Top Banner

of 16

FW e3co Star Technical Catalogue

Apr 03, 2018

Download

Documents

majortay
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/28/2019 FW e3co Star Technical Catalogue

    1/16

    e3

    CO - Star

    Energy Recovery Unit > Technical Brochure

    CFD Optimised Compact Design

    Plate Heat Exchanger Efficiency up to 70%

    Plug & Play Controls

    Indoor or Outdoor Installation

    Side-by-side Format

    Up to 1.0 m3/s (3600 m3/h)

    Full BMS Communication

    EC Motors = Low SFP Values: 0.17 w/l/s

    Very Low Noise Levels: 30 dBA Breakout*

    Integrated Exchanger

  • 7/28/2019 FW e3co Star Technical Catalogue

    2/16

    Description- Sel-supporting casing made o galvanised steel;

    - Reduced height allows or easy installation into

    ceiling voids;

    - Side access or inspection and maintenance;

    - Dierential pressure switches mounted on board (or

    plug-n-play solution);

    - Condensation drainage system, with side mounteddrain point to minimise height

    Double Skin Sandwich Panels

    - Steel panels thickness is 0.9mm/0.7mm (inner/

    outer skins)

    - Internal rockwool insulation thickness is 25mm.

    Density is 60Kg/m3 - giving a low noise solution,

    whilst optimising product weight

    Exchanger

    - Cross-low aluminium heat exchanger with a thermal

    eiciency o up to 70%, has proven perormance asit is Eurovent certiied

    Filters

    - G4 class or exhaust air and resh air, but higher

    ilter grades are available on request

    Range

    - 6 models rom 300m3/h (0.08 m3/s) up to

    3600 m3/h (1.0 m3/s)

    Available Configurations

    Unit ormat:

    Side-by-sidewithinternalby-passnoheater;

    Integralpostheateroption;waterorelectric

    Pre-heateroption(fittedexternally)

    100% By-Pass via motorised Damper

    The plate heat exchanger is complete with a bypass

    damper which is itted with an actuator, giving a

    100% by-pass capability - control is via our integrated

    e3co Star control package.

    Accessories available on request

    Accessories or rost protection - Pre-Heater

    ESFP round electric heater with electronic

    regulation or duct mounting

    Accessories or post-heating: HWLG temperate water coil (45/35 C) available

    on request

    Accessories or air iltration:

    - F7 & F9 Optional ilter (media) is available on

    request

    Protective accessories:

    ESWC Weather cowl c/w bird guard

    ESWR External weather protective roo

    1

    Speciication

    Application

    High perormance sel regulating ventilation and energy recovery or oice and industrial applications

    Thermalefficiencyupto70%(EN308),incompliancewithErP2009/125/ECdirective,usingaEuroventcertiied core.

    Airfiltrationandtemperaturecontrolincluded.OndemandventilationisavailableviaPIRorCO2

    sensors

    Compact, plug n play units complete with integrated BMS communications (MODBUS) and touch screen HMI

    Range

    Available in 6 models, the e3co Star range covers low rates rom 300 to 3600 m3/h (0.08 to 1.00m3/s).e3co Star range is available in 3 variants:

    e3ssential ERU with plate heat exchanger and ilters itted

    e3

    nhanced ERU with plate heat exchanger, ilters and post heater itted (water or electric)e3lite ERU with plate heat exchanger, ilters and post heater plus pre heater (electric)

    A shining example of excellence

  • 7/28/2019 FW e3co Star Technical Catalogue

    3/162

    Speciication

    Integrated Exchanger

    Fans and Motors

    Completewithdirectdrivencentrifugalfans;singleordoubleinletwithforwardcurvedimpellerblades

    DirectdrivenviaEC(ElectronicallyCommutated)motorswithhigh-performance,thermalprotectionandbuilt in speed control. EC technology is an ecological solution guaranteeing low energy consumption and

    better management and control o the operating point (air lows can be controlled rom 30 to 100 %)

    ControlsUserfriendlyinterface-colourtouchscreen

    Fastandeasycommissioning-savingtimeonsite

    Pre-configuredcontrols.VariableAirVolume,ConstantAirVolumeandConstantPressureoptions

    Plugandplaysolution

    FullBMScapabilityasstandard,usinganopentableversionoftheMODBUSprotocol-easytointegrate

    controls

    Heat Exchanger

    Cross-flowheatexchangercorewithaluminiumplatesisEUROVENTcertified

    Efficiencyuptothan70%(EN308)undertypicaloperatingconditionsasstatedbelow:

    Fresh air : -5C/90 % RH Return air 20C/50 % RH

    Automaticdefrostfunctionisincludedtoprotecttheheatexchangercorefromtheriskoffreezing.

