9 6" 6" 2" MAIN DRAIN ALARM TEST VALVE 6" O.S.&Y. VALVE WITH TAMPER SWITCH 1 15 16 14 2 3 4 1 5 6 7 8 9 10 11 13 12 VIKING WATER MOTOR ALARM #F-1 WITH POTTER ROEMER NEW 6"FP MAIN SIGN # 6340, "WHEN BELL RINGS CALL FIRE DEPARTMENT" 2" DRAIN PIPED 6" ABOVE FINISHED GRADE 6" VIKING ALARM CHECK VALVE 2" MAIN DRAIN VALVE PIPE SUPPORT TEE PRESSURE SWITCH MODEL A-1 VIKING RETARDING CHAMBER #B-3 WATER GUAGE FLOW SWITCH BALL DRIP CHECK VALVE 4 2 1 5 11 8 16 12 13 14 15 FLOOR NO SCALE WET SPRINKLER RISER DIAGRAM 7 10 THIS RISER DIAGRAM IS FOR GENERAL INFORMATION ONLY. THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE IN COMPLIANCE WITH NFPA 13 AND LOCAL AUTHORITY HAVING JURISDICTION. 17 CHROME FIRE DERAPTMENT CONNECTION WITH "AUTO SPRINKLER' LETTERING. VERIFY TYPE AND LOCATION WITH LOCAL FIRE DEPT. 6" 17 WATTS DOUBLE DETECTOR CHECK ASSEMBLY, MODEL NO. 709DCDA-OSY-GPM 6 RISER DIAGRAM NOTES GENERAL SPRINKLER NOTES: 1. PROVIDE A WET PIPE SYSTEM. THE WET SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED TO PROVIDE THE PRESCRIBED DENSITY UNIFORMLY OVER THE MOST REMOTE AREA. COPIES OF THE CALCULATIONS SHALL BE SUBMITTED WITH THE SHOP DRAWINGS. THE BUILDING IS LIGHT HAZARD OCCUPANCY. THE WET DENSITY SHALL BE 0.10 GPM/SQ. FT. OVER THE MOST REMOTE 1500 SQ. FT. FOR LIGHT HAZARD AND .15 OVER 1500 SQ. FT. FOR ORDINARY HAZARD WITH 250 GPM ALLOWANCE FOR HOSE STREAMS. 2. SPRINKLER HEAD LOCATIONS SHALL BE AS SHOWN ON THE REFLECTED CEILING PLAN DRAWINGS. SPRINKLER HEADS SHALL BE CENTERED IN CEILING TILES AND LOCATED SYMMETRICALLY WITH LIGHTING FIXTURES AND DIFFUSERS AS REQUIRED, UNLESS NOTED OTHERWISE. 3. THE SPRINKLER HEAD SPACING AND LOCATIONS IN THE ENTIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA-13. 4. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING SHOP DRAWINGS AND HYDRAULIC CALCULATIONS TO ALL AGENCIES HAVING JURISDICTION FOR REVIEW AND APPROVAL, INCLUDING THE LOCAL BUILDING INSPECTOR. DRAWINGS AND CALCULATIONS SHALL BEAR THE SEAL OF A LICENSED FIRE PROTECTION ENGINEER. 5. THE ENTIRE BUILDING SHALL BE SPRINKLERED. THIS SHALL INCLUDE THE CONCEALED COMBUSTIBLE SPACES. AREAS SUBJECT TO FREEZING SHALL HAVE DRY PENDENT TYPE HEADS. CONCEALED COMBUSTIBLE SPACES WILL INCLUDE BUT NOT LIMITED TO: ATTIC SPACE, AND OVERHANGING ROOF SPACES. 6. SPRINKLER HEADS IN FINISHED SPACES SHALL BE CONCEALED TYPE 1/2" ORIFICE WITH WHITE COVER PLATE. THE TWO PIECE DESIGN SHALL ALLOW FOR REMOVAL OF THE CEILING TILES WITHOUT DISTURBING THE SPRINKLER SYSTEM. 7. SPRINKLER HEADS IN CONCEALED SPACES AND MECHANICAL ROOMS SHALL BE BRASS PENDENT TYPE WITH SPRINKLER GUARDS. 8. THE SPRINKLER DISTRIBUTION SYSTEM SHALL BE SCHEDULE 10 PIPE WITH ROLL GROOVED FITTINGS FOR 2 1/2" AND LARGER, AND SCHEDULE 40 THREADED PIPE FOR 2" AND SMALLER. 