This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
● TheGX90XAanaloginputmoduleprovidesfourtypes:(1)universaltypethatallowsthemeasurementinputforDCV(directvoltage),TC(thermocouple),RTD(resistancetemperaturedetector),andDI(contactorTTLlevelvoltage),(2)current input type with the built-in shunt resistor to directlyinputastandardsignalof4-20mADC,(3)electromagneticrelayscannertypeinsusceptibletonoisesthatallowsthemeasurementinputforDCV,TC,andDI,and(4)lowwithstandvoltagerelaytypethat offers a low cost.
The GX90XA-04-H0 high-speed analog input modulecanmeasureDCV(DCvoltage),TC(thermocouple),RTD(resistancetemperaturedetector),DI(contactorTTLlevelvoltage)inputsattheshortestintervalof1ms.IthasanA/Dconverterforeachinputchannelandemploysascannerlessmethod,whichislesssusceptibletohighfrequencynoise.
Ineachsystem,ameasurementinputsignalcanbeassigned to each channel.
● TheGX90YAanalogoutputmoduleiscapableofretransmissionoutputofvarioustypesofchannelsandalsomanualoutput.Itprovidescurrentoutputwith channels that are isolated.
● TheGX90XDdigitalinputmodule,whichallowsupto 16 digital inputs or pulse inputs, can be used as amultipointdigitalinputorpluseinput.Thismodulecanalsobeusedasaremotecontrolinput.
● TheGX90WDdigitalinput/outputmoduleprovideseight digital inputs or pulse inputs and six relay outputs.Whentherearesmallamountsofdigitalinputs and digital outputs, you do not need to mounttwomodules.Thisenablesefficientchannelconfiguration.
Measurement accuracy (digital display) Max. resolution of digital display
A/D integration time: 16.7ms or more *22 A/D integration time: 1.67ms *23
DCV 20mV -20.000 to 20.000mV ±(0.05%ofrdg+12μV) ±(0.1%ofrdg+40μV) 1μV60mV -60.00 to 60.00mV ±(0.05%ofrdg+0.03mV) ±(0.1%ofrdg+0.15mV) 10μV200mV -200.00 to 200.00mV ±(0.05%ofrdg+0.03mV) ±(0.1%ofrdg+0.4mV) 10μV1V -1.0000 to 1.0000V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV2V -2.0000 to 2.0000V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV6V -6.000 to 6.000V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+15mV) 1mV20V -20.000 to 20.000V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+40mV) 1mV50V -50.00 to 50.00V ±(0.05%ofrdg+0.03V) ±(0.1%ofrdg+0.15V) 10mV
Standard signal
0.4-2V 0.3200 to 2.0800V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV1-5V 0.800 to 5.200V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+15mV) 1mV
DC current 0-20mA 0.000 to 20.000mA ±(0.3%ofrdg+5μA) ±(0.3%ofrdg+90μA) 1μVDC current(standardsignal
4-20mA 3.200 to 20.800mA
TC(ExcludingRJCac-curacy)
R*3 0.0 to 1760.0 °C ±(0.15%ofrdg+1.0°C)However, R, S; 0.0 to 800.0°C: ±2.2°C, B; 400.0 to 800.0°C: ±3.0°CAccuracy at less than 400.0°C is not guaranteed.
±(0.2%ofrdg+6.0°C)However, R, S; 0.0 to 800.0°C: ±7.6°C, B; 400.0 to 800.0°C: ±11.0°CAccuracy at less than 400.0°C is not guaranteed.
