Unit Substation - Specifications Unit Suon Dimensions Height: 62.80" -6 8 . 80" (1,595.12mm -1,747.52mm) Width: 50.76" -71.50" (1,289. 30 mm -1,816.10 mm) Dep: 36.00" (914.40 mm) Appximate Weight: 775 lbs.-2,800 lbs. ( 354.3 kg -1,280.0 kg) General Specifications for Unit Substions All Substations Must Meet the Followlng: Pa I. Genel: 1.1 General Requi remenʦ: A. Shall be tested and ceified to be in complian with UL 1&2entitled "Unit Substions· B. Shall be ifi to be in mpliance with UL 1561 entitled "D Type Genel Puse and Power Transe" C. Shall be ifi to be in mpliance wi UL 67 entied "Panelboas• D. Shall be rtifi to be in mpliance with UL 4 89 entitled "Molded Case Cirit Breake" E Shall be ifi to be in mpliance with UL 50 entl "Cabineʦ and Boxes" F. Shall be rtifi to meet all sections NFPA 303 DTD "20& Manas and Boaas• G. Oveoad paci shall meet ANSI L57.91.250. Pa II. Pu: 2.1 Distribution Equipment: A. Dock Boxes Unlimited, Inc. 1-800-559-4269 www.dockboxes.com 2.2 Unit Substions - Genel Speccation A. Main Housing: a. The housing shall conscd of 14 or 16 gauge, 316L low n stainless steel and shall be ad withUV-sistant lyurethane sin over a der ng. It shall UL listed as a 3R weatherpf enclosu. .dockboxes.m b. The housing shall have a solar shield top to reduce heat tnsr from the sun and to ru the heat transfer from e tnser. c. Long-life thermostatilly controlled fans shall be lated such at the ns move air fm the nsrmer mpament . 10559-4269 Unn Suon - Puct Sפcltlons
9

General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Sep 28, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Unit Substation

Dimensions Height: 62.80" -6 8. 80" (1,595.12 mm -1,747.52 mm) Width: 50.76" -71.50" (1,289. 30 mm -1,816.10 mm) Depth: 36.00" (914.40 mm)

Approximate Weight: 775 lbs. -2,800 lbs. ( 354.3 kg -1,280.0 kg)

General Specifications for Unit Substations

All Substations Must Meet the Followlng: Part I. General: 1.1 General Requi rements:

A. Shall be tested and certified to be in compliance with UL 1062 entitled "Unit Substations·B. Shall be certified to be in compliance with UL 1561 entitled "Dry Type General Purpose

and Power Transformers"C. Shall be certified to be in compliance with UL 67 entitled "Panel boards•D. Shall be certified to be in compliance with UL 4 89 entitled "Molded Case Circuit Breakers"E. Shall be certified to be in compliance with UL 50 entitled "Cabinets and Boxes"F. Shall be certified to meet all sections NFPA 303 DTD "2006 Marinas and Boatyards•G. Over1oad capacity shall meet ANSI L57.9&-01.250.

Part II. Products:

2.1 Distribution Equipment: A. Dock Boxes Unlimited, Inc.

1-800-559-4269www.dockboxes.com

2.2 Unit Substations - General Specification A. Main Housing:

a. The housing shall be constructed of 14 or 16 gauge, 316L low carbonstainless steel and shall be coated withUV-resistant polyurethane resin over apowder coating. It shall be UL listed as a type 3R weatherproof enclosure.

www.dockboxes.com

b. The housing shall have a solar shield top to reduce heat transfer from the sunand to reduce the heat transfer from the transformer.

c. Long-life thermostatically controlled fans shall be located such that the fansmove air from the transformer compartment .

1-800-559-4269 Unn Substation - Product Speclllcatlons

E0076490
Text Box
UL File No. E229729-1-1
Page 2: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

B. Doors:a. Stainless steel access doors to the transformer and panelboard

compartments shall use key-entry, quarter turn, wing-nut handles.b. The doors shall be sealed by 360° neoprene gaskets and be watertight.

