Peace of mind through reliable pressure transducers GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM Each series of Greystone low pressure transducers comes standard with an ABS enclosure. These transducers feature high level outputs, environmental protection, and temperature compensation. FEATURES: • Jumper selectable 2 wire current and 3 wire voltage outputs standard • 24 Vac/dc power supply standard • Six variable jumper selectable pressure range’s, WC and PA. • Functional weather resistant ABS Enclosure • Available options include LCD display and mounted static probe LOW PRESSURE TRANSDUCERS LP1 Series Shown above c/w LCD and mounted static probe options
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Peace of mind through reliable
pressure transducers
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
Each series of Greystone low pressure transducers comes standard with an ABS enclosure. These transducers feature high level outputs, environmental protection, and temperature compensation.
FEATURES: • Jumper selectable 2 wire current and
3 wire voltage outputs standard • 24 Vac/dc power supply standard • Six variable jumper selectable pressure
range’s, WC and PA. • Functional weather resistant ABS Enclosure • Available options include LCD display and
mounted static probe
LOW PRESSURETRANSDUCERS
LP1 Series
Shown above c/w LCD and mounted static probe options
SPECIFICATIONS: LP1 Series Pressure Ranges See ordering information
Calibration Accuracy
Measurement Type Differential (two port)
Response Time 1 mS maximum
Stability <±1% F.S.O. per year
Thermal Effects <±3% over compensated range
Compensated Range 10 – 50°C (50 – 122°F)
Over Pressure 20 psi or 2 x range (whichever is greater)
Media Compatibility Limited only to those that will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM, and neoprene seals. Typically dry air or inert gas but liquid is allowed.
Input Voltage Effect Negligible over specified operating range
Protection Circuitry Reverse voltage protected and output limited
Output Signal 4 – 20 mA (2-wire), 0 – 5 Vdc or 0 – 10 Vdc (3-wire)
Current Output Drive Capability 400 ohms maximum @ 24 Vdc
Voltage Output Drive Capability 2 Kohms minimum for 0-5 Vdc signal 10 Kohms minimum for 0-10 Vdc signal
Zero Adjustment Pushbutton auto-zero
Wiring Connections Screw terminal block (14 to 22 AWG)
Pressure Connections Barbed ports for 0.170” ID flexible tubing
Conduit Connection Access hole for 1/2” NPT conduit or cable gland
Optional LCD 3½ digit, 0.4” digit height
Enclosure High Impact Black ABS, plenum rated with optional gasket 116 mm W x 84 mm H x 53 mm D (4.55” x 3.3” x 2.1” )
± 1% F.S.O. (LP1A/B Series)
• HVAC/VAV • Process Control • Air Flow Monitoring
• Drop Across Air Filters • Hydraulic Pressures • Pneumatic Pressures
APPLICATIONS:
GREYSTONE ENERGY SYSTEMS INC.
LP1 c/w LCD LP1 c/w LCD & Mounted static probe
ISO 9001:2000
JUMPER SELECTABLE LP1 SERIES: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC.
The LP1 Low Pressure Transmitter can be used to measure positive, negative or differential pressure in the ranges of 1”wc to 12”wc (200 TO 2000Pa). The piezoresistive sensor is ideal for monitoring the pressure for air or other clean inert gas and is limited only to those media which will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM and neo-prene seals.
The LP1 features field selectable pressure ranges and output signal types for the most flexible application. Typical HVAC applications include monitoring of filter differential pressure, or VAV applications. The output signal is factory calibrated and temperature compensated for highest startup accuracy and trouble-free operation. Available options include accu-racy’s, LCD and mounted static pressure probes
Please read the installation instructions carefully before commissioning the pressure transmitter. Failure to follow the in-structions may result in product damage. A qualified technician must install this device.
The LP1 Pressure Transmitter mounts on any surface using the two holes provided on the base of the unit. Make sure there is enough space around the unit to connect the pressure tubing without kinking and avoid locations where severe vibrations or excessive moisture are present. Mount the enclosure with two user-supplied screws but do not over-tighten.
The unit may be mounted in any position but typically is installed on a vertical surface with the pressure ports on the right and the cable entrance on the left. The enclosure has a standard ½” conduit opening and may be installed with either con-duit and a conduit coupler or a cable gland type fitting. Do not use in an explosive or hazardous environment, with combustible or flammable gasses, as safety or emergency stop devices or in any other application where failure of the product could result in personal injury. Use electrostatic discharge precautions during installation and do not exceed the device ratings.