0.1°CS *3 0.0 to 1760.0 °CB *3 0.0 to 1820.0 °C
K *3 -270.0 to 1370.0 °C ±(0.15%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.35 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.2%ofrdg+5.0°C)However, -200.0 to 0.0°C: ±(3 % of rdg + 5.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C-200.0 to 500.0 °C
E *3 -270.0 to 800.0 °C ±(0.15%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.35 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.2%ofrdg+4.0°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 4.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°CJ *3 -200.0 to 1100.0 °C
T *3 -270.0 to 400.0 °C ±(0.15%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.35 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.2%ofrdg+2.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 2.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
N *3 -270.0 to 1300.0 °C ±(0.15%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.7 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.3%ofrdg+6.0°C)However, -200.0 to 0.0°C: ±(5 % of rdg + 6.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
W *4 0.0 to 2315.0 °C ±(0.15%ofrdg+1.5°C) ±(0.3%ofrdg+14.0°C)However,morethan1000.0°C:±(0.8%ofrdg+9.0°C)
0.1°C
L *5 -200.0 to 900.0 °C ±(0.15%ofrdg+0.5°C)Lessthan0.0°C:±(0.5%ofrdg+0.5°C)
±(0.2%ofrdg+4.0°C)Lessthan0.0°C:±(3%ofrdg+4.0°C)
0.1°C
U *5 -200.0 to 400.0 °C ±(0.15%ofrdg+0.5°C)Lessthan0.0°C:±(0.7%ofrdg+0.5°C)
±(0.2%ofrdg+2.5°C)Lessthan0.0°C:±(3%ofrdg+2.5°C)
0.1°C
WRe3-25*6 0.0 to 2320.0 °C ±(0.2%ofrdg+2.5°C) ±18.0°CMorethan2000.0°C:±0.9%ofrdg
0.1°C
KpvsAu7Fe*7 0.0 to 300.0 K ±(0.15%ofrdg+2.0K) ±(0.2%ofrdg+7.0K) 0.1 KPLATINEL II *7 0.0 to 1395.0 °C ±(0.25%ofrdg+2.3°C) ±(0.25%ofrdg+8.0°C) 0.1°CPR20-40*8 0.0 to 1900.0°C ±(0.7%ofrdg+0.4°C)
However, accuracy at less than 800.0°C is not guaranteed.
±20.0°CHowever, accuracy at less than 800.0°C is not guaranteed.
0.1°C
NiNiMo *7 0.0 to 1310.0°C ±(0.25%ofrdg+0.7°C) ±(0.5%ofrdg+5.0°C) 0.1°CW/WRe26*9 0.0 to 2320.0°C ±(0.2%ofrdg+2.0°C)
However, accuracy at less than 300.0°C is not guaranteed.
±(0.4%ofrdg+12.0°C)However, accuracy at less than 300.0°C is not guaranteed.
0.1°C
N(AWG14)*10 0.0 to 1300.0°C ±(0.2%ofrdg+1.3°C) ±(0.5%ofrdg+7.0°C) 0.1°CXK GOST *11 -200.0 to 600.0°C ±(0.25%ofrdg+0.8°C) ±(0.5%ofrdg+4.0°C) 0.1°C
Measurement accuracy (digital display) Max. resolution of digital display
A/D integration time: 16.7ms or more *22 A/D integration time: 1.67ms *23
RTD(Measuredcurrent:1mA)
Pt100 *12 -200.0 to 850.0°C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+1.5°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt100 *12 -200.00 to 550.00°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu10 GE -200.0 to 300.0°C ±(0.2%ofrdg+2.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
±(0.4%ofrdg+6.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10 at 20°Cα=0.00392
-200.0 to 300.0°C
Cu10 at 20°Cα=0.00393
-200.0 to 300.0°C
Cu25 at 0°Cα=0.00425
-200.0 to 300.0°C ±(0.3%ofrdg+0.8°C) ±(0.5%ofrdg+3.0°C) 0.1°C
Cu53 at 0°Cα=0.00426035