    An optional electric pre-heater (rost heater) is also available as part o rost protection strategy

    Filters

    Filtersareincludedtoprovideprotectiontoothercomponents(ie,exchanger/fans)Mediaismountedwithinrunnersforeasyfitting/removal

    Thee3coStar unit is equipped with G4 grade ilter media itted to the resh air intake and return air

    intake. F7 & F9 grade ilter media can be itted i desired and are available as optional accessories

    Benefits and Features

    IntegratedventilationcontrolcanbeaccessedviaourHMI(displaypanel),whichusestouchscreen

    technology, BMS communication uses a MODBUS protocol is via an RS485 port. Alternatively, the built-in

    Ethernet port can be used.

    100%bypassviaintegraldamperisfittedwithservomotorscontrolledautomaticallybyourbuilt-in

    controls, which can provide FREE-COOLING and NIGHT-COOLING unctions

    WidechoiceofairflowcontrolscenariosareavailabletooptimiseenergyconsumptionTemperatureprobesareincludedtomonitorsupplyair,exhaustairandexternaltemperature

    Anintegratedde-icingsensorisincludedtoprotectthehotwatercoil(whereheaterisfitted)

    Electric heaters are complete with a manual reset saety thermostat to protect the electric heater elements

    Programmableschedulerfunctionisincludedtoallowuserstocustomisetheirownoperatingschedule

    Weekly,dateperiodorsingledatescheduleoptionsareavailable.Externaltimercontrolisalsoavailable

    Airpressureswitchesmonitorfiltersandprovideadirtyfilteralarmfunction

    Pressureswitchesareusedwithinthecontrolofairflowsforeachfan,andprovidefanfailalarms,both

    locally (on the HMI) and to the BMS

    Installation

    Side-by-Sideformat-designedtobecompact

    Lowprofile-suitableformountinginceilingvoids

    Indoororoutdoor(whenweatherroofandweathercowlsaccessoriesarefitted)

  • 7/28/2019 FW e3co Star Technical Catalogue

    4/163

    Applications

    e3co Stare3co Star

    OFFICES

    Flkt Woods offer a highperformance product rangecovering all key elements of

    the overall ventilation system.Our products are designedto secure the best overallperformance of the system as awhole, considering parameters

    such as health and air quality,energy efficiency, noise, firesafety and ease of installation.

    EDUCATION

    High occupancy levelsduring teaching periodsrequire energy-efficient andcontrollable demand-based

    management of air quality andtemperature. The comfort,health and alertness ofstaff and pupils is ensured

    during the learning process,but operating costs can beminimised when these facilitiesare unoccupied.

    GYMNASIUM/INDOOR SPORTS

    Differing types of activityand occupancy mean abroad spectrum of functionalrequirements to ensure efficientremoval of used air and the

    introduction of fresh supplies.

    Systems need to contain andcontrol the periodic build upof high humidity levels andtemperature.

    HEALTHCARE

    For a hospital to operate atits maximum potential, it has tohave all systems workingat the optimum. This not

    only applies to staff,communications and lifesupport systems, but alsoto pipework, cleaning andventilation systems.

    RETAIL/SHOPPING AREAS

    With high activity levelsduring the working week andweekends, its important to

    make sure that all areas ofventilation are maintained andFlkt Woods has the systemsto achieve all requirements.

    APARTMENTS

    The purpose of ventilation is toprovide clean good quality airby removing the stale, pollutedair from our homes. The maintask is of course to ensure that

    the indoor air is healthy and

    safe to breathe. Ventilationtoday is also about energy andsaving energy costs by addingheat recovery to the ventilation

    system.

    INDUSTRY

    Flkt Woods technologyis used widely in industrialprocessing plants and factoriesfor ventilation of work spaces,as vital components in high

    tech manufacturing facilities,

    and for maintaining delicateenvironments within hightolerance levels inpetrochemical andpharmaceutical plants.