Example: LCD, ±0.5” to 0-4” wc, Static Pressure Probe
S
CODE
S
Options
Mounted Static Pressure Probe
Typical Model Number
ISO 9001:2000
Greystone Energy Systems Inc. is one of North America’s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems.
We have conscientiously established a worldwide reputation as an industry leader by maintaining leading- edge design technology, prompt technical support, and
a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9001 certified,
assuring our customers of consistent product reliability.
150 English Drive, Moncton, NB, Canada E1E 4G7 e-mail: [email protected] Toll-free: (800) 561-5611 (North America Only) Tel.: (506) 853-3057 Fax: (506) 853-6014 web site: www.greystoneenergy.com
DIMENSIONS:
84 mm (3.3")
116 mm (4.55") 53 mm (2.1")
OPTIONS:
Pitot Tube HFO & HSO Series
Differential Pressure Probe SSS Series
The SS series DP probe is used for sensing velocity pressure in the duct. Available in 4”, 6”, 8” & 10” lengths. Kits are available that come complete with pneumatic tubing.
The HFO and HSO series are used to sense velocity pressure or static pressure respectively. Available in 6” length. Kits are available for differential and static that are complete with pneumatic tubing.
ABS enclosure dimensions
Static Probe Option The S option is a high accuracy static tube. It is available as an option on the LP1 Series low pressure transducer.
ISO 9001:2000
Peace of mind through reliable
pressure transducers
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
High strength corrosive resistant stainless steel sensor construction. No silicone oil, no welds, no internal “O” rings. Compatible with a wide range of liquids and gases. Suitable for high shock and vibration applications.
FEATURES: Excellent long-term stability and high accuracy Backlit LCD for display of differential or gauge pressure Jumper selectable LCD backlight for low power consumption applications Four switch selectable pressure ranges Jumper selectable output types, 4-20 mA, 0-5 and 0-10 Vdc NEMA 4 (IP54) enclosure Pushbutton and remote zeroing terminal Uni-directional or bi-directional pressure range selection switch High / low port swap switch to solve incorrect plumbing for differential Normal or slow surge damping switch to prevent false alarms and reduce noise Output polarity reverse switch
LIQUID PRESSURETRANSDUCERS
WP-D & WP-G Series
SPECIFICATIONS: Media compatibility 17-4 PH stainless steel
Input power 15 to 30 Vdc / 24 Vac nominal
Supply Current @ 24 Vdc (max)
100 mA with LCD backlight 35 mA LCD backlight disabled
Output 3-wire transmitter; user selectable 4-20mA, 0-5V and 0-10V
5, 10, 25 and 50 PSI ranges10, 20, 50 and 100 PSI ranges 20, 40, 100 and 200 PSI ranges 50, 100, 250 and 500 PSI ranges 0.5, 1.0, 2.5 and 5.0 Bar 0.75, 1.50, 3.75 and 7.50 Bar 1, 2, 5 and 10 Bar 3, 6, 15, and 30 Bar50, 100, 250 and 500 kPa 75, 150, 375 and 750 kPa 100, 200, 500 and 1000 kPa 300, 600, 1500 and 3000 kPa
The Wet-Wet pressure transmitter is designed with dual sensors that enable it to accept high differential pressures in the ranges of 5PSI to 500PSI. All models can handle overload pressure 2X the maximum full scale range and burst pressure is 5X the maximum full scale range.
The gauge pressure transmitter is designed with a single sensor that enables it to accept high pressures in the ranges of 5PSI to 500PSI. All models can handle overload pressure 2X the maximum full scale range and burst pressure is 5X the maximum full scale range.
Features include field selectable pressure ranges and output signal types for the most flexi-ble applications. Typical HVAC applications include monitoring of water differential and gage pressure. The output signal is factory calibrated and temperature compensated for the high-est start-up accuracy.
ISO 9001:2000
Greystone Energy Systems Inc. is one of North America’s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems.
We have conscientiously established a worldwide reputation as an industry leader by maintaining leading- edge design technology, prompt technical support, and
a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9001 certified,
assuring our customers of consistent product reliability.