-50.0 to 150.0°C ±(0.15%ofrdg+0.8°C) ±(0.3%ofrdg+4.0°C) 0.1°C
Cu100 at 0°Cα=0.00425
-50.0 to 150.0°C ±(0.2%ofrdg+1.0°C) ±(0.4%ofrdg+5.0°C) 0.1°C
J263B *13 0.0 to 300.0 K ±1.0 KLess than 40.0 K: ±3.0 K
±3.0 KLess than 40.0 K: ±9.0 K
0.1 K
Ni100(SAMA) -200.0 to 250.0°C ±(0.15%ofrdg+0.4°C) ±(0.3%ofrdg+2.0°C) 0.1°CNi100(DIN)*14 -60.0 to 180.0°CNi120 *15 -70.0 to 200.0°CPt25 *16 -200.0 to 550.0°C ±(0.15%ofrdg+0.8°C) ±(0.3%ofrdg+4.0°C) 0.1°CPt50 *17 -200.0 to 550.0°C ±(0.3%ofrdg+0.6°C) ±(0.6%ofrdg+3.0°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.3%ofrdg+1.0°C)Cu10 GOST *18 -200.0 to 200.0°C ±(0.2%ofrdg+2.0°C) ±(0.4%ofrdg+6.0°C) 0.1°CCu50 GOST *19 -200.0 to 200.0°C ±(0.15%ofrdg+0.6°C) ±(0.3%ofrdg+4.0°C) 0.1°CCu100 GOST *20
-200.0 to 200.0°C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+1.5°C) 0.1°C
Pt46 GOST *19 -200.0 to 550.0°C ±(0.3%ofrdg+0.8°C) ±(0.6%ofrdg+4.0°C) 0.1°CPt100 GOST *20 -200.0 to 600.0°C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+2.0°C) 0.1°C
4-wireRTD(Measuredcurrent: 1mA)
Pt100*12 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt100*12 -200.0 to 550.0°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu10 GE -200.0 to 300.0°C ±(0.1%ofrdg+2.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
±(0.2%ofrdg+5.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10 at 20°Cα=0.00392
-200.0 to 300.0°C
Cu10 at 20°Cα=0.00393
-200.0 to 300.0°C
Cu25 at 0°Cα=0.00425
-200.0 to 300.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°C
Cu53 at 0°Cα=0.00426035
-50.0 to 150.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Cu100 at 0°Cα=0.00425
-50.0 to 150.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
J263B*13 0.0 to 300.0K ±0.4 KLess than 40.0 K: ±0.8 K
±1.5 KLess than 40.0 K: ±3.0 K
0.1K
Ni100(SAMA) -200.0 to 250.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°CNi100(DIN)*14 -60.0 to 180.0°C 0.1°CNi120*15 -70.0 to 200.0°C 0.1°CPt25*16 -200.0 to 550.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°CPt50*17 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.05%ofrdg+1.0°C) ±(0.1%ofrdg+3.0°C) 0.1°CCu10 GOST*18 -200.0 to 200.0°C ±(0.1%ofrdg+2.0°C) ±(0.2%ofrdg+5.0°C) 0.1°CCu50 GOST*19 -200.0 to 200.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CCu100 GOST*20
-200.0 to 200.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Pt46 GOST*19 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt100 GOST*20 -200.0 to 600.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
4-wireRTD(Measuredcurrent: 0.25mA)
Pt500 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt1000 -200.0 to 850.0°C
Resistance(4-wire)
20Ω(Meas-ured current: 1mA)
0.0 to 20.000Ω ±(0.05%ofrdg+0.007Ω) ±(0.1%ofrdg+0.025Ω) 0.001Ω
200Ω(Meas-ured current: 1mA)
0.0 to 200.00Ω ±(0.05%ofrdg+0.03Ω) ±(0.1%ofrdg+0.15Ω) 0.01Ω
2000 Ω(Measuredcurrent: 0.25 mA)
0.0 to 2000.0Ω ±(0.05%ofrdg+0.3Ω) ±(0.1%ofrdg+1.0Ω) 0.1Ω
Measurement accuracy (digital display) Max. resolution of digital display
Scan interval: 50 ms or more(Only the Values in [ ] apply when the
scan interval is 50/100/200 ms)
