FOOTING DESIGN FOR HEALTH CLUB STRUCTURAL DESIGN CALCULATION Submitted Date April 26, 2012
Oct 27, 2014
FOOTING DESIGN
FOR HEALTH CLUB
STRUCTURAL DESIGN CALCULATION
Submitted Date April 26, 2012
Table of Contents Page No.
1. Design of Footing F1 3
2. Design of Footing F2 13
3. Design of Footing F3 20
4. Design of Footing F4 27
5. Design of Grade Beam GB1 39
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Column Base Design : CORNER COLUMN C15
Input Data
Base length A (m)Base width B (m)Column(s)
C (m)D (m)E (m)F (m)Stub column height X (m)Base depth Y (m)Soil cover Z (m)Concrete density (kN/m3)Soil density (kN/m3)Soil friction angle (°)Base friction constantRebar depth top X (mm)Rebar depth top Y (mm)Rebar depth bottom X (mm)Rebar depth bottom Y (mm)ULS ovt. LF: Self weight
ULS LF: Self weightMax. SLS bearing pr. (kN/m²)S.F. Overturning (ULS)S.F. Slip (ULS)
fcu base (MPa)fcu columns (MPa)fy (MPa)
4.53.5
Col 1 Col 2
.7
.5
1.5.81.3525
18220.575
7575750.9
1.425011
3030460
Unfactored Loads
Load Case
Colno.
LFULSovt
LFULS
P(kN)
Hx(kN)
Hy(kN)
Mx(kNm)
My(kNm)
1 1 1.5 1.4 225 171 1 1.5 1.4 114 156 1 1.5 1.6 272 374
2 1 1.5 1.4 225 171 1 1.5 1.4 114 156 1 1.5 1.4 -219 -244
3 1 1.5 1.4 225 171 1 1.5 1.4 114 156 1 1.5 1.4 -196 -234
4 1 1.5 1.4 225 171 1 1.5 1.4 114 156 1 1.5 1.4 -253 -302
5 1 1.5 1.2 225 171 1 1.5 1.2 114 156 1 1.5 1.2 272 374
1 1.5 1.2 -219 -244 6 1 1.5 1.2 225 171 1 1.5 1.2 114 156 1 1.5 1.2 272 374 1 1.5 1.2 -196 -234 7 1 1.5 1.2 225 171
1 1.5 1.2 114 156 1 1.5 1.2 272 374 1 1.5 1.2 -253 -302
3 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
A
X
Y
Y
BC1
D1
PMx
Z
Hx
Y
X
BS8110 - 1997
Sketch of Base
Output for Load Case 1
Output for Load Case 1Soil pressure (ULS) (kN/m²) 372.98Soil pressure (SLS) (kN/m²) 244.69
SF overturning (SLS) 1.83SF overturning (ULS) 1.44Safety Factor slip (ULS) 1.08Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 414.11Reinforcement X (mm²/m) 1372Design moment Y (kNm/m) 65.41
Reinforcement Y (mm²/m) 217Top
Design moment X (kNm/m) -111.35Reinforcement X (mm²/m) 369
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.380vc (MPa) 0.386
Linear Shear Y (MPa) 0.062vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.289vc (MPa) 0.376Cost 6652.42
4 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
244.69 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
372.98 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:1
BS8110 - 1997
Output for Load Case 2
Output for Load Case 2Soil pressure (ULS) (kN/m²) 95.72Soil pressure (SLS) (kN/m²) 68.37
SF overturning (SLS) 9.69SF overturning (ULS) 6.38Safety Factor slip (ULS) 6.62Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 49.32Reinforcement X (mm²/m) 163Design moment Y (kNm/m) 12.46
Reinforcement Y (mm²/m) 41Top
Design moment X (kNm/m) -9.33Reinforcement X (mm²/m) 31
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.045vc (MPa) 0.357
Linear Shear Y (MPa) 0.012vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.033
vc (MPa) 0.357Cost 5796.56
5 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
68.37 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
95.72 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:2
BS8110 - 1997
Output for Load Case 3
Output for Load Case 3Soil pressure (ULS) (kN/m²) 100.49Soil pressure (SLS) (kN/m²) 71.78
SF overturning (SLS) 8.89SF overturning (ULS) 5.94Safety Factor slip (ULS) 6.03Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 56.54Reinforcement X (mm²/m) 187Design moment Y (kNm/m) 14.76
Reinforcement Y (mm²/m) 49Top
Design moment X (kNm/m) -9.17Reinforcement X (mm²/m) 30
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.051vc (MPa) 0.357
Linear Shear Y (MPa) 0.014vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.038
vc (MPa) 0.357Cost 5816.07
6 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
71.78 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
100.49 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:3
BS8110 - 1997
Output for Load Case 4
