with care for your comfort! HEAT RECOVERY UNITS TANGRA EVB HiE with care for your comfort!
with care for your comfort!
HEAT RECOVERY UNITSTANGRA EVB HiE
with care for your comfort!
2 3www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
Company profile
Gold medal from ITF Plovdiv
2003
Award of the German Economy
2013
Innovative Enterprice from the President
2016
Excellence in Innovation from the President
2019
TANGRA is specialized in the field of ventilation, heating and air conditioning equipment and HVAC engineering. The company was recovered in 1989 by Dipl. Eng. July Armianov. His father has founded the commercial and production company TANGRA-Lazar Armianov in the late 1930’s. After WW II the company was nationalized by the government and private business was forbidden in Bulgaria till 1989.
Today TANGRA employs approximately 140 people and has industrial facilities with total floor area around 5000 sq. m. The company uses highest class of production equipment and qualified specialist.
In the portfolio of the enterprise are also HVAC design bureau, R&D department and HVAC laboratory, installing and service teams, 3 commercial centers in Bulgaria and wide sales and service network in Europe.
TANGRA is company with a sense of the typical values of the family-run corporations. July Armianov and Ivan Armianov are in charge of the business and management of the enterprise. TANGRA is run in constant striving for dvelopment of energy efficient equipment and projects, innovation, and last but not least - maintaining high quality standards.
TANGRA provides its partners with complete solutions and HVAC systems. Our aim is to support the best indoor microclimate using high efficiency equipment with minimal energy consumption and top life cycle cost.
TANGRA has rich experience in execution of HVAC systems for commercial centers, public and office buildings, hotels and spa complexes, industrial enterprises and factories, hospitals and recreation centers, swimming pools, automobile showrooms and service centers.
TANGRA guarantee and secure its partners, consultants, designers, architects and investors when choosing a solution for their project. Some of the major benefits for all our partners are:
• Providing the optimal solution with best indoor climate combined with reasonable initial investment and low energy and operating costs.
• High reliability and quality due to expertise in engineering, developing, manufacturing, testing, installing and maintenance during the life cycle of HVAC systems.
• Large selection of components, materials and accessories on stock in order to provide short delivery terms. This is a key strength and opportunity to be your complete HVAC solution partner.
• Customized tailor-made solutions thanks to our professionalism and commitment of our employees lead to space and system efficiency of every single TANGRA product and HVAC system we execute.
• 100 % Production in EU
We believe that the satisfied customers are our best advertisement!
MSc. Ivan ArmianovManager Sales Department
Dipl. eng. July ArmianovCEO “TANGRA-AV” Ltd.
Dipl. eng. July ArmianovCEO “TANGRA-AV” Ltd.
With care for your comfort!
4 5www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
Certificates and Awards
In all activities of TANGRA, a Quality Management System ISO 9001 is implemented. In addition, the management, the production and engineering have constant policy of improvement of products and services, in order to increase the satisfaction of our customers.
Based on the expertise and customer service we offer, TANGRA energy recovery ventilation units are equipped with supreme energy efficiency components. These machines are installed in buildings passing sustainability assessment and rating programs like BREEAM, LEAD, EDGE etc.
Being motivated to minimize the impact on environment, TANGRA has implemented Environmental Management System ISO 14001. All processes are considered and we work to minimize our energy consumption, waste and carbon footprint.
TANGRA is the first corresponding member of Eurovent Association from Bulgaria. Contributing to Eurovent’s activities in the area of EU legislation, standardisation, and industry promotion, increasing awareness on European Union Ecodesign legislation in Bulgaria.
Our company is a member of the Bulgarian Machine Building Chamber and Dipl. Eng. July Armianov is a member of the management board of the chamber. The company is also F-Gas certified for working with different refrigerants.
TANGRA is a member of the Bulgarian Construction Chamber and is listed in the Central Professional Register of the Builders performing building in all categories from Ist to Vth.
Eurovent Certita Certification has tested and certified the series of standard and hygienic air handling units produced by TANGRA. TANGRA AHU Modular range is designed for air volumes between 3000 and 70000 m3/h.
DEDAL Attestation and Cerification tested and certified our Smoke and heat control systems. Annual audits are performed to guarantee the highest quality of our smoke duct systems.
Our air handling units are tested for the housing characteristics and performance by TUV Rheinland. The testing standards certify the AHUs according to EN 1886, EN 13053, EN 13779, VDI 6022, DIN 1946, etc.
High efficiency plate heat exchangers air to air produced by TANGRA are also certified by Eurovent Certitia Certification in 2018. Software for precise calculation is available for download on our web site.