C. Transformer:a. Transformers shall be wound with class H heavily insulated copper bar and

double dipped in tough insulating varnish that protects the copper.b. The temperature rise of the transformer shall not exceed 150° C.c. The insulation class for the transformer shall not exceed 220° C per UL

standards.d. Standard frequency shall be designed for 60-Hertz operation. 50-Hertz

operation is available upon request.e. Standard taps shall be FCAN (+2) and FCBN (-2) at 2.5% each. Custom taps

are available upon request.f. Standard primary voltages shall be:

1. 480V, 3-phase, Delta2. 480V, 1-phase3. 600V, 3-phase, Delta4. 600V, 1-phase5. Other voltages available upon request

g. Standard secondary voltages shall be:1. 120/208V, 3-phase, Wye2. 127/220V, 3-phase, Wye3. 277/480V, 3-phase, Wye4. 120/240V, 1-phase5. Other voltages available upon request

h. Standard primary circuit breaker protection shall be provided for incomingelectrical feeds. Primary circuit protection may be removed where acceptableper the NEC upon request.

D. Panelboard:a. Panelboard shall be Cutler-Hammer Pow-R-Line.b. All bus work shall be density rated copper.c. All circuit breakers shall be bolt-on type.d. Panel board shall be provided with a main circuit breaker or main lug only.e. Branch circuit breakers shall be provided per the customer's specifications.

E. Internal Wiring:

www.dockboxes.com

a. All secondary wire shall be completed with 600 V insulated copper wire.b. This wire shall pass through a special molded grommet assembly between

the transformer and the distribution panel chambers.

1-800-559-4269 Unit Substation - Product Specifications

Page 3: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

F. Grounding:a. All exposed metallic parts must have an integral ground that is a part of the

equipment grounding system.

G. Electrical Components:a. All electrical components shall be located at least 12" above the mounting

surface.

H. Installation Equipment:a. Two heavy-duty stainless steel "C" channels shall be provided for easy

mounting of the unit to the dock.b. Removable louvered skirting shall be provided to cover the mounting area.c. Cable gland plates shall be provided on both the primary and secondary side

of the unit base.d. Four Lifting eyes shall be provided with each unit, located on the top of the

unit. These eye-bolts shall be stainless steel and can be found under thesolar shield.

I. Optional Ground Fault Monitoring:a. Monitoring can be single-level (monitoring for a single main circuit breaker) or

multi-level (monitoring for multiple branch circuits).b. Indicator lights shall be visible on the outside of the substation enclosure

when ground fault monitors are included.

J. Optional Lighting Equipment:

www.dockboxes.com

a. Photocell for external lighting equipmentb. Lighting contactorsc. Three Position Hand-Off-Auto Control

(END OF SECTION)

1-800-559-4269 Unit Substation - Product Specifications

Page 4: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Product Features

HANDLE MECHANISM

FOR PRIMARY

CIRCUIT BREAKER

LOCKABLE

TRANSFORMER

ACCESS DOOR

E LOCKABL

PANELACCES

000

......

R

www.dockboxes.com

I

i,z. •

80

-

0

FRONT-TRANSFORMER

DOOR CLOSED

..

I

0

0

8

SIDE-PANEL

DOOR CLOSED

1-800-559-4269

I

D

REMOVABLE

SOLAR SHIELD

GROUND FAULT

MONITOR

8" C-CHANNEL

BEHIND REMOVABLE

LOUVERED ACCESS

PLATES

31 6STAINLESS

TEEL HOUSING

ITH POL VESTER

OWDER-COATED

NISH

s .. ••

p

Fl

R EMOVABLE LOUVERED

CCESS PANEL A

Unit Substation - Product Specifications

Page 5: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Product Features (cont.)