    A shining example

    of excellence

  • 7/28/2019 FW e3co Star Technical Catalogue

    5/164

    Legislation

    Environmental Assessment SchemesIt is now very common for new build projects to be designed to achieve environmental standards such

    as those set out in LEED and BREEAM programs. Flkt Woods, with its market leading knowledge and

    products in energy recovery, has helped many projects achieve the very highest levels in both of these

    schemes.

    Energy Performance of Buildings Directive (EPBD)

    TheCommissionoftheEuropeanUnionhasrecentlyproposedarevisionoftheEPBD(EnergyPerformance

    in Buildings Directive, 2002/91/EC). The objective is to further strengthen the effectiveness and impact

    of the existing Directive.

    The background to this initiative is to optimise energy usage. It was noted that even in member states

    where the existing Directive has been successfully implemented, the Commission still identified an untapped

    potential for improvements that could further reduce the energy consumption and CO2

    emissions from

    buildings.

    Building Regulations - Part L for New (A) and Existing Buildings (B)BuildingRegulationsPartLandFoutlinetheneedforahealthierworking/indoorenvironment,withthe

    aim of decreasing CO2

    emissions. The eco design of our e3co Star range will allow specifiers to create

    designs which incorporate the necessary energy usage reductions, whilst still providing precise control of

    mechanical ventilation.

    European Energy Related Products Directive (ErP)

    Directive2009/125/ECwasintroducedbytheEuropeanParliamentin2009withtheaimtoset

    requirements for energy-related products being placed on the European Market. The intention is to

    contribute to sustainable development by increasing the energy efficiency of those products having

    significant environmental impact.

    As a result, a series of implementing measures have been introduced and Regulation (EU) No 327/2011

    applies to fans driven by electric motors with an electrical input power of between 125 W and 500 kW.

    The fans installed in the e3co Star product benefit from EC technology and exceed the requirements of this

    regulation.

    Further measures relating more generally to domestic ventilation and non-domestic ventilation are yet tobe implemented. This will also have an impact on heat recovery units. The overall performance of the

    e3co Star product has been developed with this in mind. In addition, at the heart of the product, its heat

    exchanger is Eurovent certified, which provides reassurance that it will deliver performance that has been

    independently confirmed.

    LEGISLATION

    In Europe, all countries now have to design their new buildings to meet energy targets that

    are set out in the Energy Performance in Buildings Directive (EPBD). All Flkt Woods Energy

    Performance of Buildings Directive solutions are designed to enable full compliance with this

    and other directives regarding ventilation and air conditioning.

    Being a global manufacturer and supplier makes meeting legislation easier for Flkt Woods. It means that

    Flkt Woods must produce solutions at standards that equal the most stringent legislation and guidelines

    around. Only by doing this can we ensure that we meet relevant standards within every market.

  • 7/28/2019 FW e3co Star Technical Catalogue

    6/165

    Performance-CompositeCurves

    Size 1 Size 2 Size 3 Size 4 Size 5 Size 6

    Fan DataMaxInstalledPower:Wattsinput 175 x2 171 x2 465 x2 450 x2 750 x2 1000 x2

    Nominal Running speed: rpm 2150 1740 1640 1085 1030 880

    Fan Motor FLC: amps (note 1) 1.3 x 2 1.3 x 2 3.0 x 2 2.8 x 2 3.4 x 2 1.7 x 2

    FanMotorIPrating 44 44 54 54 54 54

    Motor Insulation class B B B B B B

    Unit Data

    Max Running temperature: C +40 +40 +40 +40 +40 +40

    Min Running temperature: C (note 2) -10 -10 -10 -10 -10 -10

    ElectricalSupply:V/Ph/Hz(note3) 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 415/3/50

    ElectricalSupply:V/Ph/Hz(note4) 230/1/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50

    Thermal Recovery Perormance

    RecoveredThermalPower:kW(note5) 2.5 3.6 6.1 7.1 11.0 16.0

    Air o temperature: C 9.9 10.0 8.2 8.3 9.3 9.4

    Condensate rate: l/h 0.5 0.8 0.9 1.1 2.1 3.1

    Filters

    Supply / Exhaust Air Filter class (note 6) G4 G4 G4 G4 G4 G4

    Note 1: Starting currents are the same as ull load currents as EC motors have a sot start unction