The complete range of pellet boilers and air heaters/ coolers, produced by TANGRA are tested for performance and characteristics by TUV Rheinland. The excelent parameters are confirmed by the results for both ranges.
All products of TANGRA comply with the applicable EU directives, regulations, laws and are marked with CE according to 2006/42/EC. Ecodesign directives are implemented. Heat recovery systems and air handling units conform with directives 1253/2014 & 1254/2014, as well as with directive 2009/125/EC.
6 7www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
Company portfolio
RESEARCH AND DEVELOPMENTA team of qualified specialists is in charge with new products development, including material design, production and implementation. We are in constant contact with our partners in Europe and develop new products to meet their needs.
HVAC DESIGN BUREAUExperiensed engineers are responsi-ble for the design of HVAC systems and for project management. The regular professional trainings allow TANGRA to be on the forefront of the actual norms and legislation and to provide optimal finan-cial and energy efficient solutions.
Heat recovery units range
HVAC AcademyBased on the years of experience and constant desire for improvement, the company has developed TANGRA HVAC Academy. New products and solutions, technical trainings, legislation changes and increased knowledge of technicians, engineers and specialists in the HVAC area are the main focuses of TANGRA Academy.
HVAC SoftwareTANGRA has developed and provides free of charge selection software for heat recovery ventilation, plate heat exchang-ers and air handling units. Software tools help engineers, partners and customers in precise and easy calculations in their work in front of customers, investors and stake holders.
INSTALLATION AND COMMISSIONINGOur installation team is focused on the execution of HVAC systems, providing all services and takeing care of execution of mechanical works, according to a sched-ule, providing on-site tests and integra-tion of the HVAC systems with building management system (BMS). Startup and precise tuning after all construction and installation activities are also provided.
INDUSTRIAL ENTERPRISEOur production facilities are equipped with specialized industrial machines for manufacturing of air handling units and heat recovery ventilation, centrifugal fans and accessories, pellet boilers and air heaters, ventilation grilles and diffusers, ventilation elements and air ducts.
SERVICE AND MAINTENANCEPost-installation, periodic checks and preventive maintenance visits help to extend the life of the HVAC equipment. TANGRA`s dedicated helpdesk provides short response time, remote service help and wide stock of spare parts, remote monitoring of the HVAC systems.
COMMERCE AND EXPORTTANGRA has own retail centers in Bulgaria – Sofia, Varna and Bourgas and a wide distribution network. Our sales support team of HVAC engineers help customers in making the right choice. Variety of HVAC products are exhibited in our shopping halls. TANGRA is export-ing own production and has partners in more than 15 countries in Europe.
8 9www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
EVB range consists of eight models of units, separated in thitrteen sizes, differing in construction, type of installation and functionality. Air volume ranges between 100 and 6200 m3/h and efficiency, measured in accordance with EN 308 is above 79%.All counter-flow heat exchangers, which are incorporated in the EVB units are EUROVENT Certified.
HEAT RECOVERY UNITS RANGE
EVB ___ ___
Model:HiE HM - Horizontal monoblockHiE HS - Horizontal splitHiE VM - Vertical monoblockHiE VS - Vertical split
Heat recovery unit
Size - 02 ÷ 60
ORDER FORM
AIR VOLUMES
Model/ Size 02 04 06 08 10 12 16 20 24 30 36 42 48 60
EVB HiE HM _ _ • • • • • • • • •EVB HiE HS _ _ • • • • • •EVB HiE VM _ _ • • • • • • • •EVB HiE VS _ _ • • • • • • •
The different models can be horizontal or vertical, monoblock or split as a construction. All possible configurations are as follows:
CONFIGURATIONS
EVB _ _ _ 60
EVB _ _ _ 48
EVB _ _ _ 42
EVB _ _ _ 36
EVB _ _ _ 30
EVB _ _ _ 24
EVB _ _ _ 20
EVB _ _ _ 16
EVB _ _ _ 12
EVB _ _ _ 10
EVB _ _ _ 08
EVB _ _ _ 06
EVB _ _ _ 04
EVB _ _ _ 02
0 5500 60003500 4000 4500500 1000 1500 2000 2500 3000 5000
1
23
4
57
9
10
11
6
8
1. Construction Heat recovery units TANGRA EVB HiE are produced in compact or modu-lar construction with aluminum anodized framework with two types of side panels:- Single panel with internal sound and thermal insulation (13mm)- Double wall panels (sandwich type) with 25mm sound and thermal insulation.
2. Air filters (EN779 / ISO16890)All heat recovery units TANGRA EVB are with incorporated filters for fresh and exhaust air. The standard filters are panel or mini-pleat M5÷F7 (EN779) or ePM1÷ePM2.5 (ISO16890). On request additional filters can be added after the unit in a filter box with fan, due to pressure drop and needed available free static pressure from the unit.
