-
SIGNAL CONDITIONER5500 SERIES
OPERATION AND INSTALLATIONMANUAL
Corporate Headquarters 3860 Calle Fortunada San Diego, CA
92123-1825 Phone: (858) 278-2900FAX: (858) 278-6700Web-Site:
http://www.hardyinstruments.com
Hardy Instruments Document Number: 0296-0026-01 Rev ECopyright
November 2000 Hardy Instruments, Inc. All Rights Reserved. Printed
in the U.S.A. (941028)
-
Table of Contents
Table of Contents
TABLE OF CONTENTS - - - - - - - - - - - - - - - - - - - - - -
I
TABLE OF ILLUSTRATIONS- - - - - - - - - - - - - - - - - - - -
I
OVERVIEW - - - - - - - - - - - - - - - - - - - - - - - - - - -
-1-1A Brief Description of Chapter 1 - - - - - - - - - - - - - - -
- - - -1-1About Hardy Manuals - - - - - - - - - - - - - - - - - - -
- - - - -1-2Description - - - - - - - - - - - - - - - - - - - - - -
- - - - - - -1-3Industries- - - - - - - - - - - - - - - - - - - - -
- - - - - - - - -1-3Applications - - - - - - - - - - - - - - - - -
- - - - - - - - - - -1-4Options- - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - -1-4
HI 5500PS Power Supply - - - - - - - - - - - - - - - - - - -
-1-4Transducers - - - - - - - - - - - - - - - - - - - - - - - - -
-1-5NEMA Enclosures - - - - - - - - - - - - - - - - - - - - - -
-1-5
Back Plate/Not Wired - - - - - - - - - - - - - - - - - - -
-1-5Back Plate/Wired - - - - - - - - - - - - - - - - - - - - -
-1-5
CHAPTER 2 - SPECIFICATIONS- - - - - - - - - - - - - - - - -
-2-1A Brief Description of Chapter 2 - - - - - - - - - - - - - - -
- - - -2-1Specifications for a Standard HI 5000 Series Signal
Conditioning Module - - - - - - - - - - - - - - - - - - - - - -
-2-1Electrical Characteristics - - - - - - - - - - - - - - - - - -
- -2-1
Input Sensor Sensitivity - - - - - - - - - - - - - - - - - -
-2-1Sensor Excitation Current- - - - - - - - - - - - - - - - -
-2-1Current Output - - - - - - - - - - - - - - - - - - - - - -
-2-1Voltage Output - - - - - - - - - - - - - - - - - - - - - -
-2-1Maximum Load Resistance - - - - - - - - - - - - - - - -
-2-1Frequency Range (3 dB) - - - - - - - - - - - - - - - -
-2-1Vibration Range - - - - - - - - - - - - - - - - - - - - -
-2-1Sensor Fault - - - - - - - - - - - - - - - - - - - - - - -
-2-2
Power Requirements - - - - - - - - - - - - - - - - - - - - -
-2-2Physical Characteristics - - - - - - - - - - - - - - - - - - -
-2-2
Mounting - - - - - - - - - - - - - - - - - - - - - - - - -
-2-2Physical Dimensions - - - - - - - - - - - - - - - - - - -
-2-2
Length - - - - - - - - - - - - - - - - - - - - - - - - -2-2Width
- - - - - - - - - - - - - - - - - - - - - - - - -2-2Height - - - -
- - - - - - - - - - - - - - - - - - - - -2-2
Weight - - - - - - - - - - - - - - - - - - - - - - - - - -
-2-2Environmental Characteristics - - - - - - - - - - - - - - - -
-2-3
Temperature Range - - - - - - - - - - - - - - - - - - -
-2-3i
Operating - - - - - - - - - - - - - - - - - - - - - - -2-3
-
HI 5500 SERIES SIGNAL CONDITIONERS
Storage - - - - - - - - - - - - - - - - - - - - - - -
-2-3Humidity - - - - - - - - - - - - - - - - - - - - - - - - -
-2-3
Ordering Information for the HI 5501 - - - - - - - - - - - - - -
- -2-3Ordering Information for the HI 5502 - - - - - - - - - - - -
- - - -2-4HI 5501E (Only) - - - - - - - - - - - - - - - - - - - - -
- - - - -2-4
Temperature Range - - - - - - - - - - - - - - - - - - - - -
-2-4Operating - - - - - - - - - - - - - - - - - - - - - - - -
-2-4
Humidity - - - - - - - - - - - - - - - - - - - - - - - - - - -
-2-4Enclosure Requirements - - - - - - - - - - - - - - - - - - -
-2-4Approvals - - - - - - - - - - - - - - - - - - - - - - - - - -
-2-4
Optional Equipment- - - - - - - - - - - - - - - - - - - - - - -
- -2-5HI 5500PS Power Supply - - - - - - - - - - - - - - - - - - -
-2-5
Regulation - - - - - - - - - - - - - - - - - - - - - - - -
-2-5Environmental - - - - - - - - - - - - - - - - - - - - - -
-2-5
Operating - - - - - - - - - - - - - - - - - - - - - -
-2-5Storage - - - - - - - - - - - - - - - - - - - - - - -
-2-5Temperature Coefficient - - - - - - - - - - - - - - - -2-5
Dimensions- - - - - - - - - - - - - - - - - - - - - - - -
-2-5Physical - - - - - - - - - - - - - - - - - - - - - - -
-2-5Weight - - - - - - - - - - - - - - - - - - - - - - - - -2-5
Output Power- - - - - - - - - - - - - - - - - - - - - - -
-2-5Options- - - - - - - - - - - - - - - - - - - - - - - - - -
-2-5HI 5532 - - - - - - - - - - - - - - - - - - - - - - - - -
-2-5HI 5533 - - - - - - - - - - - - - - - - - - - - - - - - -
-2-5
CHAPTER 3 - INSTALLATION - - - - - - - - - - - - - - - - - -
-3-1A Brief Description of Chapter 3 - - - - - - - - - - - - - - -
- - - -3-1Unpacking - - - - - - - - - - - - - - - - - - - - - - - -
- - - - -3-1Pre-Installation Engineering Procedures- - - - - - - -
- - - - - - -3-2Electrical Wiring Precautions - - - - - - - - - - -
- - - - - - - - -3-3Installing the HI 5500 Standard Module Onto a
DIN Rail - - - - - - -3-4Electrical Installation Procedures - - - -
- - - - - - - - - - - - - -3-5
LED OK Indicator - - - - - - - - - - - - - - - - - - - - - - -
-3-6BNC Connector- - - - - - - - - - - - - - - - - - - - - - - -
-3-7Terminal Assignments - - - - - - - - - - - - - - - - - - - -
-3-7
TB2-1,2 - - - - - - - - - - - - - - - - - - - - - - - - -
-3-7TB2-3,4 - - - - - - - - - - - - - - - - - - - - - - - - -
-3-7TB2-5,6 - - - - - - - - - - - - - - - - - - - - - - - - -
-3-7TB1-1 - - - - - - - - - - - - - - - - - - - - - - - - - -
-3-7TB1-2 - - - - - - - - - - - - - - - - - - - - - - - - - -
-3-8TB1-3 - - - - - - - - - - - - - - - - - - - - - - - - - -
-3-8TB1-4 - - - - - - - - - - - - - - - - - - - - - - - - - -
-3-8TB1-5 - - - - - - - - - - - - - - - - - - - - - - - - - -
-3-8ii
-
Table of Contents
Installing modules in an Enclosure (See Fig. 3-5) - - - - - - -
- - -3-8Pump Monitoring with Transducers and HI 5500 Series Module
- - -3-9
Threaded Stud - - - - - - - - - - - - - - - - - - - - - -
-3-10Cementing Pad- - - - - - - - - - - - - - - - - - - - - -
-3-10
Wiring Diagram Example for 5501/55032/5533 with no Power Supply
- - - - - - - - - - - - - - - - - - - - - - - - - -3-12
Wiring Diagram for Acceleration and Velocity Monitoring System
with Alarm and Danger Relays - - - - - - - - - - - - - -3-13
CHAPTER 4 - SETUP - - - - - - - - - - - - - - - - - - - - - -
-4-1A Brief Description of Chapter 4 - - - - - - - - - - - - - - -
- - - -4-1Test Equipment and Tools Required - - - - - - - - - - - -
- - - -4-1Quick Calibration Check Using An HI 813 Portable
Shaker
Calibration System - - - - - - - - - - - - - - - - - - - - - - -
-4-2Calibration Setup Procedures Using a Frequency
Generator and Power Supply - - - - - - - - - - - - - - - - - -
-4-4Full Scale and Zero Scale Adjustment - - - - - - - - - - - - -
- - -4-6Input Sensitivity Selection- - - - - - - - - - - - - - - -
- - - - - -4-9Monitoring System Configuration - - - - - - - - - - -
- - - - - - -4-10
Reference Voltage Jumper Setting Procedures - - - - - - - -
-4-10
CHAPTER 5 - CALIBRATION - - - - - - - - - - - - - - - - - -
-5-1A Brief Description of Chapter 5 - - - - - - - - - - - - - - -
- - - -5-1Full Scale Output/Span Adjustment - - - - - - - - - - - -
- - - - -5-1
Bench Calibration Using the Hardy HI 813 Portable Shaker System
- - - - - - - - - - - - - - - - - - - - - - - -5-1
Bench Calibration Using a Frequency Generator and Power Supply -
- - - - - - - - - - - - - - - - - - - - - - -5-5
Current Limit Test - - - - - - - - - - - - - - - - - - - - - -
-5-6Final Check - - - - - - - - - - - - - - - - - - - - - - - - -
-5-6
Calculation of HI 5501/5502 Full Scale Calibration voltage - - -
- - -5-7Acceleration or Velocity - - - - - - - - - - - - - - - - -
- - - -5-7Accelerometer or Velocity Input with Signal Integration -
- - - -5-7
Log Mid-Frequency - - - - - - - - - - - - - - - - - - - -
-5-8Convert Output EUs F.S. to Input EUs for Three
Different HI 5501/HI 5502 Configurations - - - - - - - -
-5-8Three Examples Based on Part Numbers - - - - - - - - - -5-8
CHAPTER 6 - TROUBLESHOOTING- - - - - - - - - - - - - - - -6-1A
Brief Description of Chapter 6 - - - - - - - - - - - - - - - - - -
-6-1Problem: Green Light Not Illuminated - - - - - - - - - - - - -
- - -6-1Check Output Amperage - - - - - - - - - - - - - - - - - - -
- - -6-1iii
-
HI 5500 SERIES SIGNAL CONDITIONERSiv
-
Table of Illustrations
Table of Illustrations
OVERVIEW - - - - - - - - - - - - - - - - - - - - - - - - - - -
-1-1
FIG. 1-1 STANDARD HI 5500 SIGNAL CONDITIONER MODULE -1-1FIG. 1-2
HI 5500PS +24VDC POWER SUPPLY - - - - - - - - - -1-4
CHAPTER 2 - SPECIFICATIONS- - - - - - - - - - - - - - - - -
-2-1
FIG. 2-1 SPECIAL PRODUCT CONFIGURATION MENU - HI 55012-3FIG. 2-2
SPECIAL PRODUCT CONFIGURATION MENU - HI 55022-4
CHAPTER 3 - INSTALLATION - - - - - - - - - - - - - - - - - -
-3-1
FIG. 3-1 INSTALLING THE MODULE ONTO A DIN RAIL - - - - -3-4FIG.