Output for Load Case 4Soil pressure (ULS) (kN/m²) 76.89Soil pressure (SLS) (kN/m²) 54.92
SF overturning (SLS) 30.85SF overturning (ULS) 19.86Safety Factor slip (ULS) 21.31Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 23.37Reinforcement X (mm²/m) 77Design moment Y (kNm/m) 9.06
Reinforcement Y (mm²/m) 30Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.021vc (MPa) 0.357
Linear Shear Y (MPa) 0.009vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.015
vc (MPa) 0.357Cost 5736.44
7 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
54.92 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
76.89 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:4
BS8110 - 1997
Output for Load Case 5
Output for Load Case 5Soil pressure (ULS) (kN/m²) 200.31Soil pressure (SLS) (kN/m²) 161.65
SF overturning (SLS) 2.34SF overturning (ULS) 1.74Safety Factor slip (ULS) 1.68Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 194.33Reinforcement X (mm²/m) 644Design moment Y (kNm/m) 34.05
Reinforcement Y (mm²/m) 113Top
Design moment X (kNm/m) -82.09Reinforcement X (mm²/m) 272
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.178vc (MPa) 0.357
Linear Shear Y (MPa) 0.032vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.133
vc (MPa) 0.357Cost 6137.89
8 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
161.65 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
200.31 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:5
BS8110 - 1997
Output for Load Case 6
Output for Load Case 6Soil pressure (ULS) (kN/m²) 204.48Soil pressure (SLS) (kN/m²) 165.15
SF overturning (SLS) 2.34SF overturning (ULS) 1.75Safety Factor slip (ULS) 1.67Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 200.60Reinforcement X (mm²/m) 665Design moment Y (kNm/m) 36.02
Reinforcement Y (mm²/m) 119Top
Design moment X (kNm/m) -81.85Reinforcement X (mm²/m) 271
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.183vc (MPa) 0.357
Linear Shear Y (MPa) 0.034vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.137
vc (MPa) 0.357Cost 6154.78
9 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
165.15 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
204.48 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:6
BS8110 - 1997
Output for Load Case 7
Output for Load Case 7Soil pressure (ULS) (kN/m²) 183.00Soil pressure (SLS) (kN/m²) 145.88
SF overturning (SLS) 2.60SF overturning (ULS) 1.91Safety Factor slip (ULS) 1.88Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 170.90Reinforcement X (mm²/m) 566Design moment Y (kNm/m) 31.14
Reinforcement Y (mm²/m) 103Top
Design moment X (kNm/m) -70.78Reinforcement X (mm²/m) 235
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.156vc (MPa) 0.357
Linear Shear Y (MPa) 0.029vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.116
vc (MPa) 0.357Cost 6083.92
10 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
145.88 kN/m²
4.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.3
5
Hx
0.80
1.50
183.00 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:7
BS8110 - 1997
11 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Schematic reinforcement of Base
23Y25-B-200 (B2)
18Y25-A-200 (B1)
23Y20-D-200 ABR (T2)
18Y20-C-200 ABR (T1)
col1
PLAN
SECTION
B B B B B B B B B B B B B B B B B B B B B B B
3R10-H
R10-H
6Y32-G6Y32-F +4Y32-E +
E
E
E
E
F FF FF F
G
G
G
G
G
G
SECTION: col1
12 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Column Base Design : CORNER COLUMN-F2 C15
Input Data
Base length A (m)Base width B (m)Column(s)
C (m)D (m)E (m)F (m)Stub column height X (m)Base depth Y (m)Soil cover Z (m)Concrete density (kN/m3)Soil density (kN/m3)Soil friction angle (°)Base friction constantRebar depth top X (mm)Rebar depth top Y (mm)Rebar depth bottom X (mm)Rebar depth bottom Y (mm)ULS ovt. LF: Self weight
ULS LF: Self weightMax. SLS bearing pr. (kN/m²)S.F. Overturning (ULS)S.F. Slip (ULS)
fcu base (MPa)fcu columns (MPa)fy (MPa)
3.63
Col 1 Col 2
.7
.5
1.2.71.0525
18220.575
7575750.9
1.425011
3030460
Unfactored Loads
Load Case
Colno.
