1 Rao S. Thallam Fellow, IEEE Salt River Project Phoenix, AZ, USA Presented at: National Workshop on Electric Power Quality Nov 10, 2004 Indian Institute of Technology, Kanpur Kanpur, UP, India Harmonics - Application of Standards • Introduction • THD and TDD • Displacement and True Power Factor • K-Factor and Transformer Derating • When should you be concerned? • Application of IEEE 519 Standard • Harmonics Measurements • Industrial Customers • Commercial Customers • IEC Standards • Conclusions
37
Embed
Harmonics - Application of Standardshome.iitk.ac.in/~spdas/rao2.pdf · • Industrial Customers • Commercial Customers ... IEEE C57.110 “Recommended Practice ... • SDw is weighted
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1
Rao S. ThallamFellow, IEEE
Salt River ProjectPhoenix, AZ, USA
Presented at:National Workshop on Electric Power Quality
Nov 10, 2004Indian Institute of Technology, Kanpur
Kanpur, UP, India
Harmonics -Application of Standards
�������• Introduction• THD and TDD• Displacement and True Power Factor• K-Factor and Transformer Derating• When should you be concerned?• Application of IEEE 519 Standard• Harmonics Measurements• Industrial Customers• Commercial Customers• IEC Standards• Conclusions
2
"This alternating current thing is just a fad. It is much too dangerous for general use"
Thomas Alva Edison
What Are Harmonics ?�Harmonics are due to distortion of the voltage or
current waveform�The distortion comes from nonlinear devices,
principally loads
V(t)
I(t)
V
I
Nonlinear Resistor
3
Decomposition into Harmonic Components
·
+
+
+
+
+
+
··
+
60 Hz(h = 1)
300 Hz(h = 5)
420 Hz(h = 7)
540 Hz(h = 9)
660 Hz(h = 11)
780 Hz(h = 13)
180 Hz(h = 3)
Current vs. Voltage Harmonics
PureSinusoid Distorted Load
Current
Distorted Voltage
+ -(Voltage Drop)
Harmonic currents flowing through the system impedance results in harmonic voltages at the load
4
Why bother about Harmonics?
�Important aspect of power quality�Damaging Effects to Consumer Loads
and Power System�Problems may be incipient�Non-Linear Loads are Increasing�Power Factor Correction Capacitors
Total Harmonic Distortion
�Defines the total harmonic content of current or voltage
�Ratio of the RMS of the harmonic content to the RMS of the Fundamental, as % of Fundamental
5
THD = sum of squares of amplitudes of all harmonics
square of amplitude of fundamental x 100 .
Mathematically, THD of a voltage wave form can be defined as,
THD = V
V
100 .x h
h
h 2
122=
= ∞�
Total Harmonic Distortion
THD for Current Waveform
THD = I
I
100 x h
h
h 2
1
22=
=∞�
6
Total Demand Distortion Factor (TDD)
�Applies for current distortion only.�The total rms harmonic current
distortion, in % of the maximum demand load current (15 or 30 min demand)
Displacement Power Factor
�When V and I are not distorted, PF is:�“Ratio of the active power of the
fundamental, in watts, to the apparent power of the fundamental wave, in volt-amperes”
�P = V1rms I1rms Cos ��PF = Cos �
7
Power and Power Factor�When significant distortion is present
PF = Cos θθθθ
“Displacement Power Factor”
True Power Factor
�Ratio of the total power, in watts, to the total volt-amperes. This includes fundamental and all harmonic components.
�This is also called “Distortion Power Factor”
8
True Power Factor
PFPS
=
S Vrms Irms=
PT
v t i t dtT
= �1
0( ) ( )
Where:
Engineering Speak
“We are looking at a number of approaches”
Translation:We are guessing.
9
Engineering Speak
“We are making modifications to address minor difficulties”
Translation:We are starting over.
Engineering Speak
“Test results are gratifying”
Translation:It worked and boy are we surprised!
10
Engineering Speak
“We are trying some new approaches”
Translation:We threw some new guys on it.