3. Antifreeze protection / pre-heater (option)Due to high efficiency of the heat exchanger in winter conditions the air flow can lead freezing and ice blockage of the exchanger. In order to prevent it an electric heater for anti-freeze protection of the fresh is in-corporated in the units. It turns on automatically based on the conditions and is smoothly controlled to minimize the consumption. 4. By-pass (Regulations EU 1253 and 1254)Automatic bypass damper with servomotor actuator that allows free cool-ing in summer mode (without heat recovery) or variable control when mixing section is in use.
5. Heat exchanger (Eurovent cetrified)All heat recovery units TANGRA EVB are with high efficient plate heat ex-changer and heat recovery coefficients exceeding 79% (EN308). No odors or moisture transfer between the streams. The plate heat exchangers in TANGRA EVB are certified by Eurovent Certita Certification S.A.S.
6. FansHeat recovery units TANGRA EVB are equiped with 2 different types of centrifugal fans. The fans are marked on every graph, based on the electric motors: AC or EC/EC+ . - The units with AC are with centrifugal fans with forward blade wheel - economic solution with easy variable control on the voltage. - The units with EC/EC+ are with high performance radial freewheel impeller and IE5 EC motors.
7. Electric boardTANGRA EVB are plug and play solution. Their intelligent control systems allow quick and easy commissioning. The state of art controls have BMS connection or control through internet (Modbus, BACnet, etc.). TANGRA control systems can be equipped with wall mounted remote LCD display. Sensors for constant flow or pressure, CO2, VOC or rH.
8. Thermal boxTANGRA EVB HiE can be equipped with an external module with integrated water heating coil or DX coil for connection with outdoor VRF. Removable mist eliminator is on request.
9. Multi-leaf dampers (option)Aluminum louver dampers for tightly closing of the inlets and outlets with external servomotor actuator. Tightness category 2 to EN 1751.
10. Flexible joint (option)Rectangular flexible joint for easy connection to ventilation ducts and eliminating all the vibrations between the unit and the duct system.
11. Round connector Round connectors designed for direct connection to spiral ventilation ducts.
10 11www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
Model Air flow[m3/h]
B[mm]
B max[mm]
H[mm]
H max[mm]
L [mm]
E[mm]
C[mm]
D[mm]
Weight[kg]
EVB 02 HiE HM 200 590 730 335 365 1500 230 295 200 70
EVB 04 HiE HM 400 690 830 370 400 1880 260 330 200 100
EVB 06 HiE HM 600 790 930 370 400 1880 310 330 250 115
EVB 08 HiE HM 800 1090 1230 370 400 1880 360 330 250 140
EVB 10 HiE HM 1000 1290 1430 370 400 1880 360 330 250 160
EVB 12 HiE HM 1200 1115 1255 590 630 2200 500 530 315 230
EVB 16 HiE HM 1600 1315 1455 590 630 2200 500 530 315 245
EVB 20 HiE HM 2000 1515 1655 590 630 2200 500 530 355 255
EVB 24 HiE HM 2400 1815 1955 590 630 2280 500 530 355 275
Model Air flow[m3/h]
B [mm]
B max [mm]
H [mm]
H max [mm]
L [mm]
L1 [mm]
L2 [mm]
E [mm]
C [mm]
D [mm]
Weight [kg]
EVB 12 HiE HS 1200 1115 1255 590 630 2440 560 1320 500 530 315 250
EVB 16 HiE HS 1600 1315 1455 590 630 2440 560 1320 500 530 315 260
EVB 20 HiE HS 2000 1515 1655 590 630 2440 560 1320 500 530 355 280
EVB 24 HiE HS 2400 1815 1955 590 630 2440 560 1320 500 530 355 300