LFULSovt
LFULS
P(kN)
Hx(kN)
Hy(kN)
Mx(kNm)
My(kNm)
1 1 1.5 1.4 200 116 1 1.5 1.4 95 102 1 1.5 1.6 228 243
2 1 1.5 1.4 200 116 1 1.5 1.4 95 102 1 1.5 1.4 -246 -244
3 1 1.5 1.4 200 116 1 1.5 1.4 95 102 1 1.5 1.4 -109 -127
4 1 1.5 1.2 200 116 1 1.5 1.2 95 102 1 1.5 1.2 228 243
1 1.5 1.2 -246 -244 5 1 1.5 1.2 200 116 1 1.5 1.2 95 102
1 1.5 1.2 228 243 1 1.5 1.2 -109 -127
A
X
Y
Y
B
C1
D1
PMx
Z
Hx
Y
X
BS8110 - 1997
Sketch of Base
13 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 1
Output for Load Case 1Soil pressure (ULS) (kN/m²) 365.31Soil pressure (SLS) (kN/m²) 241.11
SF overturning (SLS) 1.89SF overturning (ULS) 1.56Safety Factor slip (ULS) 1.13Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 254.09Reinforcement X (mm²/m) 977Design moment Y (kNm/m) 56.65
Reinforcement Y (mm²/m) 218Top
Design moment X (kNm/m) -52.99Reinforcement X (mm²/m) 204Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.323vc (MPa) 0.362
Linear Shear Y (MPa) 0.070vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.223
vc (MPa) 0.360Cost 3908.40
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
241.11 kN/m²
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
365.31 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:1
BS8110 - 1997
14 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 2
Output for Load Case 2Soil pressure (ULS) (kN/m²) 68.49Soil pressure (SLS) (kN/m²) 48.92
SF overturning (SLS) 16.25SF overturning (ULS) 10.46Safety Factor slip (ULS) 11.77Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 15.41Reinforcement X (mm²/m) 59Design moment Y (kNm/m) 5.36
Reinforcement Y (mm²/m) 21Top
Design moment X (kNm/m) -1.00Reinforcement X (mm²/m) 4
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.019vc (MPa) 0.357
Linear Shear Y (MPa) 0.007vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.011
vc (MPa) 0.357Cost 3435.84
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
48.92 kN/m²
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
68.49 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:2
BS8110 - 1997
15 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 3
Output for Load Case 3Soil pressure (ULS) (kN/m²) 112.92Soil pressure (SLS) (kN/m²) 80.66
SF overturning (SLS) 6.07SF overturning (ULS) 4.42Safety Factor slip (ULS) 4.12Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 54.58Reinforcement X (mm²/m) 210Design moment Y (kNm/m) 19.23
Reinforcement Y (mm²/m) 74Top
Design moment X (kNm/m) -2.83Reinforcement X (mm²/m) 11
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.068vc (MPa) 0.357
Linear Shear Y (MPa) 0.024vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.046
vc (MPa) 0.357Cost 3522.28
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
80.66 kN/m²
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
112.92 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:3
BS8110 - 1997
16 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 4
Output for Load Case 4Soil pressure (ULS) (kN/m²) 158.58Soil pressure (SLS) (kN/m²) 126.05
SF overturning (SLS) 2.94SF overturning (ULS) 2.25Safety Factor slip (ULS) 2.15Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 91.56Reinforcement X (mm²/m) 352Design moment Y (kNm/m) 24.44