150 English Drive, Moncton, NB, Canada E1E 4G7 e-mail: [email protected] Tel.: (506) 853-3057 Fax: (506) 853-6014 web site: www.greystoneenergy.com
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
FEATURES: 1/4” NPT NIST traceable calibration Weather resistant for harsh environments Fast response time Capacitance sensing element Ranges 0 through 500 PSIG
(0 through 3400 kPa) Accuracy to ±0.25% FSO
DC inputs, current output Compensated temperature range:
-20°C to 80°C (-4°F to 176°F) Operating temperature range:
-40°C to 127°C (-40°F to 260°F) 17-4PH Stainless Steel has excellent corrosion resistance (comparable to grade 304 stainless)
HVAC Systems Energy Management Systems Steam Pressures Refrigerants and Ammonia Gas Chromatography Paint Spraying Systems
Electronic Pressure Switch Heat Pumps Hydraulic Systems Irrigation Systems Compressor Control Propane
ORDER EXAMPLE:To order a PGS-100A , 0 – 200 PSIG Range, supply voltage of 24 VDC, output of 4-20mA,the following order number would apply: PGS100A14A1A
Greystone Energy Systems Inc. is one of North America’s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems.
We have conscientiously established a worldwide reputation as an industry leader by maintaining leading-edge design
technology, prompt technical support, and a commitment to on-time deliveries. We take pride in our Quality
Management System which is ISO 9001 certified, assuring our customers of consistent product reliability.
Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
PRESSURE RANGES:
PRODUCT DESCRIPTION: PGS100A is a compact gauge pressure transducer complete with a 2 wire 4-20mA output, various pres-sure ranges, 1/4” NPT connection and 2 foot cable for electrical termination.
MEDIA COMPATIBILITY: The PGS100 Series transducers are designed to be used with any gases or liquids compatible with 17-4PH stainless steel. The 17-4PH stainless has excel-lent corrosion resistance. Corrosion tests and serv-ice experience have shown that in all aged conditions it is superior to standard hardenable stainless grades such as 420, 431 and 410 stainless. This corrosion resistance is comparable to 304 stainless. Note it is not recommended for hydrogen applications.
Moisture Proof Connection
SPECIFICATIONS:
Accuracy at Constant Temp. .25% F.S.O
Supply Voltage Minimum supply voltage (VDC) = 9 + 0.02 x (Resistance of receiver plus line). Maximum supply voltage (VDC) = 30 + 0.004 x (Resistance of receiver plus line).
Output 4 to 20 mA
External Load 0 to 800 ohms
Media Compatibility 17 – 4PH stainless steel
Pressure Port 1/4” - 18 NPT External
Operating Temp. Range (sensor) -40°C – 127°C (-40°F–260°F)
Compensated Temp. Range -20°C – 80°C (-4°F – 176°F)
The Greystone air pressure switch is a general purpose airflow proving switch designed for HVAC and Energy Management applications. It may be used to sense positive, negative, or differential air pressure.
FEATURES: The plated housing contains a diaphragm, a calibration spring and a snap-acting SPDT switch. The sample connections located on each side of the diaphragm accept 6.35 mm (0.25”) OD tubing via the integral compression ferrule and nut. An enclosure cover guards against accidental contact with the live switch terminal screws and the set point adjusting screw. The enclosure cover will accept a 12.7 mm (0.5”) conduit connection. Optional pressure ranges and manual resets available.
NRT L/
SPECIFICATIONS:
MODEL AFS-222 AFS-262 AFS-460
Sample Media Air Air Air
Mounting Position Diaphragm in any vertical plane Diaphragm in any vertical plane Diaphragm in any vertical plane
Field Adjustable Range 0.05±, 0.02” w.c. to 12” w.c. 0.05±, 0.02” w.c. to 2” w.c. 0.40±, 0.06” w.c. to 12” w.c.
Switch Differential Progressive, increasing from approx. 0.02± 0.01” w.c. at min. set point, to approx. 0.8” w.c. at max. set point
Progressive, increasing from 0.02± 0.01” w.c. at min. set point to approx. 0.1” w.c. at max. set point
Progressive, increasing from approx. 0.06± 0.01” w.c. at min. set point, to approx. 0.8” w.c. at max. set point