EVB 30 HiE HS 3000 2115 2275 590 630 2640 660 1320 500 530 355 350
EVB 36 HiE HS 3600 2315 2455 590 630 2640 660 1320 500 530 355 390
TANGRA EVB HiE _ _ HMHorizontal installation, monoblock execution
TANGRA EVB HiE _ _ HSHorizontal installation, split execution
Model Air flow [m3/h]
B [mm]
B max [mm]
H [mm]
H max [mm]
L [mm]
E [mm]
C [mm]
D [mm]
Weight [kg]
EVB 02 HiE VM 200 335 365 590 730 1500 230 295 200 70
EVB 04 HiE VM 400 370 400 690 830 1880 260 330 200 100
EVB 06 HiE VM 600 370 400 790 930 1880 310 330 250 115
EVB 08 HiE VM 800 370 400 1090 1230 1880 360 330 250 140
EVB 10 HiE VM 1000 370 400 1290 1430 1880 360 330 250 160
EVB 12 HiE VM 1200 590 630 1115 1255 2200 500 530 315 230
EVB 16 HiE VM 1600 590 630 1315 1455 2200 500 530 315 245
EVB 20 HiE VM 2000 590 630 1515 1655 2200 500 530 355 255
EVB 24 HiE VM 2400 590 630 1815 1955 2280 500 530 355 275
Model Air flow[m3/h]
B[mm]
B max [mm]
H [mm]
H max [mm]
L [mm]
L1 [mm]
L2[mm]
E [mm]
C[mm]
D [mm]
Weight[kg]
EVB 24 HiE VS 2400 1200 1240 1150 1255 2620 650 1320 500 1040 355 290
EVB 30 HiE VS 3000 1200 1240 1300 1355 2820 750 1320 550 1040 355 350
EVB 36 HiE VS 3600 1200 1240 1400 1455 2820 750 1320 600 1040 355 390
EVB 42 HiE VS 4200 1200 1240 1550 1555 2820 750 1320 650 1040 400 410
EVB 48 HiE VS 4800 1200 1240 1700 1695 2820 750 1320 700 1040 450 450
EVB 60 HIE VS 6200 1200 1240 2050 2055 2820 750 1320 900 1040 500 520
TANGRA EVB HiE _ _ VMVertical installation,
monoblock execution
TANGRA EVB HiE _ _ VSVertical installation, split execution
HEAT RECOVERY UNITS RANGE
L
B
E
C
BB max
H max
E
H
L1 L2 L1L
BBB max
EE
H
H max
C
L
H
E
C
HH max
B max
E
B
100
L1 L2 L1
H
L
H max
E x C
E x C
BE
E
C
B max
150
12 13www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
AC EC Nominal Voltage [V] - 1~ 230VMax power [W] - 2 x 27 WMax current [A] - 2 x 0.27 AOperation temperature [ C⁰] - -25⁰÷ 60⁰Level of protection - IP 54Pre-heater capacity [kW]* 0.75 kW
Air flow[m3/h]
Efficiency [%]Dry Wet
80 88.9 93.4120 86.7 91.9160 85.2 90.8200 84.1 89.9
TANGRA EVB HiE 02
Octave brands [Hz] at 160 m3/h, 150 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 39,0 47,0 49,5 52,0 50,0 47,0 51,0 46,5 57
Outlet sound power dB 39,0 50,0 49,5 55,0 59,0 58,0 58,0 56,5 65
Casing sound pressure dB, at 1.5 m 22,0 40,8 42,6 41,3 40,5 39,7 39,4 33,3 47
AC
Inlet sound power dB - - - - - - - - -
Outlet sound power dB - - - - - - - - -
Casing sound pressure dB, at 1.5 m - - - - - - - - -
AC ECNominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 180 W 2 x 170 WMax current [A] 2 x 0.85 A 2 x 1.7 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -30⁰÷ 60⁰Level of protection IP 44 IP 54Pre-heater capacity [kW]* 1.5 kW
TANGRA EVB HiE 04
Octave brands [Hz] at 400 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 45,0 45,0 58,0 59,0 56,0 54,0 54,0 46,0 62
Outlet sound power dB 43,0 49,0 59,0 69,0 71,0 73,0 66,0 60,0 77
Casing sound pressure dB, at 1.5 m 26,0 39,8 52,1 55,3 52,5 54,7 47,4 36,8 59
AC
Inlet sound power dB 46,0 54,0 56,5 59,0 57,0 54,0 58,0 53,5 64
Outlet sound power dB 46,0 57,0 56,5 62,0 66,0 65,0 65,0 63,5 72
Casing sound pressure dB, at 1.5 m 29,0 47,8 49,6 48,3 47,5 46,7 46,4 40,3 54
Air flow[m3/h]
Efficiency [%]Dry Wet
200 81.4 91.8300 80.1 88.0400 79.0 86.8500 78.1 85.7
AC ECNominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 350 W 2 x 170 WMax current [A] 2 x 1.5 A 2 x 1.7 AOperation temperature [ C⁰] -20⁰÷ 55⁰ -30⁰÷ 60⁰Level of protection IP 44 IP 54Pre-heater capacity [kW]* 1.5 kW