    Note 2: BasedonPre-Heaterbeingfitted,theminimuminlettemperatureis-5C

    Note 3: Electrical supply when no electric heater is itted ie, e3ssential variant

    Note 4: Electrical supply when integral electric heater is itted ie, e3

    nhanced and e3

    lite variantsNote 5: Data relates to nominal airlow rates, which are a mid-curve duty point. Thermal recovery data is based on the ollowing conditions:

    External air: -5C @ 90%RH ; Return air: 20C @ 50%RH ; Nominal airlow as deined above

    Note 6: F7 and F9 grade ilter media is available as an optional extra. The extra pressure drop, when F7 grade ilter media is itted is approx 40Pa

  • 7/28/2019 FW e3co Star Technical Catalogue

    7/166

    Technical Details

    ESFP: Electric Pre-Heater Data (Frost Protection)

    Note 7: NominalPowerbasedonnominalairflowperunitNote 8: Stated Unit Max current rating includes Fans FLC and Electric Pre-Heater ratingNote 9: Heater o temperature is based on air entering the pre-heater at -10C at nominal airlow

    AirpressurelossforPre-Heaterisbetween2and5Pa

    ESHE: Electric Post-Heater Data

    Note 10: Stated Unit Max current rating includes Fans FLCandElectricPost-Heaterrating,butexcludestheElectricPre-HeaterratingNote 11: HeaterontemperatureisbasedairofftemperatureofPlateHeatExchangeratnominalairflow Note 12: Heater o temperatures are stated at nominal airlow

    AirpressurelossforPre-Heaterisbetween2and5Pa

    HWLP: Hot Water Coil (Post Heater) 82C / 71C

    Heater o temperature is based on ollowing conditions: nominal air on value o 7C ; Nominal airlowValues reer to the ollowing conditions: Water Flow and Return temperatures o 82/71C; Nominal Airlow Reer to our sales oice (see backpage or contact numbers) or other design options such as alternative low and return temperatures or optional chilled water coil or heatpump system.

    HWLG: Hot Water Coil (Post Heater) 45C / 35C

    Heater o temperature is based on ollowing conditions: nominal air on value o 7C ; Nominal airlowValues reer to the ollowing conditions: Water Flow and Return temperatures o 45/35C; Nominal airlow

    Electro Valve Kits

    Actuator Motors used within all Electro Valve Kits are suitable or an electrical supply AC 24 V. Motors are designed to be controlled via aDC 010 V signal to provide proportional control. All actuator motors include an Actuator Return Spring

    Size 1 Size 2 Size 3 Size 4 Size 5 Size 6NominalPower:kW(note7) 0.85 1.24 2.1 2.7 3.9 5.6

    MaxRatedPower:kW 0.90 1.50 2.1 3.0 5.0 6.0Supply Voltage: V 230 230 230 400 400 400

    SupplyPhasePh 1 1 1 3 3 3

    ProportionalControl Yes Yes Yes Yes Yes Yes

    Pre-Heater Absorbed Current: amps 3.9 6.52 9.13 7.5 12.5 8.64

    Max Absorbed Current: amps (note 8) 6.5 9.12 15.13 13.1 19.3 12.04

    Duct Connection Diameter 200 250 315 315 400 500

    Heater o temperature: C (note 9) -5 -5 -5 -5 -5 -5

    Size 1 Size 2 Size 3 Size 4 Size 5 Size 6NominalPower:kW 2.7 3.9 7.0 8.7 12.6 17.9

    MaxRatedPower:kW 2.7 4.3 7.0 9.5 13.6 19.0Supply Voltage: V 230 415 415 415 415 415

    SupplyPhasePh 1 3 3 3 3 3

    ProportionalControl Yes Yes Yes Yes Yes Yes

    Max Unit Absorbed Current: amps (note 10) 14.3 8.8 16.1 19.3 26.4 30.8

    Heater on temperature: C (note 11) 9.9 10.0 8.2 8.3 9.3 9.4

    Heater o temperature: C (note 12) 25 24.1 20.9 23.2 22.7 23.3

    Size 1 Size 2 Size 3 Size 4 Size 5 Size 6Number o Rows 1 1 1 1 1 1

    NominalPower:kW 2.8 4.7 8.1 9.6 14.1 22.8Heater o temperature: C 23.7 26.2 24.5 24.9 25.1 27.4

