Annexure-1: Estimation of Heat load calculation for proposed MV Switchgear
Building & Control Room Building for Electrical equipments
1.1 33 KV Switchgear
This Swotchgear having four Nos. of 33 KV switchgears
(a). Incomer module with 2500A breaker:
2 Nos. Incomers of 2500A VCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays & width of panel is 1200 mm
Breaker loss = 3x25002x60x10
-6 = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
Busbars = 0.0724x2500x3x1.2 = watts
The heat loss one incomer feeder = wattsTherefore, total heat loss for 2 incomer feeders = watts
= KW
(b). Outgoing module with 1250A breaker:
2 Nos. outgoing feeders of 1250A VCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays & width of panel is 1200 mm
Breaker loss = 3x12502x60x10
-6 = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
Busbars = 0.0724x1250x3x1.2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = watts= KW
1.2 Lighting Load = KW Assumed
1.3 Power Cable = KW Assumed
Therefore Total Heat Load For MV Building = KW
12
12
8
FORM T9-P REV-A
13
0
0.5
12
12
652
1304
8
References / Remarks
Sheet No.
Project
18223643
13
0
Rev.Doc. No.SubjectNHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
1125
652
Description
3.64
1.3
0.72
6.17
281
326
File Name Originator / Dept.
KR / EL 11
8/10/2019 Heat Load Calculation.xls
2/20
FICHTNERIndia
2
References / Remarks
Sheet No.
Project Rev.Doc. No.SubjectNHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
2. Control Room Building
2.1 CRP Panels = watts Assumed
Therefore, total heat loss for 11 CRP = KW
2.2 MLDB & ELDB = watts Assumed
Therefore, total heat loss for 3 ACDBs = KW
2.3 Lighting Load = KW Assumed
2.4 Power Cable = KW Assumed
2.5 AC Automatic Transfer Switch (ATS)
This Switchgear having four Nos. of 415V switchgears
Incomer & Outgoing module with 2000A breaker:
2 Nos. Incomers & 2 Nos. Outgoing feeders of 2000A ACB, having 2 CT's of 15VA burden,
5 indicating lamps, 4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = 3x20002x60x10
-6 = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
Busbars = 0.0724x2000x3x1.8 = watts
Therefore, total heat loss for ATS = KW
2.6 AC Normal Supply Panel
(a). Incomer module with 2000A breaker:
1 No. Incomer of 2000A ACB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = 3x20002x60x10
-6 = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 1 incomer feeder = KW
(b). Outgoing module with 1000A MCCB:
1 No. outgoing feeder of 1000A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
8
12
12
8
720
8
245
0.25
Project Subject
13
0
12
0
12
4.04
FORM T9-P REV-A
Rev. Section
2.75
References / Remarks
Project Subject
Doc. No.
720
1.35
13
450
0.5
-
13
0
12
NHPTL HIGH POWER
SHORT CIRCUIT TESTFACILITY AT BINA (MP)
HEAT LOAD CALCULATION
4.5
Doc. No. Rev.
Description
Section
Sheet No.ETHS&PS/620P-90801/ED2.131.001.B
250
977
765
0.77
200
12
File Name Originator / Dept.
KR / EL 11
8/10/2019 Heat Load Calculation.xls
3/20
FICHTNERIndia
3
References / Remarks
Sheet No.
Project Rev.Doc. No.Subject
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
(c). Outgoing module with 630A MCCB:
3 Nos. outgoing feeders of 630A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 3 outgoing feeders = KW
(d). Outgoing module with 400A MCCB:
2 Nos. outgoing feeders of 400A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(e). Outgoing module with 300A MCCB:
2 Nos. outgoing feeders of 300A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(f). Outgoing module with 200A MCCB:
1 No. outgoing feeder of 200A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp isAux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
100
12
145
0
12
12
0.21
40
Doc. No.
NHPTL HIGH POWER-
12
Description References / Remarks
200
245
85
13
Rev. SectionProject Subject
12
8
FORM T9-P REV-A
0.09
60
13
8
105
13
12
0
12
8
0.74
13
0
12
8
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.B
- Sheet No.
0
0.29
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
4/20
FICHTNERIndia
4
References / Remarks
Sheet No.
Project Rev.Doc. No.Subject
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
(g). Outgoing module with 160A MCCB:
1 No. outgoing feeder of 160A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
(h). Outgoing module with 125A MCCB:
2 Nos. outgoing feeders of 125A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(i). Outgoing module with 100A MCCB:
2 Nos. outgoing feeders of 100A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(j). Outgoing module with 80A MCCB:
1 No. outgoing feeder of 80A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED typeRelays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
20
0
0
12
12
0.15
73
FORM T9-P REV-A
28
65
0.07
13
12
Doc. No.