3-2 MOUNTING LATCH HIGHLIGHTED - - - - - - - - - - -3-5FIG. 3-3
MODULES INSTALLED ON DIN RAIL - - - - - - - - - -3-5FIG. 3-4
FUNCTIONAL BLOCK DIAGRAM FOR HI 5501/HI 5502 -3-6FIG. 3-5
CONNECTIONS/5501 - - - - - - - - - - - - - - - - - -3-6FIG. 3-6
INSTALLING THE MODULES IN AN ENCLOSURE - - -3-9FIG. 3-7 PUMP
MONITORING - - - - - - - - - - - - - - - - - -3-9FIG. 3-8 CEMENTING
PAD INSTALLATION - - - - - - - - - - -3-11FIG. 3-9 WIRING DIAGRAM
FOR 5501/5532/5533 WITH
NO POWER SUPPLY - - - - - - - - - - - - - - - - -3-12FIG. 3-10
WIRING DIAGRAM FOR MONITORING SYSTEM
WITH ALARM AND DANGER RELAYS - - - - - - - - -3-13
CHAPTER 4 - SETUP - - - - - - - - - - - - - - - - - - - - - -
-4-1
FIG. 4-1 FIELD CHECKOUT USING HI 813 CALIBRATION SHAKER - - - -
- - - - - - - - - - - - - - - - - - - -4-3
FIG. 4-2 CONNECTING TRANSDUCER LEADS TO HI 5501 MODULE - - - - -
- - - - - - - - - - - - - -4-3
FIG. 4-3 CALIBRATION EQUIPMENT SETUP- - - - - - - - - - -4-5FIG.
4-4 HI 5500 SERIES SIGNAL CONDITIONER
CIRCUIT BOARDS - - - - - - - - - - - - - - - - - - -4-6FIG. 4-5
REMOVING THE MODULE COVER - - - - - - - - - - -4-7FIG. 4-6 J4
SENSITIVITY JUMPER SETTINGS - - - - - - - - - -4-10FIG. 4-7 JUMPER
SETTINGS FOR REFERENCE VOLTAGE - - -4-11
CHAPTER 5 - CALIBRATION - - - - - - - - - - - - - - - - - -
-5-1I
FIG. 5-1 REMOVE PHILLIPS PAN HEAD SCREWS- - - - - - - -5-4
-
HI 5532/5533 MODULESII
-
Chapter 1 - Overview
CHAPTER 1 - OVERVIEW
A BRIEF DESCRIPTION OF CHAPTER 1
This manual provides the user and service personnel with a
description of the specifications, installation, setup,
configuration, operation, communication, maintenance, and
troubleshooting procedures for the Hardy Instruments HI 5500 Series
Signal Condition-ers. The HI 5500 Series Signal Conditioner
provides a modular and versatile solution to predictive
mainte-nance of machinery. Modules can be configured as a stand
alone monitoring system with shutdown capa-bility or as a simple
signal conditioner feeding vibra-tion information to a plants
control computer (PLC or DCS). The modules process vibration
signals and allow plant computers or recording devices to monitor
the overall vibration levels on important production machinery.
Machinery vibration monitoring is a cost effective way to implement
predictive maintenance for sustained machine reliability.
FIG. 1-1 STANDARD HI 5500 SIGNAL CONDITIONER MODULE
The modules can be used on a variety of machine types. Each HI
5500 module contains the circuitry to condition and convert the
dynamic signal produced by 1-1
-
HI 5500 SERIES SIGNAL CONDITIONERS
the vibration transducer (HI 111, HI 113) to a cali-brated
4-20mA current output. The 4-20mA output is proportional to the
measured vibration amplitude for trending by a PLC or DCS. The HI
5500 Series can be used with either a set point module (HI 5532)
and a relay module (HI 5533) to provide a monitoring sys-tem (HI
5500 MS) with alarm and/or shut down capa-bilities. The HI 5500
Series conditioning monitoring system detects machine problems
early so that cata-strophic failure can be minimized and any
problems can be repaired during scheduled downtime. The HI 5500
Series Signal Conditioner Modules are essential for successful
predictive maintenance.
To get the maximum service life from this product, users should
operate this module in accordance with recommended practices either
implied or expressed in this manual. Before using the HI 5500
Signal Condi-tioning modules, all users and maintenance personnel
should read and understand all cautions, warnings, and safety
procedures, either referenced or explicitly stated in this manual,
to ensure the safe operation of the module. Hardy Instruments
appreciates your busi-ness. Should you not understand any
information in this manual or experience any problems with the
product, please contact our Customer Support Depart-ment at:
Phone: (858) 278-2900FAX: (858) 278-6700e-mail:
[email protected] Address:
http://www.hardyinstruments.com
ABOUT HARDY MANUALS
Every Hardy Installation and Operation manual is organized into
easily referenced chapters, that are almost always the same:
Chapter 1 - Provides an introduction to the instrument and an
Overview of the equipment and its capabilities.
Chapter 2 - Provides a complete list of Specifi-cations.1-2
-
Chapter 1 - Overview
Chapter 3 - Contains complete instructions needed to install the
HI 5500 Series Vibration Signal Conditioners.
Chapter 4 - Provides complete hardware Con-figuration
instructions for setting dip switches and jumpers.
Chapter 5 - Pertains to the firmware/software Setup and
preparation procedures to calibrate and operate the instrument.
Chapter 6 - Provides all Calibration instruc-tions.
Chapter 7 - Pertains to the Operating Proce-dures of the HI 5500
Series Vibration Signal Conditioners.
Chapter 8 - Pertains to the Troubleshooting procedures for
repair of the instrument.
Hardy Instruments hopes that this manual meets your needs for
installation and operation. All corrections or suggestions for
improvements of this manual are wel-come and can be sent to the
Technical Publications Department or Customer Support Department at
Hardy Instruments Inc.
DESCRIPTION The Hardy Instruments DI 5500 Series Signal
Condi-tioning Modules are specifically designed to:
Continuously monitor the condition rotating machinery
vibration.
Monitor machine vibration in a plant computer using 4-20
milliamp and 0-5 VDC outputs.
Set off an alarm to alert maintenance personnel of excessive
vibration.
Provide vibration analysts the raw vibration sig-nal for
diagnosing machine vibration essential for predictive
maintenance.