Reinforcement Y (mm²/m) 94Top
Design moment X (kNm/m) -25.79Reinforcement X (mm²/m) 99
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.115vc (MPa) 0.357
Linear Shear Y (MPa) 0.030vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.078
vc (MPa) 0.357Cost 3591.03
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
126.05 kN/m²
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
158.58 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:4
BS8110 - 1997
17 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 5
Output for Load Case 5Soil pressure (ULS) (kN/m²) 217.28Soil pressure (SLS) (kN/m²) 177.12
SF overturning (SLS) 2.30SF overturning (ULS) 1.85Safety Factor slip (ULS) 1.60Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 140.62Reinforcement X (mm²/m) 541Design moment Y (kNm/m) 36.33
Reinforcement Y (mm²/m) 140Top
Design moment X (kNm/m) -39.44Reinforcement X (mm²/m) 152
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.177vc (MPa) 0.357
Linear Shear Y (MPa) 0.045vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.120
vc (MPa) 0.357Cost 3690.36
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
177.12 kN/m²
3.60
X
Y
Y
3.0
0
0.70
0.50
PMx
1.0
5
Hx
0.70
1.20
217.28 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:5
BS8110 - 1997
18 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Schematic reinforcement of Base
19Y20-B-200 (B2)
15Y20-A-200 (B1)
19Y20-D-200 ABR (T2)
15Y20-C-200 ABR (T1)
col1
PLAN
SECTION
B B B B B B B B B B B B B B B B B B
3R10-H
R10-H
2Y25-G2Y32-F +4Y32-E +
E
E
E
E
F F
G
G
SECTION: col1
19 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Column Base Design : CORNER COLUMN-F3 C15
Input Data
Base length A (m)Base width B (m)Column(s)
C (m)D (m)E (m)F (m)Stub column height X (m)Base depth Y (m)Soil cover Z (m)Concrete density (kN/m3)Soil density (kN/m3)Soil friction angle (°)Base friction constantRebar depth top X (mm)Rebar depth top Y (mm)Rebar depth bottom X (mm)Rebar depth bottom Y (mm)ULS ovt. LF: Self weight
ULS LF: Self weightMax. SLS bearing pr. (kN/m²)S.F. Overturning (ULS)S.F. Slip (ULS)
fcu base (MPa)fcu columns (MPa)fy (MPa)
1.71.5
Col 1 Col 2
.7
.5
1.2.41.0525
18220.575
7575750.9
1.425011
3030460
Unfactored Loads
Load Case
Colno.
LFULSovt
LFULS
P(kN)
Hx(kN)
Hy(kN)
Mx(kNm)
My(kNm)
1 1 1.5 1.4 95 4 1 1.5 1.4 18 6 1 1.5 1.6 43 13
2 1 1.5 1.4 95 4 1 1.5 1.4 18 6 1 1.5 1.4 -48 -21
3 1 1.5 1.4 95 4 1 1.5 1.4 18 6 1 1.5 1.4 -56 -6
4 1 1.5 1.2 95 4 1 1.5 1.2 18 6 1 1.5 1.2 43 13
1 1.5 1.2 -48 -21 5 1 1.5 1.2 15 4 1 1.5 1.2 18 6
1 1.5 1.2 43 13 1 1.5 1.2 -56 -6
A
X
Y
Y
B
C1
D1
PMx
Z
Hx
Y
X
BS8110 - 1997
Sketch of Base
20 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 1
Output for Load Case 1Soil pressure (ULS) (kN/m²) 208.66Soil pressure (SLS) (kN/m²) 142.52
SF overturning (SLS) 5.40SF overturning (ULS) 4.68Safety Factor slip (ULS) 5.67Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 19.13Reinforcement X (mm²/m) 141Design moment Y (kNm/m) 11.39
Reinforcement Y (mm²/m) 84Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.084vc (MPa) 0.376
Linear Shear Y (MPa) 0.050vc (MPa) 0.376Linear Shear Other (MPa) 0.000Punching Shear (MPa) N.A.
