Horizontal Exposed and Concealed Fan Coil Unit (Model FH)
Model FH Horizontal Exposed and Concealed fan coil units are designed to maximize flexibility of selection and installation.
The units are designed to exceed the stringent quality standards of the institutional market, while remaining cost competitive in the light commercial segment of the market.
Figure 1: Model FHP Horizontal Concealed
Figure 2: Model FHF Horizontal Free Return
Figure 3: Model FHX Horizontal Exposed
Code No. LIT-1201997 www.johnsoncontrols.com
Physical Data
Table 1: ARI Standard Ratings Coil Cooling Capacity Water
Note: Based on 80°F Dry Bulb (DB) and 67°F Wet Bulb (WB) Entering Air Temperature (EAT), 45°F Entering Water Temperature (EWT), 10°F temperature rise, high fan speed. Motor type is Permanent Split Capacitor (PSC) and motor voltage is 115/1/60. Airflow under dry coil conditions. Model FH tested at 0.0” External Static Pressure (ESP). Models FHF and FHP tested at 0.05” ESP.
2 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin
Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin 3
Fan Performance CurvesFan curves on the following pages depict actual performance of each motor tap without any additional fan balance adjustment. Actual capacities that fall below each curve can be obtained by adding an adjustment device. Do not run units prior to installation of downstream ductwork; otherwise, damage to the motor may result.
FH fan coil units are equipped with PSC motors with three separate windings (High, Medium, and Low) that provide variable horsepower outputs. Most often, size selections are conservative and actual CFM requirements and/or external static pressure requirements are lower than those specified. In this case, the unit fan motor can run at low or medium tap, substantially reducing the operating cost of the unit.
All fan curves are for 115/1/60 motors and include pressure losses for cabinets, electric heaters, and 3- or 4-row coils. Plenum units include a clean 1” throwaway filter. For other coil configurations, adjust performance curves based on pressure losses for the coils.
For additional high static pressure applications and rating points, contact your local representative.
4 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin
Figure 4: Model FHP (Plenum) Size 20
Figure 5: Model FHP (Plenum) Size 25
Figure 6: Model FHP (Plenum) Size 30
Figure 7: Model FHP (Plenum) Size 40
Figure 8: Model FHP (Plenum) Size 50
Figure 9: Model FHP (Plenum) Size 60
Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin 5
Figure 10: Model FHF (Free Return) Size 20
Figure 11: Model FHF (Free Return) Size 25
Figure 12: Model FHF (Free Return) Size 30
Figure 13: Model FHF (Free Return) Size 40
Figure 14: Model FHF (Free Return) Size 50
Figure 15: Model FHF (Free Return) Size 60
6 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin
Figure 16: Model FHX (Exposed Cabinet) Size 20
Figure 17: Model FHX (Exposed Cabinet) Size 25
Figure 18: Model FHX (Exposed Cabinet) Size 30
Figure 19: Model FHX (Exposed Cabinet) Size 40
Figure 20: Model FHX (Exposed Cabinet) Size 50
Figure 21: Model FHX (Exposed Cabinet) Size 60
Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin 7
Motor, Fan, and Sound Data
Table 4: Motor and Fan Data (All Models) 115 Volts 208/230 Volts 277 Volts Unit
Size Fan
Speed Motor hp
(Qty.) # Of Fans Amperes Watts Amperes Watts Amperes Watts
High (1) 1/30 0.5 57 0.4 77 0.3 71 Medium (1) 1/50 0.4 39 0.2 49 0.2 48 20
Notes: Motor electrical data is nameplate data. Actual data varies with application. 230 volt motor is nameplated for 208/230/1/60. Use 230 volt motor data for 208 volt applications. Unit size 30, 208/230, and 277 volt motors are 1/12 hp at high tap.
8 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin
Table 5: Sound Data (All Models) Total Sound Power Level
Octave Band/Center Frequency (Hz) Unit Size Fan Speed SCFM 2/125 3/250 4/500 5/1000 6/2000 7/4000 8/8000
High 282 55 59 53 50 46 38 36 Medium 216 50 52 47 44 38 31 32 20
Notes: Sound data tested in accordance with ARI 350-86. Sound levels are expressed in decibels, dB RE: 1 x 10-12 watts. Total sound power level data is based on Model FHP with fan CFM at corresponding motor tap with 115/1/60 volt motor, 3- or 4-row coil, 1” throwaway filter, 0.0” external static pressure, and standard rated internal pressure losses.
Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin 9
Dimensional Data Drawings are not to scale and are not for installation purposes.
Figure 22: Model FHF – Free Return Units
10 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin
Figure 23: Model FHP – Plenum Units
Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin 11
Figure 24: Model FHX – Exposed Cabinet Units
12 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin
Figure 25: Telescoping Bottom Panel
Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin 13
Controls Group 507 E. Michigan Street P.O. Box 423 Published in U.S.A.Milwaukee, WI 53201 www.johnsoncontrols.com
14 Horizontal Exposed and Concealed Fan Coil Unit (Model FH) Technical Bulletin