GSW Series 50Hz - R22 Submittal Data Eng/SI Contractor: P.O.: Engineer: Project Name: Unit Tag: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. Page ______ of ______ Rev.: 04/16/02 *LC275* LC275 RELEASE: 04/16/02 SERIES: HZ: UNIT OF MEAS: LANG: GSW - R22 50 SI ENGLISH GSW Series Water to Water Submittal Data Models GSW 036, 060 & 120 50 Hz - R22 English Language/SI Units
21
Embed
GSW Submittal Set - files.climatemaster.com 50Hz R22 LC275.pdf · GSW Series 50Hz - R22 Submittal Data Eng/SI Contractor: P.O.: Engineer: Project Name: Unit Tag: ClimateMaster works
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
RELEASE: 04/16/02
SERIES:HZ:UNIT OF MEAS:LANG:
GSW - R2250SI
ENGLISH
GSW SeriesWater to WaterSubmittal Data
Models GSW 036, 060 & 12050 Hz - R22
English Language/SI Units
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
MODEL DECODER
Controls & Agency Listing
FUGS 036 A 1 FW S0 C C
Revision LevelA = Current
ConfigurationW = Water-to-Waterl
GS = Genesis Series High Efficiency
Cabinet Insulation1 = Extended Range2 = Extended Range w/UltraQuiet
Source Water Coil OptionsC = CopperN = Cupro-Nickel
Water Connection LocationF = FrontR = Right, 120 onlyL = Left, 120 onlyB = Back, 120 only
0 = None1 = Hot Water Generator coil & pump - 036 & 060 only2 = Hot Water Generator coil only
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
All ratings based upon lower voltage of dual voltage operation. Rev.: 4/16/02 B
Indoor coil also called "Load" and Outdoor coil also called "Source"
cfm*0.472 = l/sgpm*0.0631 = l/sin wg*249 = pascalsft of hd *2990 = pascals
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Indoor 53.6 °FOutdoor 86 °F
Indoor 104 °FOutdoor 68 °F
Indoor 53.6 °FOutdoor 59 °F
Indoor 104 °FOutdoor 50 °F
Indoor 53.6 °FOutdoor 77 °F
Indoor 104 °FOutdoor 32 °F
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Indoor 12 °COutdoor 30 °C
Indoor 40 °COutdoor 20 °C
Indoor 12 °COutdoor 15 °C
Indoor 40 °COutdoor 10 °C
Indoor 12 °COutdoor 25 °C
Indoor 40 °COutdoor 0 °C
Data is presented in accordance with, but not certified by ARI/ISO/ASHRAE 13256-2
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Interpolation is permissible, extrapolation is not. Rev: 04/03/02 BAll performance data is based upon the lower voltage of dual voltage rated units.All performance data is based upon a load coaxial heat exchanger of single-walled copper construction. For vented double-walled performance consult the factory.Table does not reflect ISO pump corrections.
LOADSOURCE
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Interpolation is permissible, extrapolation is not. Rev: 04/03/02 BAll performance data is based upon the lower voltage of dual voltage rated units.All performance data is based upon a load coaxial heat exchanger of single-walled copper construction. For vented double-walled performance consult the factory.Operation below 5°C is based upon 15% antifreeze solution
OPERATION NOT RECOMMENDED OPERATION NOT RECOMMENDED
SOURCE LOAD
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Interpolation is permissible, extrapolation is not. Rev: 04/03/02 BAll performance data is based upon the lower voltage of dual voltage rated units.All performance data is based upon a load coaxial heat exchanger of single-walled copper construction. For vented double-walled performance consult the factory.Table does not reflect ISO pump corrections.
SOURCE LOAD
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Interpolation is permissible, extrapolation is not. Rev: 04/03/02 BAll performance data is based upon the lower voltage of dual voltage rated units.All performance data is based upon a load coaxial heat exchanger of single-walled copper construction. For vented double-walled performance consult the factory.Operation below 5°C is based upon 15% antifreeze solution
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
SOURCE LOAD
OPERATION NOT RECOMMENDED OPERATION NOT RECOMMENDED
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Interpolation is permissible, extrapolation is not. Rev: 04/03/02 BAll performance data is based upon the lower voltage of dual voltage rated units.All performance data is based upon a load coaxial heat exchanger of single-walled copper construction. For vented double-walled performance consult the factory.Table does not reflect ISO pump corrections.