128
13
0
12
8
0.15
13
8
12
12
8
85
0.09
12
73
Description References / Remarks
40
13
0
28
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION90801/ED2.131.001.B
- Sheet No.
NHPTL HIGH POWER
SHORT CIRCUIT TESTETHS&PS/620P-
Project Subject Rev. Section
-HEAT LOAD CALCULATION Sheet No.
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
5/20
FICHTNERIndia
5
References / Remarks
Sheet No.
Project Rev.Doc. No.Subject
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
(k). Outgoing module with 63A MCCB:
1 No. outgoing feeder of 63A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
(l). Outgoing module with 32A MCCB:
4 Nos. outgoing feeders of 32A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 4 outgoing feeders = KW
(m). Outgoing module with 16A MCCB:
5 Nos. outgoing feeders of 16A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 5 outgoing feeders = KW
Busbars with 1 No. of 2000A horizontal & 3 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x2000x3x5.050 = watts
(ii). Vertical Busbars = 0.0724x2000x3x3x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Normal = KW
Supply Panel
4
12
49
0
12
12
8
65
0.25
12
2346
7.82
FORM T9-P REV-A
Section
4.54
4
13
8
49
-
0.07
13
0
12
8
0.2
2194
Description References / Remarks
20
13
0
12
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.B
Project Subject Doc. No. Rev.
FACILITY AT BINA (MP). . .
Sheet No.
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
6/20
FICHTNERIndia
6
References / Remarks
Sheet No.
Project Rev.Doc. No.Subject
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
2.7 AC Preferred Supply Panel
(a). Incomer module with 1000A MCCB:
1 No. incomer feeder of 1000A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 incoming feeder = KW
(b). Outgoing module with 300A MCCB:
2 Nos. outgoing feeders of 300A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(c). Outgoing module with 200A MCCB:
1 No. outgoing feeder of 200A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
(d). Outgoing module with 160A MCCB:
1 No. outgoing feeder of 160A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = wattsThe heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
0
8
0.21
13
0
12
105
40
SectionNHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.B-
85
13
885
FORM T9-P REV-A
Sheet No.
12
8
12
12
60
13
12
12
0.09
0.09
40
0
0
12
12
8
245
0.25
Description References / Remarks
200
Project
13
Subject Rev.Doc. No.
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
7/20
8/10/2019 Heat Load Calculation.xls
8/20
FICHTNERIndia
8
References / Remarks
Sheet No.
Project Rev.Doc. No.SubjectNHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
Busbars with 1 No. of 1000A horizontal & 3 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x1000x3x4.250 = watts(ii). Vertical Busbars = 0.0724x1000x3x3x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Preferred = KW
Supply Panel
2.8 ACGE Preferred Supply Panel
(a). DG side Incomer module with 500A MCCB:
2 Nos. incomer feeders of 500A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED typeRelays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 incoming feeders = KW
(b). Outgoing module with 1000A breaker:
2 Nos. outgoing feeders of 1000A ACB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = 3x10002x60x10
-6 = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts
Meters = 4x3 = watts
Aux. contactors = 4x4 = watts
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
Busbars with 1 No. of 1000A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x1000x3x2.350 = watts
(ii). Vertical Busbars = 0.0724x1000x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for ACGE Preferred = KW
Supply Panel
2.9 Battery Charger
Heat loss (watts) = 0.05 x Rated output (Assuming Efficiency of Charger as 0.95)
Rated output of Charger = KW
(As per DC System sizing calculation)
Therefore, heat loss for Battery Charger = KW
13
0.29
0
145
13
0
12
12
ETHS&PS/620P-
90801/ED2.131.001.B-
Project
References / Remarks
9231173
812
12
2.1
4.44
100
180
8
225
0.45
510
782
1.29
2.03
50.8
2.54
Subject
Description
Doc. No.
FORM T9-P REV-A
Sheet No.
Rev. SectionNHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
9/20
FICHTNERIndia
9
References / Remarks
Sheet No.
