FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided with sound. Please switch on your loudspeakers and press the keys at the bottom of each slide to proceed.
5

FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided.

Mar 31, 2015

Download

Documents

Miguel Widger
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided.

FRONIUS STATE 104©FRONIUS 2006

The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter.

Please note that each slide is provided with sound. Please switch on your loudspeakers and press the keys at the bottom of each slide to proceed.

Page 2: FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided.

FRONIUS STATE 104©FRONIUS 2006

FRONIUS IG TroubleshootingSTATE 104

Troubleshooting

What is STATE 104?

Contact FRONIUS tech support

Page 3: FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided.

FRONIUS STATE 104©FRONIUS 2006

What is STATE 104?

• STATE 104 appears on the LCD of a FRONIUS IG inverter when the grid frequency goes out of limits. • For FRONIUS inverters, operating frequency range is 59.3–60.5 Hz.• The inverter is internally disconnected from the AC grid but still continues to

monitor the grid frequency.

• The inverter reconnects when the grid frequency is within the allowable tolerance levels.

• STATE 104 also appears when there is no AC voltage at the inverterterminals (zero frequency).

Troubleshooting >><< Main page

Page 4: FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided.

FRONIUS STATE 104©FRONIUS 2006

TroubleshootingFollow steps below to troubleshoot STATE 104:1. Check if the AC disconnect on the inverter, external AC disconnect and the circuit breaker in the main panel are turned ON.

2. If all disconnects are ON, using a multi-meter, measure the AC voltage on the top terminals of the AC disconnect on the inverter (If possible, also measure the frequency of the AC voltage).

3. If both voltage and frequency are within allowable levels and the inverter continues to show STATE 104, please contact FRONIUS tech support.

Contact FRONIUS tech support >>

=~

+

-

L1

L2

Internal

AC-DisconnectExternal

AC-DisconnectMain panel

240V

<< Main page

Page 5: FRONIUS STATE 104 ©FRONIUS 2006 The following slides explain troubleshooting the STATE 104 in a FRONIUS IG inverter. Please note that each slide is provided.

FRONIUS STATE 104©FRONIUS 2006

FRONIUS technical support