Hydro Generator Up Grades

W. Howard Moudy Director of Service Management

National Electric Coil [email protected]

724-787-4967 www.National-Electric-Coil.com

2014 North West Hydro Association Technical Seminar

1

Page 2: Generator Stator Rewinds: A Review of the Stator Rewind Process

According to Wikipedia -

• Upgrading is the process of replacing a

product with a newer version of the

same product. In computing and

consumer electronics an upgrade is

generally a replacement of hardware,

software or firmware with a newer or

better version, in order to bring the

system up to date or to improve its

characteristics.

2

Page 3: Generator Stator Rewinds: A Review of the Stator Rewind Process

Hydro Generator Trends

• Life extensions

• Enhanced reliability

• Watt per water value

• Effective upgrades enable and

support the above trends

3

Page 4: Generator Stator Rewinds: A Review of the Stator Rewind Process

Primary Hydro Generator Components for

Upgrade Consideration

• Phase Rings

• Stator Slot Wedges

• Rotor Coil – Coil to Coil Connections

– Turn and Ground Insulation

• Stator Winding – Stator Coil Insulation

– Stator Coil design (MultiTurn VS. Roebel Bar)

– Stator Coil Losses

• Stator Core – Core Lamination Steel

– Core Lamination Coating

– Continuous stacking (No Splits)

• Ventilation – Fans / Coolers

4

Page 5: Generator Stator Rewinds: A Review of the Stator Rewind Process

Phase Rings

5

Page 6: Generator Stator Rewinds: A Review of the Stator Rewind Process

Verifying Isolation

6

Page 7: Generator Stator Rewinds: A Review of the Stator Rewind Process

Completed Buss Ring Up Grade

7

Page 8: Generator Stator Rewinds: A Review of the Stator Rewind Process

Wedging

• Options:

– Conventional Flat Slab

• Less Expensive

• More time to install properly

• More difficult to get even

compression

– Piggy Back

• More expensive

• Less time to install

• Better compression

consistency

8

Page 9: Generator Stator Rewinds: A Review of the Stator Rewind Process

Checking Stator Wedge

Tightness

9

Page 10: Generator Stator Rewinds: A Review of the Stator Rewind Process

Rotor Coil to Coil Connectors

10

Page 11: Generator Stator Rewinds: A Review of the Stator Rewind Process

Case Study #1

Coil to Coil Repair and Up Grade • Original pole/rim design

– Solid, bolted lead

– Laminated rotor rim

• Problems with pole

looseness and

vibration due to rim

warp age

11

Page 12: Generator Stator Rewinds: A Review of the Stator Rewind Process

Case Study #1

• Issues

– Distorted pole mounting surface, allowing

rocking of the pole

– Uneven laminated surface coming in contact

with tapered driving keys leading to false

assumption of keys being driven tightly when

looseness existed

12

Page 13: Generator Stator Rewinds: A Review of the Stator Rewind Process

Case Study #1

• Solutions – Machining of pole

surface to eliminate rocking

– Three piece key design – smooth driving of wedges – better seating

– Flexible, laminated copper leads

• Accommodates rotor and pole movement

• Less stress

13

Page 14: Generator Stator Rewinds: A Review of the Stator Rewind Process

Rotor Coil Turn and Ground

Insulation • Depending upon the vintage, Asbestos

containing materials may be present and need properly removed and abated

• New materials have upgraded thermal properties upgraded from Class B (130 deg. C) to Class F (155 deg. C)

• New materials also:

– upgrade mechanical properties

– upgrade dielectric properties

14

Page 15: Generator Stator Rewinds: A Review of the Stator Rewind Process

15

Page 16: Generator Stator Rewinds: A Review of the Stator Rewind Process

Field Coil Reinsulation • Copper conductor is

reused

• Field pole is reused

• Older asbestos containing class B insulation is replaced

• New class F insulation: – Turn to turn insulation

– Coil to pole ground wall insulation

– Coil collars

• New leads and possible design upgrade of the coil to coil connector may also be considered

16

Page 17: Generator Stator Rewinds: A Review of the Stator Rewind Process

Hydro Pole Up Grade

Case Study #2

17

Page 18: Generator Stator Rewinds: A Review of the Stator Rewind Process

Case Study #2

Hydro Pole Up Grade

• Scope – Complete field pole

refurbishment

• 60 Poles; 30 Turns per pole

• 995 lbs. per pole

18

Page 19: Generator Stator Rewinds: A Review of the Stator Rewind Process

Poles – As Received

• Numerous Issues:

– Bent and distorted components • Bowed Poles

• Distorted end laminations

– Broken Components • Immortisuer components

• Cracked bars

• Shorting rings

19

Page 20: Generator Stator Rewinds: A Review of the Stator Rewind Process

Bent Components

20

Page 21: Generator Stator Rewinds: A Review of the Stator Rewind Process

Bent Components cont.