INDUSTRIES Petroleum Chemical Power Pulp and Paper Food/Beverage
Metal Fabrication1-3
Transportation
-
HI 5500 SERIES SIGNAL CONDITIONERS
APPLICATIONS Pumps Fans/Blowers Motors Chillers Compressors
Machine Tools
OPTIONS
HI 5500PS Power Supply
The Hardy HI 5500PS is a compact power source that converts
110VAC to 24VDC to provide power for Hardys HI 5500 Series Signal
Conditioners. It is rug-gedly constructed and designed to withstand
substan-tial overloads or short circuits for reasonable lengths of
time. The power supply can be connected to a type C or D style
mounting rail for easy installation. Rec-ognized by Underwriters
Laboratories (UL)(See Fig. 1-2)
FIG. 1-2 HI 5500PS +24VDC POWER SUPPLY1-4
-
Chapter 1 - Overview
Transducers HI 111 (General Purpose) Accelerometer - 100 mV/g,
250 F Service, 2-Pin MS connector, Case
Isolated. HI 113 (Premium) Accelerometer - 100 mV/g,
250 F Service, 2-Pin MS connector Case Iso-lated.
HI 113SM Accelerometer, 100 mV/g, 250 F Ser-vice, 2-Pin MS
Connector, Case Isolated, Side Mount.
NEMA Enclosures Enclosures constructed of Fiberglass, Mild Steel
or Stainless Steel without back plate.
Back Plate/Not Wired
Aluminum back plate with Type C Din Rail(s) and two rail stops
to mount HI 5500 Series modules. Wir-ing of modules is not
included.
Back Plate/Wired
Aluminum back plate with Type C Din Rail(s) and two rail stops
to mount HI 5500 Series modules. Wired per customer configuration.
Also includes AC input terminal and fuse block.1-5
-
HI 5500 SERIES SIGNAL CONDITIONERS1-6
-
Chapter 2 - Specifications
CHAPTER 2 - SPECIFICATIONS
A Brief Description of Chapter 2
Chapter 2 lists the specifications for the HI 5000 Series Signal
Conditioning Module. Specifications are listed for the standard
instrument and for optional equipment. The specifications listed
are designed to assist in the installation, operation and
troubleshoot-ing of the instrument. All service personnel should be
familiar with this section before attempting an instal-lation or
repair of this instrument.
Specifications for a Standard HI 5000 Series Signal Conditioning
Module
Electrical Characteristics
Input Sensor Sensitivity
10, 100, 500 mV/g User Selectable
Sensor Excitation Current
+24 VDC @ 4 mA
Current Output 4-20mA 10%
Voltage Output 0-5 VDC 10%
Maximum Load Resistance
1.2 KOhms
Frequency Range (3 dB)
See Table 2-1
Vibration Range
See Table 2-12-1
-
HI 5500 SERIES SIGNAL CONDITIONERS
NOTE: *Special Orders are available at various Frequency and
Vibration Ranges.
Sensor Fault 0mA output in Fault Condition
Power Requirements
Nominal: +24 VDCRange: +22 to +28 VDC
Physical Characteristics
Mounting DIN Rail (35mm x 15mm)
Physical Dimensions
Length Approx. 4.00 (102mm)Width Approx. 1.9 (48mm)Height
Approx. 3.25 (80mm)
Table 2-1: Frequency Range
Standard Models
Frequency Range( 3dB)
Vibration Range
HI 5501 - ASTD 2 - 10 KHz 0 - 10 g
HI 5501 - VSTD 2 - 10 KHz 0 - 1 ips
HI 5501 - VLF 2 - 1 KHz 0 - 1 ips
HI 5502 - STD 2 - 10 KHz 0 - 1 ips
Hazardous Models
Frequency Range( 3dB)
Vibration Range
HI 5501E - ASTD 2 - 10 KHz 0 - 10 g
HI 5501E - SPEC ACCEL, VEL, DISPLACE Special Order*
HI 5501E - VLF 2 - 1 KHz 0 - 1 ips
HI 5501E - VSTD 2 - 10 KHz 0 - 1 ips2-2
Weight Approx. 4.6 oz. (131 grams)
-
Chapter 2 - Specifications
Environmental Characteristics
Temperature Range
Operating 0-70 C (32-158 F)Storage 0-85 C (32-185 F)
Humidity 0-95% Non-Condensing
Ordering Information for the HI 5501
FIG. 2-1 SPECIAL PRODUCT CONFIGURATION MENU - HI 5501
NOTE: AR pertains to Active Reference, and IR to Inac-tive
Reference. Active Reference designates an HI 5501/5502 module as
the master module when it is used with multiple modules in an
auctioneering (or group) mode. For example, if one sensor is used
with two HI 5501 modules of provide acceleration and velocity
measurements, one of the two modules must be configured for AR and
the other module for IR. Similarly, if multiple modules (each with
their own sensor) are grouped together in an auctioneering mode
(AM), the module must be configured for AR and the remaining
modules for IR.2-3
-
HI 5500 SERIES SIGNAL CONDITIONERS
Ordering Information for the HI 5502
FIG. 2-2 SPECIAL PRODUCT CONFIGURATION MENU - HI 5502
NOTE: These menus are for standard product configurations only.
Special product configurations can be provided. Contact your local
Hardy Representative for more information.
HI 5501E (Only)
Temperature Range
Operating -40 to +85 C (-40 - 185 F)Humidity 0-95%
Non-Condensing
Enclosure Requirements
These devices are intended to be installed within an enclosure
rated to at least IP54/NEMA 3 or 3S
Approvals UL CUL This equipment is suitable for use in Class
I,
Division 2, Groups A,B,C and D Hazardous loca-tions.
This equipment is suitable fore use in Class I, Zone 2, Ex nL
IIC T4 X, AEx nC IIC T42-4
-
Chapter 2 - Specifications
Optional Equipment
HI 5500PS Power Supply
The HI 5500PS Power Supply is a compact power source for HI 5500
Series Signal Conditioners. Rug-ged and designed to withstand
substantial overloads or short circuits for reasonable periods of
time. The HI 5500PS can be connected to a Type C or D style
mounting rail for easy installation. Recognized by Underwriters
Laboratories. UL
Regulation 0.1% load 0.5% line Impedance: 0.07 ohms at 1kHz
0.20 ohms at 10 kHz
Environmental
Operating -20 to +71 C (-4 to +160 F)
Storage -55 to +85 C (-67 to +185 F)
Temperature Coefficient
-.015%/ C
Dimensions
Physical 4.0L x 2.875W x 3.375H (101.6mmL x 73.0mmW x
85.72mmH)
Weight 2 lbs, 1 oz. (.48Kgs)
Output Power .6 AmpsProvides power for up to 12 Signal
Conditioner Mod-ules
Options 5500PS-1: 210-250 Volt Input, 47 to 420 Hz
HI 5532 Dual Alarm Setpoint Module
HI 5533 Relay Module, DPDT2-5
-
HI 5500 SERIES SIGNAL CONDITIONERS2-6
-
Chapter 3 - Installation
CHAPTER 3 - INSTALLATION
A Brief Description of Chapter 3
All information contained in Chapter 3 pertains to unpacking,
cabling, interconnecting, configuration and installing the HI 5000
Series Signal Conditioning Module. Alternatives to any procedures
contained or implied in this chapter are not recommended. It is
very important that the user and service personnel be familiar with
the procedures contained in this chapter, before installing or
operating the HI 5500 Series mod-ule. Hardy Instruments appreciates
your business. Should you experience any problems installing this
equipment, contact Hardy Instruments Inc., Customer Support for
assistance.
Unpacking Step 1. Before signing the packing slip, inspect the
packing for damage of any kind.
Step 2. Report any damage to the carrier company
immediately.
Step 3. Check to see that everything in the pack-age matches the
bill of lading.
Step 4. Write down the Model(s) and Serial num-ber(s) of the
module(s). Store this informa-tion in a convenient location for
reference when contacting The Customer Support Department for parts
or service.
WARNING ELECTROSTATIC DISCHARGE MAY DAM-AGE SEMICONDUCTOR
COMPONENTS IN THE MODULE. DO NOT TOUCH THE CON-NECTOR PINS. PLEASE
OBSERVE THE FOL-LOWING HANDLING PRECAUTIONS:
Wear an approved wrist-strap grounding device when handling the
module.
Touch a grounded object or sur-face to rid yourself of any
elec-trostatic discharge prior to handling the module.
Only Handle the module by grasping the DIN Rail Mount.3-1
-
HI 5500 SERIES SIGNAL CONDITIONERS
Pre-Installation Engineering Procedures
Step 1. Always check the hazardous area classifi-cation of the
site where you are going to install the modules. Make absolutely
sure that the module meets the hazardous area classification before
installation. If you dont know the hazardous classification, check
with the Site or Consulting Engi-neer.
WARNING DO NOT INSTALL THE MODULES IN HAZ-ARDOUS AREAS WHERE THE
MODULE DOES NOT MEET THE HAZARDOUS AREA CLASSIFICATION.
Step 2. Choose a location in where the tempera-ture and humidity
meets the limits speci-fied for the HI 5500 Series signal
conditioners (See Chapter 2). Always keep the modules dry and try
to maintain a con-stant temperature. Temperature recycling can lead
to moisture build-up inside the module.