9. PROVIDE INSPECTOR TEST STATIONS AT THE MOST REMOTE POINT OF THE SPRINKLER RISER. 10. THE WATER SOURCE FOR THE SPRINKLER SYSTEM IS CITY WATER. PROVIDE UP-TO-DATE FLOW TEST. 11. THE SPRINKLER CONTRACTOR SHALL REVIEW ALL PROJECT DRAWINGS AND COORDINATE THE INSTALLATION OF THE PIPING WITH ALL OTHER TRADES FOR THE PROJECT. 12. ALL OS&Y VALVES TO HAVE TAMPER SWITCHES. 13. THE WET PIPE RISER SHALL BE COMPLETE WITH ALL ACCESSORIES AS REQUIRED BY NFPA 13 INCLUDING THE FOLLOWING: WET PIPE ALARM VALVE, 2" MAIN DRAIN, WATER MOTOR GONG, (2) GAGES, RETARDING CHAMBER, PRESSURE SWITCH, WATER FLOW SWITCH, ALARM TEST VALVE. 14. DO NOT INSTALL SPRINKLER PIPING OR ANY OTHER EQUIPMENT OVER ELECTRICAL PANELS AND EQUIPMENT. MAINTAIN A MINIMUM OF 36" CLEAR IN FRONT OF ELECTRICAL PANELS AND EQUIPMENT. 15. PROVIDE A FIRE DEPARTMENT CONNECTION AS SHOWN ON THE RISER DIAGRAM. COORDINATE TYPE, SIZE, AND LOCATION WITH FIRE MARSHAL. 16. PROVIDE A WATTS DETECTOR CHECK MODEL 07F WITH BY-PASS KIT AND GPM METER AT SERVICE ENTRANCE. 17. F.P.C. SHALL CUT AND PATCH EXISTING PLASTER OR DRYWALL CEILING AS REQUIRED FOR THE INSTALLATION OF HANGERS TO SUPPORT THE NEW PIPING ABOVE NEW SUSPENDED CEILING. THIS SHALL INCLUDE ALL NECESSARY STRUCTURAL MEMBERS AS REQUIRED FOR ADEQUATE SUPPORT. 18. PROVIDE 20 ADDITIONAL SPRINKLER HEADS WITH 10'-0" OF BRANCH PIPING INSTALL ABOVE CEILING PER SPRINKLER. FIRE PROTECTION SCOPE OF WORK 1. RUN UP-TO-DATE FLOW TEST. PROVIDE NEW 6" FIRE PROTECTION SERVICE TO BUILDING. 2. PROVIDE NEW 6" BACKFLOW PREVENTER FOR NEW FIRE SERVICE. 3. PROVIDE NEW FIRE PROTECTION SERVICE ENTRANCE. 4. PROVIDE SPRINKLER COVERAGE FOR ENTIRE FACILITY. 5. PROVIDE NEW RISER WITH FLOOR CONTROL ASSEMBLY ON EACH FLOOR. 6. PROVIDE NEW FIRE DEPARTMENT CONNECTION PER THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. 7. PROVIDE POST INDICATOR VALVE. FIRE PROTECTION SCOPE OF WORK INCLUDES, BUT IS NOT LIMITED TO, THE FOLLOWING: INDICATOR POST DETAIL FIRE PROTECTION ABBREVIATIONS FIRE PROTECTION SYMBOLS EFP FP BACKFLOW PREVENTER PIPE CAP PIPE RISE PIPE DROP FIRE PROTECTION EXIST FIRE PROTECTION CHECK VALVE UNION PRESSURE GAUGE DIRECTION OF FLOW OS&Y VALVE FLOW ALARM SWITCH CONCEALED PENDENT SPRINKLER HEAD RECESSED PENDENT SPRINKLER HEAD SIDEWALL SPRINKLER HEAD UPRIGHT SPRINKLER HEAD EXIST SPRINKLER HEAD TO BE REMOVED E EXTENDED COVERAGE CONCEALED SPRINKLER HEAD HOR HORIZONTAL ID INSIDE DIAMETER INT INTERIOR INV INVERT MB MOP BASIN OD OUTSIDE DIAMETER P PRESSURE GAUGE PD PRESSURE DROP PIV POST INDICATOR VALVE PRV PRESSURE REDUCING VALVE RCP REINFORCED CONCRETE PIPE SS SERVICE SINK TS TAMPER SWITCH VER VERTICAL WIV WALL INDICATOR VALVE AFG ABOVE FINISHED GRADE AFR ABOVE FINISHED ROOF BFG BELOW FINISHED GRADE BFP BACKFLOW