DEESYS TOTAL PRODUCTS GUIDE 83 GROUND OVER VOLTAGE RELAY[64] DVG-M11D The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit breaker through the use of GPT. As it is operated by detecting ground fault from third end of GPT, no concen for malfunction caused by static capacity of cable to ground. It is enconomical to use as modest power dissipation formal PT. Accordingly smaller current limiting resistor(W) will be required. Since the operation is highly sensitive, it is adequate for use in detection grounding fault of generators. Target shall show the fault condition accurately. Characteristics 1. Voltage Display / Operating Count 2. Voltage Limits Element 3. Time Lever Setting Element 4. Groud Voltage Test 5. Monitor Selection Switch 6. Time Curve Selection Switch 7. Groud Voltage Start LED 8. CPU Run LED 9. Trip Indicator(Manual Reset) 10. Draw-out Handle Front plate
4

GROUND OVER VOLTAGE RELAY[64] · The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit breaker through the use

Sep 28, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: GROUND OVER VOLTAGE RELAY[64] · The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit breaker through the use

DEESYS TOTAL PRODUCTS GUIDE 83

GROUND OVER VOLTAGE RELAY[64]

DVG-M11D

● The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit

breaker through the use of GPT.● As it is operated by detecting ground fault from third end of GPT, no concen for malfunction caused by static capacity of

cable to ground.● It is enconomical to use as modest power dissipation formal PT. Accordingly smaller current limiting resistor(W) will be

required.● Since the operation is highly sensitive, it is adequate for use in detection grounding fault of generators. ● Target shall show the fault condition accurately.

Characteristics

1. Voltage Display / Operating Count

2. Voltage Limits Element

3. Time Lever Setting Element

4. Groud Voltage Test

5. Monitor Selection Switch

6. Time Curve Selection Switch

7. Groud Voltage Start LED

8. CPU Run LED

9. Trip Indicator(Manual Reset)

10. Draw-out Handle

Front plate

Page 2: GROUND OVER VOLTAGE RELAY[64] · The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit breaker through the use

84 DEESYS TOTAL PRODUCTS GUIDE

DVG-M11D(Draw out) IEC255 JEC 2500, 2511

Specifications

■Model DVG-M11D(Draw out)

■Rating Rated Voltage AC 110V/190V

Frequency 60/50㎐±5%

Auxiliary Voltage AC/DC 110V(86~260V)

Ambient temperature -10℃ to 60℃(with no icing)

■Voltage setting Over Voltage range 10~85(steps of 5V)

■Time setting Over Voltage time tap 0.05~10.3lever(steps of 0.05)

0.05sec±25ms, 0.1~10sec±10%

Resetting Value >90%

Reset time Less than 100ms

■Burden Over Voltage Less than 2VA

Aux. Voltage 10VA(AC), 6W(DC)

■Contact Out put Relay Trip 1c, Alarm 1a

Trip & Alarm contact capacity

Make AC 240V 10A(L/R=0ms)

DC 1000W 0.5Sec(L/R=0ms)

Break AC 240V 3A(L/R=0ms)

DC 30W 0.5Sec(L/R=0ms)

■Indicator Operating start LED(Red)

Operating(trip) Target(Manual Reset)

■Operating time Over Voltage Inverse or definite time

Degree Protection IP 52

■Vibration resistance Malfunction 10㎐ 5mm double amplitude 30s

each in X and Y directions

16.7㎐ 2.5mm double amplitude

600s each in X,Y, and Z directions

■Shock resistance Destruction; 300㎨(approx. 30G) 3 time each

in 3 directions

■Insulation to IEC 255 Dielectric withstand 2kV for 1 minute between

all terminals and case earth

Insulation resistance at 500V > 100㏁

Impluse Voltage Withstand 5kV-1.2/50 ㎲

Surge transient simulator 2.5kV 1MHz/200Ω

Weight 2.0kg

GROUND OVER VOLTAGE RELAY[64]

Page 3: GROUND OVER VOLTAGE RELAY[64] · The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit breaker through the use

DEESYS TOTAL PRODUCTS GUIDE 85

Operating time curves

(%) Voltage (%) Voltage

(Inverse time) (Definite time)

Block diagram

Page 4: GROUND OVER VOLTAGE RELAY[64] · The relay is used in non-grounded power system of distribution lines of power station for the purpose of tripping circuit breaker through the use

86 DEESYS TOTAL PRODUCTS GUIDE

Dimension

Digital type draw outCase : ABS (Non flamable)Color : Black(N1.5) Cutting Size: 165 X 122mm

Wiring

Draw out

Draw out

Terminal arrangement

GROUND OVER VOLTAGE RELAY[64]