  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 1 of 45

    Installation Manual forSurge Protective Device

    Flexi Power RectifierFPRB

    Manufactured by: Artesyn Embedded TechnologiesManufacturing PN: AA27540L

    Visit us @ http://www.artesyn.com/

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 2 of 45

    Manual Number: 970-009473-0000

    Manual Issue: AC

    Manual Status: Standard

    Release Date: Jun 30, 2014

    Copyright 2014 Artesyn Embedded TechnologiesCONSIDER IT SOLVED

    Published in China

    This document, and the information it contains, are the property of Artesyn EmbeddedTechnologies Co., Ltd, and are protected by law. Both must be held in strictest confidence at alltimes. Artesyn Embedded Technologies grants no license or right to copy, use or disclose either,expressly or by implication.

    Disclaimer

    This document and the information contained herein are provided on an "AS IS" basis. ArtesynEmbedded Technologies may make improvements or changes in this documentation, at anytime and without notice and as it sees fit. The information in this documentation was preparedby Artesyn Embedded Technologies with reasonable care and is believed to be accurate.However, Artesyn Embedded Technologies shall not assume responsibility for losses or damagesresulting from any omissions, inaccuracies, or errors contained herein.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 3 of 45

    History

    Date

    DD-MM-YYYVersion Author Change Note

    30-06-2013 AA Ferdinand Sisracon First release for FPRB

    30-10-2013

    30-06-2014

    AB

    AC

    Ferdinand Sisracon

    Alex Ding

    Release to be used as a commonSPD Instruction Manual for bothFPRA and FPRB

    Added special instruction toconnect the N link cable for bothFPRA and FPRB

    Change the brand from EmersonNetwork Power to ArtesynEmbedded Technologies

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 4 of 45

    Table of Contents

    History ...................................................................................................................3Table of Contents ....................................................................................................4List of Figures ..........................................................................................................5List of Tables ...........................................................................................................5Preface...................................................................................................................9

    Application of this manual ..................................................................................10Chapter 1 Product Introduction.............................................................................11

    1.1 General Description .................................................................................111.2 Main Specification of the SPD....................................................................111.3 Properties ...............................................................................................16

    Chapter 2 Preparation ..........................................................................................182.1 Installation tools ......................................................................................182.2 Delivery contents .....................................................................................18

    Chapter 3 SPD Installation ....................................................................................203.1 Make AC connection with the SPD .............................................................20

    3.1.1 Preparation ................................................................................................... 213.1.2 Configure the Terminal Block ...................................................................... 273.1.3 3-phase star (3Y) AC connection with the SPD ........................................... 293.1.4 Single-phase (1) AC connection with the SPD.......................................... 353.1.5 2-phase AC connection with the SPD ........................................................ 383.1.6 3-phase delta (3) AC connection with the SPD ......................................... 40

    3.2 Replace the SPD .......................................................................................44

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 5 of 45

    List of Figures

    Figure 1 Internal circuit diagram of the SPD .................................................................. 11Figure 2 Structure of the SPD......................................................................................... 12Figure 3 Dimension of the SPD top view..................................................................... 13Figure 4 Dimension of the SPD side view.................................................................... 14Figure 5 SPD configuration in a TN-S system ................................................................. 16Figure 6 Checking failure of the SPD .............................................................................. 17Figure 7 PDA rear internal chassis layout ...................................................................... 21Figure 8 The AC cable connection chart ........................................................................ 27Figure 9 AC terminal block configuration 1 and 2 Configuration ......................... 28Figure 10 AC terminal block configuration 3 ............................................................ 28Figure 11 AC terminal block configuration 3Y ............................................................ 29Figure 12 Schematic diagram of AC connection with the SPD 3Y............................... 29Figure 13 - Assemble the Link Cables to SPD .................................................................... 30Figure 14 - AC Ground wire............................................................................................... 31Figure 15 - Secure the SPD into the DIN rail ..................................................................... 31Figure 16 - Connect the Link cables to Terminal Block ..................................................... 32Figure 17 - Special Instruction for N Link Cable Installation ............................................. 33Figure 18 AC connection with the SPD - 3Y ................................................................... 34Figure 19 Schematic diagram of AC connection with the SPD 1.............................. 35Figure 20 SPD configuration for single-phase AC connection ....................................... 36Figure 21 - Connection of AC link cables from SPD to Terminal Block ............................. 37Figure 22 Schematic diagram of AC connection with the SPD 2- Phase...................... 38Figure 23 - AC connection with the SPD 2- Phase.......................................................... 39Figure 24 Schematic diagram of AC connection with the SPD 3 .............................. 40Figure 25 - Connection of AC link cables and SPD ground cables..................................... 41Figure 26 Connecting the AC terminal block 3 ......................................................... 42Figure 27 3-phase delta (3) AC connection with the SPD.............................................. 43Figure 28 Removing the damaged OVP module from the SPD ..................................... 44Figure 29 The OVP module and the SPD base ............................................................... 45Figure 30 Fitting a new OVP module to the SPD ........................................................... 45