Project Rev.Doc. No.Subject
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
A
Section
ETHS&PS/620P-
90801/ED2.131.001.BHEAT LOAD CALCULATION
Description
2.10 Control Room DCDB
(a). Incomer module with 400A MCCB:
3 Nos. incoming feeders & 1 No. Bus-coupler feeder of 400A MCCB, having 2 CT's of15VA burden, 5 indicating lamps, 4 meters, 1 PT-100 VA burden, 4 auxiliary contactors &
4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 4 feeders = KW
(b). Outgoing module with 32A MCB: = KW Assumed
Busbars with 1 No. of 400A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x400x2x3.6 = watts(ii). Vertical Busbars = 0.0724x1000x2x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for Control Room = KW
DCDB
Therefore Total Heat Load For Control Room = KW
Building
Therefore Total combined Heat Load For = KW
MV & Control Room Building
521521
FORM T9-P REV-A
2.07
38.2
32
100
13
0
12
1.04
12
8
145
0.58
0.45
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
10/20
FICHTNERIndia
10
Annexure-2: Estimation of Heat load calculation for proposed Marshalling
KIOSK Building MK-1 for Electrical equipments
Marshalling KIOSK - 1
1 CRP Panels = watts Assumed
Therefore, total heat loss for 4 CRP = KW
2 Lighting Load = KW Assumed
3 Power Cable = KW Assumed
4 AC Normal Supply Panel
(a). Incomer module with 125A MCCB:
1 No. Incomer of 125A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = = wattsCT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 1 incomer feeder = KW
(b). Outgoing module with 63A MCCB:
3 Nos. outgoing feeders of 63A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp isAux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 3 outgoing feeders = KW
(c). Outgoing module with 16A MCCB:
5 Nos. outgoing feeders of 16A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = wattsTherefore, total heat loss for 5 outgoing feeders = KW
Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.BA Sheet No.
12
0.5
Project Subject Doc. No.
Description References / Remarks
0.07
20
13
0
12
0
12
12
65
FORM T9-P REV-A
0.2
4
13
49
8
0.25
73
8
250
1
0.64
12
12
8
2813
0
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
11/20
FICHTNERIndia
11
Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.BA Sheet No.
Project Subject Doc. No.
Description References / Remarks
Busbars with 1 No. of 125A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x125x3x1.2 = watts
(ii). Vertical Busbars = 0.0724x125x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Normal = KW
Supply Panel
5 AC Preferred Supply Panel
(a). Incomer module with 300A MCCB:
1 No. Incomer of 300A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 1 incomer feeder = KW
(b). Outgoing module with 200A MCCB:
2 Nos. outgoing feeders of 200A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(c). Outgoing module with 160A MCCB:
1 No. outgoing feeder of 160A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = wattsThe heat loss one outgoing feeder = watts
Therefore, total heat loss for 1 outgoing feeder = KW
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TESTFACILITY AT BINA (MP)
HEAT LOAD CALCULATION ETHS&PS/620P-90801/ED2.131.001.B
-
0.13
0.64
Sheet No.
Description References / Remarks
97.7
32.6
60
8
105
0.11
13
0
12
12
85
40
85
0.17
12
12
8
13
0
FORM T9-P REV-A
0.09
12
12
8
0
40
13
Project Subject Doc. No. Rev. Section
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
12/20
FICHTNERIndia
12
Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.BA Sheet No.
Project Subject Doc. No.
Description References / Remarks
(d). Outgoing module with 100A MCCB:
4 Nos. outgoing feeders of 100A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 4 outgoing feeders = KW
(e). Outgoing module with 63A MCCB:
2 Nos. outgoing feeders of 63A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(f). Outgoing module with 32A MCCB:
5 Nos. outgoing feeders of 32A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 5 outgoing feeders = KW
Busbars with 1 No. of 300A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x300x3x2.4 = watts
(ii). Vertical Busbars = 0.0724x300x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Preferred = KW
Supply Panel
6 Battery Charger
Heat loss (watts) = 0.05 x Rated output (Assuming Efficiency of Charger as 0.95)
Rated output of Charger = KW
(As per DC System sizing calculation)
Therefore, heat loss for Battery Charger = KW
156
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.B
- Sheet No.
Description References / Remarks
28
13
0
12
12
8
73
0.29
20
13
0
12
12
8
65
0.13
4
13
0
12
12
8
49
0.25
50.8
2.54
0.39
1.42
235
Project Subject Doc. No. Rev. Section
FORM T9-P REV-A
NHPTL HIGH POWER-
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
13/20
FICHTNERIndia
13
Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.BA Sheet No.
Project Subject Doc. No.
