the MS
4. The receiver’s antenna is intact, not bended and is attached vertically.
5. If the antenna is installed on a separate surface, check its wires.
80 HUNTER-PRO 896 Installation Guide
7.3.3 Private Dialer Fault
Make sure that:
1. The telephone line is properly connected to the LINE terminal blocks.
2. At least one private telephone number is programmed.
3. Correct telephone numbers have been entered
4. In Communication menu (section. 5.4) the “P” for telephone is programmed with “+”.
5. In Communication/Private Dialer menu the parameters are programmed.
6. If the system is connected to an extension of a private switchboard a prefix has
been programmed.
Note: Disarming immediately after alarm will stop the dialer. To test the dialer, arm
the system and wait for dialing
7.3.4 Incoming Calls Fault
If the system does not receive calls, make sure that:
1. In Communication menu (section. 5.4) the “P” for telephone is programmed
with “+”.
2. The programmed number of rings exceeds its limit.
3. The telephone line is properly connected to the LINE terminal blocks.
7.3.5 Tamper
TAMPER 1: Tamper 1 is open.
TAMPER 2: Tamper 2 is open.
7.3.6 Auto-Arming & Auto-Arming by Partition Faults
Make sure that:
1. Auto-arming start time is programmed (see HUNTER-PRO 896 User guide).
2. System time is correct.
3. The desired partition is programmed as so.
7.3.7 Opening Zone Causes no Alarm
Make sure that:
1. The zone is neither temporarily nor permanently bypassed.
2. The zone is programmed to the desired responses (sirens, relay, etc.)
3. The zone is programmed to only one partition.
4. The detectors are in order and installed correctly.
5. Zone sensitivity is correct.
6. Zone conditioning is correct.
7. Zone no. of pulses is correct.
8. Zone is not programmed as soak zone.
HUNTER-PRO 896 Installation Guide 81
7.4 MS Report Formats & Codes
7.4.1 Pulse Formats
Name Rate (pps) ACK (Hz) Error Control ID Event A B
3 - 1 162 1
3 - 2 163 1
4 - 1 162 129 Double Round
4 - 2 163 129
3 - 1 162 65
3 - 2 163 65
4 - 1 162 193
1400
Checksum
4 - 2 163 193
3 - 1 162 17
3 - 2 163 17
4 - 1 162 145 Double Round
4 - 2 163 145
3 - 1 162 81
3 - 2 163 81
4 - 1 162 209
Ademco
Slow 10
2300
Checksum
4 - 2 163 209
3 - 1 170 1
3 - 2 171 1
4 - 1 170 129 Double Round
4 - 2 171 129
3 - 1 170 65
3 - 2 171 65
4 - 1 170 193
1400
Checksum
4 - 2 171 193
3 - 1 170 17
3 - 2 171 17
4 - 1 170 145 Double Round
4 - 2 171 145
3 - 1 170 81
3 - 2 171 81
4 - 1 170 209
Silent
Knight
Fast
14
2300
Checksum
4 - 2 171 209
3 - 1 208 1
3 - 2 209 1
4 - 1 208 129 Double Round
4 - 2 209 129
3 - 1 208 65
3 - 2 209 65
4 - 1 208 193
Franklin 20 1400
Checksum
4 - 2 209 193
3 - 1 208 17
3 - 2 209 17
4 - 1 208 145
Franklin 20 2300
Double Round
4 - 2 209 145
82 HUNTER-PRO 896 Installation Guide
Name Rate (pps) ACK (Hz) Error Control ID Event A B
3 - 1 208 81
3 - 2 209 81
4 - 1 208 209 Checksum
4 - 2 209 209
3 - 1 82 17
3 - 2 83 17
4 - 1 82 145
Universal
High-
Speed
20 2300 Double Round
4 - 2 83 145
3 - 1 82 81
3 - 2 83 81
4 - 1 82 209
Universal
High-
Speed
20 2300 Checksum
4 - 2 83 209
3 - 1 120 1
3 - 2 121 1
4 - 1 120 129 Double Round
4 - 2 121 129
3 - 1 120 65
3 - 2 121 65
4 - 1 120 193
Radionics 40 1400
Checksum
4 - 2 121 193
3 - 1 120 17
3 - 2 121 17
4 - 1 120 145 Double Round
4 - 2 121 145
3 - 1 120 81
3 - 2 121 81
4 - 1 120 209
Radionics 40 2300
Checksum
4 - 2 121 209
7.4.2 TMF Formats
Name Rate (pps) ACK (Hz) Error Control ID Event A B
3 - 1 0 2
3 - 2 1 2
4 - 1 0 130 Double Round
4 - 2 1 130
3 - 1 0 66
3 - 2 1 66
4 - 1 0 194
DTMF 1400
Checksum
4 - 2 1 194
3 - 1 0 18
3 - 2 1 18
4 - 1 0 146
2300
Double Round
4 - 2 1 146
HUNTER-PRO 896 Installation Guide 83
Name Rate (pps) ACK (Hz) Error Control ID Event A B
3 - 1 0 82
3 - 2 1 82
4 - 1 0 210 Checksum
4 - 2 1 210
Contact
ID 0 230
1400 0 5 PAF™
2300
0 21
NPAF™ Call PIMA
support
P/N 4410251 XX, en, B (Nov-2007)