    List of Tables

    Table 1 Contents of this manual...........................................................................................9Table 2 Symbols in this manual ............................................................................................9Table 3 Reference documents of the SPD .........................................................................10Table 4 Main specification of the SPD ...............................................................................15Table 5 Delivery contents of the SPD .................................................................................19Table 6 Recommended preparation for AC mains cable ..................................................22Table 7 AC connection with the SPD ..................................................................................23

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 6 of 45

    Table 8 Schematic diagram of AC connection with the SPD ............................................25

    List of TermsA Ampere

    AC Alternative current

    AWG American Wire Gauge

    BAT Battery

    BR Battery Return

    BTS Base Transceiver Station

    CB Circuit Breaker

    CSA Cross Section Area

    CU Control unit

    DC Direct current

    EMC Electromagnetic Compatibility

    ESD Electrostatic Discharge

    FPRB Flexi Power Rectifier

    GND Ground

    GUI Graphical User Interface

    IE Internet Explorer

    IP Internet Protocol

    L Live cable from the AC mains

    LAN Local Area Network

    LED Light Emitting Diode

    LVD Low Voltage Disconnect

    MAC Media Access Control

    MCB Miniature Circuit Breaker

    N Neutral cable from the AC mains

    PC Personal Computer

    PCB Printed Circuit Board

    PDA Power Distribution Assembly

    PE Protective earth

    PSU Power Supply Unit

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 7 of 45

    SPD Surge Protective Device

    V Volt

    VPN Virtual Private Network

    1 Single-phase AC type

    3Y 3-phase star AC type

    3 3-phase delta AC type

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 8 of 45

    This page left intentionally blank

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 9 of 45

    Preface

    About this manual

    This manual provides all the necessary information to operate, install and maintain theSurge Protective Device (SPD) used in the Flexi Power Rectifier (FPRB).

    Table 1 lists the contents of this manual:

    Table 1 Contents of this manual

    Chapter Title Content

    1 Product instruction Describes the specifications and properties of theSPD

    2 Preparation Describes the SPD installation preparations

    3 SPD installation Describes how to install and replace the SPD into theFPRB

    Terms and Symbols in this manual

    These term and symbols in Table 2 might appear in the manual:

    Table 2 Symbols in this manual

    Symbol Description

    Warning statement identifies conditions or practices that couldresult in bodily injury or loss of life.

    It warns the reader to be extremely careful.

    Caution statement identifies conditions or practices that couldresult in damage to this product or devices connect to it.

    It indicates that the reader must be careful.

    Provides hints to the user for easier installation

    The necessary supplementary of the article to let user be clearer.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 10 of 45

    Reference documents

    Table 3 contains the reference documents of the SPD:

    Table 3 Reference documents of the SPD

    DocumentArtesyn Embedded Technologies

    File No.

    Product Specification FPRB 970-009025-0000

    FPRB Installation Manual for SPD (This manual) 970-009473-0000

    FPRB User Manual 970-009474-0000

    FPRB Installation Manual 970-009475-0000

    FPRB Quick Start Guide for SPD 970-009476-0000

    FPRB Quick Start Guide 970-009477-0000

    Application of this manual

    This manual is regarded as a substitution of the part Make AC connection without the SPD(refer to section 3.4 of the Flexi Power Rectifier - Installation Manual, Artesyn File No. 970-009475-0000).

