® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume® 3D Overview Hi-lume® 3D architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements. By providing industry leading performance with a full-range of 100% to less than 1% fluorescent dimming, Hi-lume® 3D ballasts enable you to provide the ideal visual environment for any application. Features • Continuous, flicker-free dimming from 100% to 0.7% for T8, 1% for T5 and T5HO, and 5% for T5 twin-tube • 100% compatible with all Lutron® 3-wire fluorescent controls and EcoSystem® digital controls for consistent fixture-to-fixture dimming performance • Compatible with Energi Savr NodeT with EcoSystemR devices, GRAFIK EyeR QS control unit, PowPakT dimming module with EcoSystemR connection, and QuantumR software, allowing for integration into an existing or planned EcoSystemR lighting control solution. • Programmed rapid start design preheats lamp cathodes before applying full arc voltage to ensure full-rated lamp life while dimming and cycling • Lamps turn on to any dimmed level without going to full brightness • Low harmonic distortion throughout the entire dimming range maintains power quality • Frequency of operation ensures that ballast does not interfere with infrared devices operating between 38 kHz and 42 kHz • Inrush current limiting circuitry eliminates circuit breaker tripping, switch arcing, and relay failure • Ballasts maintain consistent light output for different lamp lengths, ensuring fixture-to-fixture uniformity • Ultra-quiet operation • Ballast protected from miswires of any input power to control lead, or from lamp leads to each other and/or ground Hi-lume® 3D, case type C 1.18 in (30 mm) W x 1.00 in (25 mm) H x 18.00 in (457 mm) L Hi-lume® 3D, case type G 2.38 in (60 mm) W x 1.00 in (25 mm) H x 9.50 in (241 mm) L • 100% performance tested and burned in at factory • Non-volatile memory restores all ballast settings after power failure • Buy American Act (BAA) models available; see Model List for specific availability • RoHS compliant • NOM certified models available; see Model List for specific availability • Custom ballast factors available for UL or CSA listed products. Design tool and specifications can be found at www.lutron.com/ballasttool
14
Embed
Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 1 09.04.12
Hi-lume® 3D Overview
Hi-lume® 3D architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements. By providing industry leading performance with a full-range of 100% to less than 1% fluorescent dimming, Hi-lume® 3D ballasts enable you to provide the ideal visual environment for any application.
Features
•Continuous,flicker-freedimmingfrom100%to0.7%for T8, 1% for T5 and T5HO, and 5% for T5 twin-tube
•100%compatiblewithallLutron® 3-wire fluorescent controls and EcoSystem® digital controls for consistent fixture-to-fixture dimming performance
•CompatiblewithEnergiSavrNodeT with EcoSystemR devices, GRAFIK EyeRQScontrolunit,PowPakT dimming module with EcoSystemR connection, and QuantumR software, allowing for integration into an existing or planned EcoSystemR lighting control solution.
•Programmedrapidstartdesignpreheatslampcathodes before applying full arc voltage to ensure full-rated lamp life while dimming and cycling
•ClassPthermallyprotected•MeetsANSIC82.11HighFrequencyBallastStandard•MeetsFCCPart18Non-Consumerrequirements forEMI/RFIemissions•MeetsANSIC62.41CategoryAsurgeprotection standardsuptoandincluding4kV•ManufacturingfacilitiesemployESDreduction practices that comply with the requirements ofANSI/ESDS20.20•Lutron® Quality Systems registered to ISO9001.2008
Warranty•5-yearlimitedwarrantywithLutron® field service
