32 FR-XLPE/PVC Shielded-LCT APPLICATIONS • Predominantly used in utility substations • Can be installed indoors or outdoors, in cable trays, conduit, underground duct, or direct buried in wet or dry locations • Conductor operating temperatures are not to exceed 90°C wet or dry • Rated 600 Volts CONSTRUCTION DETAILS • Conductors • 14 AWG thru 10 AWG Annealed Class B Copper Unilay Compressed Stranded • Insulation • Flame Retardant Cross-Linked Polyethylene (FR-XLPE) • Color Coded per preferred method in ICEA S-73-532 standard • Assembly • Cabled with non-hygroscopic polyethylene fillers in order to give the cable a circular cross-section, when needed • Wrapped with a Mylar binder • Shield • Longitudinally corrugated 5 mil annealed copper tape • Overall Jacket • Heat, Moisture, and Sunlight Resistant Black Polyvinyl Chloride (PVC) • Print • SOUTHWIRE XXAWG XX/C FR-XLPE (XHHW-2) CDS 90C PVC JKT SHIELDED TYPE TC 600V SUN. RES. DIRECT BURIAL YEAR SEQUENTIAL FOOTAGE MARKS SPECIFICATIONS Southwire’s Type TC Substation Control Cable meets or exceeds: • All applicable ASTM Standards • ANSI/ICEA S-73-532 • UL 44 Type XHHW-2 rated VW-1 • UL 1277 • UL 1581 • IEEE 1202 • ICEA T-29-520 • RoHS Compliant OPTIONS Strand: • Stranding Classes – C, K • Tin Coated Copper Color Coding Methods: • Color Coding per ICEA S-73-532 • Method 1, Table E1 • Method 1, Table E2 • Method 4 • Custom, available upon request Insulation: • PE/PVC • PE • FR-XLPE • THHN Binder Tape: • Flame Retardant Shielded Constructions: • CU LCT • CU Helical Tape • AL Helical Tape • AL Longitudinal • With drain wire Jacket: • PVC • LSZH-TP • LSZH-TS • CPE-TP • CPE-TS Other: • Rip cord • 1000 Volt rated • Custom print Additional constructions available upon request SUBSTATION CONTROL CABLE | Shielded (LCT Shield) CONDUCTOR TYPE 14 – 10 AWG COPPER INSULATION TYPE FR-XLPE SHIELD TYPE LONGITUDINAL CORRUGATED COPPER TAPE JACKET TYPE PVC CONSTRUCTION AT A GLANCE 1 1 2 2 4 4 3 3