    This manual is based on the present SPD in use. Artesyn may change the SPD to a secondsource in future. However Artesyn ensures the compatibility of the new SPD in the FPRB.This manual supports all applications of the SPD that can be used in the FPRB.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 11 of 45

    Chapter 1 Product Introduction

    1.1 General Description

    The Flexi Power Rectifier (FPRX, Artesyn part number AA25020L/ CS7000013.XX for 6kWand AA27540L/ CS7000030.XX for 9kW) is a 6kW or 9kW output power AC rectifier packagerespectively. The Surge Protective Device (SPD, Artesyn part number AA25130L/CS7000002.XX) is used to prevent damage to the FPRX caused by high input voltages orsurge.

    The SPD consists of three equivalent OVP modules used between live cables and neutralcable from the AC mains; one OVP module used between the neutral cable from the ACmains and the earth; and one remote signaling contact.

    The SPDs mentioned in this manual are applicable for both 6kW and 9kW system. The SPDused is the same as the one we used in FPRA.

    1.2 Main Specification of the SPD

    The SPD illustrated in this manual is made by Phoenix Contact CO., Ltd (model number:VAL-MS 230IT/3+1-FM), or SICHUAN ZHONGGUANG LIGHTNING (model number:ZGG40-385(3+1)).

    L1 L2 L3 N

    11

    12 14

    FM

    VAL-MS 230 IT ST F-MS12 ST

    VAL-MS 230IT/3+1-FM

    Figure 1 Internal circuit diagram of the SPD

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 12 of 45

    The SPD (module name VAL-MS 230IT/3+1-FM) consists of three equivalent OVPmodules used between live cables and neutral cable from the AC mains (module nameVAL-MS 230 IT ST), one OVP module used between the neutral cable from the ACmains and the earth (module name F-MS 12 ST) and one remote signaling contact(module name VAL-MS 230IT-FM) (see Figure 1).

    The four OVP modules and the remote signaling contact are all installed on the SPD baseand can be removed from the base. This structure leads to easier configuration andreplacement of the OVP modules (seeFigure 2).

    Figure 2 Structure of the SPD

    VAL-MS230 IT ST

    F-MS12 ST

    Base

    VAL-MS230IT-FM Terminal

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 13 of 45

    Figure 3 and Figure 4 show the dimension of the SPD. The four OVP modules are of thesame dimensions.

    VAL-MS 230IT/3+1-FM

    ZGG40-385(3+1)

    Figure 3 Dimension of the SPD top view

    17.5m 17.5m70m

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 14 of 45

    VAL-MS 230IT/3+1-FM

    ZGG40-385(3+1)

    Figure 4 Dimension of the SPD side view

  • Installation Manual for SPD, Rev A

    Table 4 lists the main specifications of the OVP modules.

    Module name Parameter

    VAL-MS 230 ITST

    (OVP module forL-N)

    UN (L-N / L-L)

    UC (L-N)

    UP (L-N)

    In / Imax (8/20 S)

    Screw thread / torque

    F-MS 12 ST

    (OVP module forN-PE)

    UN (N-PE)

    UC (N-PE)

    UP (N-PE)

    In / Imax (8/20 S)

    Screw thread / torque

    VAL-MS 230IT-FM

    (Remotesignalingcontact)1

    Imax

    Screw thread / torque

    VAL-MS230IT/3+1-FM

    (The whole SPDmodule)

    Temperature

    IP-code

    Class II

    Type 2

    Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page

    lists the main specifications of the OVP modules.

    Table 4 Main specification of the SPD

    Specification Description

    230VAC / 400VAC Rated voltage

    385VAC Clamping voltage

    1.9kV Protective voltage

    (8/20 S) 20kA / 40kA Rated discharge current /maximum discharge current

    Screw thread / torque M5 / 4.5Nm

    230 VAC Rated voltage

    260VAC Clamping voltage

    1.0kV Protective voltage

    (8/20 S) 20kA / 40kA Rated discharge current /maximum discharge current

    Screw thread / torque M5 / 4.5Nm

    AC: 3A (125V)

    0.75A (250V)

    DC: 2A (30V)

    Screw thread / torque M2 / 0.25Nm

    -40C ~ +80C

    IP20 Ingress Protectiondegree

    IEC 61643-1: 2005-01

    EN 61643-11: 2002-12

    Flexi Power Rectifier FPRB

    Page 15 of 45

    Description

    Rated voltage

    Clamping voltage

    Protective voltage

    Rated discharge current /maximum discharge current

    Rated voltage

    Clamping voltage

    Protective voltage

    Rated discharge current /maximum discharge current

    Ingress Protection (IP)degree

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 16 of 45

    Note:

    1 Although the SPD remote signaling contact has three pins, only two are applied whenconfigured in the FPRB. Refer to Figure 13

    1.3 Properties

    Typical use

    Figure 5 shows the configuration of the SPD in a TN-S system.

