MAX MIN MAX MIN MAX MIN MAX MIN nerc prc-005 standards Maintenance solutions 4 CALENDAR MONTHS 18 CALENDAR MONTHS 18 18 CALENDAR MONTHS 18 6 CALENDAR YEARS 6 VLA Batteries MAXIMUM maintenance INTERVALS MUST PERFORM maintenance ACTIVITIES SOLUTIONS BY MIDTRONICS SOLUTIONS Key SOLUTIONS BY MIDTRONICS SOLUTIONS BY MIDTRONICS Must perform maintenance ACTIVITIES must perform at least one of the two maintenance ACTIVITIES MAXIMUM maintenance INTERVALS MAXIMUM maintenance INTERVALS OR Verify station DC supply voltage Inspect electrolyte level Inspect for unintentional grounds Verify Float voltage of battery charger Verify Battery continuity Verify Battery terminal connection resistance Verify Battery intercell or unit-to-unit connection resistance Inspect Cell condition of all individual battery cells where cells are visible – or measure battery cell/unit internal ohmic values where the cells are not visible Verify that the station battery can perform as manufactured by evaluating cell/unit measurements indicative of battery performance (e.g. internal ohmic values or float current) against the station battery baseline Verify that the station battery can perform as manufactured by conducting a performance or modified performance capacity test of the entire battery bank Inspect physical condition of battery rack The CELLTRON ADVANTAGE is a quick and easy solution for compliance to NERC PRC-005 Standards. User-customizable, the CELLTRON ADVANTAGE is a flexible, efficient and economical battery management tool for service providers, operations, and maintenance teams. CELLGUARD SYSTEM provides patented, wireless real time 24/7/365, continuous battery monitoring for an automated solution to NERC PRC-005 standards. The Midtronics Managed Services Program is designed for maximum effectiveness to determine battery state-of-health and effective replacement scheduling without exposure to potential load loss, thus making it a solid solution for maintaining NERC PRC-005 standards. CELLGUARD SYSTEM ELS+ Electrolyte Level Monitoring System provides 24/7/365 electrolyte level and temperature monitoring on Vented Lead Acid (VLA) batteries which complies with NERC PRC-005 electrolyte level inspection requirements.
3
Embed
Franklin Electric - nerc prc-005 standards Maintenance solutions … · 2017-06-22 · MAX MIN MAX MIN MAX MIN MAX MIN nerc prc-005 standards Maintenance solutions 4 CALENDAR MONTHS
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
nerc prc-005 standards Maintenance solutions
4 CALENDAR MONTHS
18 CALENDAR MONTHS
18
18 CALENDAR MONTHS18
6 CALENDAR YEARS6
VLA Batteries
MAXIMUM maintenance INTERVALS MUST PERFORM maintenance ACTIVITIES SOLUTIONS BY MIDTRONICS SOLUTIONS Key
SOLUTIONS BY MIDTRONICS
SOLUTIONS BY MIDTRONICS
Must perform maintenance ACTIVITIES
must perform at least one of the two maintenance ACTIVITIES
MAXIMUM maintenance INTERVALS
MAXIMUM maintenance INTERVALS
OR
Verify station DC supply voltage
Inspect electrolyte level
Inspect for unintentional grounds
Verify Float voltage of battery charger
Verify Battery continuity
Verify Battery terminal connection resistance
Verify Battery intercell or unit-to-unit connection resistance
Inspect Cell condition of all individual battery cells where cells are visible – or measure battery cell/unit internal ohmic values where the cells are not visible
Verify that the station battery can perform as manufactured by evaluating cell/unit measurements indicative of battery performance (e.g. internal ohmic values or float current) against the station battery baseline
Verify that the station battery can perform as manufactured by conducting a performance or modified performance capacity test of the entire battery bank
Inspect physical condition of battery rack
The CELLTRON ADVANTAGE is a quick and easy solution for compliance to NERC PRC-005 Standards. User-customizable, the CELLTRON ADVANTAGE is a flexible, efficient and economical battery management tool for service providers, operations, and maintenance teams.
CELLGUARD SYSTEM provides patented, wireless real time 24/7/365, continuous battery monitoring for an automated solution to NERC PRC-005 standards.
The Midtronics Managed Services Program is designed for maximum effectiveness to determine battery state-of-health and effective replacement scheduling without exposure to potential load loss, thus making it a solid solution for maintaining NERC PRC-005 standards.