Step 3. The HI 5500 Series terminal blocks permit solderless and
lugless connections of 16 to 22 GA stranded wiring. Strip back the
insulation.25 to.30 before making con-nections to make sure there
is a good con-nection.
Step 4. Always use rigid metal conduit whenever possible for
field wiring transducers to the HI 5500 Conditioners.
Step 5. Make sure to separate the low level vibra-tion signal
cabling from other instrument and control signals.
WARNING NEVER RUN THE TWISTED, SHIELDED OR COAXIAL CABLES
CONTAINING LOW LEVEL VIBRATION SIGNALS IN THE SAME CON-DUIT WITH AC
WIRING.
Step 6. Shielding must be pulled back from the transducer wire
in order to terminate them. Unshielded wire is susceptible to Radio
3-2
-
Chapter 3 - Installation
Frequency Interference (Walkie Talkie, 2-Way Radios etc.) Always
locate the DI-5500 Series units in a metal enclosure to shield
unshielded wires.
Step 7. It is important to know the machine or mounting position
resonant frequency (at running speed) in order to achieve accu-rate
measurements. Your machinery sup-plier can provide you with this
information. Mounting resonance can give a false indication of high
frequency machinery faults such as gear mesh and bearing problems.
In some cases the mounting resonance can cause sensor overload if
it is excited by a machinery fault. An accelerometers region and
linear frequency response generally extends well above and below
running speed of most rotating machinery.
Step 8. Make sure that all covers, fittings and accessories are
tightly fastened to the machine. Readings are corrupted by
vibrating loose parts and degrade the qual-ity of the
measurement.
Step 9. After completing the field installation and system
commissioning, set up a schedule for regular calibration and
maintenance. This will make sure the results from the instrument
are reliable so that others in your facility can rely on the
information. For calibration we recommend the Hardy HI 803, HI 813,
HI 823 Transducer Cali-bration Systems. Contact your local Hardy
Instruments Dealer for more information.
Electrical Wiring Precautions
1. Never route the cable along side high voltage power lines and
only cross high voltage power lines at right angles. For example,
if a power line is 440 volts and 60 Hz and the signals from the
sensor are at the milli and microvolt levels any cross talk can
severely corrupt the data.
2. Cable and Shielding should be grounded at one end only
preferably at the controller.3-3
-
HI 5500 SERIES SIGNAL CONDITIONERS
3. Shield and Common wires must be wired to earth ground.
Installing the HI 5500 Standard Module Onto a DIN Rail
Step 1. Hold the module with the DIN Rail Mounting facing down
and what appears to be a spring type mounting latch. (See Figs. 3-1
& 3-2)
Step 2. Tilt the front of the module and mount slightly down
about 30 degrees.
Step 3. Slide the mounting latch over the edge of the DIN Rail
until the rail edge touches the bottom of the DIN Mount frame.
Step 4. Slide the mount back until it stops.Step 5. Gently push
the back of the mount down
until the mount snaps onto the DIN Rail. (See Fig. 3-3)
FIG. 3-1 INSTALLING THE MODULE ONTO A DIN RAIL3-4
-
Chapter 3 - Installation
FIG. 3-2 MOUNTING LATCH HIGHLIGHTED
FIG. 3-3 MODULES INSTALLED ON DIN RAIL
Step 6. Now wire the module to the transducer and the power
supply.
Electrical Installation Procedures
The following describes the electrical components of a module
and terminal assignments. A block diagram 3-5
-
HI 5500 SERIES SIGNAL CONDITIONERS
is provided to assist in installation. (See Figs. 3-4 &
3-5)
FIG. 3-4 FUNCTIONAL BLOCK DIAGRAM FOR HI 5501/HI 5502
FIG. 3-5 CONNECTIONS/5501
LED OK Indicator A green LED illuminates when the sensor
connection and power is OK. The LED goes off when a circuit fault
exists.3-6
-
Chapter 3 - Installation
BNC Connector The vibration signal can be accesses at the BNC
con-nector or at the Terminal Connector. The Vibration signal can
be accessed in either the filtered or unfil-tered form.
WARNING DO NOT REMOVE OR REPLACE WHILE CIR-CUIT IS LIVE UNLESS
THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRA-TIONS OF
FLAMMABLE GASES OR VAPORS.
Terminal Assignments
TB2-1,2 Power supply input terminals - The voltage measured
between TB2-1 and TB2-2 should be within the range of +22 to
+28VDC. Nominal voltage should be +24VDC.
TB2-3,4 Output current (4-20mA) proportional to the mea-sured
vibration is available between terminals TB2-3 (4-20) and TB2-4
(common) This is the output to be connected to the plant DCS or
data acquisition system for tending analysis. The 4-20mA output is
clamped to approximately 0mA whenever the green OK LED is out
(Transducer Fault Condition).
TB2-5,6 Voltage output (0-5VDC) proportional to the mea-sured
vibration is available between terminals TB2-5 and TB2-6. This
0-5VDC output is driven to a nega-tive voltage whenever the green
OK LED is out. The 0-5VDC output is intended primarily as an input
signal to the HI-5532 Setpoint Module for communi-cating the
vibration level measured by the HI-5501/5502.
TB1-1 Connect the shield from the transducer cable to this
terminal if the shield is isolated from ground at the truncates
end. If the shield is common to the trans-ducer case, the shield
must be tied back to the cable and NOT connected to the HI
5501/5502 shield termi-nal.3-7
-
HI 5500 SERIES SIGNAL CONDITIONERS
TB1-2 The output signal from the field mounted sensor is
connected to this terminal. Power to accelerometers is provide via
this terminal.
TB1-3 Connect the common terminal from the transducer to this
terminal. This terminal could be called signal return.
TB1-4 The voltage at this terminal is the internal circuit
ref-erence. This terminal is used when connecting the HI 5532
Setpoint and HI 5533 Relay modules to the HI 5501/5502 Signal
Conditioners and are to provide relay outputs for annunciation or
shutdown. Self-gen-erating velocity pickups (no external voltage
applied) will require the low side or return wire to be con-nected
to this terminal. No connection will terminate at TB1-3 in this
case. For example:
When one transducer is connected to several 5501 modules, you
make one module the Active Reference Voltage (AR) by setting the
jumper at JP1. The remaining modules you set for Inactive Reference
voltage (IR) by setting the jumpers for IR.
Another example is when you have several individual modules
connected to individual sensors and you want to use the
Auctioneering mode to check each.
TB1-5 This is an optional buffered signal out connection in case
you dont have a cable with a BNC connector.
Installing modules in an Enclosure (See Fig. 3-5)
Step 1. Mount the DIN Rail(s) (Standard 35mm DIN RAIL) onto the
back plate of the enclosure. The center distance between the
installed DIN Rails should be no less than 5.5 (139.7mm) to allow
for proper wiring of the modules.
Step 2. Mount the modules onto the DIN Rail. See Installing the
HI 5500 Standard Module onto a DIN Rail above.
Step 3. It is recommended that you install a DIN Rail Stop or
Stops to prevent the modules from accidentally sliding off the DIN
Rail.3-8
Step 4. Its that easy.
-
Chapter 3 - Installation
FIG. 3-6 INSTALLING THE MODULES IN AN ENCLOSURE
Pump Monitoring with Transducers and HI 5500 Series Module
FIG. 3-7 PUMP MONITORING
Step 1. Select a sensor mounting location that minimizes the
vibration transmission route through the machine. Avoid mounting
the sensor on thin sections or vibration-free areas.3-9
-
HI 5500 SERIES SIGNAL CONDITIONERS
Step 2. Select the mounting configuration based on whether the
mount is permanent or temporary. In most cases the mounting
configuration is permanent and you should use a stud mount or
cementing pad.
Step 3. Install the sensor according to the chosen mounting
configuration and sensor sup-plier instructions. See instructions
below:
Threaded Stud Stud mounting requires a tapped hole drilled
directly into the structure. A threaded stud provides electrical
and mechanical connection between the sensor and the pump bearing
housing. The sensor requires a flat surface perpendicular to the
tapped hole. The spot face must be 1.1 times larger than the
diameter of the sensor housing to ensure flush mounting. For
mea-surements above 1,000Hz (60,000cpm), the surface should be flat
within 1 mil and have surface texture no greater than 32
microinches. Make sure that burrs between the sensor and the pump
bearing housing are removed.The center line of the tapped hole must
be perpendic-ular to within 1 of the mounting surface to ensure no
gaps are present between the base of the sensor and the bearing
housing structure.
Cementing Pad
Cementing pads eliminate drilling/tapping into the structure,
but provide high frequency capability approaching stud mounts.
Select the appropriate cementing pad for the application. Check
with your sensor supplier for the correct cementing pad and
instructions for installation. Here are some general guidelines for
installation:
Bore a spot face 1.1 times larger than the diameter of the
cement-ing pad to be installed on the bearing housing. Allow the
machine tool to groove and abrade the surface to prepare for the
adhesive bonding. Do not use cutting fluids as they may
con-taminate the bonding area.3-10
-
Chapter 3 - Installation
Apply the primer with a brush and let dry for 5 minutes.
