Combat ® Cabinet Heaters +44 (0)121 506 7700 www.rg-inc.com Over 91.5% NET Efficient! n Ideal for industrial and commercial applications n Large range of heat outputs and burner options n Easy installation with a factory fitted bolt-on burner n Durable long life stainless steel combustion chamber n Design flexibility - floor standing, horizontal mounting or external site installation options n Energy saving optimising control provided as standard n All models meet ECA efficiency requirements Quality in Any Language TM 0063
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Combat®
Cabinet Heaters
+44 (0)121 506 7700www.rg-inc.com
Over 91.5% NET Efficient!
n Ideal for industrial and commercial applications
n Large range of heat outputs and burner options
n Easy installation with a factory fitted bolt-on burner
n Durable long life stainless steel combustion chamber
n Design flexibility - floor standing, horizontal mounting or external site installation options
n Energy saving optimising control provided as standard
n all models meet ECa efficiency requirements
Quality in Any LanguageTM 0063
Combat®
Cabinet HeatersTechnical Data PGP ECA (Power Gas) & POP ECA (Pressure Jet Oil) Ranges
Natural Gas (G20) & LPG Propane (G31) Data
Model 15 20 30 40 50 60 70 80 100
maximum Heater Input- [kW] Gross [Btu/h] x [1000]
55.5189.4
73.3250.1
93.2318.0
129.9443.2
162.0552.7
208.0709.7
242.0825.7
275.2939.0
348.51189.1
maximum Heat Output [kW] [Btu/h] x [1000]
47.4161.7
61.2208.8
78.4267.5
110.2376.0
134.5458.9
177.7606.3
205.3700.5
230.4786.1
293.41001.1
Reduced Gross Input* [kW] [Btu/h] x [1000]
38.9132.7
51.3175.0
65.2222.5
90.9310.2
113.4386.9
145.6496.8
169.4578.0
192.6657.2
244.0832.5
Reduced Output* [kW] [Btu/h] x [1000]
33113
43147
55188
77263
94321
124423
144491
161549
205699
maximum Gas Rate [m³/h] Natural (G20) [ft³/h]
5.3187
7.0247
8.9314
12.4438
15.4544
19.8699
23.1816
26.2925
33.21172
minimum Gas Rate [m³/h] Natural (G20) [ft³/h]
3.8134
5.0177
6.3222
8.8311
11.0388
14.2501
16.5583
18.7660
23.7837
maximum Gas Rate [m³/h] LPG Propane (G31) [kg/h]**
2.093.87
2.765.11
3.516.49
4.899.05
6.1011.29
7.8314.49
9.1116.86
10.3619.18
13.1224.29
minimum Gas Rate [m³/h] LPG Propane (G31) [kg/h]**
'm' Left/Right Hand Return [mm] Fresh air Inlet - Height
457 560 560 560 560
'N' Left/Right Hand Return [mm] Fresh air Inlet - Width
781 781 940 1600 1918
'P' Rear of Heater [mm] To air Outlet Spigot*
401 401 426 96 96
*For models 60 - 100, the circular flue spigot is at the front of the heater with the rectangular air outlet spigot at the rear.
NOTE: External cabinet heaters are designed to be sited externally, with heat ducted into the building. These models are fitted with a special metal rain drip cover and all cabinet joints are silicone sealed to ensure that the heaters are weatherproof.
Dimension Data - External Heaters all dimensions shown in mm.
Combat®
Cabinet Heaters
ControlsEach heater is supplied with the ROBERTS GORDON® NRG Control. This will require on-site wiring.
Burner Options COmBaT® cabinet heaters are fitted with on/off burners as standard. High/Low burners are available as an option on all models, and a fully modulating burner is available as an option on all Natural Gas and LPG fired models. Oil models use class D fuel oil (gas oil) as standard. Burner can be set to operate on other oils such as class C2 fuel oil (kerosene) upon request.
Inlet & Outlet Ducts Where there is a need for the heater to be connected to fresh air or air from an adjacent area for its intake of distribution air, inlet duct connections can be provided. Note: When employing an inlet duct arrangement, there must be adequate provision for the supply of combustion air. Please contact Roberts-Gordon for advice. as standard, each heater is supplied with the specified number of discharge heads for warm air distribution. If a heater is to be attached to ducting for warm air distribution, then an outlet duct spigot can be provided. In these instances, advice should be sought to ensure that proposed duct systems are compatible with the heater.
Oil Connection KitFor all oil fired heaters, an oil line connection kit comprising of a gate valve, spring operated fire valve, oil filter and connecting nipples are supplied for installation on site.
Important NoticeThe equipment described in this Data Sheet is suitable for most commercial and industrial heating applications. However, in certain environments, particularly where there is a chlorinated atmosphere (e.g. near degreasing plant or other solvent processes), or a particularly dusty atmosphere, specialist advice should be sought at the design stage. Please consult Roberts-Gordon.
Roberts-Gordon reserves the right to alter product specification details without notice.
Installation Code and Annual Inspections: all installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor con-duct, at a minimum, annual inspections of your ROBERTS GORDON® equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.Further Information: applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service manual.This product is not for residential use.This document is intended to assist licensed professionals in the exercise of their professional judgement.
COmBaT® Cabinet Heaters are high efficiency heaters and are listed on the Enhanced Capital allowance Scheme ‘Energy Technology Product List’. The ETL symbol is a UK registered certification mark of the carbon trust.
Combat®
Cabinet Heaters
Air Outlet & Flue Arrangementsall dimensions shown in mm.
��� ��� ��� ���
������
Vertical and Horizontal Heaters - Free Blowing
Rear
Front
15/20 30 40 50 60/70/80 100
Note: models 15 and 20 are fitted with 9 inch (228.6 mm) diameter discharge heads as standard.
models 30 to 100 are fitted with 14 inch (355.6 mm) diameter discharge heads as standard.
Vertical and Horizontal Heaters - Air Outlet Spigots all dimensions shown in mm.
�� �����
���
�
���
�� �����
���
�
���
�� ����
���
�
���
�
� ��
���
���
�� ��
�
���
� ��
���
�� ��
�
Rear
Front
15/20/30 40 50 60/70/80 100
Model 15/20/30 40 50 60/70/80 100
K – Spigot Width [mm] 648 781 781 940 940
L – Spigot Depth [mm] 476 476 610 1238 1524
Outlet Spigot Dimensions
Roberts-Gordon Europe LimitedUnit a, Kings Hill Business ParkDarlaston Road, WednesburyWest midlands, WS10 7SH UKTelephone: +44 (0)121 506 7700Fax: +44 (0)121 506 7701Service Telephone: +44 (0)121 506 7709Service Fax: +44 (0)121 506 7702E-mail: [email protected]: [email protected]