21

Page 22: Generator Stator Rewinds: A Review of the Stator Rewind Process

Bent Components cont.

Bowed Pole Core

22

Page 23: Generator Stator Rewinds: A Review of the Stator Rewind Process

Bent Components cont.

Distorted Pole End Laminations

23

Page 24: Generator Stator Rewinds: A Review of the Stator Rewind Process

Broken Components

24

Page 25: Generator Stator Rewinds: A Review of the Stator Rewind Process

Broken Components cont.

Immourisuer Repair

25

Page 26: Generator Stator Rewinds: A Review of the Stator Rewind Process

Completed Pole Assembly

26

Page 27: Generator Stator Rewinds: A Review of the Stator Rewind Process

Final Mechanical Check

27

Page 28: Generator Stator Rewinds: A Review of the Stator Rewind Process

Final Mechanical Check cont.

28

Page 29: Generator Stator Rewinds: A Review of the Stator Rewind Process

Stator Trends

UP Grade – Up Rate

• Older windings at or nearing

end of life

• Newer and older vintage units

being considered for uprate

• Reliability enhancements

29

Page 30: Generator Stator Rewinds: A Review of the Stator Rewind Process

Up Grade / Up Rate

Stator Rewind Considerations • Up Grade -VS.- Up Rate?

• Stator Core

– Existing Core Condition

– Relation to Coil Options

– Options and advantages or redesign (# of slots and steel type)

• Stator Coil

– Improved materials and processes

– Design that minimizes losses

– Multi Turn –VS.- Roebel Bar?

30

Page 31: Generator Stator Rewinds: A Review of the Stator Rewind Process

Hydro Stator Coil Options

Roebel Bars Multi-Turn Coil

31

Page 32: Generator Stator Rewinds: A Review of the Stator Rewind Process

Option Comparison

Multi Turn Coil

• Less expensive to manufacture

• Usually faster to manufacture

• Turn insulation is a common failure mode

• Less ability for uprate and loss reduction

Roebel Bar

• Eliminates the turn insulation failure mode possibility

• Improved technical ability to uprate and reduce losses

• Improved ability to maintain / repair

• More expensive to manufacture

• Usually longer delivery time

32

Page 33: Generator Stator Rewinds: A Review of the Stator Rewind Process

Copper Volume, Strand Size, &

Arrangement Affect Losses

• I2R Losses

– inversely proportional to

copper area

• Strand/Eddy Current Losses

– proportional to strand

thickness

• Circulating Current Losses

– voltage potential

differences between

strands

33

Page 34: Generator Stator Rewinds: A Review of the Stator Rewind Process

Leakage Flux

• Main Flux Produces E.M.F.

– Causes current to flow through conductors

– Bottom portion of conductor linked with

maximum paths; top portion with fewer

– Top portion of conductor has lowest A.C.

impedance; bottom portion, highest

– Inequity between the two causes “skin effect”

and extra losses known as strand losses

34

Page 35: Generator Stator Rewinds: A Review of the Stator Rewind Process

Leakage Flux

35

Page 36: Generator Stator Rewinds: A Review of the Stator Rewind Process

Transpositions in A.C. Windings

• Generally used on large high voltage generator windings.

• Number of turns is seldom more than 6 turns per coil.

• Turns consist of numerous strands

The purpose of transpositions is to reduce the A.C. circulating losses of the

windings.

36

Page 37: Generator Stator Rewinds: A Review of the Stator Rewind Process

Losses

• D.C. I2R Losses

– RMS ampere of A.C. has same heating effect

as one ampere of D.C.

• Eddy Current Losses

– Reduced by making strands thinner, but each

strand must be insulated

• Circulating Current Losses

– Results from potential difference between

strands

37

Page 38: Generator Stator Rewinds: A Review of the Stator Rewind Process

Types of Transpositions

38

Page 39: Generator Stator Rewinds: A Review of the Stator Rewind Process

Multi Turn Coil

Twist Transposition

39

Page 40: Generator Stator Rewinds: A Review of the Stator Rewind Process

Roebel Transposition • Transposition Changes Position of Conductors in

Strand Bundle

– 360º - each strand crosses over to occupy each radial

position in slot once, along length of core (finishing at

same position it started)

– Change in position minimizes potential differences

between strands

40

Page 41: Generator Stator Rewinds: A Review of the Stator Rewind Process

Roebel Bar

41

Page 42: Generator Stator Rewinds: A Review of the Stator Rewind Process

Roebel, Weave & Conductor Stack

42

Page 43: Generator Stator Rewinds: A Review of the Stator Rewind Process

Summary

• Upgrades, if properly planned and executed can enhance machine operation and long term reliable operation

• Up Grades and Up Rates are different in their purpose and intent

• As major maintenance, life extensions, and output increases are planned, both up grades and up rates should be carefully consider and incorporated into planning to achieve the greatest value

43

Page 44: Generator Stator Rewinds: A Review of the Stator Rewind Process

Questions