    Figure 5 SPD configuration in a TN-S system

    Note:

    It is recommended to use the SPD with a mains utility offering the appropriate linefuse protection.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 17 of 45

    Failure Detection

    If any OVP module has been damaged, Artesyn will provide the user with the individual OVPmodule but not the whole SPD for replacement.

    In the event that any one of the four OVP modules is damaged, the PDA will send alarmsignal via the LCD.

    After opening the rear top cover of the PDA (refer to section 3.4 of the Flexi PowerRectifier Installation Manual, Artesyn File No. 970-009475-0000), the user can confirmwhich OVP module is in failure.

    Failure Indication

    If the window is transparent, the OVP is OK; if the window is red, the OVP is damagedand should be replaced in time (see Figure 6).

    Figure 6 Checking failure of the SPD

    Window

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 18 of 45

    Chapter 2 Preparation

    2.1 Installation tools

    Tool kit:

    Allen key (hex key): 8 mm (0.31 in.)

    Allen key (hex key): 4 mm

    Awl: diameter of 2mm

    ESD wrist strap and cable

    TORX screwdriver set: T10, T20, T25

    Flat screwdriver

    Cross screwdriver

    Wrench 13 mm (0.51 in.)

    Folding knife

    Adjustable (monkey) wrench

    Side cutters

    Lint-free swab or wipe and 99% alcohol for cleaning optical connectors

    Cable ties for routing cables

    Tape measure

    Flashlight, pocket lamp or torch

    Hammer drill

    Marker pen or comparable tool

    Pliers

    Wire-stripper

    Test equipment:

    Multi-meter

    2.2 Delivery contents

    The SPD is optional for the user and shipped independent from the FPRB.

    Verify that all the material listed in Table 5 has been received and is in good condition.Report any missing or damaged items to our Artesyn Embedded Technologies ServiceDepartment.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 19 of 45

    Table 5 Delivery contents of the SPD

    Part Figure Description Usage Artesyn

    Part Number

    Artesyn

    ModuleNumber

    SPD Surge Protective Device

    Manufacturer p/n:VAL-MS230IT/3+1-FM

    Manufacturer: PHOENIXCONTACT (SEA), PTE. LTD.

    1 pc 440-000700-0000

    AA25130L

    Surge Protective Device

    Manufacturer p/n: ZGG40-385(3+1)

    Manufacturer: SICHUANZHONGGUANG LIGHTNINGPROTECTION TECHNOLOGIESCO.,LTD.

    SPDJumper

    Short link for SPD terminals insingle-phase AC connection

    (Color of plastic may vary)

    1 each 502-000496-000X/

    500-001769-0000

    L lineshort link

    L1/L2/L3 for three phase,

    L for single phase (AWG10)

    1 750-000984-000X

    N lineshort link

    N for three phase star,

    N for single phase (10mm2)

    1 750-000983-000X

    SPDgroundlink

    SPD ground link to Chassis 1 750-000988-000X

    SPDsensecable

    SPD signal cable connecting tothe MCU

    1 750-001004-000X

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 20 of 45

    Chapter 3 SPD Installation

    3.1 Make AC connection with the SPD

    The AC power supply must be switched off prior to accessing the AC cable.

    This manual concentrates on the AC connection with the SPD, and omits the steps priorto the SPD installation, i.e. the AC terminal block configuration, etc. The user shouldrefer to Flexi Power Rectifier Installation Manual (Artesyn File No. 970-009475-0000)for the relevant previous steps.

    The colors of the AC mains wire used in this manual are for illustration purpose only.However, the user should verify the AC mains referring to the color-coding in therespective field or country of application.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 21 of 45

    3.1.1 Preparation

    3.1.1.1 Detach the PDA rear top cover referring to Flexi Power Rectifier InstallationManual (Artesyn File No. 970-009475-0000).

    3.1.1.2 Loosen screws A, B and C as per attached photo with a TORX screwdriver (T20)

    Figure 7 PDA rear internal chassis layout

    B

    C

    PDA earthcable

    AC groundclamp

    SPD groundclamp

    SPDDIN Rail

    ACterminalblock

    FSPD sensorconnection

    A

    Strain-relief

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 22 of 45

    3.1.1.3 Preparing the AC mains cable. The color of the wires may vary depending on thecountry where the SPD will be mounted.