Mix the Bi-pack thoroughly by removing the clip and working the
epoxy and catalyst into each other.
Apply a generous amount to the spot face and set the Cementing
pad with a turning motion.
Filet the adhesive around the sides of the pad to increase shear
strength and assist electrical iso-lation. The working time is
usu-ally 5 minutes but may vary depending the on the ambient
temperature. (See Fig. 3-8) Do not get epoxy in the sensor mounting
surface.
FIG. 3-8 CEMENTING PAD INSTALLATION
Test the electrical isolation from the pad to the machine with
an ohmmeter.
Apply a service removable threadlock such as Loctite 242 blue to
the tapped hole in the sen-sor.
Torque the sensor to the manu-facturers specifications.
Step 4. Connect the Sensor Waveform lead to the In Connection
(TB1-2) on the HI 5500 3-11
Series Signal Conditioning Module.
-
HI 5500 SERIES SIGNAL CONDITIONERS
Step 5. Connect the ground lead to the Common Connection (TB1-3)
on the HI 5500 Series Signal Conditioning Module. (See Fig.
3-9)
Wiring Diagram Example for 5501/55032/5533 with no Power
Supply
FIG. 3-9 WIRING DIAGRAM FOR 5501/5532/5533 WITH NO POWER
SUPPLY
+ 24CVDC
COM
RESET
ACK
INPUT #1
REF
INPUT #2
DUALSETPOINTMODULEHI 5532
ALARM #1 READ#1
AUX1
OUT1A
OUT1B
READ#2
AUX 2
OUT 2A
OUT 2B
TB1 TB2
ADJ.
ADJ.
ALARM #2
+ 24VDC
COM
4-20MA
COM
DCOUT
REF
OUTPUT SIGNALCONDITIONER
OK
SHD
IN
COM
REF
SIGH I 5 5 0 1 - 0 0 0 0 5 - 9 9 9 9 9
L 1 0 K - 0 1 . 0 V - 1 0 0 - P K
TB2
TB1
+ 24CVDC
COM
DISABLE
INPUT
REFRELAY CONTACTS AREDPDT 3 AMPS SUPPRESSED(MAYBE PROGRAMMED
FORFAIL SAFE. SEE MANUAL)
N.C.
COM
N.O.
TB1
TB2
RELAY MODULEHI 5533
SET
#1
N.C.
COM
N.O.
SET
#2
CO
NTA
CT
CO
NTA
CT
RELAY CONTACTS
TRANSDUCER SIGNAL (+)TRANSDUCER SIGNAL (-)
+ 24 VDCCOMMON
4-20 mA Output
+ 24 VDCDC CommonAlarm Reset
+ 24 VDCDC Common
N.C.CommonN.O.N.C.CommonN.O.
CABLE SHIELD
Relay Inhibit3-12
-
Chapter 3 - Installation
Wiring Diagram for Acceleration and Velocity Monitoring System
with Alarm and Danger Relays
FIG. 3-10 WIRING DIAGRAM FOR MONITORING SYSTEM WITH
+ 24VD C
COM
4-20MA
COM
DCOUT
RE F
OUTPUT SIGNA LCOND ITIONER
OK
SHD
IN
COM
RE F
SIGH I 5 5 0 1 - 0 0 0 0 5 - 9 9 9 9 9
L 1 0 K - 0 1 . 0 V - 1 0 0 - P K
TB2
TB1
+ 24C VD C
COM
RE SET
AC K
INPUT # 1
RE F
INPUT # 2
DUA LSETPOINTMODULEHI 5532
ALA RM #1 RE AD #1
AUX 1
OUT1A
OUT1B
RE AD #2
AUX 2
OUT 2A
OUT 2B
TB1 TB2
AD J.
AD J.
ALA RM #2
+ 24C VD C
COM
DISAB LE
INPUT
RE FRE LAY C ONTAC TS AR EDP DT 3 A MPS SUPPR ESSED(MAYB E
PROGRA MMED FORFAIL SAFE. SEE MA NUA L)
N.C.
COM
N.O.
TB1
TB2
RE LAY MODULEHI 5533
SET
#1
N .C.
COM
N.O.
SET
#2
CO
NTA
CT
CO
NTA
CT
ALARM RELAY CONTACTS
+ 24VD C
COM
4-20MA
COM
DCOUT
RE F
OUTPUT SIGNA LCOND ITIONER
OK
SHD
IN
COM
RE F
SIGH I 5 5 0 1 - 0 0 0 0 5 - 9 9 9 9 9
L 1 0 K - 0 1 . 0 V - 1 0 0 - P K
TB2
TB1
+ 24C VD C
COM
DISAB LE
INPUT
RE FRE LAY C ONTAC TS AR EDP DT 3 A MPS SUPPR ESSED(MAYB E
PROGRA MMED FORFAIL SAFE. SEE MA NUA L)
N.C.
COM
N.O.
TB1
TB2
RE LAY MODULEHI 5533
SET
#1
N .C.
COM
N.O.
SET
#2
CO
NTA
CT
CO
NTA
CT
DANGER RELAYCONTACTS
AC
AC
Mod
el 5
500P
S54
EB60
AC
TO
DC
PO
WE
R S
UPP
LY
DC COMMON
+24 VDC
InputPower
TRANSDUCER SIGNAL (+) WHITETRANSDUCER SIGNAL (-) BLACK
+ 24 VDCInputPowerRecorderOutput
COMMON4-20 mA Output
COMMON
+ 24 VDCInputPowerRecorderOutput
COMMON4-20 mA Output
COMMON
+ 24 VDCDC CommonAlarm Reset
InputPower
+ 24 VDCDC Common
InputPower
+ 24 VDCDC Common
N.C.CommonN.O.
N.C.CommonN.O.N.C.CommonN.O.3-13
ALARM AND DANGER RELAYS
-
HI 5500 SERIES SIGNAL CONDITIONERS3-14
-
Chapter 4 - Setup
CHAPTER 4 - SETUP
A Brief Description of Chapter 4
All information contained in Chapter 4 pertains to set-ting up
for a Bench Check and Calibration of the HI 5501/HI 5502 Signal
Conditioner Modules. All Ser-vice Personnel should read this
chapter before attempting to calibrate or perform a bench check of
any 5500 Series Module. Alternatives to any proce-dures explicit or
implied in this chapter are not recom-mended. Be sure to have on
hand, all the equipment necessary to perform these tests. All
safety precau-tions should be taken when performing a calibration
or bench check.
NOTE: The HI 5500 Series Signal Conditioners are shipped from
the factory with the jumpers set for default Auc-tioneering (or
group) mode unless specified at time or order and Active Reference
Voltage. When setting up a Monitoring system or any system where
more than one Signal conditioner is connected to Input #1 or Input
#2 on one HI 5532 Dual Set Point Control. See the Monitoring System
Setup Procedures below before setup of the Monitoring System.
Test Equipment and Tools Required
Phillips screw driver - #0 or #1 tip. Small Flat Head screw
driver for HI 5501 or HI
5502 terminals and potentiometers. Digital Multi-Meter
Must read DC milliamps Must be Broadband Must be capable of
accurate measure-
ments over the expected frequency ranges.
NOTE: Not all Digital Volt Meters are accurate below 50-60Hz.
Check your multi-meter specification sheet to verify that the
instrument accuracy is adequate below 50-60Hz. If the accuracy of
the meter is not adequate below 50-60Hz the calibration or
calibration check of the HI 5500 Module is not very accurate. A
rule of thumb for calibration is that the instrument you are using
to calibrate or check calibration should be 4 4-1
-
HI 5500 SERIES SIGNAL CONDITIONERS
times more accurate than the instrument being cali-brated.
Variable voltage DC Power supply - 0 to +30VDC at 250mA.
HI 813 Portable Shaker System (Desirable but not Mandatory)
Assorted test leads and connectors. Signal generator with
variable DC positive offset
capability (0 to +20VDC), required to calibrate the HI 5501 or
HI 5502
NOTE: If a signal generator with 0-20VDC offset capability is
not available, a second DC power supply is required to produce the
DC offset voltage required to simulate accelerometer bias voltage
(a 9VDC battery is sufficient).
Frequency Counter - Resolution to 0.1 Hz mini-mum
Oscilloscope
Quick Calibration Check Using An HI 813 Portable Shaker
Calibration System
Step 1. Make sure the transducer you are going to use is
calibrated.
Step 2. Make sure the HI 813 Portable Shaker is calibrated.
Step 3. Do not connect any equipment to the HI 813 Portable
Shaker unless it is OFF.
Step 4. Place the HI 813 Portable Shaker on a sur-face that is
free from any measurable vibration. If the shaker is placed on a
sur-face that is vibrating, the zero adjustment of the 4-20mA
output might be set artifi-cially high.