Description References / Remarks
7 Marshalling KIOSK-1 DCDB
(a). Incomer module with 400A MCCB:
3 Nos. incomingfeedwers & 1 No. Bus-coupler feeder of 400A MCCB, having 2 CT's of
15VA burden, 5 indicating lamps, 4 meters, 1 PT-100 VA burden, 4 auxiliary contactors &
4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 4 feeders = KW
(b). Outgoing module with 32A MCB: = KW Assumed
Busbars with 1 No. of 400A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x400x2x3.6 = watts
(ii). Vertical Busbars = 0.0724x1000x2x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for Marshalling = KW
KIOSK-1 DCDB
Therefore Total Heat Load For Marshalling = KW
KIOSK-1
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION90801/ED2.131.001.B
- Sheet No.
Description References / Remarks
100
13
0
12
12
8
145
0.58
0.45
521
521
1.04
2.07
8.81
FORM T9-P REV-A
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
14/20
8/10/2019 Heat Load Calculation.xls
15/20
FICHTNERIndia
15
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.BA Sheet No.
Description References / Remarks
Busbars with 1 No. of 125A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x125x3x1.2 = watts
(ii). Vertical Busbars = 0.0724x125x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Normal = KW
Supply Panel
5 AC Preferred Supply Panel
(a). Incomer module with 300A MCCB:
1 No. Incomer of 300A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 1 incomer feeder = KW
(b). Outgoing module with 200A MCCB:
2 Nos. outgoing feeders of 200A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(c). Outgoing module with 63A MCCB:
9 Nos. outgoing feeders of 63A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = wattsThe heat loss one outgoing feeder = watts
Therefore, total heat loss for 9 outgoing feeders = KW
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TESTFACILITY AT BINA (MP)
HEAT LOAD CALCULATION ETHS&PS/620P-90801/ED2.131.001.B
- Sheet No.
Description References / Remarks
32.6
97.7
0.13
0.69
60
13
0
12
12
8
105
0.11
40
13
0
12
12
8
85
0.17
20
13
0
12
12
865
0.59
FORM T9-P REV-A
Project Subject Doc. No. Rev. Section
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
16/20
FICHTNERIndia
16
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.BA Sheet No.
Description References / Remarks
(d). Outgoing module with 32A MCCB:
8 Nos. outgoing feeders of 32A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 8 outgoing feeders = KW
Busbars with 1 No. of 300A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x300x3x2.4 = watts
(ii). Vertical Busbars = 0.0724x300x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Preferred = KW
Supply Panel
6 Battery Charger
Heat loss (watts) = 0.05 x Rated output (Assuming Efficiency of Charger as 0.95)
Rated output of Charger = KW
(As per DC System sizing calculation)
Therefore, heat loss for Battery Charger = KW
7 Marshalling KIOSK-2 DCDB
(a). Incomer module with 400A MCCB:
3 Nos. incomingfeedwers & 1 No. Bus-coupler feeder of 400A MCCB, having 2 CT's of
15VA burden, 5 indicating lamps, 4 meters, 1 PT-100 VA burden, 4 auxiliary contactors &
4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 4 feeders = KW
(b). Outgoing module with 32A MCB: = KW Assumed
Busbars with 1 No. of 400A horizontal & 2 Nos. of Vertical drop inside the panel(i). Horizontal Busbars = 0.0724x400x2x3.6 = watts
(ii). Vertical Busbars = 0.0724x1000x2x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for Marshalling = KW
KIOSK-2 DCDB
Therefore Total Heat Load For Marshalling = KW
KIOSK-1
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATIONETHS&PS/620P-
90801/ED2.131.001.B
- Sheet No.
Description References / Remarks
4
13
0
12
12
8
49
100
13
0
50.8
0.39
0.39
1.64
521
10.8
12
12
145
0.58
2.07
FORM T9-P REV-A
156
235
2.54
8
0.45
521
1.04
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
17/20
FICHTNERIndia
17
Annexure-3: Estimation of Heat load calculation for proposed Marshalling
KIOSK Building MK-2
Marshalling KIOSK - 2
1 CRP Panels = watts Assumed
Therefore, total heat loss for 11 CRP = KW
2 Lighting Load = KW Assumed
3 Power Cable = KW Assumed
4 AC Normal Supply Panel
(a). Incomer module with 125A MCCB:
1 No. Incomer of 125A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = = wattsCT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 1 incomer feeder = KW
(b). Outgoing module with 63A MCCB:
3 Nos. outgoing feeders of 63A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp isAux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 3 outgoing feeders = KW
(c). Outgoing module with 16A MCCB:
6 Nos. outgoing feeders of 16A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = wattsTherefore, total heat loss for 6 outgoing feeders = KW
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION 3112133-PB-EL-690-001 - Sheet No.