vc (MPa) N.A.Cost 481.58
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
142.52 kN/m²
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
208.66 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:1
BS8110 - 1997
21 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 2
Output for Load Case 2Soil pressure (ULS) (kN/m²) 112.38Soil pressure (SLS) (kN/m²) 80.27
SF overturning (SLS) 6.89SF overturning (ULS) 5.39Safety Factor slip (ULS) 8.41Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 8.15Reinforcement X (mm²/m) 60Design moment Y (kNm/m) 4.73
Reinforcement Y (mm²/m) 35Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.036vc (MPa) 0.376
Linear Shear Y (MPa) 0.021vc (MPa) 0.376Linear Shear Other (MPa) 0.000Punching Shear (MPa) N.A.
vc (MPa) N.A.Cost 468.53
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
80.27 kN/m²
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
112.38 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:2
BS8110 - 1997
22 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 3
Output for Load Case 3Soil pressure (ULS) (kN/m²) 86.29Soil pressure (SLS) (kN/m²) 61.63
SF overturning (SLS) 17.87SF overturning (ULS) 13.75Safety Factor slip (ULS) 22.12Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 5.42Reinforcement X (mm²/m) 40Design moment Y (kNm/m) 4.18
Reinforcement Y (mm²/m) 31Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.023vc (MPa) 0.376
Linear Shear Y (MPa) 0.019vc (MPa) 0.376Linear Shear Other (MPa) 0.000Punching Shear (MPa) N.A.
vc (MPa) N.A.Cost 466.10
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
61.63 kN/m²
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
86.29 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:3
BS8110 - 1997
23 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 4
Output for Load Case 4Soil pressure (ULS) (kN/m²) 98.73Soil pressure (SLS) (kN/m²) 77.20
SF overturning (SLS) 49.29SF overturning (ULS) 41.05Safety Factor slip (ULS) 61.99Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 7.15Reinforcement X (mm²/m) 53Design moment Y (kNm/m) 6.62
Reinforcement Y (mm²/m) 49Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.030vc (MPa) 0.376
Linear Shear Y (MPa) 0.029vc (MPa) 0.376Linear Shear Other (MPa) 0.000Punching Shear (MPa) N.A.
vc (MPa) N.A.Cost 469.19
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
77.20 kN/m²
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
98.73 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:4
BS8110 - 1997
24 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Output for Load Case 5
Output for Load Case 5Soil pressure (ULS) (kN/m²) 97.17Soil pressure (SLS) (kN/m²) 75.91
SF overturning (SLS) 3.05SF overturning (ULS) 2.08Safety Factor slip (ULS) 4.70Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 5.98Reinforcement X (mm²/m) 44Design moment Y (kNm/m) 1.44
Reinforcement Y (mm²/m) 11Top
Design moment X (kNm/m) -3.09Reinforcement X (mm²/m) 23
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.027vc (MPa) 0.376
Linear Shear Y (MPa) 0.006vc (MPa) 0.376Linear Shear Other (MPa) 0.000Punching Shear (MPa) N.A.