Air flow[m3/h]
Efficiency [%]Dry Wet
300 80.7 90.9400 79.7 87.6500 78.8 86.6600 781 85.7700 77.5 85.0
TANGRA EVB HiE 06
Octave brands [Hz] at 600 m3/h, 240 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 43,0 40,0 54,0 59,0 56,0 56,0 56,0 50,0 63
Outlet sound power dB 40,0 45,0 55,0 65,0 69,0 73,0 68,0 63,0 76
Casing sound pressure dB, at 1.5 m 23,0 35,8 48,1 51,3 50,5 54,7 49,4 39,8 58
AC
Inlet sound power dB 46,5 52,5 61,5 63,5 58,5 54,5 57,0 52,0 65
Outlet sound power dB 46,5 55,5 61,5 66,5 67,5 65,5 64,0 62,0 73
Casing sound pressure dB, at 1.5 m 29,5 46,3 54,6 52,8 49,0 47,2 45,4 38,8 55
AC ECNominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 350 W 2 x 207 WMax current [A] 2 x 1.5 A 2 x 1.4 AOperation temperature [ C⁰] -20⁰÷ 55⁰ -25⁰÷ 50⁰Level of protection IP 44 IP 44Pre-heater capacity [kW]* 2.25 kW
TANGRA EVB HiE 08
Air flow[m3/h]
Efficiency [%]Dry Wet
500 80.0 87.9600 79.3 87.1700 78.6 86.4800 78.1 85.8900 77.6 85.2
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
HEAT RECOVERY UNITS RANGE
0
50
100
150
200
250
300
350
400
450
75 85 95 105 115 125 135 145 155 165 175 185 195 205
EC
Octave brands [Hz] at 800 m3/h, 180 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 40,0 49,0 65,0 68,0 63,0 57,0 56,0 48,0 68
Outlet sound power dB 42,0 53,0 66,0 70,0 77,0 75,0 66,0 59,0 80
Casing sound pressure dB, at 1.5 m 25,0 43,8 59,1 56,3 58,5 56,7 47,4 35,8 62
AC
Inlet sound power dB 46,5 52,5 61,5 63,5 58,5 54,5 57,0 52,0 65
Outlet sound power dB 46,5 55,5 61,5 66,5 67,5 65,5 64,0 62,0 73
Casing sound pressure dB, at 1.5 m 29,5 46,3 54,6 52,8 49,0 47,2 45,4 38,8 55
14 15www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
HEAT RECOVERY UNITS RANGE
AC EC Nominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 350 W 4 x 170 WMax current [A] 2 x 1.5 A 4 x 1.7 AOperation temperature [ C⁰] -20⁰÷ 55⁰ -30⁰÷ 60⁰Level of protection IP 44 IP 44Pre-heater capacity [kW]* 2.25 kW
TANGRA EVB HiE 10
Octave brands [Hz] at 850 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 46,0 43,0 57,0 62,0 59,0 59,0 59,0 53,0 66
Outlet sound power dB 43,0 48,0 58,0 68,0 72,0 76,0 71,0 66,0 79
Casing sound pressure dB, at 1.5 m 26,0 38,8 51,1 54,3 53,5 57,7 52,4 42,8 61
AC
Inlet sound power dB 46,5 52,5 61,5 63,5 58,5 54,5 57,0 52,0 65
Outlet sound power dB 46,5 55,5 61,5 66,5 67,5 65,5 64,0 62,0 73
Casing sound pressure dB, at 1.5 m 29,5 46,3 54,6 52,8 49,0 47,2 45,4 38,8 55
AC EC EC+Nominal Voltage [V] 1~ 230V 1~ 230V 1~ 230VMax power [W] 2 x 373 W 2 x 420W 2 x 780 WMax current [A] 2 x 3.6 A 2 x 1.8 A 2 x 4.0 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -25⁰÷ 50⁰ -20⁰÷ 55⁰Level of protection IP 20 IP 44 IP 54Pre-heater capacity [kW]* 3.0 kW
TANGRA EVB HiE 12
Octave brands [Hz] at 1200 m3/h, 250 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC / EC+
Inlet sound power dB 38,0 /39,0 47,0 /46,0 62,0 /66,0 60,0 /61,0 55,0 /56,0 52,0 /49,0 50,0 /49,0 39,0 /41,0 65 /63
Outlet sound power dB 38,0 /41,0 50,0 /53,0 62,0 /73,0 64,0 /68,0 66,0 /72,0 69,0 /69,0 62,0 /64,0 52,0 /58,0 73 /76
Casing sound pressure dB, at 1.5 m 16,0 /19,0 37,7 /40,7 52,6 /63,6 46,1 /50,1 42,1 /48,1 45,4 /45,4 38,0 /40,0 22,2 /28,2 55 /57
AC
Inlet sound power dB 46,0 54,0 56,5 59,0 57,0 54,0 58,0 53,5 64