Step 5. Install transducer and cable assembly that is the same
type that will be used with the field installed HI 5500 Series
Signal Con-ditioners, onto the adapter head of the HI 813 Portable
Shaker System for Calibra-tion. (See Fig. 4-1)
Step 6. Connect the accelerometer cable, power/signal and common
leads or velocity trans-ducer signal and common leads to the
ter-4-2
-
Chapter 4 - Setup
minals marked IN and COM which are printed on the HI5501/HI 5502
top cover assembly. (See Fig. 4-2)
FIG. 4-1 FIELD CHECKOUT USING HI 813 CALIBRATION SHAKER
FIG. 4-2 CONNECTING TRANSDUCER LEADS TO HI 5501 MODULE
Step 7. Make sure the power supply is off. Step 8. Connect the
+24VDC Power Supply to the
TB2-1 and TB2-2 terminals on the HI 4-3
-
HI 5500 SERIES SIGNAL CONDITIONERS
5501/HI 5502. Do not apply power to the module yet. (See Fig.
4-1)
Step 9. Connect the Ammeter to the4-20mA and Com terminals. (See
Fig. 4-1)
Step 10. Using the +24VDC Power Supply apply power to the TB2-1
and TB2-2 terminals on HI 5501/HI 5502.
Step 11. Apply the +24VDC power to the module. Step 12. Turn ON
the HI 813 Portable Shaker. Step 13. On the shaker set the
Amplitude to the full
scale Gs that the 5501 or 5502 you are checking is rated for.
For example: If you bought an HI 5501 with a full scale rating of
10 Gs, set the amplitude for 10Gs.
Step 14. Check the ammeter. If the ammeter is reading 20mA
(within a tolerance range of 19.5 to 20.5mA), the HI 5500 Series
Mod-ule is in calibration.
Step 15. Set the Amplitude to 0Gs. If the ammeter is reading 4mA
( 5%), the HI 5500 Series module is in calibration.
Step 16. If the reading is outside the tolerance range, check to
be sure the cables are securely fastened and the transducer is
securely fastened to the shaker.
Step 17. If the reading continues to be outside the tolerance
range, calibrate the HI 5500 Series Module.
Calibration Setup Procedures Using a Frequency Generator and
Power Supply
It is important to note that the Frequency Generator creates a
known input frequency and the power sup-ply generates a know input
voltage thereby simulating the output from a transducer.
Step 1. Connect the Frequency Generator output to the HI 5501/HI
5502s transducer input terminals marked IN+ and COM-. The IN
terminal is positive and the COM ter-minal is negative. (See Fig.
4-3)
NOTE: If you do not have a 10VDC Power Supply you can use a 9VDC
battery in its place.4-4
-
Chapter 4 - Setup
FIG. 4-3 CALIBRATION EQUIPMENT SETUP
Step 2. Set the Frequency Generators DC offset to +10VDC.
NOTE: The AC (sinewave) output from the frequency genera-tor
remains OFF until an input signal is required.
Step 3. Using the +24VDC Power Supply apply power to the TB2-1
and TB2-2 terminals on HI 5501/HI 5502. (See Fig. 4-3)
Step 4. The Green LED on the cover should illu-minate indicating
that the circuitry senses an acceptable bias voltage at the
trans-ducer input terminals.
Step 5. If the LED does not light up turn off the power to the
system and check all the con-nections to be sure they are securely
fas-tened.
Step 6. Apply power to the system again. If the LED lights up
the system is ready for test-ing.4-5
-
HI 5500 SERIES SIGNAL CONDITIONERS
Step 7. If the LEd still does not light up, contact the Hardy
Customer Support Department for assistance.
Step 8. Go to Chapter 5 - Calibration.
Full Scale and Zero Scale Adjustment
This adjustment is required if you find the milliamp output at
full scale or zero scale is not stable. This adjustment is
performed by adjusting potentiometer R14 located on the Top Circuit
board (Prt. # 0235-0106-01) and potentiometers R24, R25 located on
the Bottom circuit board (Prt. # 0235-0105-01). (See Fig. 4-4)
FIG. 4-4 HI 5500 SERIES SIGNAL CONDITIONER CIRCUIT BOARDS
Step 1. Make sure that you have completed the Calibration setup
and have all the equip-ment installed correctly. (See Chapter 4 -
Setup/Calibration Setup Procedures)
Step 2. Check to be sure the +24VDC Input Power Supply is
OFF.4-6
-
Chapter 4 - Setup
Step 3. Use a phillips head screw driver and remove the two
phillips pan head screws that fasten the cover to the two
standoffs. (See Fig. 4-5)
FIG. 4-5 REMOVING THE MODULE COVER
Step 4. Lift off the cover and move it to the side. Be careful
not to damage the attached wires.
Step 5. Turn ON the +24VDC Input Power Sup-ply.
NOTE: The HI 5500 Series Signal Conditioners are cali-brated
using a +24VDC Power input.
Step 6. Set the frequency to full scale of the HI 5501/HI 5502
you are going to calibrate and the frequency generator power supply
to 10VDC.
NOTE: It is a good idea if you have two multimeters to install
them both. One to read output amperage (4-20mA) connected to
terminals TB2-3 and TB2-4 as in the diagram. One to read voltage
connected to terminals TB2-5 and TB2-6. (See Fig. 4-4)
Step 7. Set the multimeter to read volts and con-nect the
multimeter to terminals TB2-5+ 4-7
-
HI 5500 SERIES SIGNAL CONDITIONERS
and TB2-6- on the input side of the HI 5501/HI 5502 module. (See
Fig. 4-4)
Step 8. Use the small flat head screw driver and adjust the R14
potentiometer until the voltmeter reads 5.0VDC.
Step 9. Set the multimeter to read milliamps. Con-nect the
multimeter leads back to terminals TB1-3+ and TB1-4-.If the
milliamp read-ing is 20.0mA you are done.
Step 10. If the milliamp reading is more than 5% of 20.0mA go to
Step 11.
Step 11. Use the small flat head screw driver to adjust the R24
potentiometer until the meter reads 20mA.
Step 12. Set the frequency to 0 output. Step 13. Set the
multimeter to voltage. Connect the
leads to terminals TB2-5 and TB2-6. See if the output voltage
reading is 0 volts.
Step 14. Set the multimeter to read milliamps. Con-nect the
leads to terminals TB1-3 and TB1-4. The reading should be within 5%
of 4.0mA. If it is you are done and ready to calibrate.
Step 15. If the milliamp reading is above 5% of 4.0mA go to Step
16
Step 16. Use the small flat head screw driver to adjust the R25
potentiometer until the multimeter reads 4.0mA.
Step 17. Set the frequency to full scale again. Step 18. Again
check the voltage and milliamp
readings and set them as close to 5VDC and 20mA as possible by
adjusting the R24 potentiometer. (See Fig. 4-4)
Step 19. Continue going through this adjustment process by going
from full scale frequency to zero scale frequency until you have a
5VDC reading @ 20mA and a 0VDC reading @ 4mA 5%. Do the adjustment
process a few times. If you cannot get the voltage or amperage
readings within toler-ance, contact Hardy Instruments Customer
Support for further assistance. 4-8
-
Chapter 4 - Setup
CAUTION: NEVER ALLOW THE POWER SUPPLY VOLT-AGE TO EXCEED
+30VDC.
Step 20. Turn off the +24VDC power supply. Step 21. Place the
cover on the standoffs. Step 22. Use the phillips head screw driver
and
replace the two phillips pan head screws that fasten the cover
to the standoffs.
Input Sensitivity Selection
The Input Sensitivity of the HI 5501 & HI 5502 can be halved
or doubled relative to a HI 5501/5502s as delivered configuration
by changing the J4 jumpers. (See Fig. 4-6) The table below shows
the effect the J4 jumpers have on the full scale amplitude for all
HI 5501/5502. However, the voltage input column is valid for this
example and for the HI 5501 or HI 5502 calibrated for 1.0 EU full
scale and a transducer sensi-tivity of 100 mV/EU.
Examples:
X 1.0 - with J4 pins 2 to 3 jumpered. An HI 5501 or HI 5502
calibrated for 1.0 IPS full scale, will produce 20mA at the 4-20mA
output terminal when the vibration input is 1.0 IPS.
X 2.0 - with J4 pins 1 to 2 jumpered. An HI 5501 or HI 5502 will
produce 20mA output with a vibration input of 0.5 IPS 0-pk or
35.35mVrms.
X 0.5 - with jumpers at J4 removed entirely, the HI 5501 or HI
5502 will produce 20mA output with a vibration input of 2.0 IPS
0-pk. This in effect halves the sensitivity.
Pins Jumpered Full Scale MultiplierVoltage Input
Current Output
1 to 2 X2.0 35.35mVrms 20mA
2 to 3 X1.0 70.70mVrms 20mA
None X.5 141.4mVrms 20mA4-9
-
HI 5500 SERIES SIGNAL CONDITIONERS
This capability is designed to make it possible under some
circumstances to half or double the HI 5501 or HI 5502 full scale
range without the necessity for a complete re-calibration. After
changing jumpers we suggest a field checkout to confirm the HI
5501/02 accuracy was maintained. A change in jumper posi-tion
should maintain the calibration and should not cause a shift in
calibration greater than 2%.