vc (MPa) N.A.Cost 464.49
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
75.91 kN/m²
1.70
X
Y
Y
1.5
0
0.70
0.50
PMx
1.0
5
Hx
0.40
1.20
97.17 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:5
BS8110 - 1997
25 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Schematic reinforcement of Base
9Y16-B-200 (B2)
8Y16-A-200 (B1)
9Y16-D-200 ABR (T2)
8Y16-C-200 ABR (T1)
col1
PLAN
SECTION
B B B B B B B B B
3R10-H
R10-H
2Y20-G2Y20-F +4Y20-E +
E
E
E
E
F F
G
G
SECTION: col1
26 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Column Base Design : CORNER COLUMN-F4 C15
Input Data
Base length A (m)Base width B (m)Column(s)
C (m)D (m)E (m)F (m)Stub column height X (m)Base depth Y (m)Soil cover Z (m)Concrete density (kN/m3)Soil density (kN/m3)Soil friction angle (°)Base friction constantRebar depth top X (mm)Rebar depth top Y (mm)Rebar depth bottom X (mm)Rebar depth bottom Y (mm)ULS ovt. LF: Self weight
ULS LF: Self weightMax. SLS bearing pr. (kN/m²)S.F. Overturning (ULS)S.F. Slip (ULS)
fcu base (MPa)fcu columns (MPa)fy (MPa)
3.503.50
Col 1 Col 2
.7
.5
1.20.501.0525
18220.575
7575750.9
1.425011
3030460
Unfactored Loads
Load Case
Colno.
LFULSovt
LFULS
P(kN)
Hx(kN)
Hy(kN)
Mx(kNm)
My(kNm)
1 1 1.5 1.4 120 24 1 1.5 1.4 44 28 1 1.5 1.6 105 66
2 1 1.5 1.4 120 24 1 1.5 1.4 44 28 1 1.5 1.4 -122 -84
3 1 1.5 1.4 120 24 1 1.5 1.4 44 28 1 1.5 1.4 -129 -68
4 1 1.5 1.2 120 24 1 1.5 1.2 44 28 1 1.5 1.2 105 66
1 1.5 1.2 -122 -84 5 1 1.5 1.2 120 24 1 1.5 1.2 44 28
1 1.5 1.2 105 66 1 1.5 1.2 -129 -68 6 1 1.5 1.4 120 24 1 1.5 1.4 44 28 1 1.5 1.4 -207 -179 95 7 1 1.5 1.4 120 24
1 1.5 1.4 44 28 1 1.5 1.4 -214 -163 95 8 1 1.5 1.2 120 24 1 1.5 1.2 44 28 1 1.5 1.2 105 66 1 1.5 1.2 -207 -179 -95
9 1 1.5 1.2 120 24 1 1.5 1.2 44 28 1 1.5 1.2 105 66 1 1.5 1.2 -214 -163 -95
27 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
A
X
Y
Y
B
C1
D1
PMx
Z
Hx
Y
X
BS8110 - 1997
Sketch of Base
Output for Load Case 1
Output for Load Case 1Soil pressure (ULS) (kN/m²) 119.29Soil pressure (SLS) (kN/m²) 81.74
SF overturning (SLS) 5.74SF overturning (ULS) 4.38Safety Factor slip (ULS) 3.14Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 62.72Reinforcement X (mm²/m) 355Design moment Y (kNm/m) 37.00
Reinforcement Y (mm²/m) 209Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.146vc (MPa) 0.357
Linear Shear Y (MPa) 0.081vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.120vc (MPa) 0.357Cost 3027.33
28 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
81.74 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
119.29 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:1
BS8110 - 1997
Output for Load Case 2
Output for Load Case 2Soil pressure (ULS) (kN/m²) 59.86Soil pressure (SLS) (kN/m²) 42.76
SF overturning (SLS) 13.85SF overturning (ULS) 8.85Safety Factor slip (ULS) 8.74Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 12.79Reinforcement X (mm²/m) 72Design moment Y (kNm/m) 5.90
Reinforcement Y (mm²/m) 33Top
Design moment X (kNm/m) -2.52Reinforcement X (mm²/m) 14
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.030vc (MPa) 0.357
Linear Shear Y (MPa) 0.013vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.023
vc (MPa) 0.357Cost 2807.06
29 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
42.76 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
59.86 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:2
BS8110 - 1997
Output for Load Case 3
Output for Load Case 3Soil pressure (ULS) (kN/m²) 53.73Soil pressure (SLS) (kN/m²) 38.38