PREVENTER BLW BELOW BOTT BOTTOM BV BUTTERFLY VALVE CA COMPRESSED AIR CIP CAST IRON PIPE DIP DUCTILE IRON PIPE EXT EXTERIOR FA FIRE ALARM FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FDV FIRE DEPARTMENT VALVE FH FIRE HYDRANT FHC FIRE HOSE CABINET FD FLOOR DRAIN FS FLOW SWITCH FTG FOOTING NO SCALE MIN. 48" GATE VALVE FIRE PROTECTION MAIN OPERATING WRENCH LOCKING STAPLE 40" 30" GRADE BODY SHUT T TAMPER SWITCH PROVIDED BY FPC, WIRED BY EC (TYPICAL) (VERIFY EXACT LOCATION WITH FIRE MARSHAL AND ARCHITECT) COMMON ABBREVIATIONS COMMON SYMBOLS CONNECT TO EXISTING EXISTING TO BE REMOVED PLAN NORTH SECTION ID A H1.1 SHEET NO. WHERE SECTION IS DIRECTIONAL VIEW OF SECTION 1 REVISION NUMBER ELEVATION 100.00' 1 KEYNOTE EQUIPMENT TAG SHOWING TYPE AND ID. SEE EQUIPMENT SCHEDULES FOR DETAILS EXISTING TO REMAIN REMOVE EXISTING PROVIDE NEW N TYPE ID REVISION CLOUD DETAIL ID 1 H1.1 SHEET NO. WHERE DETAIL IS 101 ROOM/SPACE NO. 11 H1.1 DIRECTION OF VIEW SHEET NO. WHERE EL. IS DRAWN ELEVATION ID A/E ARCHITECT/ENGINEER AC ABOVE CEILING ABV ABOVE AFF ABOVE FINISHED FLOOR AFI ARC-FAULT INTERRUPTER AFR ABOVE FINISHED ROOF ALT ALTERNATE ATS AUTOMATIC TRANSFER SWITCH ATC AUTOMATIC TEMPERATURE CONTROL - COORDINATE LOCATION C/G COUNTERTOP GFI CD CORD DROP CL CENTERLINE CLG CEILING CM CEILING MOUNT COL COLUMN CT COUNTERTOP HEIGHT-44" AFF UNO OR CURRENT TRANSFORMER CR CORD REEL DBF DOWN BELOW FLOOR DET DETAIL DIA DIAMETER DIM DIMENSION DN DOWN DW DISHWASHER DWG DRAWING EC ELECTRICAL CONTRACTOR EL ELEVATION ELEV ELEVATOR EMER EMERGENCY EO EMERGENCY ONLY (NORMALLY OFF) EWC ELECTRIC WATER COOLER (PROVIDE GFI RECEPTACLE) EQ EQUIPMENT, COORDINATE LOCATION EX EXISTING FA FIRE ALARM FBO FURNISHED BY OWNER FLR FLOOR FPC FIRE PROTECTION CONTRACTOR FSC FOOD SERVICE CONTRACTOR GC GENERAL CONTRACTOR GFI GROUND-FAULT INTERRUPTER GND GROUND HC HVAC CONTRACTOR HCP HANDICAPPED HGT HEIGHT HR HOUR IR INFRARED JB JUNCTION BOX KES KITCHEN EQUIPMENT SUPPLIER LV LOW-VOLTAGE MC MECHANICAL CONTRACTOR MCA MINIMUM CIRCUIT AMPACITY MOCP MAXIMUM OVERCURRENT PROTECTION MT MULTITECHNOLOGY MO MICROWAVE OVEN NA NOT APPLICABLE NE NORMAL/EMERGENCY (NORMALLY ON) NIC NOT IN CONTRACT NTS NOT TO SCALE OFCI OWNER FURNISHED- CONTRACTOR INSTALLED EQ FOR EQUIPMENT, COORDINATE LOCATION P PEDESTAL PC PLUMBING CONTRACTOR PIR PASSIVE INFRARED SE SERVICE ENTRANCE SECT SECTION SHT SHEET SIM SIMILAR SPD SURGE PROTECTION DEVICE SPEC SPECIFICATION SS SERVICE SINK STD STANDARD SUSP SUSPENDED SB SMARTBOARD COORDINATE LOCATION TL TASK LIGHT TR TAMPER RESISTANT TSTAT THERMOSTAT TV FOR TV, COORDINATE LOCATION TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER UNO UNLESS NOTED OTHERWISE US ULTRASONIC USB 2 USB PORTS IN ADDITION TO RECEPTACLES W/ WITH W/O WITHOUT W