FIG. 4-6 J4 SENSITIVITY JUMPER SETTINGS
Monitoring System Configuration
If no HI 5532 Dual Set Point Module is being used, or if one (1)
Set Point Module is being used per HI 5500 Series Signal
Conditioner, no jumper changes are required to the Signal
Conditioners. The factory set Default Modes are AM (Auctioneering
Mode) and AR (Active Reference Voltage) for individually shipped
modules.
Reference Voltage Jumper Setting Procedures
You need to set jumper (JP1) to Inactive Reference Mode when
more than one Signal Conditioner is con-nected to one HI 5532 Set
Point Module and if the modules are being powered with a +24VDC
Power Supply. (See Fig. 4-6) One module must be set for AR (the
master module) in group mode.4-10
-
Chapter 4 - Setup
Step 1. Turn the +24VDC Input Power Supply OFF.
Step 2. Use a phillips head screw driver and remove the two
phillips pan head screws that fasten the cover to the two
standoffs. (See Fig. 4-5)
Step 3. Lift off the cover and move it to the side. Be careful
not to damage the attached wires.
Step 4. Jumper JP1 is located on the Bottom board and can be
removed without taking off the Top board. (See Fig. 4-6)
FIG. 4-7 JUMPER SETTINGS FOR REFERENCE VOLTAGE
Step 5. To set the module Reference Voltage to Inactive.
Use a small needle nose pliers and gently lift the jumper off
the pins.
Step 6. To set the module Reference Voltage to Active.
Use a small needle nose pliers and gently press the jumper on
the pins.4-11
-
HI 5500 SERIES SIGNAL CONDITIONERS4-12
-
Chapter 5 - Calibration
CHAPTER 5 - CALIBRATION
A Brief Description of Chapter 5
Chapter 5 pertains to the calibration procedures for the HI 5500
Series Signal Conditioners. Alternatives to any procedures either
implied or explicitly con-tained in this chapter are not
recommended. In order for the signal conditioners to work properly,
it must be calibrated prior to operation. It is recommended that
the module be re-calibrated periodically or when not in use for
extended periods of time. Be sure to fol-low all the procedures in
this chapter completely to insure that the module is accurate. It
is very important that the user and service personnel be familiar
with the procedures contained in this chapter, before installing or
operating the HI 5500 Series Signal Con-ditioners.
Full Scale Output/Span Adjustment
The HI 5501/HI 5502 full scale output may be set with an
accelerometer or velocity transducer mounted on a Hardy HI 813
Portable Shaker System or by using the signal generator to produce
the AC and DC voltages required to represent the transducer output.
You must perform the setup (See Chapter 4) before calibration.
Bench Calibration Using the Hardy HI 813 Portable Shaker
System
NOTE: See Chapter 4 for the Setup using the HI 813 Portable
Shaker System.
Step 1. Calculate the Log Mid-Frequency by using the following
formula:
NOTE: See the calibration example below. This is one exam-ple
only, do not use these values for all transducers.
The HP Frequency = 00002 Hz The LP Frequency = 02000 Hz5-1
-
HI 5500 SERIES SIGNAL CONDITIONERS
Log Mid Frequency = AntiLog ((Log HP Freq + Log LP Freq) 2)
CALCULATION EXAMPLE FOR HI 5501 (MODEL
#5501-00002-02000-1.0V-100):
Log Mid Frequency = 10x ((Log2 + Log 2,000) 2)
Log Mid Frequency = 10x ((.3 + 3.3) 2)
Log Mid Frequency = 10x ((3.6) 2)
Log Mid Frequency = 10x (1.80)
The Log Mid Frequency for calibrating this HI 5501 = 63.09
Hz
HP Frequency is the corner frequency in Hz of the HP (Highpass)
filter.LP Frequency is the corner frequency in Hz of the LP
(Lowpass) filter.
Low Pass Frequency
High Pass Frequency
Log Mid Frequency
2 Hz 1 KHz 44.7 Hz
2 KHz 63.1 Hz
3 KHz 79.4 Hz
5 KHz 100 Hz
10 KHz 141.3 Hz
30 KHz 251.2 Hz
5 Hz 1 KHz 70.8 Hz
2 KHz 100 Hz
3 KHz 125.9 Hz
5 KHz 158.5 Hz
Table 5-1: Log Mid Frequency Table5-2
-
Chapter 5 - Calibration
Step 2. Turn the HI 813 Shaker amplitude knob to
counter-clockwise until it stops. This is the minimum
frequency.
Step 3. Set the HI 813 Shaker Function Display Switch to Acc,
Vel, or Disp to match the HI 5501/HI 5502 output mode. In our
example the HI 813 switch is set to Vel to match the V (velocity)
output mode of the HI 5501 model 5501-00002-02000-1.0V-100
Step 4. Set the HI 813 power switch to ON. Step 5. Adjust the HI
813 vibration amplitude to
the desired full scale amplitude which is shown in the display.
In our example the HI 5501 is calibrated for a full scale of 1.0
IPS, indicated by the 1.0V in the model number. Set the shaker
amplitude to 1.0 for our example by turning the amplitude knob
clockwise until 1.0 appears in the display.
Step 6. Adjust the HI 813 vibration frequency to the Log Mid
Frequency from the Log Mid Frequency Table 5-1or as calculated
using
10 KHz 223.9 Hz
30 KHz 398.1 Hz
10 Hz 1 KHz 100 Hz
2 KHz 141.3 Hz
3 KHz 177.8 Hz
5 KHz 223.9 Hz
10 KHz 316.2 Hz
30 KHz 562.3 Hz
Low Pass Frequency
High Pass Frequency
Log Mid Frequency
Table 5-1: Log Mid Frequency Table5-3
-
HI 5500 SERIES SIGNAL CONDITIONERS
the formula provided. The Log Mid Fre-quency in our example is
63.09Hz.
Step 7. Verify the Analog output reading to be 20 mA 5%.
Step 8. Check to be sure the +24VDC Input Power Supply is
OFF.
Step 9. Use a phillips head screw driver and remove the two
phillips pan head screws that fasten the cover to the two
standoffs. (See Fig. 5-1)
FIG. 5-1 REMOVE PHILLIPS PAN HEAD SCREWS
Step 10. Lift off the cover and move it to the side. Be careful
not to damage the attached wires.
Step 11. Turn ON the +24VDC Input Power Sup-ply.
Step 12. If necessary use a small flat head screw driver to
adjust the R14 potentiometer until the multimeter is reading 20.0mA
5%.
Step 13. This completes the calibration of an HI 5501 Signal
Conditioner that contains a 2Hz HP filter, a 2,000Hz LP filter and
one stage of integration with 20.0mA output when the vibration
input is 1.0 inches per second.5-4
-
Chapter 5 - Calibration
Step 14. This completes the span or full scale cali-bration
using the HI 813 Portable Shaker System to the full scale
amplitude.
Step 15. Shut OFF the +24VDC power supply. Step 16. Place the
cover on the standoffs. Step 17. Use the phillips head screw driver
and
replace the two phillips pan head screws that fasten the cover
to the standoffs.
Step 18. Using the formula above and the fre-quency range to be
monitored by the HI 5500 Series Signal Condition Monitor, calculate
the Log Mid-Frequency for each HI 5500 Series Monitor in your
system.
Bench Calibration Using a Frequency Generator and Power
Supply
NOTE: See Chapter 4 for the Setup using the Frequency Gen-erator
and Power Supply.
Step 1. Set the Frequency Generators DC Offset to +10VDC.
Step 2. Make sure the Green OK light is on. Step 3. Adjust the
frequency generators AC sine-
wave output to the voltage the vibration transducer would
produce when set to the full scale output for the HI 5501/HI 5502
module you are calibrating. For example:
To calibrate an HI 5501 for 20mA at 2 Gs of acceleration when
connected to a 100mV per G accelerometer, the frequency generators
sinewave out-put would be set to 200mV 0-pk or 141.1mV RMS.
Step 4. Check the milliamp reading. Step 5. Check to be sure the
+24VDC Input Power
Supply is OFF. Step 6. Use a phillips head screw driver and
remove the two phillips pan head screws 5-5
-
HI 5500 SERIES SIGNAL CONDITIONERS
that fasten the cover to the two standoffs. (See Fig. 4-5)
Step 7. Lift off the cover and move it to the side. Be careful
not to damage the attached wires.
Step 8. Turn ON the +24VDC Input Power Sup-ply.
Step 9. Use a small flat head screw driver to adjust the R14
potentiometer until the multimeter is reading 20.0mA 5%.
Step 10. This completes the calibration of an HI 5501 Signal
Conditioner that contains a 2Hz HP filter, a 2,000Hz LP filter and
one stage of integration with 20.0mA output when the vibration
input is 1.0 inch per second.
Step 11. This completes the span or full scale cali-bration
using the Frequency Generator to duplicate the full scale
amplitude.
Current Limit Test The Current Limit Test insures the 4-20mA
circuitry is properly limiting the output current to approxi-mately
34mA.