SF overturning (SLS) 27.25SF overturning (ULS) 17.25Safety Factor slip (ULS) 17.25Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 8.18Reinforcement X (mm²/m) 46Design moment Y (kNm/m) 5.00
Reinforcement Y (mm²/m) 28Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.019vc (MPa) 0.357
Linear Shear Y (MPa) 0.011vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.014
vc (MPa) 0.357Cost 2792.08
30 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
38.38 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
53.73 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:3
BS8110 - 1997
Output for Load Case 4
Output for Load Case 4Soil pressure (ULS) (kN/m²) 68.51Soil pressure (SLS) (kN/m²) 51.80
SF overturning (SLS) 16.21SF overturning (ULS) 11.51Safety Factor slip (ULS) 11.03Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 21.52Reinforcement X (mm²/m) 122Design moment Y (kNm/m) 16.69
Reinforcement Y (mm²/m) 94Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.050vc (MPa) 0.357
Linear Shear Y (MPa) 0.037vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.041
vc (MPa) 0.357Cost 2860.12
31 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
51.80 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
68.51 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:4
BS8110 - 1997
Output for Load Case 5
Output for Load Case 5Soil pressure (ULS) (kN/m²) 72.39Soil pressure (SLS) (kN/m²) 55.04
SF overturning (SLS) 10.88SF overturning (ULS) 7.68Safety Factor slip (ULS) 7.43Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 24.13Reinforcement X (mm²/m) 136Design moment Y (kNm/m) 15.92
Reinforcement Y (mm²/m) 90Top
Design moment X (kNm/m) 0.00Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) 0.00Reinforcement Y (mm²/m) 0Linear Shear X (MPa) 0.056vc (MPa) 0.357
Linear Shear Y (MPa) 0.035vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.046
vc (MPa) 0.357Cost 2865.11
32 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
55.04 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
72.39 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:5
BS8110 - 1997
Output for Load Case 6
Output for Load Case 6Soil pressure (ULS) (kN/m²) 122.76Soil pressure (SLS) (kN/m²) 87.69
SF overturning (SLS) 2.24SF overturning (ULS) 1.23Safety Factor slip (ULS) 1.66Safety Factor uplift (ULS) 5.42
Bottom Design moment X (kNm/m) 31.27Reinforcement X (mm²/m) 177Design moment Y (kNm/m) 25.56
Reinforcement Y (mm²/m) 145Top
Design moment X (kNm/m) -29.62Reinforcement X (mm²/m) 167
Design moment Y (kNm/m) -24.58Reinforcement Y (mm²/m) 139Linear Shear X (MPa) 0.072vc (MPa) 0.357
Linear Shear Y (MPa) 0.055vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.058
vc (MPa) 0.357Cost 2910.75
33 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
87.69 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
122.76 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:6
BS8110 - 1997
Output for Load Case 7
Output for Load Case 7Soil pressure (ULS) (kN/m²) 114.04Soil pressure (SLS) (kN/m²) 81.46
SF overturning (SLS) 2.39SF overturning (ULS) 1.29Safety Factor slip (ULS) 1.78Safety Factor uplift (ULS) 4.66
Bottom Design moment X (kNm/m) 25.79Reinforcement X (mm²/m) 146Design moment Y (kNm/m) 24.25
Reinforcement Y (mm²/m) 137Top
Design moment X (kNm/m) -26.81Reinforcement X (mm²/m) 152
Design moment Y (kNm/m) -25.80Reinforcement Y (mm²/m) 146Linear Shear X (MPa) 0.060vc (MPa) 0.357
Linear Shear Y (MPa) 0.056vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.048