    AirSidePressureloss:Pa 21 19 29 25 29 41

    WaterSidePressureloss:KPa 1.0 5.0 15.0 4.0 9.0 5.0

    Water Side Flow Rate : l/s 0.06 0.10 0.18 0.21 0.31 0.50

    PipeConn.sizes:DN/inches 15 / 15 / 15 / 25 / 1 25 / 1 25 / 1

    ProportionalControl Yes Yes Yes Yes Yes Yes

    Size 1 Size 2 Size 3 Size 4 Size 5 Size 6

    Valve Model : 1 row (82C / 71C) E SM PV A- 02 5 E SM PV A-0 40 E SM PV A- 10 0 E SM PV A-1 00 E SM PV A- 16 0 E SM PV A- 25 0

    Kvs Value (m3/h) 0.25 0.4 1 1 1.6 2.5

    PipeConn.sizes:DN 15 15 15 25 25 25

    Valve Model : 2 row (45C / 35C) E SM PV A- 02 5 E SM PV A-0 40 E SM PV A- 10 0 E SM PV A-1 00 E SM PV A- 16 0 E SM PV A- 16 0Kvs Value (m3/h) 0.25 0.4 1 1 1.6 1.6

    PipeConn.sizes:DN 15 15 25 25 25 25

    Size 1 Size 2 Size 3 Size 4 Size 5 Size 6Number o Rows 2 2 2 2 2 2

    NominalPower:kW 2.7 4.3 8.1 8.9 14.3 17.4Heater o temperature: C 22.8 24.8 24.6 23.7 25.3 22.6

    AirSidePressureloss:Pa 41 37 64 48 65 71

    WaterSidePressureloss:KPa 3.0 10.0 5.0 8.0 9.0 15.0

    Water Side Flow Rate : l/s 0.06 0.10 0.19 0.21 0.34 0.42

    PipeConn.sizes:DN/inches 15 / 15 / 25 / 1 25 / 1 25 / 1 25 / 1

    ProportionalControl Yes Yes Yes Yes Yes Yes

  • 7/28/2019 FW e3co Star Technical Catalogue

    8/167

    Sound Levels & Conigurations

    ModelSpeeds

    % oDuty

    Inlet Sound Power Levels (LwA)*Breakout

    dB(A)@ 3m

    SFPPowerSaving

    %

    PowerSaving(Watts)

    63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHzTotalLwA

    Size 1

    Boost Max 42 54 50 46 42 43 37 20 57 29 0.88 - -

    75% 75% 42 53 48 43 41 40 34

  • 7/28/2019 FW e3co Star Technical Catalogue

    9/16

  • 7/28/2019 FW e3co Star Technical Catalogue

    10/169

    IndividualPerformanceCurves

    0

    50

    100

    150

    200

    250

    300

    350

    0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16

    S

    tatic

    Pressure

    (Pa)

    Volume Flow (m /s)

    Boost Mode

    75%

    60%

    45%

    Trickle Mode

    3

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0 0.05 0.1 0.15 0.2 0.25 0.3

    Boost Mode

    75%

    60%

    45%

    Trickle Mode

    Static

    Pressure

    (Pa)

    Volume Flow (m /s)3

    e3co Star - Size 1

    e3co Star - Size 2

  • 7/28/2019 FW e3co Star Technical Catalogue

    11/1610

    IndividualPerformanceCurves

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5

    S

    tatic

    Pressure

    (Pa)

    Volume Flow (m /s)

    Boost Mode

    75%

    60%

    45%

    Trickle Mode

    3

    Boost Mode

    75%

    60%

    45%

    Trickle Mode

    0

    50

    100

    150

    200

    250

    300

    350

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7

    Static

    Pressure

    (Pa)

    Volume Flow (m /s)3

    e3co Star - Size 3

    e3co Star - Size 4

  • 7/28/2019 FW e3co Star Technical Catalogue

    12/161

    IndividualPerformanceCurves

    Boost Mode

    75%

    60%

    45%

    Trickle Mode

    0

    50

    100

    150

    200

    250

    300

    350

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

    Static

    Pressure

    (Pa)