CELLGUARD SYSTEM ELS+ Electrolyte Level Monitoring System provides 24/7/365 electrolyte level and temperature monitoring on Vented Lead Acid (VLA) batteries which complies with NERC PRC-005 electrolyte level inspection requirements.
nerc prc-005 standards Maintenance solutions
4 CALENDAR MONTHS
6 CALENDAR MONTHS
6
18 CALENDAR MONTHS
18
18 CALENDAR MONTHS18
6 CALENDAR YEARS6
VRLA Batteries
MAXIMUM maintenance INTERVALS MUST PERFORM maintenance ACTIVITIES SOLUTIONS BY MIDTRONICS
MAXIMUM maintenance INTERVALS MUST PERFORM maintenance ACTIVITIES SOLUTIONS BY MIDTRONICS
SOLUTIONS Key
SOLUTIONS BY MIDTRONICS
SOLUTIONS BY MIDTRONICS
Must perform maintenance ACTIVITIES
must perform at least one of the two maintenance ACTIVITIES
MAXIMUM maintenance INTERVALS
MAXIMUM maintenance INTERVALS
OR
Verify station DC supply voltage
Inspect for unintentional grounds
Condition of all individual units by measuringbattery cell/unit internal ohmic values
Verify Float voltage of battery charger
Verify Battery continuity
Verify Battery terminal connection resistance
Verify Battery intercell or unit-to-unit connection resistance
Verify that the station battery can perform as manufactured by evaluating cell/unit measurementsindicative of battery performance (e.g. internal ohmic values or float current) against the station battery baseline
Verify that the station battery can perform as manufactured by conducting a performance or modified performance capacity test of the entire battery bank
Inspect physical condition of battery rack
The CELLTRON ADVANTAGE is a quick and easy solution for compliance to NERC PRC-005 standards. User-customizable, the CELLTRON ADVANTAGE is a flexible, efficient and economical battery management tool for service providers, operations, and maintenance teams.
CELLGUARD SYSTEM provides patented, wireless real time 24/7/365, continuous battery monitoring for an automated solution to NERC PRC-005 standards.
The Midtronics Managed Services Program is designed for maximum effectiveness to determine battery state-of-health and effective replacement scheduling without exposure to potential load loss, thus making it a solid solution for maintaining NERC PRC-005 standards.
nerc prc-005 standards Maintenance solutions
4 CALENDAR MONTHS
18 CALENDAR MONTHS
18
6 CALENDAR YEARS
6
nICKEL CADMIUM Batteries
MAXIMUM maintenance INTERVALS MUST PERFORM maintenance ACTIVITIES SOLUTIONS BY MIDTRONICS SOLUTIONS Key
SOLUTIONS BY MIDTRONICS
SOLUTIONS BY MIDTRONICS
Must perform maintenance ACTIVITIES
must perform at least one of the two maintenance ACTIVITIES
MAXIMUM maintenance INTERVALS
MAXIMUM maintenance INTERVALS
Verify Float voltage of battery charger
Verify Battery continuity
Verify Battery terminal connection resistance
Verify Battery intercell or unit-to-unit connection resistance
Verify that the station battery can perform as manufactured by conducting a performance or modified performance capacity test of the entire battery bank.
Inspect physical condition of battery rack
Verify station DC supply voltage
Inspect electrolyte level
Inspect for unintentional grounds
Inspect Cell condition of all individual battery cells
CELLGUARD SYSTEM ELS+ Electrolyte Level Monitoring System provides 24/7/365 electrolyte level and temperature monitoring on Vented Lead Acid (VLA) batteries which complies with NERC PRC-005 electrolyte level inspection requirements.
The Midtronics Managed Services Program is designed for maximum effectiveness to determine battery state-of-health and effective replacement scheduling without exposure to potential load loss, thus making it a solid solution for maintaining NERC PRC-005 standards.
The CELLTRON ADVANTAGE is a quick and easy solution for compliance to NERC PRC-005 Standards. User-customizable, the CELLTRON ADVANTAGE is a flexible, efficient and economical battery management tool for service providers, operations, and maintenance teams.
CELLGUARD SYSTEM provides patented, wireless real time 24/7/365, continuous battery monitoring for an automated solution to NERC PRC-005 standards.