WALL-MOUNTED WP WEATHERPROOF FULL SHEET SIZE: 30" x 42" SHEET NUMBER PROJECT NUMBER REGISTRATION CURRENT ISSUE COPYRIGHT 2016 SFA DRAWING HISTORY SITE / CIVIL ENGINEER LANDSCAPE ARCHITECT STRUCTURAL ENGINEER MECHANICAL / ELECTRICAL / PLUMBING FIRE PROTECTION ENGINEER TELECOM ENGINEER AUDIO VISUAL ENGINEER SECURITY ENGINEER ACOUSTICAL ENGINEER F0.1 LVE-14179 Cover Sheet BUCKS COUNTY COMMUNITY COLLEGE FOUNDERS HALL RENOVATIONS 275 Swamp Rd, Newtown, PA 18940 275 Swamp Rd, Newtown, PA 18940 CONFORMED CONSTRUCTION SET 12/07/2016 N/A N/A BARRY ISETT ASSOCIATES 85 PA-100, Allentown, PA 18106 LEHIGH VALLEY ENGINEERING 1 W Broad St #500, Bethlehem, PA 18018 LEHIGH VALLEY ENGINEERING N/A N/A N/A N/A DRAWING LIST F0.1 Cover Sheet F2.0 Ground Floor Plan F2.1 First Floor Plan F2.2 Second Floor Plan F2.3 Third Floor Plan P0.1 Cover Sheet P1.0 Foundation Plan - Demolition P1.0A Ground Floor Plan - Demolition P1.1 First Floor Plan - Demolition P1.2 Second Floor Plan - Demolition P1.3 Roof Plan - Demolition P2.0 Foundation Plan - Labs - Drainage P2.0A Ground Floor Plan - Labs - Drainage P2.1 First Floor Plan - Labs - Drainage P2.2 Second Floor Plan - Labs - Drainage P2.3 Roof Plan - Drainage P3.0 Foundation Plan - Labs - Supply P3.0A Ground Floor Plan - Labs - Supply P3.1 First Floor Plan - Labs - Supply P3.2 Second Floor Plan - Labs - Supply P7.1 Riser Diagrams P8.1 Details and Schedules H0.1 Cover Sheet H1.0 Ground Floor Plan - Demolition H1.1 First Floor Plan - Demolition H1.2 Second Floor Plan - Demolition H1.3 Third Floor Plan - Demolition H2.0 Ground Floor Plan - HVAC H2.1 First Floor Plan - HVAC H2.2 Second Floor Plan - HVAC H2.3 Third Floor Plan - HVAC H3.0 Ground Floor - HVAC - Piping H3.1 First Floor - HVAC - Piping H3.2 Second Floor - HVAC - Piping H3.3 Third Floor - HVAC - Piping H5.1 Enlarged Plans & Sections-HVAC H5.2 Sections H5.3 Sections H7.0 Details H7.1 Details H7.2 Details H7.3 Details H7.4 Details H7.5 Details H8.0 Schedules H8.1 Schedules H8.2 Schedules H8.3 Schedules E1.0 Ground Floor Plan - Demolition E1.1 First Floor Plan - Demolition E1.2 Second Floor Plan - Demolition E1.3 Third Floor Plan - Demolition E2.0 Ground Floor Plan - Lighting E2.1 First Floor Plan - Lighting E2.2 Second Floor Plan - Lighting E2.3 Third Floor Plan - Lighting E3.0 Ground Floor Plan - Power E3.1 First Floor Plan - Power E3.2 Second Floor Plan - Power E3.3 Third Floor Plan - Power E4.0 Ground Floor Plan - Low-Voltage E4.1 First Floor Plan - Low-Voltage E4.2 Second Floor Plan - Low-Voltage E4.3 Third Floor Plan - Low-Voltage E5.1 Enlarged Kitchen Plan E7.1 Single Line Diagrams E7.2 Details E7.3 Teledata Details E8.1 Schedules E8.2 Schedules E8.3 Schedules E8.4 Schedules E8.5 Schedules NO. ISSUE DATE: DESCRIPTION