OUTPUT RATING 60 Hz, 3 Phase Prime Voltages 90 kW 208/120, 220/127 112.5 kVA 440/254, 480/277 GENERAL SPECIFICATIONS Liters Gallons 29.7 7.8 26.9 7.1 20.2 5.3 14.1 3.7 200 52.8 145 38.3 Blue Power gensets are compliant with EC mark which include the following directives: * 2006/42/EC Machinery Safety. * 2006/95/EC Low Voltage. 1136 1632 1571 Width (W)mm Height (H)mm Net Weight kg Open 2210 750 1410 SX460 AVR Fuel Consumption /hr Fuel Tank Capacity, Canopy Unit Fuel Tank Capacity, Open Unit Standby Rating: According to ISO 8528-1:2005, standby power is the maximum power available during variable electrical power sequence, under the stated operational conditions for which a generating set is capable of delivering in the event of a utility power outage for up to 200 hrs. per year while meeting manufacturers recommended operation and maintenance requirements. The permissible average power output over a 24 hr. period shall not exceed 70% of this rating. Prime Rating: According to ISO 8528-1:2005, prime power is the maximum power which a generating set is capable of delivering continuously while supplying a variable electrical load when operated for an unlimited number of hours per year while meeting manufacturers recommended operation and maintenance requirements. The permissible average output (Ppp) over a 24 hr. period shall not exceed 70% of this rating. 100% Standby Power 100% Prime Power 75% Prime Power 100 kW 125 kVA Standby TAL-A44-E 3 Phase 12 Lead 4 pole, 1 Bearing Engine Alternator Control Panel 1104C-44TAG2 4 cyl in Line Turbo/Air Chrg Cool Length (L)mm Silent 2700 Mechanical 12 lead re-connectable 50% Prime Power 4.4 Ltr. InteliLite IL-9 Auto Start 7 inputs/6 outputs 1140 3 analog inputs Remote Monitor Weights & Dimensions 0.8 Pf P125 www.bluepowergenerators.com
3
Embed
GENERAL SPECIFICATIONS Engine Alternator Control Panel
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Blue Power gensets are compliant with EC mark which include the following directives:* 2006/42/EC Machinery Safety.* 2006/95/EC Low Voltage.
113616321571
Width (W)mmHeight (H)mmNet Weight kg
Open2210750
1410
SX460 AVR
Fuel Consumption /hr
Fuel Tank Capacity, Canopy UnitFuel Tank Capacity, Open Unit
Standby Rating:According to ISO 8528-1:2005, standby power is the maximum power available during variable electrical power sequence, under the stated operational conditions for which a generating set is capable of delivering in the event of a utility power outage for up to 200 hrs. per year while meeting manufacturers recommended operation and maintenance requirements. The permissible average power output over a 24 hr. period shall not exceed 70% of this rating.
Prime Rating:According to ISO 8528-1:2005, prime power is the maximum power which a generating set is capable of delivering continuously while supplying a variable electrical load when operated for an unlimited number of hours per year while meeting manufacturers recommended operation and maintenance requirements. The permissible average output (Ppp) over a 24 hr. period shall not exceed 70% of this rating.
100% Standby Power100% Prime Power75% Prime Power
100 kW125 kVA
Standby
TAL-A44-E3 Phase12 Lead
4 pole, 1 Bearing
Engine Alternator Control Panel
1104C-44TAG24 cyl in Line
Turbo/Air Chrg Cool
Length (L)mmSilent2700
Mechanical
12 lead re-connectable
50% Prime Power
4.4 Ltr.
InteliLite IL-9Auto Start
7 inputs/6 outputs
1140
3 analog inputsRemote Monitor
Weights & Dimensions
0.8 Pf
P125
w w w .b luepow er genera to rs .com
P125
Alternator Performance Data
Voltage Series Star 416/240 440/254 460/266 480/277Voltage Parallel Star 208/120 220/127 230/133 240/138Voltage Series Delta 240/120 254/127 266/133 277/138
kVA Base Rating at 0.8 Pf 116.3 125 125 133Locked Rotor Motor Starting kVA* 250 272 300 338Base Ratings are for Standby - 150/40°C*at 30% voltage dip
Mechanical12.6 L8.0 L
Engine H.P. at 100% Standby Power 157.5
Electrical System Voltage 12vdc
Intake Air Flow, m³/min 7.8
Ingress Protection IP23 TIF <50
Voltage Regulation ±1.0%Max. Overspeed 2250 rpmTHF <2%
Insulation Class H Winding Pitch 2/3
Standard AVR Model R120Excitation Type Shunt
Leroy Somer Model TAL-A44-EWinding Type 12 Lead, 3 PhasePower Factor 0.8
Leroy Somer complies with international standards and regulations: IEC 60034 and derivitive, they are designed, manufactured and marketed in ISO 9001 & 14001 environment and can be integrated into a CE market generator set.
60 Hz
Engine Model
Exhaust Gas Flow, m³/min 20.4Exhaust Gas Temp. 574 C°
Engine TypeBore x Stroke (mm)Displacement (L)
P125
w w w .b luepow er genera to rs .com
ComAp InteliLite IL-9
Benefits
Features
ComAp InteliLite AMF 20 Control Panel meets the following certificates and standards:
• EN61000-6-2• EN61000-6-4• EN61010-1• EN61000-2-1 (-20°C/16h for std version)
� Single gen-set controller for standby and prime applications� Direct Communications with EFI engines� All-in-one intuitive & powerful PC tool for configuration/monitoring/control, locally or remotely
� Standby and Prime power application in one unit� 5 languages in the controller and translator functionality� 3 levels of password security� 3 sets of alternative configurations� Magnetic pick-up input� ECU support and TIER4 Final ready� Plug-in Module concept for more capabilities (Modbus, Internet, SMS, inputs/outputs)� 1 slot for Plug-in modules� Power over USB for controller adjustments� Adjustable D+ threshold� Ventilation pulse� Flexible Choke� Fuel pump control� 3 analog inputs, 6+1 binary inputs, 6 binary outputs� 2 higher current binary outputs� Adjustable delay for binary inputs
� Alarms and gen-set status asignable to binary outputs� Run hours source ECU or internal� Real time clock� Multi purpose scheduler functionality� 3 maintenance timers� Detailed history log with up to 150 records� Zero power mode� Possibilty to disable protections� Modbus register mapping possibility� Start on Low Battery (only for native prime power configuration)� Cutout dimensions: 172mm x 112mm (same as Intellilite NT family)