Description References / Remarks
250
2.75
0.64
0.5
2813
0
12
12
8
73
0.07
20
13
0
1212
8
65
0.2
4
13
0
12
12
8
490.29
FORM T9-P REV-A
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
18/20
FICHTNERIndia
18
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION 3112133-PB-EL-690-001 - Sheet No.
Description References / Remarks
Busbars with 1 No. of 125A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x125x3x1.2 = watts
(ii). Vertical Busbars = 0.0724x125x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Normal = KW
Supply Panel
5 AC Preferred Supply Panel
(a). Incomer module with 300A MCCB:
1 No. Incomer of 300A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,
1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one incomer feeder = watts
Therefore, total heat loss for 1 incomer feeder = KW
(b). Outgoing module with 200A MCCB:
2 Nos. outgoing feeders of 200A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 2 outgoing feeders = KW
(c). Outgoing module with 63A MCCB:
9 Nos. outgoing feeders of 63A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = wattsThe heat loss one outgoing feeder = watts
Therefore, total heat loss for 9 outgoing feeders = KW
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TESTFACILITY AT BINA (MP)
HEAT LOAD CALCULATION 3112133-PB-EL-690-001 - Sheet No.
Description References / Remarks
32.6
97.7
0.13
0.69
60
13
0
12
12
8
105
0.11
40
13
0
12
12
8
85
0.17
20
13
0
12
12
865
0.59
FORM T9-P REV-A
Project Subject Doc. No. Rev. Section
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
19/20
FICHTNERIndia
19
Project Subject Doc. No. Rev. Section
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION 3112133-PB-EL-690-001 - Sheet No.
Description References / Remarks
(d). Outgoing module with 32A MCCB:
8 Nos. outgoing feeders of 32A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,
4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 8 outgoing feeders = KW
Busbars with 1 No. of 300A horizontal & 2 Nos. of Vertical drop inside the panel
(i). Horizontal Busbars = 0.0724x300x3x2.4 = watts
(ii). Vertical Busbars = 0.0724x300x3x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for AC Preferred = KW
Supply Panel
6 Battery Charger
Heat loss (watts) = 0.05 x Rated output (Assuming Efficiency of Charger as 0.95)
Rated output of Charger = KW
(As per DC System sizing calculation)
Therefore, heat loss for Battery Charger = KW
7 Marshalling KIOSK-2 DCDB
(a). Incomer module with 400A MCCB:
3 Nos. incomingfeedwers & 1 No. Bus-coupler feeder of 400A MCCB, having 2 CT's of
15VA burden, 5 indicating lamps, 4 meters, 1 PT-100 VA burden, 4 auxiliary contactors &
4 relays
Breaker loss = watts
CT+PT = (2x15+100)x0.1 = watts
Indicating lamps = = watts Negligible, since the type
Meters = 4x3 = watts of indication lamp is
Aux. contactors = 4x4 = watts assumed as LED type
Relays = 4x2 = watts
The heat loss one outgoing feeder = watts
Therefore, total heat loss for 4 feeders = KW
(b). Outgoing module with 32A MCB: = KW Assumed
Busbars with 1 No. of 400A horizontal & 2 Nos. of Vertical drop inside the panel(i). Horizontal Busbars = 0.0724x400x2x3.6 = watts
(ii). Vertical Busbars = 0.0724x1000x2x2x1.8 = watts
Therefore, total heat loss for Busbars = KW
Therefore, total heat loss for Marshalling = KW
KIOSK-2 DCDB
Therefore Total Heat Load For Marshalling = KW
KIOSK-1
NHPTL HIGH POWER
SHORT CIRCUIT TEST
FACILITY AT BINA (MP)
HEAT LOAD CALCULATION 3112133-PB-EL-690-001 - Sheet No.
Description References / Remarks
4
13
0
12
12
8
49
0.39
156
235
0.39
1.64
50.8
2.54
100
13
0
12
12
8
145
0.58
0.45
521
521
1.04
2.07
10.8
FORM T9-P REV-A
File Name Originator / Dept.
KR / EL . 11
8/10/2019 Heat Load Calculation.xls
20/20
The heat load dissipation of electrical equipment as follows.
Sl. No. Description of Building/Room Load In KW
1 MV Building
2 Control Room
3 Marshlling KIOSK-1 8.814 Marshlling KIOSK-2 10.84
5 Comressor Room 1.30
Total heat load dissipation Load 59.16
38.21