Top Banner
Freezer Floor Heaving and Solution Prepared By H. Charles Woolley and John Fountain For International Association for Cold Storage Contractors November 2-5, 2011
42

Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Mar 16, 2018

Download

Documents

vantu
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Freezer Floor Heaving and Solution

Prepared By H. Charles Woolley and John Fountain For International Association for Cold Storage Contractors

November 2-5, 2011

Page 2: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Introduction

• Mr. Charles Woolley -Vice President • Mr. John Fountain -Director of Energy

Page 3: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Overview

• What is Floor Heaving? • What Prevents Floor Heaving • Types of Construction • Floor Heaving Effects • Repairs and Solutions

Page 4: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

What is Frost Heaving in Freezers?

• As the earth below a freezer drops below freezing, the moisture in the soil will freeze, form ice, and expand.

• The formation of this ice can cause floors to crack, break, and lift up or “heave”.

• Ice Formation will lift columns, push foundation walls over, and rip open roofs.

Page 5: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

How Do You Prevent Frost Heaving?

• Underfloor heating is the most common method of preventing floors from heaving in refrigerated warehouses

• There are a few methods of underfloor heating – Electric Heat – Pumped Fluid-Glycol – Forced Ventilation – Natural Ventilation

Page 6: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Construction Detail

• Most Common Approach – UF Heat System – Concrete Sub Slab – 10 mill Poly Vapor Barrier – 2 Layers of Extruded Polystyrene(5”-6”-7”) – 6 mill Poly Slip Sheet – Concrete Finish Floor(5”-8”)

Page 7: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

What Is The Best System?

• Everyone has different opinions • Each system has pros and cons • Use your and others experience to solve

your problem • Key Factors:

– Design and Installation – Life Cycle Cost – Maintenance – Repairs

Page 8: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Electric Heating

Page 9: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Electric Heating

Page 10: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Electric Heating • Electric heat trace is placed in metal

conduit that is buried in the concrete sub slab

• Temperature of the sub slab is monitored by a control system

• Controls cut on and off the heat and electricity as you need it

Page 11: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Electric Heating PROS: • Easily monitored by maintenance

personnel • Easily Installed by a local electrician • Easy replacement of heat trace cable • Lower Capital Expense

Page 12: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Electric Heating CONS: Must be monitored by maintenance Maintenance Turnover and Lack of Control Cost Rate for Electricity Lack of Insulation-Run time Troubleshooting if not installed properly

Page 13: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Forced Fluid-Glycol • Glycol or other warm fluids is pumped

through pipes. Glycol is most common. • Fluids are usually heated from waste heat

off the refrigeration system • Piping or circuits are typically overlapped

in case of a leak or problem with a circuit.

Page 14: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Forced Fluid-Glycol

Page 15: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Forced Fluid-Glycol

Page 16: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Glycol PROS: • Refrigeration contractors love these

systems because they use their waste • Reliable System when maintained properly • Maintenance personnel may be more

familiar with these systems

Page 17: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Glycol CONS: • Piping material deteriorate and causes

leaks • No easy way to find and repair leaks • Pipe Blockage-Ice or Building Settling • Creating Environmental Issue? • Requires Monitoring of Fluid

Concentration • Troubleshooting if not installed properly

Page 18: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Natural Ventilation • Most Commonly Known As Vent Pipes • Many Different Methods

– Ductwork or Pipes Straight Through – Ductwork or Pipes in U Bend Shape – Concrete Block Channels

Page 19: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Natural Ventilation

Page 20: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Natural Ventilation Design

Most Commonly Uses 6” or 8” diameter pipe on 6’ centers

Ductwork should be sloped to allow for condensation to drain

Pros: -Inexpensive construction -Low or No operating expense

Page 21: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Natural Ventilation CONS

• Cons: • Complex Thermodynamic calculations • Piping material deteriorates • Ductwork becomes clogged • Ice forming inside of ductwork • Air flows to least resistance, not with

construction design • Expensive Repairs

Page 22: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Forced Ventilation • Air is forced through ductwork • Requires ductwork or piping that needs to

last for many years • Requires a fan to blow air through the

system. (may require supplemental heat)

Page 23: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Forced Ventilation

Page 24: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Problems with Forced Ventilation

• Ductwork material deteriorates • Ductwork clogs with debris or rodents • Condensation and drainage issues • Ice forming from condensation leads to

plugged pipes • Fan failure (access and silent)

Page 25: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

RECAP • WHAT DID WE LEARN? • ALL REQUIRE PREVENATIVE

MAINTENANCE AND ATTENTION!!

Page 26: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Effects of Floor Heaving

• Interruption of Operations • Building Structure Compromised • OSHA Violations-Safety Concerns • Initial Repair Expenses • Long Term Repair Expenses • Lost Production Time • Lost Rental Income

Page 27: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Foundation Walls

Page 28: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Freezers and Blast Cells

Page 29: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Doorways

Page 30: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Refrigerated Docks

Page 31: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Wall to Roof Juncture

Page 32: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

How Can I Fix My Problem?

• Turn on floor heating system or make sure yours is hooked up properly!

• Demo the floor and install a new floor heat system

• Retrofit a floor heat system

Page 33: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Financially What Makes Sense?

• If the system was turned off or not hooked up properly, this will save you tons of $$$$.

• Empty Freezer and Replace With New Construction.

• Retrofit an UF Heat System • What makes sense for your business??

Page 34: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Demolition of Freezer Slab

• Shut Down Freezer • Empty Racks • Remove Racks • Demo Floor System • Install New Floor Heat System • Install New Floor Insulation and Concrete • Big Expenses and NO INCOME!!!

Page 35: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Retrofit a Floor System

• Install Glycol System, Pumps, Tubing

• Install and Electric Heat System

Page 36: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Retrofitted Electric Heat System

• Get a specific design completed • From outside, drill holes under the freezer • Add heat to these holes to melt the ice

formation • Once Melted, floor can be maintained at a

normal operating temperature and at normal budget costs.

Page 37: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Getting Started

Page 38: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Retrofitted UF Heat System

Page 39: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Retrofitted UF Heat System

Page 40: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Retrofitted UF Heat System

Page 41: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

Retrofitted Vent Pipe

Page 42: Freezer Floor Heaving and Solution · PDF fileFreezer Floor Heaving and Solution ... – Design and Installation ... conduit that is buried in the concrete sub slab

QUESTIONS? Thanks for your time and patience, please