I

• COPPER WOUND, i----t-t-----t-----t-tlGH EFFICIENCY

TRANSFORMER

TEMPERATURE l_������_J�:!::::=:::::::=::!:�±f-��-B-��--coNTROLLED

COOLING FANS

www.dockboxes.com

FRONT-TRANSFORMER DOOR OPEN

SIDE- PANEL DOOR OPEN

1-800-559-4269

I

I

MAIN CIRCUIT BREAKER

GASKETED ACCESS DOORS

BRANCH CIRCUIT BREAKERS

OPTIONAL SURGE PROTECTION DEVICE

Unit Substation - Product Specifications

Page 6: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Product Dimensions -Standard Single Panel Substation -250KVA Transformer or Below

I I

80 •

62. O"

0 D

i-l ·-----..... 50.76"'--------

FRONT

I

I

I

0

8

0

-I· -----:3s.oo"�-· I

SIDE

I

Base Dimensions -Standard Single Panel Substation -250KVA Transformer or Below

8" C-CHANNE L

R ACCESS OPENING FO SECONDARY CABLE

(29.00R X 4.00 ")

R ISOLATION WALL FO TRANSFORMER AND PANE L

R ACCESS OPENING FO PRIMARY CABLE

(18.00R X 4.00

�-")

www.dockboxes.com

I

I

E:::,

,----

�•

• rol-w

.

1-800-559-4269

�8.85" 0.38"

33 . 70"

. . . I I �I. . .

..

Unit Substation - Product Specifications

Page 7: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Product Dimensions -Standard Single Panel Substation -Above 250KVA Transformer

I I

80 D

0 D

-------5!"10.76"--------�

FRONT

I

I

68. O"

I

0

8

0

-I • ------'36.oo"'-----· I

SIDE

I

Base Dimensions -Standard Single Panel Substation -Above 250KVA Transforme

8" C-CHANNE L

R ACCESS OPENING FO SECONDARY CABLE

(29.00R X 4.00 ")

R ISOLATION WALL FO TRANSFORMER AND PANE L

R ACCESS OPENING FO PRIMARY CABLE

(18.00R X 4.00

�-")

www.dockboxes.com

I

I

E:::,

,---

�•

• rol-

w

.

1-800-559-4269

�8.85" 0.38"

33 . 70"

. . .

I I �I . . .

..

Unit Substation - Product Specifications

Page 8: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Product Dimensions - Side-By-Side Single Panel Substation -250KVA Transformer or Below

I

80 0

8

0 0

i----------71.50R'---------Pi

FRONT

I

62. O"

i-l • ------:36.oo"�--i· I

SIDE

I

Base Dimensions - Side-By-Side Single Panel Substation -250KVA Transformer or Below

a• C-CHANNE

RISOLATION WALL FO TRANSFORMER AND PANE L

R ACCESS OPENING FO SECONDARY CABLE

(29.00" x 4.00

... -

")

R ACCESS OPENING FO PRIMARY CABLE

(18.00" x4.00")

www.dockboxes.com

I

::, ..

. . .

r l

.,

1-800-559-4269

:9.60"

� �

33 70"

. . .

� I I � l . . .

c--

� -

Unit Substation - Product Specifications

Page 9: General Specifications r Unit fo Substations · Unit Substation -Specifications . F. Grounding: a. All exposed metallic parts must have an integral ground that is a part of the equipment

Unit Substation - Specifications

Product Dimensions - Side-By-Side Single Panel Substation -Above 250KVA Transformer

I

80 0

8

0 0

i-----------71.50"·----------i

FRONT

I

I

68. O"

I

-I ·--3s.oo"....__ __, I

SIDE

I

Base Dimensions - Side-By-Side Single Panel Substation -Above 250KVA Transforme

a• C-CHANNE

RISOLATION WALL FO TRANSFORMER AND PANE L

R ACCESS OPENING FO SECONDARY CABLE

(29.00" x 4.00

... -

")

R ACCESS OPENING FO PRIMARY CABLE

(18.00" x4.00")

www.dockboxes.com

I

::, ..

. . .

rl

.,

1-800-559-4269

:9.60"

� �

33 70"

. . .

� I I � l . . .

c--

� -

Unit Substation - Product Specifications