SOURCE LOAD
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Interpolation is permissible, extrapolation is not. Rev: 04/03/02 BAll performance data is based upon the lower voltage of dual voltage rated units.All performance data is based upon a load coaxial heat exchanger of single-walled copper construction. For vented double-walled performance consult the factory.Operation below 5°C is based upon 15% antifreeze solution
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
OPERATION NOT RECOMMENDED
SOURCE LOAD
OPERATION NOT RECOMMENDED OPERATION NOT RECOMMENDED
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW PHYSICAL DATA
GSW UNIT ELECTRICAL DATAProduct Rated Voltage Optional Total Min Max
Model Class Voltage Min/Max HWG Pump Unit Circ Fuse/
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
1 - Source Water In2 - Source Water Out3 - Load Water In4 - Load Water Out5 - HWG Water In6 - HWG Water Out
3/4” FPT3/4” FPT3/4” FPT3/4” FPT1/2” FPT1/2” FPT
1” FPT1” FPT1” FPT1” FPT
1/2” FPT1/2” FPT
Water Connection 036 060
Note:Commercial Class Connections ShownDistributor Class Utilizes 1” Swivel Throughout
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Source Water Connections Elect KnockOverall CabinetWater to
3.91in [9.93 cm]
Rev.: 03/12/02 B
D
E
K
L
D
E
KL
D E
L
K
NM
GF
H
J
Right Water Connections Left Water Connections
Rear Water Connections Front Water Connections
A
B
C
3.91 in [9.93 cm]
1.81
Source Water1-1/2” FPT
Load Water1-1/2” FPT
1.81 in [4.60 cm]
1.81 in[4.60 cm]
1.56 in[3.96 cm]
2.25 in[5.72 cm]
7/8 in[4.60 cm]
LV Knockout
1-3/8 & 1-3/4 in[3.49 & 4.45 cm]
HV DoubleKnockout
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
GSW036-060 208-230/60/1, 265/60/1, 220-240/50/1 CXM Commercial 96B0048N01 9/4/01 Rev: A
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW036 WIRING DIAGRAM220-240/50/1DXM COMMERCIAL CLASS
GSW036-060 208-230/60/1, 265/60/1, and 220-240/50/1DXM Comm 96B0048N02 9/4/01 Rev: A
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW036-060 WIRING DIAGRAM380-420/50/3CXM COMMERCIAL CLASS
GSW036-060 208-230/60/3, 460/60/3, 575/60/3, and 380-420/50/3CXM Comm 96B0049N01 9/4/01 Rev: B
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW120 WIRING DIAGRAM380-420/50/3CXM COMMERCIAL CLASS
GS
W12
0 2
08-2
30/6
0/3,
460
/60/
3, 5
75/6
0/3,
and
380
-420
/50/
3 C
XM
C
omm
erci
al 9
6B00
87N
01
10/
03/0
1 R
ev: -
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW036 WIRING DIAGRAM220-240/50/1 CXM CECOMMERCIAL CLASS
GS
W03
6 22
0-24
0/50
/1C
XM
CE
96
B00
50N
01R
ev A
2
/19/
02
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW036 WIRING DIAGRAM220-240/50/1 DXM CECOMMERCIAL CLASS
GS
W03
6 2
20-2
40/5
0/1
DX
M C
E
96B
0050
N02
Rev
A
2/2
0/02
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW036, 060 WIRING DIAGRAM380-420/50/3 CXM CECOMMERCIAL CLASS
GS
W03
6, 0
60 3
80-4
20/5
0/3
CX
M C
E96
B00
51N
01R
ev A
2
/19/
02
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW036-060 WIRING DIAGRAM380-420/50/3 DXM CECOMMERCIAL CLASS
GS
W03
6, 0
60 3
80-4
20/5
0/3
DX
M C
E
96B
0051
N02
Rev
-
2/2
0/02
GSW Series 50Hz - R22 Submittal Data Eng/SI
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com .
Page ______ of ______Rev.: 04/16/02*LC275*
LC275
GSW120 WIRING DIAGRAM380-420/50/3 CXM CECOMMERCIAL CLASS