1 -1- IEEE/PES Substation Committee - GIS Subcommittee T&D Chicago GIS IEEE/PES Substation Committee - GIS Subcommittee Substations Committee GIS Subcommittee K2 Module Gas Insulated Substation (GIS) Basics IEEE -2- IEEE/PES Substation Committee - GIS Subcommittee T&D Chicago GIS IEEE/PES Substation Committee - GIS Subcommittee Contents GIS Basics A Introduction to GIS C Design Features of GIS
13

Gas Insulated Substation Presentation

Mar 08, 2015

Download

Documents

Vatsal Jain
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Gas Insulated Substation Presentation

1

- 1 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Substations CommitteeGIS Subcommittee K2

ModuleGas Insulated Substation (GIS)

Basics

IEEE

- 2 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

ContentsGIS Basics

A Introduction to GISC Design Features of GIS

Page 2: Gas Insulated Substation Presentation

2

- 3 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

ContentsGIS Basics

A Introduction to GIS

- 4 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISTypical Air Insulated Substation 345/230/115kV

Page 3: Gas Insulated Substation Presentation

3

- 5 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISTypical Gas Insulated Substation 345/115kV

- 6 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISCable Feeder Unit

Page 4: Gas Insulated Substation Presentation

4

- 7 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISDimension ComparisonGIS Technology

SF6 used as the insulating media

Reduced clearances- 345 kV AIS 4.6 m (15 feet)- 345 kV GIS 380 mm (15 inches)

- 8 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISView into Bus Bar: Conductor/Enclosure Dimension

Page 5: Gas Insulated Substation Presentation

5

- 9 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Busbar DisconnectorCurrent TransformerCircuit Breaker

CableConnection

DisconnectorCurrent TransformerCircuit Breaker

Introduction to GISClassic Single Phase Enclosure of GIS

- 10 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISMidway Sunset Sunoco Cogen 242 kV GIS

4

242 kV

2000 A

40 kA

No. of breakers

Rated voltage

Rated current

Rated short-circuit current

1988Supply year

Page 6: Gas Insulated Substation Presentation

6

- 11 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISClassic Three Phase Enclosure of 72.5 to 170 kV GIS

- 12 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISAdvanced Three Phase GIS 72.5 to 145 kV

Page 7: Gas Insulated Substation Presentation

7

- 13 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISAdvanced Three Phase GIS 72.5 to 145 kV

- 14 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

ContentsGIS Basics

B Design Features of GIS

Page 8: Gas Insulated Substation Presentation

8

- 15 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design Features

GIS technology: compact, low-life cycle cost andmodular for indoor and outdoor applications

Modular design, factory pre-assembled and tested units

Space requirement less than 20 % of comparable AIS

Safety (enclosed energized components)

Continous monitoring of SF6 densitity

Sealed for operating life > 50 years

Major inspection: not before 25 years 1)

1) Is influenced by the operation duties

- 16 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design Features

GIS technology: compact, low-life cycle cost andmodular for indoor and outdoor applications

Corrosion-resistant

Low fault-probability/high availability

Protected against aggressive environmental conditions

Seismic resistant

Low EMF and susceptibility to EMC

Page 9: Gas Insulated Substation Presentation

9

- 17 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesSpace Savings

Space Reductionappr. 70 %

Previous

Afterwards

Retrofit of an existing AIS Substation byCompact Substation

145 kV/31,5 kA 4000 A

- 18 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesModular Structure (schematic)

Page 10: Gas Insulated Substation Presentation

10

- 19 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesModular Structure (devices)

- 20 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesGIS Pressure Systems

Closed pressure systems:

The closed pressure system uses isolated apparatus compartments with o-ring sealed bolted flanges.

The tightness characteristic of a closed pressure system stated by the manufacturer shall be consistent with a minimum maintenance and inspection philosophy.

The leakage rate from any single compartment of GIS to atmosphere and between compartments shall not exceed 0.5 % per year for the service life of the equipment.*

Practical experiences to the today’s design of GIS show as low as 0.2 % per year.

* IEC 62271-203 Gas Insulated Switchgear for voltages above 52 kV

Page 11: Gas Insulated Substation Presentation

11

- 21 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Sealant

O-Ring

Insulating Spacer

Air Side

SF6 Gas Side

Flange

■ O-RING

■ LIQUID SILICONE SEALANT

GAS SEALING

PROTECTION AGAINSTGISEnclosure

� WATER INGRESS FROM AIR SIDE

� RUST OF FLANGE

Design FeaturesExample for Static Double Sealing System

- 22 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesExample for Corrosion Protection

– – – Tectyl 506 coating for external area A- - - - Trost Multifunction Oil coating for inner area B

Grease bolts with “Molykote Longterm 2”before inserting

gap protection by seal coating

Page 12: Gas Insulated Substation Presentation

12

- 23 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesExample for Dynamic Sealing System

Coupling of operating rodSF6 gas compartmentSF6 gas compartment

Coupling of operating rod

Shaft SF6 seal Operating lever

- 24 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesTypical Grounding / Earthing Arrangement of GIS

Earthing of the buildingConnection to GIS bayOutside the buildingEarthing in the floor/ceilingConnection earthing of floor/ceiling to building

Page 13: Gas Insulated Substation Presentation

13

- 25 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Thank you for your attention.