    Table 6 Recommended preparation for AC mains cable

    (Tolerance: 3mm)

    AC type L1 L2 L3 N PE

    Single-phase

    (1)

    A (mm) 55 70 100

    B (mm) 20 20 20

    2-phase A (mm) 55 100 N/A

    B (mm) 20 20 N/A

    3-phase delta

    (3)

    A (mm) 55 60 70 N/A 100

    B (mm) 20 20 20 N/A 20

    3-phase star

    (3Y)

    A (mm) 55 60 70 85 100

    B (mm) 20 20 20 20 20

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 23 of 45

    Table 7 AC connection with the SPD

    AC type Terminals connection Short link available (1) AC terminal block

    Configuration (2)SPD configuration

    ACmains

    SPD AC terminalblock

    Chassis (3)

    1

    N/A L1 6 N/A L1 for three-phase Short terminals 1,2,3 and4,5,6 respectively

    Short terminals L1,L2, L3

    L L2 5 N/A L2 for three-phase

    N/A L3 4 N/A L3 for three-phase

    N N 2 N/A N for single phase

    PE N/A N/A AC ground clamp N/A

    N/A N/A SPD ground clamp SPD ground link

    2-Phase N/A L1 6 N/A L1 for three-phase Short terminals 1,2,3 and4,5,6 respectively

    Short terminals L1,L2, L3

    L1 L2 5 N/A L2 for three-phase

    N/A L3 4 N/A L3 for three-phase

    L2 N 2 N/A N for single phase

    N N/A N/A AC ground clamp N/A

    N/A N/A SPD ground clamp SPD ground link

    3YL1 L1 6 N/A L1 for three-phase Short terminals 1,2,3 N/A

    L2 L2 5 N/A L2 for three-phase

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 24 of 45

    L3 L3 4 N/A L3 for three-phase

    N N 2 N/A N for three-phase star

    PE N/A N/A AC ground clamp N/A

    N/A N/A SPD ground clamp SPD ground link

    3

    L1 L1 5 N/A L1 for three-phase Short terminals 1,2 and 3,4and 4,5 respectively

    N/A

    L2 L2 3 N/A L2 for three-phase

    L3 L3 1 N/A L3 for three-phase

    PE N/A N/A AC ground clamp

    N/A N N/A SPD ground clamp SPD ground link

    Note:

    (1) The short link names listed herein are in accordance with the actual labels on the short links.

    (2) The AC terminal block should be configured before the AC connection. User shall refer to section 3.4 in

    Flexi Power Rectifier Installation Manual (Artesyn file No.970-009475-0000) for more details

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 25 of 45

    (3) Refer to Table 3for the corresponding clamps.

    Table 8 Schematic diagram of AC connection with the SPD

    ACType

    Schematic diagram Configuration of ACterminal block

    3Y

    L1 L2 L3 N

    1 2 3 4 5 6SPD

    AC Terminal Block

    L1 L2PE

    AC Mains

    L3 N

    Short terminals 1,2,3

    1

    L1 L2 L3 N 1 2 3 4 5 6

    SPDAC Terminal Block

    L NPE

    AC mains

    Short terminals 1,2,3;4,5,6 respectively

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 26 of 45

    3

    L1 L2 L3 N

    1 2 3 4 5 6SPD

    AC Terminal Block

    L1 L2PE

    AC mains

    L3

    Short terminals 1,2; 3,4;5,6 respectively

    2-phase

    Short terminals 1,2,3;4,5,6 respectively

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 27 of 45

    3.1.2 Configure the Terminal Block

    Verify the AC power system types in field, and make sure the corresponding bridgeconfiguration is used.

    The AC terminal block has been already configured for 3-phase star AC mains beforethe shipment. Therefore the user has to change the AC terminal block configurationif required referring to the actual AC type in field.

    Insert the bridges and screws (provided as accessories) to the corresponding slots ontop of the AC terminal block referring to the AC CABLE CONNECTION CHART locatedon the chassis (and reproduced in Figure 8).

    Secure the screws with a flat screwdriver, tightening to 0.8Nm.

