Top Banner
High Voltage Substation Surveillance using Radio Frequency Interference Measurement
12

High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Jan 18, 2018

Download

Documents

Ann Ramsey

Partial discharge RFI Thermal Light Chemical Pressure/ Acoustic Electric Detecting partial discharge (indirect measurement) Acoustic
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

High Voltage Substation Surveillance using Radio Frequency Interference Measurement

Page 2: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.
Page 3: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Partial discharge

RFI

Thermal

Light

Chemical

Pressure/ Acoustic

Electric

Detecting partial discharge(indirect measurement)

Acoustic

Page 4: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Partial discharge pulse RFI emission FFT frequency spectrum of

PD pulse

RF pulse from a PD related source

Page 5: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

CASE Inkoo 110 kV CT

• Selective testing targeting mainly old 110 kV CTs discovered a unit with a high C2 power factor ~0,95 %. (Strömberg KOTU F41 type, manuf. 1972)

• A DGA follow up showed considerable gassing TCG 18 000 ppm (H2 12037 ppm, CH4 4839 ppm, C2H6 1058 ppm) diagnosed as D1 low energy discharge

• Suitable test case...?• Doble were asked for a PDS100

blind test.

5

Page 6: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Pvm Esityksen nimi / Tekijä

6

Page 7: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Baseline measurement7

GSMTypical frequency zone for air discharges <150 MHz

Discharges in oil will have higher frequency content

Baseline measured outside the fencesLow backround noise levels

Page 8: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

-70

-60

-50

-40

-30

-20

-10

0

50 145 240 335 430 525 620 715 810 905 1000

dB

MHz

Baseline

Tr167

8

-70

-60

-50

-40

-30

-20

-10

0

50 145 240 335 430 525 620 715 810 905 1000

Tr166-Baseline Tr171

-70

-60

-50

-40

-30

-20

-10

0

50 145 240 335 430 525 620 715 810 905 1000

Tr166 Baseline

Tr170

-70

-60

-50

-40

-30

-20

-10

0

50 145 240 335 430 525 620 715 810 905 1000

dB

MHz

Baseline

Tr169 - Phase T

-70

-60

-50

-40

-30

-20

-10

0

50 145 240 335 430 525 620 715 810 905 1000

Baseline

TR168 Phase R

Measuring points on the service road between CBs and CTs

Suspected item

No signals

Baseline

Page 9: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Measurements

The faulty unit was succesfully located– A small PD signal was registered ~15dB

above baseline– Attennuation of high frequencies is useful in

the location process– The 110 kV CT was replaced - no signal

after replacement (one month later)

9

Page 10: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

HV Lab testing of the CT

• PD Ignites at 74 kV phase-to-earth voltage (128 kV main voltage), apparent charge was 50-60 pC

• Extinguishing voltage is considerably lower around 45 kV (77 kV main voltage)

• At 1,2 x Um/ (85 kV) discharge level was 150 pC• Internal pressure 0,75 bar (0,6 considered normal)• Tandelta slightly increasing as a function of voltage up to 70 kV,

0,43...0,59 % • Tandelta increases rapidly when PD ignites at 74 kV being 1,76 %

at 123 kV• CT passed the 0,75 x 230 kV, 50 Hz 1 min overvoltage test

10

Page 11: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

• Non-invasive, no need for physical or electrical connection.

• Does not require equipment under test to be taken out of service.

• May be adopted for first-line substation surveillance.

• Rate and severity of discharge can be monitored and trended.

Advantages of RFI

Page 12: High Voltage Substation Surveillance using Radio Frequency Interference Measurement.

Thanks for your kind attention!Questions?

Contact:Alan NesbittBrian StewartGlasgow Caledonian UniversityScotland, [email protected]

Contact:Micael HellquistHans Ove Kristiansen Doble TransiNor AS

[email protected]