    Volume Flow (m /s)3

    Boost Mode

    75%

    60%

    45%

    Trickle Mode

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0 0.2 0.4 0.6 0.8 1 1.2

    Static

    Pressure

    (Pa

    )

    Volume Flow (m /s)3

    e3co Star - Size 5

    e3co Star - Size 6

  • 7/28/2019 FW e3co Star Technical Catalogue

    13/1612

    Control Solutions

    Pa

    HS air flow

    LS air flow

    Air flow

    HS constant air flow

    LS constant air flow

    Air flow

    Pa

    CAVConstant Air Volume2 Constant Air low Options

    VAVVariable Air Volume - Trickle & Boost Strategy2 Air low rates - Low Speed/High Speed

    Pa HS air flow

    LS air flow

    Air flow

    COPConstantPressureControl

    VAV AQVariable Air Volume plus CO

    2sensor

    ProportionalairflowcontrolviaCO2sensor

    The e3co Star unit has a factory-pre-set controller as standard, which can be used to configure how air flows can

    be modulated:

    Pa

    Constant pressure

    Air flow

    HMI Screen OverviewAlarm indication, building parameters, operation mode,

    temperature, on demand set points and alarm statuscan all be viewed and set via our touch screen HMI

  • 7/28/2019 FW e3co Star Technical Catalogue

    14/163

    Accessories

    Filter media upgrade

    The Filter Media grade ftted to the supply air side, can be upgraded rom G4 to F7,

    or enhanced protection.

    Alternatively, The Filter Media grade or the supply air side can be upgraded rom

    G4 to F9, or ultimate protection.

    e3co-Star units can have a number o accessories ftted:

    ESDC ESMPVA

    Connectors 3-Port Valve + Actuator

    BDER ESMF (set o 4)

    Cylindrical Duct Silencers Mounting eet

    HMI extension cables ESFP

    10m ESC10 Optional

    25m ESC25 Pre-Heater

    ESPIR BDEP-46-024

    PIR Occupancy Sensor Inlet damper

    and actuator

    e3co-Star units can be installed outside when a weather proo kit is ftted.

    ESWR: Weather Roo

    ESWC Weather Cowl / Bird GuardFit to inlet and discharge spigots

  • 7/28/2019 FW e3co Star Technical Catalogue

    15/1614

    AccessoriesandProductCodes

    1 2 3 4 5

    e3co-Star 1 SS-R e3ssential Control optione3nhanced HW/HE

    e3lite HW/HE

    1 - Thermal Efficiency unit (up to 70%) - completewithautomaticcontrolandCrossFlowPlate Heat Exchanger

    2 - Unit Model Code Examples:

    1 Unitsize=1(0.12m3/s) e3co-Star 1 6 Unitsize=6(0.90m3/s) e3co-Star 6

    3 - Unit Configuration Options:SS-R Side-by-Side format (access and controls on right side)SS-L Side-by-Side format (access and controls on left side)

    4 - Unit Version Options:

    e3ssential Unit with NO coils fittede3nhanced HW Hotwatercoil(POSTHeater)plusappropriatecontrolsfitted

    e3nhanced HE Electricheater(POSTHeater)plusappropriatecontrolsfitted e3lite HW UnitwithElectricPRE-HeaterandhotwaterPOSTHeaterpluscontrols

    e3

    lite HE UnitwithElectricPRE-HeaterandElectricPOSTheaterpluscontrols

    5 - Controls: VAV Variable Air Volume - Trickle and BoostVAV AQ Variable Air Volume - + Air Quality (CO