Outlet sound power dB 46,0 57,0 56,5 62,0 66,0 65,0 65,0 63,5 72
Casing sound pressure dB, at 1.5 m 29,0 47,8 49,6 48,3 47,5 46,7 46,4 40,3 54
Air flow[m3/h]
Efficiency [%]Dry Wet
1000 80.9 88.61200 80.3 87.91400 79.8 87.31600 79.3 86.81800 78.9 86.3
TANGRA EVB HiE 16
Octave brands [Hz] at 1600 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC / EC+
Inlet sound power dB 36,0 /35,0 44,0 /36,0 58,0 /61,0 57,0 /59,0 54,0 /56,0 52,0 /49,0 55,0 /50,0 41,0 /44,0 63 /61
Outlet sound power dB 37,0 /37,0 47,0 /45,0 59,0 /67,0 61,0 /66,0 65,0 /72,0 69,0 /70,0 67,0 /65,0 54,0 /60,0 73 /76
Casing sound pressure dB, at 1.5 m 15,0 /15,0 34,7 /32,7 49,6 /57,6 43,1 /48,1 41,1 /48,1 45,4 /46,4 43,0 /41,0 24,2 /30,2 53 /54
AC
Inlet sound power dB 47,5 53,5 64,5 66,0 65,5 63,0 64,5 53,0 71
Outlet sound power dB 47,5 56,5 64,5 69,0 74,5 74,0 71,5 63,0 79
Casing sound pressure dB, at 1.5 m 25,5 44,2 55,1 51,1 50,6 50,4 47,5 33,2 56
AC ECNominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 373 W 2 x 780 WMax current [A] 2 x 3.6 A 2 x 4.0 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -20⁰÷ 55⁰Level of protection IP 20 IP 54Pre-heater capacity [kW]* 5.0 kW
TANGRA EVB HiE 20
Air flow[m3/h]
Efficiency [%]Dry Wet
1400 80.4 88.11600 80.0 87.51800 79.5 87.02000 79.2 86.62200 78.8 86.2
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
Octave brands [Hz] at 2000 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 36,0 37,0 61,0 61,0 57,0 50,0 53,0 49,0 62
Outlet sound power dB 40,0 46,0 67,0 67,0 73,0 72,0 68,0 65,0 78
Casing sound pressure dB, at 1.5 m 18,0 33,7 57,6 49,1 49,1 48,4 44,0 35,2 55
AC
Inlet sound power dB 50,5 56,5 67,5 69,0 68,5 66,0 67,5 56,0 74
Outlet sound power dB 50,5 59,5 67,5 72,0 77,5 77,0 74,5 66,0 82
Casing sound pressure dB, at 1.5 m 28,5 47,2 58,1 54,1 53,6 53,4 50,5 36,2 59
Air flow[m3/h]
Efficiency [%]Dry Wet
600 80.1 88.5700 79.5 87.6800 79.0 86.8900 78.5 86.3
1000 78.1 85.8
Air flow[m3/h]
Efficiency [%]Dry Wet
1000 80.2 87.81100 79.8 87.41200 79.5 87.01300 79.2 86.71400 79.0 86.4
AC EC EC+Nominal Voltage [V] 1~ 230V 1~ 230V 1~ 230VMax power [W] 2 x 373 W 2 x 420W 2 x 780 WMax current [A] 2 x 3.6 A 2 x 1.8 A 2 x 4.0 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -25⁰÷ 50⁰ -20⁰÷ 55⁰Level of protection IP 20 IP 44 IP 54Pre-heater capacity [kW]* 3.0 kW
16 17www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
HEAT RECOVERY UNITS RANGE
AC EC Nominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 550 W 2 x 780 WMax current [A] 2 x 4.3 A 2 x 4.0 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -20⁰÷ 55⁰Level of protection IP 44 IP 54Pre-heater capacity [kW]* 6.0 kW
TANGRA EVB HiE 24
Octave brands [Hz] at 2400 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 38,0 42,0 64,0 64,0 59,0 52,0 55,0 54,0 65
Outlet sound power dB 43,0 49,0 69,0 70,0 76,0 74,0 70,0 70,0 80
Casing sound pressure dB, at 1.5 m 21,0 36,7 59,6 52,1 52,1 50,4 46,0 40,2 58
AC
Inlet sound power dB 50,5 56,5 67,5 69,0 68,5 66,0 67,5 56,0 74
Outlet sound power dB 50,5 59,5 67,5 72,0 77,5 77,0 74,5 66,0 82
Casing sound pressure dB, at 1.5 m 28,5 47,2 58,1 54,1 53,6 53,4 50,5 36,2 59
TANGRA EVB HiE 30
Octave brands [Hz] at 2800 m3/h, 250 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 40,0 44,0 57,0 60,0 55,0 48,0 50,0 44,0 61
Outlet sound power dB 41,0 51,0 13,0 12,0 73,0 69,0 65,0 61,0 77
