Top Banner
© GCE Group Date / Name Hospital Central Gas Supply Systems
19

Hospital Central Gas Supply Systems

Jan 17, 2016

Download

Documents

Sutton

Hospital Central Gas Supply Systems. Simplex MMR. - Small cottage hospitals, veterinaries, dentists, third source of supply etc. - Suitable when automatic change over is not a demand - Connections for 3 high pressure hoses - Gaslarm C44 - 27-30 m3/h - CE-marked according to EN737-3. - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

Hospital Central Gas Supply Systems

Page 2: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Small cottage hospitals, veterinaries, dentists, third source of supply etc.

- Suitable when automatic change over is not a demand

- Connections for 3 high pressure hoses

- Gaslarm C44

- 27-30 m3/h

- CE-marked according to EN737-3

Simplex MMR

Page 3: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Small to intermediate sized hospitals, Large hospitals for N20

- (Medical Breathing) O2, Air, N2O, CO2, N2 and Argon.

- 25 Nm3/h (O2), 17 Nm3/h (N2O)

- Gas Cylinders/ Cylinder Bundles

Manifold MC25

Page 4: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- 2-stage control

- Semiautomatic Manifold

- Service without interruption of the gas flow

- Gas Alarm C44

- Slave panels: Gas Alarm C44, Connect from Relays

- CE-marked according to: EN737-3

Manifold MC25

Page 5: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Intermediate to large sized hospitals

- (Medical Breathing) O2, Air, N20

- 90 m3/h (O2)

- Gas Cylinders/ Cylinder Bundles

- CE-marked according to: EN737-3

Manifold MM90 Auto & Semiauto

Page 6: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- LOX backup

- Automatic Change of Operating side, Automatic Manifold

- Service without interruption of the gas flow

Manifold MM90 Auto

Page 7: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- LOX-backup

- Manual Change of Operating side, Semiautomatic Manifold

- Service without interruption of the gas flow

Manifold MM90 Semiauto

Page 8: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- For all medical gases

- Inlet from LOX-tank and from Manifold

- Service and repair without interrupting the flow

- Sometimes one for every building

- Normal operation, use only one regulator, one for backup

- 80 Nm3/h (with dP2<0,3 bar)

- Adjustable outlet pressure (P2=3-7 bar)

- Inlet and outlet 22 mm (Int.)

- CE-marked according to: EN737-3

Stabilizer MC80

Page 9: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Same basic design and outer appearance as MC80 Stabilizer

- Service and repair without interrupting the flow

- Suitable for double LOX- systems

- Normal operation, use only one regulator

- 150 Nm3/h (with dP2<0,3 bar)

- Variable outlet pressure, (P2=3-7 bar)

- Inlet and outlet 35 mm (Int.)- CE-marked according to: EN737-3

Stabilizer MC150

Page 10: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Gas alarm intended for Manifolds (MM90, MC25 and Simplex MMR) and Pressure Watch

- Backup battery (30 min)

- Mute (15 min) /Test button

- Alarm signal according to EN475.

- Optical and audible signal

- Adjustable audible signal

- 4 Channels = 4 alarm points

- EMC Approved

- CE-marked according to EN737-3,

SIS HB370, EN60601

Gas Alarm C44

Page 11: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

IN-SIGNAL:- Pressure switches, contact gauges,

relays or any other type of switch (e.g. light switch)

OUT-SIGNAL: - Connection by relays

1. Can be connected to a PC (PLC). Using the PC as a slave panel

2. To another Gas Alarm C44

Gas Alarm C44

Page 12: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

-Can send the signal a long distance

- Connect the transmitters directly to PLC (PC).

- For local alarm; connect PLC to Gas Alarm C44

- 4-20 mA is the signal that most used in hospitals for other alarms

- Specially designed for usage with high pressure oxygen

- Accuracy 1% of FS better accuracy than Pressure Switches

- Can be fitted to all products (MM90, MC25, Simplex MMR, Line regulators, Pressure Watch)

- Pressure port G1/4”

- 0-16 bar, 0-25 bar and 0-250 bar versions

- CE-marked

4-20 mA Alarm System

Page 13: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- 100% steel.

- Gas-specific connection to all kind of cylinders

- Length: 1250 or 2000 mm

- Product life 5 years

- Maximum allowed operating pressure 230 bar

- Pressure tested at 345 bar

- Safety wire

- O2, N20, Air, CO2, Nitrogen

- CE-marked according to: ISO 2196, EN13221

High Pressure Hoses

Page 14: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Evacuates if the pressure exceeds 6,8 bar

- Evacuates 130 m3/h

- 2 models, one is intended to be mounted immediately after Simplex MMR

- CE-marked according to EN737-3

Medical Piping System - Safety Valve for pipe system

Page 15: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Safety and service reasons

- Service free

- Can be locked

- Degreased for oxygen service

- PN 40 class

- DN10, 15, 25, 32 and 40

Medical Piping System - Shut-off Valves

Page 16: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- For safety and service reasons

- Usually outside every ward. In some wards outside every room.

- Exposed installation / Recessed installation

- Pipes turning

- 1-5 valves

- Sealed front

- Pressure and leak tested

- Service free valves

- CE-marked according to EN737-3

Emergency Shut-Off Valve Box

Page 17: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Exposed / Recessed /Bed head (Panel) Installation

- Service valve- Quick Coupling

- Gas specific (MINI parts can be mixed up)

- O2, N20, Air, Vacuum, Gas exhaust, Instrumental Air, N2, CO2

- CE-marked according to EN737-3, EN737-1, ISO9170-1, SS8752430

Gas Outlets Nordic (MC70 and MINI)

Page 18: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Exposed / Recessed /Bed head (Panel) Installation

- Service valve

- Quick Coupling

- Gas specific

- O2, N20, Air, Air 8 bar, Vacuum, N2, CO2

- CE-marked according to EN737-3, EN737-1,

NFS 90.116

Gas Outlets Afnor

Page 19: Hospital Central Gas Supply Systems

© GCE Group

Date / Name

- Exposed / Recessed /Bed head (Panel) Installation

- Service valve

- Quick Coupling

- Gas specific

- O2, N20, Air, Air 8 bar, Vacuum, N2, CO2

- CE-marked according to EN737-3, EN737-1

Gas Outlets DIN