    Figure 8 The AC cable connection chart

    There are three AC power system types (see above Figure), and thus three ACconfigurations of the AC terminal block.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 28 of 45

    Single-phase (1) and Two-phase (2 ) configuration

    For Single- phase AC system, use two 3-pole bridges to short the terminals 1, 2,3 and 4, 5, 6 respectively on the AC terminal block (see Figure 9)

    Figure 9 AC terminal block configuration 1 and 2 Configuration

    3- phase delta (3) configuration

    For 3-phase delta AC system, use three 2-pole bridges to short the terminals 1, 2and 3, 4 and 5, 6 respectively on the AC terminal block (see Figure 10 )

    Figure 10 AC terminal block configuration 3

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 29 of 45

    3- phase star (3Y) configuration

    For 3-phase star AC system, use one 3-pole bridges to short the terminals 1, 2, 3on the AC terminal block (see Figure 11)

    Figure 11 AC terminal block configuration 3Y

    3.1.3 3-phase star (3Y) AC connection with the SPD

    L1 L2 L3 N

    1 2 3 4 5 6SPD

    AC Terminal Block

    L1 L2PE

    AC Mains

    L3 N

    Figure 12 Schematic diagram of AC connection with the SPD 3Y

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 30 of 45

    The terminal marks in Figure 12 are in accordance with the actual SPD and ACterminal block.

    Use the indicated L or N short link for the AC mains as shown in Figure 12 and Table7 referring to labels on the short links.

    The terminals 1, 2, 3 on the AC terminal block should be shorted before theconnection. Refer to section 3.4 in Flexi Power Rectifier Installation Manual(Artesyn file No.970-009475-0000) for details.

    3.1.3.1 Detach the cable strain-relief from the chassis by loosening the screw C inFigure 7 with a TORX screwdriver (T20). Insert the AC mains cable on thestrain relief.

    3.1.3.2 Detach the AC ground clamp and SPD ground clamp from the chassis byloosening the screws A and B with a TORX screwdriver (T20).

    3.1.3.3 Prepare the AC mains of 3-phase star as per Table 6.

    3.1.3.4 Assemble the Link cables, the AC mains cable, the SPD sensor cable and theSPD grounding cable into the SPD. Refer to Figure 13

    Figure 13 - Assemble the Link Cables to SPD

    L1 forthree-phase

    L2 forthree-phase

    L3 forthree-phase

    N forthree-phasestar SPD

    groundcable

    SPDsensecable

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 31 of 45

    Insert the connector of the SPD sense cable into the left two contacts; otherwise it willblock the SPD from installing onto the chassis.

    3.1.3.5 Fix the AC ground wire into the terminal lug.

    .

    Figure 14 - AC Ground wire

    3.1.3.6 Secure the SPD into the SPD DIN rail. Connect the SPD sense cable to thestand by mating connector. Connect the SPD grounding cable into theterminal lug. Refer to Figure 15.

    Figure 15 - Secure the SPD into the DIN rail

    SPDsensecable

    SPDGroundingcable

    SPD

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 32 of 45

    3.1.3.7 Connect the AC link cables from SPD to the Terminal Block. Assemble theSPD grounding cable and the AC grounding cable into the PDA

    Figure 16 - Connect the Link cables to Terminal Block

    1. Use the appropriate L and N short link referring to the label on the short linksand the indications in Figure 12 and Table 7.

    2. Rotate the N link cable 90 degrees either clockwise or counter clockwise whenassembling the SPD on the FPRA due to the smaller slot of the terminal block.Refer to Figure 17 - Special Instruction for N Link Cable Installation

    SPDgroundingcable lug

    ACgroundingcable lug

    N linkcable

    L3 linkcableL2 linkcable

    L1 linkcable

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 33 of 45

    Figure 17 - Special Instruction for N Link Cable Installation

    It is recommended to clamp the AC wire and the corresponding short link with oneoverlapping on another.

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 34 of 45

    Below figure shows the PDA rear layout after completing the 3-phase star ACconnection with the SPD.

    Figure 18 AC connection with the SPD - 3Y

    3.1.3.8 After finishing and checking the AC cable installation, re-install the PDA rearcover referring to Flexi Power Rectifier Installation Manual (Artesyn FileNo. 970-009475-0000).

    After installation of the SPD kit has been completed, the installer should check theinstallation against the steps outlined within this document, supported by a multi-meter to check for wiring continuity.