Casing sound pressure dB, at 1.5 m 19,0 38,7 3,6 -5,9 49,1 45,4 41,0 31,2 52
AC
Inlet sound power dB 52,0 60,5 69,5 68,5 67,5 64,5 65,5 54,5 73
Outlet sound power dB 52,0 63,5 69,5 71,5 76,5 75,5 72,5 64,5 81
Casing sound pressure dB, at 1.5 m 30,0 51,2 60,1 53,6 52,6 51,9 48,5 34,7 59
Air flow[m3/h]
Efficiency [%]Dry Wet
2800 80.1 87.63000 79.6 87.13200 79.3 86.83400 79.1 86.53600 78.9 86.3
TANGRA EVB HiE 36
Octave brands [Hz] at 3500 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 44,0 49,0 62,0 62,0 56,0 53,0 54,0 49,0 63
Outlet sound power dB 45,0 55,0 69,0 71,0 76,0 77,0 73,0 69,0 81
Casing sound pressure dB, at 1.5 m 23,0 42,7 59,6 53,1 52,1 53,4 49,0 39,2 59
AC
Inlet sound power dB 55,0 63,5 72,5 71,5 70,5 67,5 68,5 57,5 76
Outlet sound power dB 55,0 66,5 72,5 74,5 79,5 78,5 75,5 67,5 84
Casing sound pressure dB, at 1.5 m 33,0 54,2 63,1 56,6 55,6 54,9 51,5 37,7 62
AC ECNominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 750 W 2 x 1350 WMax current [A] 2 x 7.8 A 2 x 6.8 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -20⁰÷ 55⁰Level of protection IP 20 IP 54Pre-heater capacity [kW]* 12.0 kW
TANGRA EVB HiE 42
Air flow[m3/h]
Efficiency [%]Dry Wet
3400 80.2 87.83600 79.8 87.43800 79.6 87.24000 79.5 86.94200 79.3 86.7
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
Octave brands [Hz] at 4200 m3/h, 200 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 44,0 50,0 62,0 63,0 56,0 51,0 53,0 46,0 63
Outlet sound power dB 46,0 58,0 69,0 72,0 75,0 74,0 69,0 65,0 80
Casing sound pressure dB, at 1.5 m 24,0 45,7 59,6 54,1 51,1 50,4 45,0 35,2 58
AC
Inlet sound power dB 55,0 63,5 72,5 71,5 70,5 67,5 68,5 57,5 76
Outlet sound power dB 55,0 66,5 72,5 74,5 79,5 78,5 75,5 67,5 84
Casing sound pressure dB, at 1.5 m 33,0 54,2 63,1 56,6 55,6 54,9 51,5 37,7 62
Air flow[m3/h]
Efficiency [%]Dry Wet
1800 80.9 88.62000 80.4 88.12200 80.0 87.52400 79.5 87.02600 79.2 86.6
Air flow[m3/h]
Efficiency [%]Dry Wet
2400 80.3 87.92600 79.7 87.22800 79.4 86.93000 79.2 86.63200 78.9 86.3
AC EC Nominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 550 W 2 x 740 WMax current [A] 2 x 4.3 A 2 x 3.8 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -20⁰÷ 40⁰Level of protection IP 44 IP 54Pre-heater capacity [kW]* 6.0 kW
AC EC Nominal Voltage [V] 1~ 230V 1~ 230VMax power [W] 2 x 750 W 2 x 1300 WMax current [A] 2 x 7.8 A 2 x 6.6 AOperation temperature [ C⁰] -20⁰÷40⁰ -20⁰÷ 50⁰Level of protection IP 20 IP 55Pre-heater capacity [kW]* 9.0 kW
18 19www.tangra.bg www.tangra.bg*We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development *We reserve the rights to introduce alternations both in design and technical data without prior notice, due to continuous products development
FUNCTIONAL SCHEME EVB-HiE
INSTALLED IN THE UNIT
REC – AAHE plate heat exchangerM1 & M2 – Multi-leaf damper of fresh and exhaust airT – Temperature sensorsTs1 – Temperature sensor 1 at fresh airTs2 – Temperature sensor 2 at supply after the heat exchangerTs3 – Temperature sensor 3 at supply air after heat exchanger and additional heaterTe1 – Temperature sensor 1 at extract airTe2 – Temperature sensor 2 at exhaust air after the exchangerΔP – Differential pressure switch on air filters for dirty filters signalization EK – Anti-freeze protection – electric heater with smooth control 0-100% works with Te2 sensor.BS – Automatic by-pass for free cooling with servomotor actuator