K-Factor�K-Factor is ratio of eddy current losses
due to distorted current compared to the losses for the same rms fundamental frequency current
�Example: �Eddy Current Losses with 100 A rms with harmonics =
270 Watts�Eddy Current Losses with 100 A rms 60 Hz sine wave =
27 Watts
�K - Factor = 270/27 = 10
11
K-Factor
K = I ( ) 2pu
= h
h
hh
=
∞�
1
2
K-Factor�Assumes eddy current losses are
proportional to f 2 - OK for small conductor sizes and low harmonics
�At higher frequencies, eddy current loses are proportional to f
�Transition frequency depends on winding configuration, material
�Al - 2200 Hz, Cu - 700 Hz �K-factor over estimates harmonics effect
at higher frequencies
12
THD and K-Factor(Example Calculation)
�Harmonics for 3-ph PWM type ASD�Fund. = 100 A rms�5th : 60 A rms = 0.6 pu�7th : 40 A rms = 0.4 pu�11th : 30 A rms = 0.3 pu�13th : 20 A rms = 0.2 pu�THD = Sqrt (0.62 + 0.42 + 0.32 +0.22)* 100 = 81 %�K = 12 + 0.62 * 52 + 0.42 * 72 + 0.32 *112+0.22*132
� = 1 + 9 + 7.84 + 10.89 + 6.76 = 35.49
Transformer Derating
�Non K-rated transformers have to be derated when load current has harmonics
�IEEE C57.110 “Recommended Practice for Establishing Transformer Capability When Supplying Nonsinusoidal Load Currents”
13
K-rating
�K-rated transformers can handle non-sinusoidal load current up to the full load rating with k-factor up to the k-rating of the transformer
�K-rated transformers are designed to have lower eddy current losses
Type of Load Typical WaveformCurrent
DistortionWeightingFactor (Wi)
Single PhasePower Supply
0 10 20 30 40
-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current 80%
(high 3rd)2.5
Semiconverter
0 10 20 30 40
-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current
high 2nd,3rd,4th at partial
loads2.5
6 Pulse Converter,capacitive smoothing,no series inductance
Design Power FactorCorrection and/or HarmonicControl Equipment (includeresonance and interaction
concerns)
Verification Measurementsand Calculations
(if necessary)
Yes
No
UTILITY CUSTOMER
26
Applying Harmonic Limits For Industrial Facilities
1. Usually supplied by dedicated transformer2. Several nonliner loads – ASDs, Rectifiers, DC
drives, Induction furnaces 3. Loads are relatively low PF - Power factor
correction capacitors are installed4. Industrial loads like motors do not provide
much damping for resonance conditions5. Problems inside the facility before causing
problems in utility system6. Limit Voltage distortion to 5% at PCC – provide
some margin for distortion within facility
Applying Harmonic Limits For Industrial Facilities
1. Choose PCC2. Characterize Harmonic Loads3. Determine if PF Correction Needed4. Calculate Expected Current Harmonics
at PCC5. Design Harmonic Control Equipment, if
necessary6. Verify performance with measurements
27
Applying Harmonic Limits For Commercial Customers
• Significant percentage of Load is Electronic Equipment and Switch mode Power Supplies
• High Efficiency Fluorescent Lighting• HVAC Load is ASD drives• Significant harmonic cancellation -Meeting
IEEE 519 at SES is rarely a problem• Internal Harmonic Problems – neutral
overheating, transformer overloading, communication interference
Overview of Proposed Revisions to IEEE 519
• Immediate– Increased voltage limits for buses < 1 kV– Limits for time-varying harmonics– Revised notch and ringing limits and
definitions• Near-term
– Measurements• Limits for Single-Phase Equipment
– Dropped
28
Voltage Distortion Limits(% of nominal fundamental frequency
voltage)
Bus Voltage at PCC (Vn) Individual Harmonic
Voltage Distortion (%) Total Voltage
Distortion - THDVn (%)
V kVn ≤ 69 3.0 5.0
69 161kV V kVn< ≤ 1.5 2.5
V kVn > 161 1.0 1.5
Harmonic Voltage Limits
• Add a new voltage limit category for buses less than 1 kV– 5% limit for individual harmonics– 8% limit for voltage THD
• Main concern is associated with multiple zero crossings– Research has shown that concern has
merit
29
Time-Varying Harmonics
• Limits must be based on factual cause/effect– Thermal effects occur over time– Burst distortion effects can be instantaneous– Startup/abnormal conditions should be tolerated
• The facts suggest providing– Significant limit increases for short periods– Some limit increases for intermediate periods– No increases for the majority of the time