    Its strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.

    L1 short link

    L2 short link

    L3 short link

    N short link

    SPD sense cable

    L2

    L3

    L1

    SPD groundcable

    N

    PE of ACmains

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 35 of 45

    3.1.4 Single-phase (1) AC connection with the SPD

    L1 L2 L3 N 1 2 3 4 5 6

    SPDAC Terminal Block

    L NPE

    AC mains

    Figure 19 Schematic diagram of AC connection with the SPD 1

    The terminal marks in Figure 19 are in accordance with the actual SPD and ACterminal block.

    Use the indicated L or N short link for the AC mains as shown in Figure 19 and Table7 referring to labels on the short links.

    The terminals 1,2,3 and 4,5,6 on the AC terminal block should be shortedrespectively before the connection. Refer to section 3.4 in Flexi Power Rectifier Installation Manual (Artesyn file No.970-009475-0000) for details.

    3.1.4.1 Perform the same procedure in preparing the AC cables SPD grounding cablesand the SPD sense cables.

    3.1.4.2 As indicated in Figure 19 and Table 7, the SPD terminals L1, L2 and L3 have to beparalleled by the SPD jumper (see Figure 20).

    L1 for three-phase

    L2 for three-phase

    L3 for three-phase

    N for single phase

    AC groundclamp

    SPD groundclamp

    SPD ground link

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 36 of 45

    The user should loosen the three terminal clamps of L1, L2 and L3, and hold the SPDupside down. Thus the SPD jumper can be easily inserted into the parallel clamps.

    The jumper should be fixed in the SPD together with the live cables of the AC mainsand L line short links.

    Figure 20 SPD configuration for single-phase AC connection

    3.1.4.3 Connect the live cable from the AC mains and L2 short link into terminal L2 onthe SPD referring to Figure 19 and Table 7, tightening the top screw to 4.5Nmwith a cross screwdriver (see Figure 21).

    SPD jumper

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 37 of 45

    Figure 21 - Connection of AC link cables from SPD to Terminal Block

    3.1.4.4 After finishing and checking the AC cable installation, re-install the PDA rearcover referring to section 3.4 in Flexi Power Rectifier Installation Manual(Artesyn File No. 970-009475-0000).

    L1 forthree-phase

    L2 forthree-phase

    L3 forthree-phase

    N for singlephase

    AC groundclamp

    SPD groundclamp

    SPDgroundlink

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 38 of 45

    3.1.5 2-phase AC connection with the SPD

    Figure 22 Schematic diagram of AC connection with the SPD 2- Phase

    3.1.5.1 Perform the same procedure in preparing the AC cables SPD grounding cablesand the SPD sense cables

    3.1.5.2 As indicated in Figure 19 and Table 7, the SPD terminals L1, L2 and L3 have to beparalleled by the SPD jumper (see Figure 20).

    L1 for three-phase

    L2 for three-phase

    L3 for three-phaseAC groundclamp

    SPD groundclamp

    SPD ground link

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 39 of 45

    3.1.5.3 Connect the AC link cables and the AC cables to the SPD and to terminal block.Refer to Figure 23)

    Figure 23 - AC connection with the SPD 2- Phase

    3.1.5.4 After finishing and checking the AC cable installation, re-install the PDA rearcover referring to section 3.4 in Flexi Power Rectifier Installation Manual(Artesyn File No. 970-009475-0000).

    After installation of the SPD kit has been completed, the installer should check theinstallation against the steps outlined within this document, supported by a multi-meter to check for wiring continuity.

    Its strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.

    Use DMM to measure L1-L2 voltage

    Ensure L1-L2 voltage between 180VAC-276VAC

    L1 forthree-phase

    L2 forthree-phase

    L3 forthree-phase

    N for singlephase

    AC groundclamp

    SPD groundclamp

    SPDgroundlink

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 40 of 45

    The terminal marks in Figure 22 are in accordance with the actual SPD and ACterminal block.

    Refer to Single-phase (1) AC connection for details.

    3.1.6 3-phase delta (3) AC connection with the SPD

    L1 L2 L3 N

    1 2 3 4 5 6SPD

    AC Terminal Block

    L1 L2PE

    AC mains

    L3

    Figure 24 Schematic diagram of AC connection with the SPD 3

    The terminal marks in Figure 24 are in accordance with the actual SPD and ACterminal block.