Scan interval: 20 ms or less(Only the Values in [ ] apply when the
scan interval is 1/2/5 ms)DCV 20mV -20.000 to 20.000mV ±(0.05%ofrdg+5[12]μV) ±(0.1%ofrdg+25[40]μV) 1μV
60mV -60.00 to 60.00mV ±(0.05%ofrdg+0.02mV) ±(0.1%ofrdg+0.1mV) 10μV200mV -200.00 to 200.00mV ±(0.05%ofrdg+0.02[0.03]mV) ±(0.1%ofrdg+0.1[0.4]mV) 10μV1V -1.0000 to 1.0000V ±(0.05%ofrdg+0.2mV) ±(0.1%ofrdg+1.0mV) 100μV2V -2.0000 to 2.0000V ±(0.05%ofrdg+0.5[1.2]mV) ±(0.1%ofrdg+1.0[4.0]mV) 100μV6V -6.000 to 6.000V ±(0.05%ofrdg+2mV) ±(0.1%ofrdg+10mV) 1mV20V -20.000 to 20.000V ±(0.05%ofrdg+2[3]mV) ±(0.1%ofrdg+10[40]mV) 1mV50V -50.00 to 50.00V ±(0.05%ofrdg+0.02V) ±(0.1%ofrdg+0.10V) 10mV100V -100.00 100.00V ±(0.05%ofrdg+0.02V) ±(0.1%ofrdg+0.10V) 10mV
Standard signal
0.4-2V 0.3200 to 2.0800V ±(0.05%ofrdg+0.5[1.2]mV) ±(0.1%ofrdg+1.0[4.0]mV) 100μV1-5V 0.800 to 5.200V ±(0.05%ofrdg+2mV) ±(0.1%ofrdg+10mV) 1mV
TC(ExcludingRJCac-curacy)
R*3 0.0 to 1760.0 °C ±(0.05%ofrdg+1.0°C)However, R, S; 0.0 to 800.0°C: ±1.4°C, B; 400.0 to 800.0°C: ±1.5 [3.0] °CAccuracy at less than 400.0°C is not guaranteed.
±(0.1%ofrdg+4.0[6.0]°C)However, R, S; 0.0 to 800.0°C: ±4.8 [7.6] °C, B; 400.0 to 800.0°C: ±7.0 [11.0]°CAccuracy at less than 400.0°C is not guaranteed.
0.1°CS *3 0.0 to 1760.0 °CB *3 0.0 to 1820.0 °C
K *3 -270.0 to 1370.0 °C ±(0.05%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.2 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+3.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 3.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C-200.0 to 500.0 °C
E *3 -270.0 to 800.0 °C ±(0.05%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.2 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+2.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 2.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°CJ *3 -200.0 to 1100.0 °C
T *3 -270.0 to 400.0 °C ±(0.05%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.2 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+2.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 2.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
N *3 -270.0 to 1300.0 °C ±(0.05%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.5 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+4.0°C)However, -200.0 to 0.0°C: ±(3.5 % of rdg + 4.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
W *4 0.0 to 2315.0 °C ±(0.05%ofrdg+1.0°C)Morethan1000.0°C:±(0.15%ofrdg)
L *5 -200.0 to 900.0 °C ±(0.05%ofrdg+0.5°C)Lessthan0.0°C:±(0.25%ofrdg+0.5°C)
±(0.1%ofrdg+2.5°C)Lessthan0.0°C:±(3%ofrdg+4.0°C)
0.1°C
U *5 -200.0 to 400.0 °C ±(0.05%ofrdg+0.5°C)Lessthan0.0°C:±(0.5%ofrdg+0.5°C)
±(0.1%ofrdg+2.5°C)Lessthan0.0°C:±(2%ofrdg+2.5°C)
0.1°C
WRe3-25*6 0.0 to 2320.0 °C ±(0.05%ofrdg+2.0°C)Morethan2000.0°C:±(0.15%ofrdg)
±(0.1%ofrdg+8.0°C)Less than 200.0°C: 12.0°CMorethan2000.0°C:±(0.1%ofrdg+13.0°C)
0.1°C
KpvsAu7Fe*7 0.0 to 300.0 K ±(0.05%ofrdg+0.7[2.0]K) ±(0.1%ofrdg+3.5[7.0]K) 0.1 KPLATINEL II *7 0.0 to 1395.0 °C ±(0.05%ofrdg+1.0°C) ±(0.1%ofrdg+4.0°C) 0.1°CPR20-40*8 0.0 to 1900.0°C ±(0.05%ofrdg+2.5[5.5]°C)
However, accuracy at less than 800.0°C is not guaranteed.
