Harland Simon Baby Tagging Solution
21

Harland simon baby overview

Aug 18, 2015

Download

Technology

Declan Begley
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Harland simon baby overview

Harland SimonBaby Tagging Solution

Page 2: Harland simon baby overview

System Overview

Baby tagging solution consist of: • Elpas Hardware, ELC, RFs, LFs, Bus Network and tags• Elpas Software, Server based Eris and EV2 front end• Harland Simon Software, HS Baby Tagging

Page 3: Harland simon baby overview

18/04/2023 3

Elpas HardwareELCs, RFs, LFs, Bus Network, Nurse and Baby Tags

Page 4: Harland simon baby overview

ELC – Elpas Local Controller

ELC - Elpas Local Controller• Receives Tag Messages• Forwards Messages to Eiris via XML• 32 Programmable Control Rules• On Board IO• Master of the Bus• Takes control if Eiris Server if offline• Flush Ceiling Mounted

Page 5: Harland simon baby overview

RF – Radio Frequency Reader

• ARM9 Processor• Connects to the Bus Network• 2 Open Collector Digital Outputs (Rated 100mA)• 1 Dry Contact Digital Input• Real Time Clock with Backup Battery• Buzzer and Status LED• Same Form as ELC – Flush ceiling mounted

Page 6: Harland simon baby overview

LF – Low Frequency Exciter

• 125 KHz Field, good for covering exits• Continuously transmits magnetic signal with ID• ID Set via DIP Switches• Tuneable Range• Up to 3 meter range• Can be powered off Bus or separate power supply

Page 7: Harland simon baby overview

Infant Tag

• Active long-range Radio Frequency Tag• Consists of reusable tag and disposable anklet band• Transmits low power UHF (433MHz)• Transmits device supervision for lost away babies• Tamper• Low frequency receiver (125KHz) – LF detection• Bath and Shower Proof, Simple to clean

Page 8: Harland simon baby overview

Nurse Tag

• Active long range Radio Frequency Tag• 2 Programmable buttons, alarm cancel and nurse attack• Used for when system is running in ELC mode to stop alarms

Page 9: Harland simon baby overview

System Architecture

Network Switch

ELC – Bus Master RF1 RF2 RFn

LF Exciter

Tagged Baby

Server WorkstationWard 1

WorkstationWard 2

LF – Excites Tag

Tag Communicates via RF

Page 10: Harland simon baby overview

18/04/2023 10

Software - Elpas

Page 11: Harland simon baby overview

Elpas System Overview

• Eiris – server based software• Runs as a service• SDK – Allows tracking of events from Eiris

• EV2 – Client based software• Configuration of ELC• Automatically adds tags to system• Allows monitoring of ELC / RF / LFs and Tags• System fault finding

Page 12: Harland simon baby overview

EV2 - Setup

• Add the Elpas hardware, ELC, RFs and LFs

• Configure the Local Control – ELC Backup mode

• Set the properties to Automatically add Tags

Page 13: Harland simon baby overview

18/04/2023 13

Software – Harland Simon

Page 14: Harland simon baby overview

Overview

• HS Monitoring application, HSTagMonitoringSVC, runs as a service• Elpas API connects to Eiris Server to receive tag messages• HSEirisIF.dll connects to Eiris via the API• Harland Simon Baby Tracking Workstation Applicaiton

Elpas Eiris API HSEirisIF.dll HSRFIDReaderMessaging.dll LHM / CMH

Monitoring Service

Main Application

Page 15: Harland simon baby overview

Harland Simon Baby Tracking

• Workstation Based Application• Logs all user events, Add / Edit / Remove Baby• Allows Cancel of Alarms• User Access• Allow Outs• Trigger Alarm

Page 16: Harland simon baby overview

HS - Alarms

• Tag is at exit – detected by an LF• Tag is out of ward for too long, no detection via RF• Tag is lost• Tag is tampered• Battery level low

Page 17: Harland simon baby overview

Setting Reader Outputs

• When baby at exit LF or on tag tamper the ELC and RFs fire outputs• Sound Alarm and flash light• Lock a mag-lock door• Disable a lift request• Disable a swipe card reader• Software can set state and duration of output

Page 18: Harland simon baby overview

18/04/2023 18

Installation At North DurhamBaby Tagging Solution covering 4 wards

Page 19: Harland simon baby overview

North Durham Brief

• 1 Main Entrance / Exit – Alarm and Lock• 2 Fire Exits - Alarm• 1 Lift Exit – Disable Lift Access• 2 Secondary Exits / Swipe card Access – Alarm and Lock plus Disable• Babies need to move around wards• Backup system if Server down• Up to 50 Babies

Page 20: Harland simon baby overview

System Diagram

• 1 ELC• 11 RFs• 8 Exciters• 6 Alarm Towers• 1 Server• 2 Workstations

Page 21: Harland simon baby overview

Thank youAny Questions?