commissioning (3-year standard warranty) from date of purchase.ForadditionalWarrantyinformation,pleasevisit: www.lutron.com/TechnicalDocumentLibrary/Ballast%20and%20Driver%20Warranty.pdf
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 3 09.04.12
Hi-lume® 3D Ballasts for Linear and U-Bent T8 Lamps For proper dimming all lamps must comply to accepted standards, 17, 25, 32 and 40 W (NEMA LL9-2009)Not for use with Reduced Wattage Lamps Lamp Type
Lamp Watts (length)
Lamps per Ballast
Case Size
Hi-lume® 3D Model Number
Input Voltage (V~)
Ballast Current (A)
Ballast Factor (BF)
Input Power (W)
System Lumens3 (lm)
System Efficacy3 (lm/W)
Ballast Efficacy Factor (BEF)
Relative System Efficacy (RSE)
T8 and U-Bent
40W (60in [1524mm])
1 C H3DT840CU110 120240277
0.380.180.16
1.001.001.00
43.843.042.8
380038003800
878889
2.282.332.34
0.910.930.94
1 C H3DT840CU117 120240277
0.420.210.18
1.171.171.17
50.649.449.6
444644464446
889090
2.312.372.36
0.920.950.92
2 C H3DT840CU210 120240277
0.760.370.32
1.001.001.00
90.988.488.9
760076007600
848686
1.101.131.13
0.900.910.94
2 C H3DT840CU217 120240277
0.850.410.36
1.171.171.17
100.397.298.2
889288928892
899291
1.171.201.19
0.930.960.95
32W (48in [1219mm])
1 C H3DT832CU1101,2 120240277
0.290.140.12
1.001.001.00
34.833.633.2
300030003000
868990
2.872.983.01
0.920.950.96
G H3DT832GU1101,2 120240277
0.130.150.30
1.001.001.00
34.835.035.1
300030003000
868685
2.872.852.85
0.920.910.91
1 C H3DT832CU1171,2 120240277
0.340.170.15
1.171.171.17
40.840.841.6
351035103510
868684
2.872.872.82
0.920.920.90
G H3DT832GU1171 120240277
0.150.170.34
1.171.171.17
39.740.040.1
351035103510
888888
2.952.922.92
0.940.940.93
2 C H3DT832CU2101,2 120240277
0.570.280.24
1.001.001.00
68.467.266.5
600060006000
888990
1.461.491.50
0.940.950.96
G H3DT832GU2101,2 120240277
0.240.280.54
1.001.001.00
65.766.366.5
600060006000
919090
1.521.511.50
0.970.970.96
2 C H3DT832CU2171,2 120240277
0.650.320.28
1.171.171.17
78.076.877.6
702070207020
909191
1.501.521.51
0.960.980.97
G H3DT832GU2171 120240277
0.280.310.67
1.171.171.17
75.476.576.9
702070207020
939291
1.551.531.52
0.990.980.97
3 G H3DT832GU3101,2 120240277
0.830.400.37
1.001.001.00
99.696.0102.5
900090009000
909488
1.001.040.98
0.961.000.94
3 G H3DT832GU3171 120240277
0.950.470.41
1.171.171.17
114.0112.8113.6
10,53010,53010,530
929393
1.031.041.03
0.991.000.99
Continued on next pageNotes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 4 09.04.12
Hi-lume® 3D Ballasts for Linear and U-Bent T8 Lamps (continued) For proper dimming all lamps must comply to accepted standards, 17, 25, 32 and 40 W (NEMA LL9-2009)Not for use with Reduced Wattage Lamps Lamp Type
Lamp Watts (length)
Lamps per Ballast
Case Size
Hi-lume® 3D Model Number
Input Voltage (V~)
Ballast Current (A)
Ballast Factor (BF)
Input Power (W)
System Lumens3 (lm)
System Efficacy3 (lm/W)
Ballast Efficacy Factor (BEF)
Relative System Efficacy (RSE)
T8 and U-Bent
25W (36in [914mm])
1 C H3DT825CU1102 120240277
0.260.110.11
1.001.001.00
31.226.430.5
190019001900
617262
3.213.793.28
0.800.950.82
1 C H3DT825CU117 120240277
0.280.140.12
1.171.171.17
33.633.633.2
222322232223
666667
3.483.483.52
0.870.870.88
2 C H3DT825CU2102 120240277
0.470.230.20
1.001.001.00
56.455.255.4
380038003800
676969
1.771.811.81
0.890.910.90
2 C H3DT825CU217 120240277
0.510.250.22
1.171.171.17
61.260.060.9
444644464446
737473
1.911.951.92
0.960.980.96
17W (24in [610mm])
1 C H3DT817CU1101,2 120240277
0.180.090.08
1.001.001.00
21.621.622.2
130013001300
606059
4.634.634.51
0.790.790.77
G H3DT817GU1101,2 120240277
0.080.090.19
1.001.001.00
22.922.622.8
130013001300
575857
4.374.424.39
0.740.750.75
1 C H3DT817CU1171 120240277
0.190.100.08
1.171.171.17
22.824.022.2
152115211521
676369