±(0.1%ofrdg+12.0[18.0]°C)However, accuracy at less than 800.0°C is not guaranteed.
0.1°C
NiNiMo *7 0.0 to 1310.0°C ±(0.05%ofrdg+0.7°C) ±(0.1%ofrdg+2.7°C) 0.1°CW/WRe26*9 0.0 to 2320.0°C ±(0.05%ofrdg+2.0°C)
However, accuracy at less than 300.0°C is not guaranteed.
±(0.1%ofrdg+10.0°C)However, accuracy at less than 300.0°C is not guaranteed.
0.1°C
N(AWG14)*10 0.0 to 1300.0°C ±(0.05%ofrdg+0.7°C) ±(1.0%ofrdg+4.0°C) 0.1°CXK GOST *11 -200.0 to 600.0°C ±(0.05%ofrdg+0.5°C)
Less than 0.0°C:±(0.2%ofrdg+0.5°C)±(0.1%ofrdg+2.5°C)Less than 0.0°C: ±(1%ofrdg+2.5°C)
Measurement accuracy (digital display) Max. resolution of digital display
Scan interval: 50 ms or more(Only the Values in [ ] apply when the
scan interval is 50/100/200 ms)
Scan interval: 20 ms or less(Only the Values in [ ] apply when the
scan interval is 1/2/5 ms)RTD(Measuredcurrent: 1mA)
Pt100 *13 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt100 *13 -200.0 to 550.0°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu25 at 0°Cα=0.00425
-200.0 to 300.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°C
Cu53 at 0°Cα=0.00426035
-50.0 to 150.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Cu100 at 0°Cα=0.00425
-50.0 to 150.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
J263B *14 0.0 to 300.0 K ±4.0 KLess than 40.0 K: ±0.8 K
±1.5 KLess than 40.0 K: ±3.0 K
0.1 K
Ni100(SAMA) -200.0 to 250.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°CNi100(DIN)*15 -60.0 to 180.0°CNi120 *16 -70.0 to 200.0°CPt25 *17 -200.0 to 550.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°CPt50 *18 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.05%ofrdg+1.0°C) ±(0.1%ofrdg+3.0°C) 0.1°CCu50 GOST *20 -200.0 to 200.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CCu100 GOST *21
-200.0 to 200.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Pt46 GOST *20 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt100 GOST *21 -200.0 to 600.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
RTD(Measuredcurrent: 1.6mA)
Cu10 GE -200.0 to 300.0°C ±(0.1%ofrdg+0.7[2.0]°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
±(0.2%ofrdg+2.5[5.0]°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10 at 20°Cα=0.00392
Install it in a location where people cannot touch theterminalscarelessly.
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceother than the front-panel control area with an instrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
Power Supply SuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.• Powerconsumption: GX90XA-10-U2: 0.7 W or less GX90XA-10-T1: 0.9 W or less GX90XA-10-C1: 0.7 W or less GX90XA-10-L1: 0.7 W or less GX90XA-04-H0: 2.0 W or less GX90XA-06-R1:0.7Worless
• UL: UL61010-1,UL61010-2-030(CSANRTL/C) UL61010-2-201(CSANRTL/C)*5• CE/EMCdirective *3: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective*3: EN61010-1, EN 61010-2-030 Installation category II *1
Pollution degree 2 *2
MeasurementcategoryII*3 EN61010-2-201compliance*5
• EMCRegulatoryArrangementinAustraliaandNewZealand(RCM):EN55011compliance,Class A Group 1
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O)Specifications:GS
04L53B00-01ENGMSpecifications:GS04L55B01-01EN
Transport and Storage Conditions• Ambienttemperature:–25to70°C• Ambienthumidity:5to95%RH(no
Effects of Operating ConditionsIntegraltime16.67msormoreorscaninterval50msormore(forthehigh-speeduniversaltype)• Influenceofambienttemperature:variation
Safety and EMC Standards• CSA: CAN/CSA22.2 No.61010-1, installation category
II *1, pollution degree 2 *2
CAN/CSA-IEC61010-2-201*4
• UL: UL61010-1(CSANRTL/C) UL61010-2-201(CSANRTL/C)*4• CE/EMCdirective*3: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective EN61010-1 Installation category II *1
Install it in a location where people cannot touch theterminalscarelessly.
