DSEWebNet®
DSEWebNet® IS THE IDEAL SOLUTION FOR EFFICIENTGENSET
MAINTENANCE, FLEET MANAGEMENT,ASSET TRACKING, REMOTE/PERIODIC
GENSETTESTING, FUEL MANAGEMENT, FAULT ANALYSIS &MUCH MORE. The
DSEWebNet® system offers features such as mapping with
staticlocations, real time instrumentation and control, event log
tables andautomatic system alerts which are sent to multiple
DSEWebNet® users viaemail and SMS.
Comprehensive on-screen information is presented in clear,
graphical andnumerical formats which is easy to navigate and
operate.
DSEWebNet® can be utilised to maximise system up-time by
offering themost effective remote management tool.
The DSEWebNet® Gateway device provides the user with full
instant accessto the DSEWebNet® system. A single Gateway device can
be connected toa maximum of twenty supported DSE controllers. This
creates a vast andextensively featured remote control and site
monitoring solution.
An unlimited number of DSEWebNet® users can access a single
Gatewaydevice. Additionally a single user can access an infinite
number of Gatewaydevices. To gain access to either the Gateway
Device or the DSEWebNet®,secure login information is required. This
low cost solution makes thesystem a secure and effective remote
monitoring and control solution formultiple users and sites.
DSEWebNet®
Smart Phone DevicesTablet Devices
DSEWebNet® GatewayDSEWebNet® Gateway
DSE Module
DSE Module DSE Module DSE Module
DSEWebNet® GatewayDSEWebNet® Gateway
Laptop / PC
055-117/02/12 (1) US
DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial
Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE
+44 (0) 1723 893303EMAIL [email protected] WEBSITE
www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL
61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316
8708EMAIL [email protected] WEBSITE www.deepseausa.com
Registered in England & Wales No.01319649VAT
No.316923457
Deep Sea Electronics Plc maintains a policy of continuous
development and reserves the right to changethe details shown on
this data sheet without prior notice. The contents are intended for
guidance only.
SPECIFICATION
DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V continuous
CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply
was at least 10 V before dropoutand supply recovers to 5 V. This is
achievedwithout the need for internal batteries
MAXIMUM OPERATING CURRENTGSM 700 mA at 12 V, 450 mA at 24 VGSM
& GPS 700 mA at 12 V, 450 mA at 24 VEthernet 200 mA at 12 V,
110 mA at 24 VEthernet & GPS 700 mA at 12 V, 450 mA at 24 V
MAXIMUM STANDBY CURRENTGSM 270 mA at 12 V, 150 mA at 24 VGSM
& GPS 270 mA at 12 V, 150 mA at 24 VEthernet 150 mA at 12 V, 90
mA at 24 VEthernet & GPS 270 mA at 12 V, 150 mA at 24 V
COMMUNICATIONSUSB (Single DSE Controller)RS232 (Single DSE
Controller)RS485 (Multiple DSE Controllers)Ethernet (Multiple DSE
Controllers)
DIMENSIONS85mm x 149mm x 51mm
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic
Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC
Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETYBS EN 60950Safety of Information Technology
Equipment, including Electrical Business Equipment
TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN
60068-2-2Bb/Be Dry Heat +70 oC
VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5
Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn
HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48
HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48
Hours
SHOCKBS EN 60068-2-27Three shocks in each of three major axes15
gn in 11 mS
www.deepseaplc.com
COMMUNICATIONSINTERFACE
DSEWebNet® Gateway
The DSEWebNet Gateway is used in conjunction withsupported DSE
controllers to provide monitoring andcommunications data via the
DSEWebNet® advancedcommunications system.
The DSEWebNet Gateway communicates to theconnected DSE
controller(s), monitoring theinstrumentation and operating state.
When this datachanges, the new data is logged in the internal
memory.At regular intervals the logged data is transmitted to
theDSE host server.
The DSE host server is then integrated into theDSEWebNet® which
can be accessed via an internetconnected device and web browser to
allow remotemonitoring and control of multiple DSE
controllersaround the globe. GSM, GPS and GSM/GPS antenna’sare
available as accessories.
DSE890DSEWebNet®Gateway - 3G (GSM)/Ethernet
The Gateway connects to the DSE data server byintegral Ethernet
connection or GPRS (DSM or 3Gmobile internet) and includes GPS
(satellite location)functionality. This is most suited to remote
and/or mobilelocations.
DSE891DSEWebNet®Gateway - Ethernet Only
The Gateway connects to the DSE data server by anintegral
Ethernet connection only. This is most suited forfixed
installations where an ADSL / DSL cablebroadband service is
available (external broadbandmodem required, not supplied by
DSE).
TITLEDSEGateway DSE890 Installation InstructionsDSEGateway
DSE890 Hardware ManualDSEWebnet Software Manual
PART NO’S053-140057-165057-168
PARTGSM AntennaGPS AntennaGSM/GPS Antenna
PART NO’S020-141020-130020-150
RELATED MATERIALS
ACCESSORIES
COMPATIBLE DSE CONTROLLERS INCLUDE:
DSE4410DSE6010DSE6110DSE7110
DSE7210DSE7310DSE7410DSE8610
DSE4420DSE6020DSE6120DSE7120
DSE7220DSE7320DSE7420
AUTO START MODULES AUTO MAINS FAILURE MODULES
The DSEWebNet Gateway will soon be compatible with the DSE45xx,
DSE87xx & DSE88xx range ofGenset Controllers.