for free coolingBSsp1 – Set point for open of by-pass for free coolingBSsp2 – Set point for close of by-pass for free coolingSAF – Supply air fan with smooth control 0-10VEAF – Exhaust air fan with smooth control 0-10VTB – Thermal boxTBE – Thermal box with electric heater with smooth control 0-100%TBWH – Thermal box with water heating coil and valve with actuator 0-10VTBWHC – Thermal box with water heating and water cooling coils with valves and actuators 0-10VTBDX – Thermal box with direct expansion coil for connection with VRF outdoor unit. Power board – Electric board with power supply, PLC controller and BMS connection
IN THE PREMISE
LCD display - remote controlTsp – Indoor temperature set point [0C]Vsp – Air speed set point [%]S – Sensor for automatic control of the heat recovery unit, based on the values of the sensor. SrH – Sensor for relative humiditySvoc – Sensor for VOC (volatile organic compounds)Sco2 – Sensor for CO2
ODA – Fresh air SUP – Supply air ETA – Extract air EHA – Exhaust air
HEAT RECOVERY UNITS RANGE
AC EC Nominal Voltage [V] 3 ~ 380V 3~ 380VMax power [W] 2 x 1500 W 2 x 2500 WMax current [A] 2 x 5.0 A 2 x 4.0 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -20⁰÷ 50⁰Level of protection IP 20 IP 55Pre-heater capacity [kW]* 12.0 kW
TANGRA EVB HiE 48
Octave brands [Hz] at 4800 m3/h, 300 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 48,0 50,0 65,0 67,0 59,0 53,0 57,0 50,0 67
Outlet sound power dB 49,0 57,0 72,0 74,0 77,0 76,0 73,0 68,0 82
Casing sound pressure dB, at 1.5 m 27,0 44,7 62,6 56,1 53,1 52,4 49,0 38,2 60
AC
Inlet sound power dB 54,5 63,5 71,5 74,5 75,5 71,5 72,0 63,0 80
Outlet sound power dB 54,5 66,5 71,5 77,5 84,5 82,5 79,0 73,0 88
Casing sound pressure dB, at 1.5 m 32,5 54,2 62,1 59,6 60,6 58,9 55,0 43,2 65
TANGRA EVB HiE 60
Octave brands [Hz] at 6000 m3/h, 380 Pa
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB (A)
EC
Inlet sound power dB 53,0 59,0 71,0 71,0 63,0 58,0 60,0 54,0 71
Outlet sound power dB 53,0 64,0 76,0 79,0 81,0 80,0 76,0 72,0 86
Casing sound pressure dB, at 1.5 m 31,0 51,7 66,6 61,1 57,1 56,4 52,0 42,2 64
AC
Inlet sound power dB 50,5 60,5 67,5 74,5 71,5 68,5 69,5 59,5 77
Outlet sound power dB 50,5 63,5 67,5 77,5 80,5 79,5 76,5 69,5 85
Casing sound pressure dB, at 1.5 m 28,5 51,2 58,1 59,6 56,6 55,9 52,5 39,7 62
H ext, [
Pa]
V, [m3/h]
H ext, [
Pa]
V, [m3/h]
Air flow[m3/h]
Efficiency [%]Dry Wet
4000 80.2 87.74400 79.6 87.14600 79.5 87.04800 79.3 86.85000 79.2 86.6
Air flow[m3/h]
Efficiency [%]Dry Wet
4400 79.6 83.94800 79.3 83.55200 79.0 83.25600 78.7 82.96000 78.5 82.6
AC EC Nominal Voltage [V] 3~ 380V 3~ 380VMax power [W] 2 x 2200 W 2 x 2500 WMax current [A] 2 x 4.3 A 2 x 4.0 AOperation temperature [ C⁰] -20⁰÷ 40⁰ -20⁰÷ 50⁰Level of protection IP 44 IP 55Pre-heater capacity [kW]* 6.0 kW
100
200
300
400
500
600
700
800
900
1000
1100
3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 5200 5400 5600 5800 6000 6200
AC
GR
Europe Sales & Service
AlbaniaBosnia & HerzegovinaCroatiaCzech RepublicGreece
HungaryKosovoMoldovaMontenegroPoland
Republic North MacedoniaRomaniaSerbiaSloveniaSwitzerland
Extensive Distribution & Service Network
Sofia, 174, Europe blvd.Phone: +359 2 925 05 99; Mobile: +359 887 73 73 75
Varna, West Industrial Zone INCOVES warehousePhone: +359 52 611 767
Burgas, 6, Transportna Str.Phone: +359 56 86 12 00
Headquarter
www.tangra.bg