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceother than the front-panel control area with an instrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):GS04L53B00-
Install it in a location where people cannot touch theterminalscarelessly.
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceother than the front-panel control area with an instrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
Safety and EMC Standards• CSA: CAN/CSA22.2 No.61010-1, installation category
II *1, pollution degree 2 *2
CAN/CSA-IEC61010-2-201*4
• UL: UL61010-1(CSANRTL/C) UL61010-2-201(CSANRTL/C)*4• CE/EMCdirective*3: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective EN61010-1 Installation category II *1
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.However,excludingtheshockat energization.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):ThisGeneral
SpecificationsGMSpecifications:GS04L55B01-01EN
Transport and Storage ConditionsSameastheGX90XA.
Installation limitationsUp to a total of 10 GX90WD digital input/output
Safety and EMC Standards• CSA: CAN/CSA22.2 No.61010-1, installation category
II *1, pollution degree 2 *2
CAN/CSA-IEC61010-2-201*4
• UL: UL61010-1(CSANRTL/C) UL61010-2-201(CSANRTL/C)*4• CE/EMCdirective*3: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective EN61010-1 Installation category II *1
Install it in a location where people cannot touch theterminalscarelessly.
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceother than the front-panel control area with an instrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
Note: Output channels are functionally isolated. In consideration of safety standards, do not connect theoutputchanneltoamixtureofMainsCircuits(primarypowersupplycircuits)andcircuitsderivedfromMainsCircuits(secondarypowersupplycircuits).
Terminal arrangementsM3 screw terminal
No. Symbol No. Symbol No. Symbol301 DI3 201 DI2 101 DI1
• CE/EMCdirective *3: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective*3: EN61010-1, EN 61010-2-030 Installation category II *1
Install it in a location where people cannot touch theterminalscarelessly.
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceother than the front-panel control area with an instrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications:GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):
• UL: UL61010-1,UL61010-2-030(CSANRTL/C) UL61010-2-201(CSANRTL/C)*4• CE/EMCdirective *3: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective*3 EN61010-1, EN 61010-2-030 Installation category II *1
Install it in a location where people cannot touch theterminalscarelessly.
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceother than the front-panel control area with an instrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):GS04L53B00-
MODEL and SUFFIX Code (GX90XD)Model Suffix Code Description
GX90XD Digital Input Module*Numberofchannels -16 16 channelsType -11 Opencollector/Non-voltage,contact(sharedcommon),Rated5VDC- N Always NTerminalform -3 Screwterminal(M3)
-C ClampterminalArea N General
* Ifyouwanttointegratepulseinput,amathfunction(/MToption)isrequiredintheGX/GP/GMmainunit.MODEL and SUFFIX Code (GX90YD)
Model Suffix Code DescriptionGX90YD Digital Output ModuleNumberofchannels -06 6 channelsType -11 Relay,SPDT(NO-C-NC)- N Always NTerminalform -3 Screwterminal(M3)Area N General
MODEL and SUFFIX Code (GX90WD)Model Suffix Code Description
Test certificate (QIC, sold separately)WhenorderingtheGX10/GX20/GP10/GP20withoptions(analog/digialI/O),theQICforeachmoduleisincludedinandshippedwiththeQICofthemainunit.WhenorderinganaloginputmodulesanddigitalI/Omodules,eachmodulegetsitsownQIC(oneQICpermodule).
and GX90YA, . Theotherwayistopurchasethemasanoption(/UCxxor/USxx).Purchasingthemasanoptionisconvenient,butthisplaceslimitationsonthenumberofanaloginputsthatyoucanobtain.