Top Banner
PREMIUM FEATURES 95% AFUE – High efficiency and low emissions! Six wall hung models; 85, 110, 155, 205, 270 MBH 155 MBH combi model available! – Best-in-class DHW performance Field-proven, stainless steel fire tube heat exchanger Advanced Sage2.2 boiler control provides “out-of-the-box” high performance and easy setup – Ergonomically angled touch screen display simplifies installation, operation, and diagnostics – Easily connects to optional Sage Zone Control for additional energy savings, system optimization, and “short cycle” prevention High altitude – zero or minimal de-ratings, reduces the costs of oversizing, field adjustable FULL SIZE easy access side service panel VALUABLE EXTRAS INCLUDED Versatile top and bottom connections for supply & return (on heating-only boilers) Universal vent connection for CPVC/PVC, polypropylene Split-voltage junction box, fused easy-connect terminals Outdoor reset and sensor (wired) Piped & wired for low water cutoff installation (probe not included) 5-year parts warranty ANYWHERE UNMATCHED ANYWHERE UNMATCHED High Efficiency, Gas Fired, Stainless Steel, Condensing Boiler COMBI AVAILABLE! MADE IN U.S.A.
2

High Efficiency, Gas Fired, Stainless Steel, Condensing Boiler Product Data Sheet.pdf• 155 MBH combi model available! – Best-in-class DHW performance • Field-proven, stainless

Aug 08, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: High Efficiency, Gas Fired, Stainless Steel, Condensing Boiler Product Data Sheet.pdf• 155 MBH combi model available! – Best-in-class DHW performance • Field-proven, stainless

PREMIUM FEATURES

• 95%AFUE –Highefficiencyandlowemissions!

• Sixwallhungmodels;85,110,155,205,270MBH

•155 MBH combi model available! –Best-in-classDHWperformance

• Field-proven,stainlesssteelfiretubeheatexchanger

• AdvancedSage2.2boilercontrolprovides “out-of-the-box”highperformanceandeasysetup –Ergonomicallyangledtouchscreendisplay simplifiesinstallation,operation,anddiagnostics –Easilyconnectstooptional Sage Zone Control foradditionalenergy savings,system optimization,and“short cycle”prevention

• Highaltitude–zeroorminimalde-ratings, reducesthecostsofoversizing,fieldadjustable

• FULL SIZEeasyaccesssideservicepanel

VALUABLE EXTRAS INCLUDED

• Versatile top and bottom connections for supply & return (on heating-only boilers)

• UniversalventconnectionforCPVC/PVC, polypropylene

• Split-voltagejunctionbox,fusedeasy-connect terminals

• Outdoorresetandsensor(wired)• Piped&wiredforlowwatercutoffinstallation (probenotincluded)

• 5-yearpartswarranty

ANYWHEREUNMATCHED

ANYWHEREUNMATCHED

High Efficiency, Gas Fired, Stainless Steel, Condensing Boiler

COMBI AVAILABLE!

MADE IN U.S.A.

Page 2: High Efficiency, Gas Fired, Stainless Steel, Condensing Boiler Product Data Sheet.pdf• 155 MBH combi model available! – Best-in-class DHW performance • Field-proven, stainless

©2016U.S.BoilerCompany,Inc.Lancaster,PAPhone:1-888-432-8887

FormNo.USBL16020120m6/16

www.usboiler.net

K2 Firetube: Technical InformationK2FT Ratings & Specifications

Model AFUE%

Input(MBH)

min-max

DOE HeatingCapacity(MBH)

Net AHRI

(MBH)MAWP(PSI)

Vent Size

(Inches)

Approx. Shipping Weight (lbs.)

K2FT-085 95.0 17-85 79 69 30 2or3 140K2FT-110 95.0 22-110 102 89 30 2or3 145K2FT-155 95.0 31-155 145 126 30 3 160K2FT-205 95.0 41-205 190 165 80 3 175

K2FT-270 95.0 54-270 251 218 80 3 185COMBIMODEL*

K2FTC-155 95.0 31-155 145 126 30 3 170

Standard Equipment • Directvent,sealedcombustionappliance• 5:1turndown• NaturalorLPgas,fieldconvertible• Stainlesssteelheatexchanger,firetube• Easyaccesscontrolpanel• Separated,fusedhighandlowvoltageconnections• Sage2.2ControlSystem –LCDtouchscreendisplay,angled –Self-guidedcontrolmenus –Built-inselfdiagnostics –(3)Circulatoroutputsavailable –Built-insequencer,stagesupto(8)boilers –Outdoorresetincludingoutsidesensor –DHWpriority –Warmweathershutdown –Modbuscommunications –Passwordsecurity• Variablespeedcombustionblower• Gasvalve• Polypropylenecondensatetrap• LWCO-readyNPTconnection• Supply,return,andautoresethighlimitwatersensors• Universalventconnection(CPVC/PVC,PP)• Fluegastemperaturesensoranddifferentialpressureswitch• 30PSIsafetyreliefvalve• Pre-installedhangingbracketandwallmountkit• Fieldadjustableforhighaltitudewithminimalderate• Thermostatic DHW mixing valve(K2FTC-155combionly)

SafetyReliefValvePressure,Water–30PSIstd.ASMEcertified“H”.Maxallowabletemperaturesetting210ºF.Targetsetpointis180°F,manualresethighlimitsetpointis210°F.Boilersshippedsetfornaturalgas.Aboveperformanceisforelevationsto2000’.Consultmanualforinstructionsandperformanceforinstallationsupto10,100’.Allowableventlengthsupto135ft.

Typical Venting Configurations (Horizontal and Vertical)

Horizontal2-pipelowprofile

Horizontal2-pipeconcentric

Illustrationsareforrepresentationonly.Forcompleteventinginformation,pleaseseeInstallationmanual.

Vertical2-pipe

Vertical2-pipeconcentric

Horizontal2-pipe

Hybrid

Verticalexhaust/sealedB-ventforcombustionair

*DHWflowrateofoptionalcombi-equippedmodelK2FTC-155is4.0GPM@70°TR

Accessories:• SageZoneControl(P/N:104590-01)• Wirelessadapteroutdoorreset(PN:105121-01)• LWCOkit(P/N:100592-01or105591-01)• Servicepartsrepairkit(P/N:107118-01)• Kit,CPVCstarterandPVCventterminations: (2”P/N:107039-01)(3”P/N:107039-02)

Control Access Panel

33-5/16”Gas Connection1/2”

CondensateConnection

Condensate Trap Cleanout

Drain Valve

VentConnection

Relief Valve

Air IntakeConnection

Temperature/Pressure

Gauge

Alternate Return/InletWater Connection

(heating-only models)

ServiceAccess

Panel

AlternateSupply/Outlet

Water Connection(heating-only models)

Return/Inlet Water

Connection1”

Supply/OutletWater Connection - 1”

Outsideof Wall

Insideof Wall

19-13/16”

A

Dimensions (Inches)

Model A

K2FT-085 20

K2FT-110 20

K2FT-155 20

K2FT-205 21

K2FT-270 21

K2FTC-155 23

ASM

E

H