    Use the indicated L or N short link for the AC mains as shown in Figure 24 and Table7 referring to labels on the short links.

    The terminals 1,2 and 3,4 and 5,6 on the AC terminal block should be shortedrespectively before the connection. Refer to section 3.4 in Flexi Power Rectifier Installation Manual (Artesyn file No.970-009475-0000) for details.

    L1 for three-phase

    L2 for three-phase

    L3 for three-phase

    SPD ground link

    AC groundclamp

    SPD groundclamp

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 41 of 45

    3.1.6.1 Perform the same procedure in preparing the AC cables SPD grounding cablesand the SPD sense cables

    3.1.6.2 Configure the terminal block as per Figure 10

    3.1.6.3 Assemble the AC cables, AC link cables into the SPD.

    3.1.6.4 Assemble the AC link cables into the Terminal Block.

    Figure 25 - Connection of AC link cables and SPD ground cables

    SPDgroundingcableconnected toN terminal ofthe SPD.

    N connectedto Ground

  • Installation Manual for SPD, Rev A

    3.1.6.5 Connect the L1, L2 and L3 short links to terminals 5, 3, 1 on the AC terminalblock respectively referring toto 1.5Nm with a Cross screwdriver (see

    Figure 26

    SPDSenseCable

    SPDgroundlink

    Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page

    Connect the L1, L2 and L3 short links to terminals 5, 3, 1 on the AC terminalblock respectively referring to Figure 24 and Table 7, tightening the top screwsto 1.5Nm with a Cross screwdriver (see Figure 26).

    26 Connecting the AC terminal block 3

    Flexi Power Rectifier FPRB

    Page 42 of 45

    Connect the L1, L2 and L3 short links to terminals 5, 3, 1 on the AC terminal, tightening the top screws

    L1shortlink

    L2shortlink

    L3shortlink

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 43 of 45

    3.1.6.6 Figure 27 shows the PDA rear internal layout after completing the 3-phase deltaAC connection with the SPD.

    Figure 27 3-phase delta (3) AC connection with the SPD

    3.1.6.7 After finishing and checking the AC cable installation, replace the PDA rear coverreferring to section 3.4 in Flexi Power Rectifier Installation Manual (ArtesynFile No. 970-009475-0000).

    After installation of the SPD kit has been completed, the installer should check theinstallation against the steps outlined within this document, supported by a multi-meter to check for wiring continuity.

    Its strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.

    L1 forthree-phase

    L2 forthree-phase

    L3 forthree-phase

    AC groundclamp

    SPD groundclamp

    SPDgroundlink

  • Installation Manual for SPD, Rev A

    3.2 Replace the SPD

    The AC power supply must be switched off prior to accessing the SPD.

    Ask Artesyn Embedded Technologiesbeen damaged. Artesynnot the whole SPD for replacement.

    The user shall only replace thethe whole SPD from the PDA chassis.

    The user can verify which OVP module has been damaged Referring to sectionProperties.

    3.2.1 Hold the two sides of the damaged OVP module and pulbase (see Figure

    Figure 28 Removing the damaged OVP module from the SPD

    Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page

    The AC power supply must be switched off prior to accessing the SPD.

    Artesyn Embedded Technologies service people for help if any OVP module hasArtesyn will provide the user with the individual OVP module but

    not the whole SPD for replacement.

    The user shall only replace the damaged OVP module of the SPD without removingthe whole SPD from the PDA chassis.

    The user can verify which OVP module has been damaged Referring to section

    Hold the two sides of the damaged OVP module and pull it out from the SPDFigure 28)

    Removing the damaged OVP module from the SPD

    Flexi Power Rectifier FPRB

    Page 44 of 45

    service people for help if any OVP module haswill provide the user with the individual OVP module but

    damaged OVP module of the SPD without removing

    The user can verify which OVP module has been damaged Referring to section

    l it out from the SPD

    Removing the damaged OVP module from the SPD

  • Flexi Power Rectifier FPRB

    Installation Manual for SPD, Rev AC Page 45 of 45

    3.2.2 The SPD base is designed such that the two kinds of OVP modules cannot bemixed when installing onto it (see Figure 29).

    Figure 29 The OVP module and the SPD base

    3.2.3 Fit the new module into its position on the SPD base (see Figure 30).

    Figure 30 Fitting a new OVP module to the SPD