5.134.885.28
0.870.830.90
G H3DT817GU1171 120240277
0.090.100.20
1.171.171.17
25.325.325.6
152115211521
606059
4.624.624.57
0.790.790.78
2 C H3DT817CU2101,2 120240277
0.350.180.15
1.001.001.00
42.043.241.6
260026002600
626063
2.382.312.41
0.810.790.82
G H3DT817GU2101,2 120240277
0.140.160.32
1.001.001.00
38.738.439.1
260026002600
676866
2.582.602.56
0.880.890.87
2 C H3DT817CU2171 120240277
0.350.170.15
1.171.171.17
42.040.841.6
304230423042
727573
2.792.872.82
0.950.980.96
G H3DT817GU2171 122240277
0.150.180.36
1.171.171.17
41.841.743.1
304230423042
737371
2.802.812.71
0.950.950.92
3 H3DT817GU3101 120240277
0.480.250.21
1.001.001.00
57.660.058.2
390039003900
686567
1.741.671.72
0.890.850.88
3 H3DT817GU3171 120240277
0.550.270.23
1.171.171.17
66.064.863.7
456345634563
697072
1.771.811.84
0.900.920.94
Notes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 5 09.04.12
Lamp Type
Lamp Watts (length)
Lamps per Ballast
Case Size
Hi-lume® 3D Model Number
Input Voltage (V~)
Ballast Current (A)
Ballast Factor (BF)
Input Power (W)
System Lumens3 (lm)
System Efficacy3 (lm/W)
Ballast Efficacy Factor (BEF)
Relative System Efficacy (RSE)
T5 Linear
28W(45.2in [1148mm])
1 C H3DT528CU1101,2 120240277
0.280.130.12
1.001.001.00
33.631.233.0
290029002900
869388
2.983.213.63
0.830.900.85
2 C H3DT528CU2101,2 120240277
0.520.260.22
1.001.001.00
62.462.459.8
580058005800
939397
1.601.601.67
0.900.900.94
21W(33.4in [848mm])
1 C H3DT521CU1101,2 120240277
0.220.110.10
1.001.001.00
26.326.326.6
210021002100
808079
3.813.813.76
0.800.800.79
2 C H3DT521CU2101,2 120240277
0.410.200.18
1.001.001.00
48.748.648.5
420042004200
868687
2.052.062.06
0.860.860.87
14W(21.6in [549mm])
1 C H3DT514CU1101,2 120240277
0.160.080.07
1.001.001.00
19.219.219.4
135013501350
707070
5.215.215.16
0.730.730.72
2 C H3DT514CU2101,2 120240277
0.300.150.13
1.001.001.00
36.036.036.0
270027002700
757575
2.782.782.78
0.780.780.78
Hi-lume® 3D Ballasts for Linear T5 Lamps For proper dimming all lamps must comply to accepted standards, 14 W (60081-IEC-6520), 21 W (60081-IEC-6530) and 28 W (60081-IEC-6640)Not for use with Reduced Wattage Lamps
Notes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 6 09.04.12
Lamp Type
Lamp Watts (length)
Lamps per Ballast
Case Size
Hi-lume® 3D Model Number
Input Voltage (V~)
Ballast Current (A)
Ballast Factor (BF)
Input Power (W)
System Lumens3 (lm)
System Efficacy3 (lm/W)
Ballast Efficacy Factor (BEF)
Relative System Efficacy (RSE)
T5HO 54W(45.2in [1148mm])
1 C H3DT554CU1101,2 120240277
0.540.260.23
1.001.001.00
64.862.463.7
500050005000
778078
1.541.601.57
0.830.870.85
2 C H3DT554CU2101,2 120240277
0.950.480.42
1.001.001.00
114.0115.2116.3
100001000010000
888786
0.880.870.86
0.950.940.93
39 W(33.4in [848mm])
1 C H3DT539CU1101,2 120240277
0.370.190.17
1.001.001.00
44.444.946.0
350035003500
797876
2.252.232.17
0.880.870.85
2 C H3DT539CU2101,2 120240277
0.700.350.29
1.001.001.00
84.084.081.4
700070007000
838386
1.191.191.23
0.930.930.96
24W(21.6in [549mm])
1 C H3DT524CU1101,2 120240277
0.250.120.10
1.001.001.00
30.028.827.7
200020002000
676972
3.333.473.61
0.800.830.87
2 C H3DT524CU2101,2 120240277
0.460.230.20
1.001.001.00
54.655.255.4
400040004000
737272
1.831.811.81
0.880.870.87
Hi-lume® 3D Ballasts for Linear T5HO Lamps For proper dimming all lamps must comply to accepted standards, 24W (60081-IEC-6620), 39 W (60081-IEC-6730), 54 W (60081-IEC-6840) Not for use with Reduced Wattage Lamps
Notes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 7 09.04.12Hi-lume® 3D Ballasts for Twin-Tube T5 Lamps Not for use with Reduced Wattage Lamps
•Hi-lume® 3D ballast line voltage and 3-wire input terminalsacceptone18to16AWG(0.75to1.5 mm2) solid copper wire per terminal.
