Top Banner
PRESENTATION ON GENERATOR PRESENTED By: Mr. R. S. Bose; Mgr.(EE)
37

Genarator (Final)

Dec 10, 2015

Download

Documents

Kumar Saurav

ppt
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Genarator (Final)

PRESENTATION ON GENERATOR

PRESENTED By:

Mr. R. S. Bose; Mgr.(EE)

Page 2: Genarator (Final)

. Working PrincipleThe A.C Generator or alternator is based upon the principle of electromagnetic induction & consists a stationary part called Stator & a rotating part called Rotor. The armature windings are placed in the stator. Field winding is placed in the Rotor & DC supply is given to the field winding. When rotor is rotated, the lines of magnetic flux (viz magnetic field) cut through the stator windings. This induces an electromagnetic force (e.m.f) in the stator windings.

The magnitude of e.m.f (E) = 4.44 f N volts

= Strength of magnetic field in webers

N = Number of turns in a coil of stator winding

f = Frequency in Hz = P n/120

where n = revolutions of rotor

P = Number of poles. For same frequency increase in number of poles decrease the machine speed & vice versa. Hence low speed hydro turbines have 14 to 20 poles & high speed steam turbines have generally 2 poles.

Page 3: Genarator (Final)

VIEW OF GENERATOR TURBINE ASSEMBLY OF STAGE-I

Page 4: Genarator (Final)

GENERATOR OF STAGE-I

Page 5: Genarator (Final)
Page 6: Genarator (Final)

. Generator Components

1. Stator

2. Stator Windings

3. Rotor

4. Rotor Windings

Page 7: Genarator (Final)

. Stator Core

The Stator core is built up from a large number of “punchings” or sections of thin steel plates. The Stator core comprises of an inner frame & outer frame. The outer frame is a rigid fabricated structure of welded steel plates, within this shell is a fixed cage of grider built circular and acial ribs. The ribs divide the yoke in the compartment through which hydrogen flows into radial ducts in the stator core & circulate through gas coolers housed in the frame. The inner cage is usually fixed in to the yoke by an arrangement of springs to dampen the double frequency vibrations inherent in 2 pole generators. RTDs are mounted at the bottom of Stator slots to measure temperature.

Page 8: Genarator (Final)

.

Stator Windings

Windings for the Stator are made up from copper strips wound with insulated tape which is impregnated with varnish, dried under vacuum & hot pressed to form an solid insulation bar. This bars are then placed in the stator slots and held in with wedges to form the complete winding which is connected together at each end of the core forming the end turns. These end turns are rigidly braced & packed with blocks of insulating material to withstand the heavy forces which might result from a short circuit or other fault conditions.

Page 9: Genarator (Final)

Details of Stator Slot

Page 10: Genarator (Final)

. Rotor

The Rotor is a cast steel ingot and it is further forged & machined. It should have sufficient dynamic strength to withstand the high speed of the generators.Very often a hole is bored through the centre of the rotor axially from one end to the other for inspection. Slots are then machined for windings & ventilation.

Rotor Windings

Silver bearing copper is used for the winding & mica is used as the insulation between conductors. A mechanically strong insulator like micanite is used for lining the slots.While rotating at high speed centrifugal force tries to lift the windings out of the slots & hence they are contained by wedges.

Page 11: Genarator (Final)

. Retaining Ring

The centrifugal forces of the rotor end windings are contained by single-piece rotor retaining rings. The retaining rings are made of non-magnetic high-strength steel in order to reduce stray losses.

Page 12: Genarator (Final)

Rotor Slot Details

1

2

3

4

5

6

8 97

Page 13: Genarator (Final)

Rotor End Winding

2

5

6

78

1

3

4

Page 14: Genarator (Final)

Technical Data Sheet of 500 MW Generator

Page 15: Genarator (Final)

. Comparison of 200MW & 500MW Generator

Page 16: Genarator (Final)

.

Generator Cooling System

1. Rotor Cooling System

2. Stator Cooling System

Page 17: Genarator (Final)

. Rotor Cooling System

Page 18: Genarator (Final)

. Hydrogen Cooling System

Page 19: Genarator (Final)

Merits & Demerits of H2 CoolingMerits

1. Excellent thermal properties

2. One of the lightest gasses (Low density resulting low windage losses in rotating machine)

3. .Non toxic

4. High diffusion properties giving efficient coolingDemerits1. .Flammable/ Highly explosive when mixed with air/O2

2. Highly sensitive to ignition/sparks/static charges3. Asphixiant in closed spaces4. Auto ignition properties

(Temp 500C, H2: Air / O2 4% - 74% ) under this condition H2 is explosive

Page 20: Genarator (Final)

Stator Cooling System

Page 21: Genarator (Final)

The closed loop cooling system consists of the following:-

Page 22: Genarator (Final)

GENERATOR COOLING WATER CIRCUIT

Page 23: Genarator (Final)

PRIMARY WATER SYSTEM21

3

Page 24: Genarator (Final)

. GENERATOR SEALING SYSTEM

Page 25: Genarator (Final)

.

Page 26: Genarator (Final)

Seal Oil Diagram

(Simplified)

Page 27: Genarator (Final)

EXCITATION METHODS

1. Brush type system apply the output of a separate DC generator (exciter) to the slip rings of the rotor.

Disadvantage :- Brush gives sparking & may cause fire hazards.

2. Brushless excitation systems utilize an integral exciter and rotating rectifier assembly that eliminates the need for brushes and slip rings. Here we have A.C exciter. AC is converted to D.C by power diodes which are mounted to shaft as bridge rectifier. Output of the rectifier goes to field winding without any slip.

Page 28: Genarator (Final)

Brush Type Excitation System

Page 29: Genarator (Final)

Brushless Excitation System

Page 30: Genarator (Final)

Basic Arrangement of Excitation System

1

8

5

4

3

2

7

6

9

10

Page 31: Genarator (Final)

Faults for Generator1. Internal faults

a) Stator Faults (Phase to ground, Phase to Phase & Inter turn)

b) Rotor Faults (Winding to Earth, Interturn)

2. Abnormal operating conditions

a) Loss of Excitation

b) Overload

c) Overvoltage

d) Under freq / Over freq

e) Unbalance Current

f) Motoring

g) Loss of synchronism

h) Sub synchronous oscillations

3. Mechanical Faults or Conditions

a) Over speed b) Failure of Prime Mover c) Loss of Vacuum

4. External Faults

a) Faults in Lines & busbars

Page 32: Genarator (Final)

Generator Protections1. Single Phase to earth fault protection

2. Over load protection

3. Negative Sequence Current protection

4. Earth fault protection on the HV side of transformer

5. Generator differential protection

6. Unit differential protection

7. Generator transformer differential protection

8. Gas protection (from Transformer side)

9.Protection against Inter turn faults

10. Rotor Over current protection

11. Rotor Earth fault protection

12. Pole slipping protection

13. Over Voltage & over fluxing protection

14.Backup Impedance protection

Page 33: Genarator (Final)

Generator Synchronization

Generator is synchronized with the grid when following conditions are satisfied:-

1. Voltage should be same (Changed by changing excitation)

2. Frequency should match (Changed by changing steam input)

3. Phase sequence should match

4. Phase difference should be zero

(For Synchronization there is both manual & auto mode. For Auto mode ATRS system is there. In manual mode the closing impulse to Generator breaker is given when the synchroscope pointer is between 11 to 12 Clock position).)

Page 34: Genarator (Final)
Page 35: Genarator (Final)
Page 36: Genarator (Final)
Page 37: Genarator (Final)