    2) Sensor

    CAV Constant Air VolumeCOP ConstantPressure

    All motors are EC type

    Dia A

    Length

    Dia B

    BDER Silencer Information

    Product Coding Guide

    Dia A(mm) Length(mm) Dia B mm Code

    Attenuation, dB

    63Hz 125Hz 250Hz 500Hz 1KHz 2KHz 4KHz 8KHz

    200 600 300 BDER-30-020-060 -1 -3 -7 -14 -20 -26 -15 -7

    200 900 300 BDER-30-020-090 -2 -3 -9 -24 -30 -36 -20 -9

    200 1200 300 BDER-30-020-120 -3 -5 -14 -30 -37 -46 -25 -12

    250 600 355 BDER-30-025-060 0 -2 -7 -12 -18 -23 -10 -5

    250 900 355 BDER-30-025-090 -2 -2 -8 -19 -25 -32 -12 -6

    250 1200 355 BDER-30-025-120 -2 -4 -11 -25 -30 -39 -14 -10

    315 600 415 BDER-30-031-060 0 -2 -7 -10 -15 -20 -7 -4

    315 900 415 BDER-30-031-090 -1 -2 -7 -16 -22 -24 -10 -6

    315 1200 415 BDER-30-031-120 -2 -4 -10 -22 -28 -30 -12 -9

    400 900 500 BDER-30-040-090 -1 -2 -6 -13 -19 -16 -8 -6

    400 1200 500 BDER-30-040-120 -2 -4 -8 -18 -25 -20 -10 -8

    500 900 630 BDER-30-050-090 -1 -1 -5 -11 -14 -12 -9 -6

    500 1200 630 BDER-30-050-120 -1 -3 -7 -16 -20 -15 -10 -7

  • 7/28/2019 FW e3co Star Technical Catalogue

    16/16

    Flkt Woods Group - Ventilation Solutions

    Flkt Woods LimitedAxial Way, ColchesterEssex, C04 5ZDUNITED KINGDOMTel: +44 (0)1206 222 555

    Fax: +44 (0)1206 222 777E-mail: [email protected]

    Flkt Woods OyKalevantie 39FI-20520TurkuFINLANDTel: +358 20 442 3000Fax: +358 20 442 3018E-mail: [email protected]

    Flkt Woods OyHmeentie 23FI-37800ToijalaFINLANDTel: +358 20 442 3500Fax: +358 20 442 3502E-mail: [email protected]

    Flkt Woods ABGesllgatan 17745 39EnkpingSWEDENTel: +46 36 19 30 00Fax: +46 171-240 97E-mail: [email protected]

    Flkt Woods ABKung Hans vg12 192 68, SollentunaSwedenTel: +46 (0)771 26 26 26

    Fax: +46 (0)8 626 73 10E-mail: [email protected]

    Flkt Woods ABFlktvgen 2, Box 84153 22JrnaSWEDENTel: +46 8-551795 00Fax: +46 8-551744 80E-mail: [email protected]

    Flkt Woods4 Avenue LaurentCELY-Batiment C - Etage 3Asnieres Sur Seine92600 FRANCETel: +33 1 80 21 07 00Fax: +33 1 80 21 07 00E-mail: [email protected]

    Flkt Woods Ventilatoren GmbHAmSportplatz4DE-40882RatingenGERMANYTel: +49 2012 61038 11Fax: +49 2102 61038 18E-mail: [email protected]

    Flkt Woods SpAViaPacinotti,28IT-20092, Cinisello BalsamoITALYTel: +39 02 6186 6091

    Fax: +39 02 6186 0947E-mail: [email protected]

    Flkt Bovent Sp. z o.o.PanattoniParkPruszkwIIul.Poudniowa2,Otarzew05-850OarwMazowieckiPOLANDTel: +48 22 392 43 43Fax: +48 22 392 43 44E-mail: [email protected]

    LLC Flkt Industrial& Building Systems23,ul.ProfsojuznayaRU-117418 MoscowRUSSIATel: +7 (495) 589-31-08Fax: +7 (495) 589-31-74E-mail: [email protected]

    The Flkt Woods Group is divided into three businesses:

    Global Inrastructure and Industry (GII)A leader or Air Movement using ans to improve perormance o equipment and industrialprocesses

    Air Climate Solutions (ACS)AworldwideHVACleaderrecognizedbyourcustomersasaproviderofsuperiorAirClimateSolutions combining Indoor Air Quality and Energy Efciency applied to specifed buildings

    Ventilation Solutions (VS)A European Ventilation Specialist Servicing our customers with a complete range o

    ventilation products ocused on Non residential buildings. For more specifc productinormation or Ventilation Solutions, please visit:

    www.vsecatalogue.flaktwoods.com

    VS/ESTB-ENG-02/0912

    Flkt Woods Limited

    Axial Way, Colchester, Essex, C04 5ZD

    Tel 01206 222 555 Fax 01206 222 777

    email [email protected] www.laktwoods.co.uk