Emergency
•ForemergencywiringpleaseseeLutron® AppNote#106.
E1E2
NEU LINE
HOTDH
Class 2Bus
E1E2
NEU
HOTDH
Class 2Bus
LUTRON
LINEHot / Black
3-Wire Dimmer
Ground
Green
GroundRed
Yellow
Whi
te
Ora
nge
Black
White
Neutral
Ground
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming
369280h 10 09.04.12
Hi-lume® 3D Wiring Diagrams
E1E2
NEU
HOTDH
Class 2Bus
E1E2
NEU
HOTDH
Class 2Bus
LINELINE
Ballast Terminals
Ballast Terminals
EcoSystem® Digital Link Overview
•TheEcoSystem®DigitalLinkwiring(E1andE2)connects digital ballasts and drivers together to form a lighting control system.
•SensorsdonotdirectlyconnecttoHi-lume® 3D ballasts.•E1andE2(EcoSystem®digitallinkwires)arepolarity
insensitive and can be wired in any topology.•AnEnergiSavrNodeTM with EcoSystem® unit,
GRAFIK Eye® QS control unit with EcoSystem®, or Quantum® dimming module with EcoSystem® provides power for the EcoSystem®digitallinkwhichsupportsupto64digitalballastsorLEDdrivers,64 occupantsensors,16daylightsensorsand64wallstationsorIRreceivers.
•PowPakTM dimming module with EcoSystem® provides power for the EcoSystem®digitallinkwhichsupportsupto32digitalballastsorLEDdrivers, 6 occupantsensors,1 daylightsensorand9 Pico® wireless controllers.
•AllEcoSystem®DigitalLinkprogrammingiscompletedby using the Energi Savr App for an Apple iPad, iPod Touch or iPhonemobiledigitaldevice;GRAFIKEyeR QS with EcoSystem®,PowPakT dimming module with EcoSystem® ; or Quantum® System.
Lamp SocketsLutronrequiresandNEMA®recommendssocketscomplyingwithIEC60400.InspectsocketsformarkstoensurethesocketcomplieswithIEC60400. Twoexamplesofthesemarksare:E and Q. Socketsmust have a Zmarkaswell.UseRapidStartsockets.DO NOTuseInstantStartsockets.SeeLutron® AppNote#122orNEMA®docLSD-34-2006.
Lamp Socket Wiring TesterUseSocketTester(FDB-LSWT-T5/T8)toverify proper lamp holder wiring.Available for purchase at www.lutronstore.com
Lamp MountingManyfluorescentlampsocketsareavailablewithmounting slots to vary the height of the lamp away from the grounded metal surface. Having a fluorescent lamp too close to the grounded metal will reduce lamp life. Having a fluorescent lamp too far awayfromthegroundedmetalwillmakethelampflickerornotturnonatall.Pleasenotethatallofthelamp heights are measured between the grounded metal surface and the glass wall of the lamp.
Mounting for T8 LampsMountlamps1/8to3/4in(3.2to19mm)awayfromthe grounded metal surface.
Mounting for T5 and T5HO LampsMountlamps1/16to3/8in(1.6to9.5mm)awayfromthe grounded metal surface.
Mounting for T5 Twin Tube LampsMountlamps1/16to1/2in(1.6to13mm)awayfromthe grounded metal surface.
Ballast Operating TemperatureBallastcasetemperaturemustnotexceed75 °Catany point on the ballast.
Cold Air FlowEnsurethatnocoldair(fromHVACsystem,etc)isblowingacrossthelamps.CoolingthelampwillcauseperformanceissuesasnotedinNEMA LSD-34.
Wiring and GroundingBallast and lighting fixture must be effectively grounded. Ballasts must be installed per national and local electrical codes.
ATTENTION FACILITIES MANAGERS
PERFORMANCE
Lamp SeasoningConsultlampmanufacturer’srecommendationsonlamp seasoning prior to dimming.
SERVICE
Replacement PartsUseLutron® replacement parts with exact model numbers.ConsultLutronifyouhaveanyquestions.
Further InformationFor further information, please visit us at www.lutron.com/ballastsorcontactour24-hourTechnicalSupportCenterat1.800.523.9466.
IMPORTANT: Lamps must never touch ground plane and should be placed without obstruction.