Step 1. With the Frequency Generator apply 100Hz sinewave of
100mV RMS ampli-tude to the HI 5501 transducer input termi-nals
with the DC Offset set to +10VDC.
Step 2. Increase the AC input voltage to approxi-mately 2V RMS
while observing the 4-20mA current output. Current limiting should
begin to occur when the input volt-age gets to about 1.875V RMS,
and limit the output current to approximately 30 to 40mA.
Step 3. Shut off the +24VDC Input Power Supply. Step 4. Place
the cover on the standoffs. Step 5. Use the phillips head screw
driver and
replace the two phillips pan head screws that fasten the cover
to the standoffs.
Final Check Step 1. Turn ON the +24VDC Input Power
Sup-ply.5-6
-
Chapter 5 - Calibration
Step 2. Check the OK light and the full scale output again to
make sure no wiring was shorted on reassembly.
This completes the bench calibration of the HI 5501 or HI 5502
Signal Conditioner. The mod-ule(s) is fully calibrated and ready
for field instal-lation.
Calculation of HI 5501/5502 Full Scale Calibration voltage
Acceleration or Velocity
When the connected transducers output matches the HI 5501/HI
5502/s output mode, no signal integration is required. For this
condition, full scale calibration voltage is derived by multiplying
the number of EUs full scale by the transducers milli-volt per EU
Sensi-tivity.
For example:
HI 5501 w/Accel IN - Accel OUT:
HI 5501-00010-02000-5.0G-100 - Pk
= Calibration Voltage = EUs Full Scale * milli-volts per EU
= 5.0 * 100mV = Calibration Voltage = 500mV
HI 5502 w/ Vel IN - Vel OUT:
HI 5502-00002-01500-2.0V-400
= Calibration Voltage = EUs Full Scale * milli-volts per EU
= 2.0 * 400mV = Calibration Voltage = 800mV
Accelerometer or Velocity Input with
When the transducer input signal must be single or double
integrated to provide the desired vibration 5-7
Signal Integration parameter, the Hardy HI 5500 Signal Condition
can
-
HI 5500 SERIES SIGNAL CONDITIONERS
contain one or two stages of integration. With integra-tion
installed, the transducer input voltage required to produce the HI
5501/HI 5502s integrated full scale output must be calculated and
used as the input volt-age when calibrating the 4-20mA output.
There are three Procedures to follow when deriving the full
scale calibration voltage for HI 5500 Series Signal Conditioners
containing one or two stages of signal integration.
1. Calculate the Log Mid-Frequency (See proce-dures above)
2. Convert Output Eus F.S. to Input EUs F.S at f (Log
Mid-Freq).
3. Convert derived Input Eus F.S. to Volts for the specific
transducer.
Log Mid-Frequency
Get from Table 5-1.
Convert Output EUs F.S. to Input EUs for Three Different HI
5501/HI 5502 Configurations
1. HI 5501 with Accel to Vel Single Integration requires Vel to
Accel conversion:
Accel = 0.0162 * Vel EUs F.S. * f (Log Mid-Freq)
Three Examples Based on Part Numbers
Prt. # HI-5501-00005-01500-2.0V-100 Covers the Accel to Velocity
Configuration:
Accel = 0.0162 * V (Vel EUs F.S.) * f (Log-Mid-Freq)Accel =
0.0162 * 2.0 * 86.6Accel = 2.8064-20mA F.S. Calibration Voltage =
281mV pk.
This example covers an HI 5501, acceleration input signal, which
requires double integration to displace-ment.
Prt. # HI 5501-00003-01000-5.0D-100 Covers the 5-8
Accel to Displacement Configurations:
-
Chapter 5 - Calibration
Log Mid-Freq = 54.77 HzAccel =.0511 * f2 (Log Mid-Freq2 * Disp
EUs F.S. (inches)Accel =.0511 * (54.77)2 *.005Accel =.7664-20mA
F.S. Calibration Voltage = 76.6 mV pk.5-9
-
HI 5500 SERIES SIGNAL CONDITIONERS5-10
-
Chapter 6 - Troubleshooting
CHAPTER 6 - TROUBLESHOOTING
A Brief Description of Chapter 6
All the information in Chapter 6 pertains to the
trou-bleshooting and resolution of operating problems that may
occur. All maintenance personnel and users should be familiar with
Chapter 6 before attempting to repair an HI 5500 Series Signal
Conditioner Mod-ule.
Problem: Green Light Not Illuminated
Step 1. Use a Volt meter and check the Loop Power (Terminals
TB2-1 & 2) to see if you have +24VDC to the board. If the
voltage is not +24VDC there is a problem with the circuit board or
the power source.
Step 2. Use a Volt meter and check terminals TB2-5&6 to see
if you have 5VDC. If the voltage is not 5VDC there is a problem
with the circuit board. Go to Step 7.
Step 3. Turn the Power from your +24VDC Source OFF.
Step 4. Remove the Cover and check the BNC and LED connectors to
see if they are con-nected to the proper pins or completed seated
on the pins. Note: There is a white dot on the connector which
should match the position of the dot on the circuit board. If they
do not match up, re-connect the connector(s) so they do.
Step 5. After each Step, check to see if the green OK light
comes on. If it does not got to another step until you have found
the problem.
Step 6. If the green OK light still does not come on after going
through all the steps. Con-tact Hardy Instruments, Customer Support
Department for assistance.
Check Output Amperage
Step 1. Use an ammeter and check terminals TB2-3&4 to see if
you have 20mA. If the amperage is not 20mA there is a problem with
the circuit board.
Step 2. Check to be sure that the 4-20mA output is suppressed to
0mA whenever the DC bias 6-1
-
HI 5500 SERIES SIGNAL CONDITIONERS
voltage is outside of the normal +3VDC to +18 VDC OK range. If
the 4-20mA is not suppressed to 0mA when the DC bias voltage is
outside of the normal range there is a problem with the circuit
board.6-2
SIGNAL CONDITIONER5500 SERIESTable of ContentsTable of
IllustrationsChapter 1 - OverviewA Brief Description of Chapter
1About Hardy ManualsDescriptionIndustriesApplicationsOptionsHI
5500PS Power SupplyTransducersNEMA EnclosuresBack Plate/Not
WiredBack Plate/ Wired
Chapter 2 - SpecificationsA Brief Description of Chapter
2Specifications for a Standard HI 5000 Series Signal Conditioning
ModuleElectrical CharacteristicsInput Sensor SensitivitySensor
Excitation CurrentCurrent OutputVoltage OutputMaximum Load
ResistanceFrequency Range (3 dB)Vibration RangeSensor Fault
Power RequirementsPhysical CharacteristicsMountingPhysical
DimensionsLengthWidthHeight
Weight
Environmental CharacteristicsTemperature
RangeOperatingStorage
Humidity
Ordering Information for the HI 5501Ordering Information for the
HI 5502HI 5501E (Only)Temperature RangeOperating
HumidityEnclosure RequirementsApprovals
Optional EquipmentHI 5500PS Power
SupplyRegulationEnvironmentalOperatingStorageTemperature
Coefficient
DimensionsPhysicalWeight
Output PowerOptionsHI 5532HI 5533
Chapter 3 - InstallationA Brief Description of Chapter
3UnpackingPre-Installation Engineering ProceduresElectrical Wiring
PrecautionsInstalling the HI 5500 Standard Module Onto a DIN
RailElectrical Installation ProceduresLED OK IndicatorBNC
ConnectorTerminal
AssignmentsTB2-1,2TB2-3,4TB2-5,6TB1-1TB1-2TB1-3TB1-4TB1-5
Installing modules in an Enclosure (See Fig. 3-5)Pump Monitoring
with Transducers and HI 5500 Series ModuleThreaded StudCementing
Pad
Wiring Diagram Example for 5501/ 55032/5533 with no Power
SupplyWiring Diagram for Acceleration and Velocity Monitoring
System with Alarm and Danger Relays
Chapter 4 - SetupA Brief Description of Chapter 4Test Equipment
and Tools RequiredQuick Calibration Check Using An HI 813 Portable
Shaker Calibration SystemCalibration Setup Procedures Using a
Frequency Generator and Power SupplyFull Scale and Zero Scale
AdjustmentInput Sensitivity SelectionMonitoring System
ConfigurationReference Voltage Jumper Setting Procedures
Chapter 5 - CalibrationA Brief Description of Chapter 5Full
Scale Output/ Span AdjustmentBench Calibration Using the Hardy HI
813 Portable Shaker SystemBench Calibration Using a Frequency
Generator and Power SupplyCurrent Limit TestFinal Check
Calculation of HI 5501/ 5502 Full Scale Calibration
voltageAcceleration or VelocityAccelerometer or Velocity Input with
Signal IntegrationLog Mid- FrequencyConvert Output EUs F.S. to
Input EUs for Three Different HI 5501/HI 5502 ConfigurationsThree
Examples Based on Part Numbers
Chapter 6 - TroubleshootingA Brief Description of Chapter
6Problem: Green Light Not IlluminatedCheck Output Amperage