vc (MPa) 0.357Cost 2892.27
34 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
81.46 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
114.04 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:7
BS8110 - 1997
Output for Load Case 8
Output for Load Case 8Soil pressure (ULS) (kN/m²) 95.00Soil pressure (SLS) (kN/m²) 74.79
SF overturning (SLS) 4.11SF overturning (ULS) 2.69Safety Factor slip (ULS) 3.20Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 18.89Reinforcement X (mm²/m) 107Design moment Y (kNm/m) 29.11
Reinforcement Y (mm²/m) 165Top
Design moment X (kNm/m) -6.12Reinforcement X (mm²/m) 35
Design moment Y (kNm/m) -14.45Reinforcement Y (mm²/m) 82Linear Shear X (MPa) 0.044vc (MPa) 0.357
Linear Shear Y (MPa) 0.063vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.050
vc (MPa) 0.357Cost 2886.73
35 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
74.79 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
95.00 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:8
BS8110 - 1997
Output for Load Case 9
Output for Load Case 9Soil pressure (ULS) (kN/m²) 89.75Soil pressure (SLS) (kN/m²) 69.51
SF overturning (SLS) 4.34SF overturning (ULS) 2.82Safety Factor slip (ULS) 3.37Safety Factor uplift (ULS) >100
Bottom Design moment X (kNm/m) 14.94Reinforcement X (mm²/m) 84Design moment Y (kNm/m) 28.34
Reinforcement Y (mm²/m) 160Top
Design moment X (kNm/m) -3.51Reinforcement X (mm²/m) 20
Design moment Y (kNm/m) -15.22Reinforcement Y (mm²/m) 86Linear Shear X (MPa) 0.035vc (MPa) 0.357
Linear Shear Y (MPa) 0.061vc (MPa) 0.357Linear Shear Other (MPa) 0.000Punching Shear (MPa) 0.049
vc (MPa) 0.357Cost 2873.89
36 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
69.51 kN/m²
3.50
X
Y
Y
3.5
0
0.70
0.50
PMx
1.0
5
Hx
0.50
1.20
89.75 kN/m²
Soil Pressures at ULSSoil Pressures at SLS
LegendMax M (+)Max M (-)Max Shear
Load Case:9
BS8110 - 1997
37 of 45
SheetJob Number
Job Title
Client
Calcs by Checked by Date
Software Consultants (Pty) LtdInternet: http://www.prokon.comE-Mail : [email protected]
Schematic reinforcement of Base
18Y16-B-200 (B2)
18Y16-A-200 (B1)
18Y16-D-200 ABR (T2)
18Y16-C-200 ABR (T1)
col1
PLAN
SECTION
B B B B B B B B B B B B B B B B B B
3R10-H
R10-H
4Y20-G4Y20-F +4Y20-E +
E
E
E
E
F F
F F
G
G
G
G
SECTION: col1
38 of 45
Project Job Ref.
Section Sheet no./rev.
1
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
RC BEAM DESIGN (BS8110);CONCRETE RECTANGULAR BEAM DESIGN (CL 3.4.4.4)
BEAM DEFINITION
; Beam width; b = 300 mm
; Overall beam depth ; h = 600 mm
; Nominal cover to all reinforcement including links; cnom = 75 mm
; Tension bar diameter (try); Dtry = 32 mm
; Link bar diameter (try if applicable); Ldia_try = 10 mm
Depth to tension steel; d = h - cnom - Ldia_try - Dtry/2 = 499 mm
; Characteristic strength of reinforcement; fy = 460 N/mm2
; Characteristic strength of concrete; fcu = 30 N/mm2
; Clear span of beam; L = 9500 mm
The beam is not a deep beam - calculations OK
BS8110 - DESIGN MOMENTS AND SHEARS (SAGGING)M = 180.0 kNm
V = 100.0 kN
CONCRETE RECTANGULAR BEAM COMPRESSION STEEL REQUIRED? (CL 3.4.4.4)
Calculations also valid for flanged beams with neutral axis in flange
; Design ultimate moment; M = 180 kNm
; Moment redistribution factor; βb = 1.00
Reinforcement required
;;; K = abs(M) / ( b × d2 × fcu ) = 0.080
K' = min (0.156 , (0.402 × (βb - 0.4)) - (0.18 × (βb - 0.4)2 )) = 0.156
Compression steel not required
Beam requiring tension steel only
;; z = min (( 0.95 × d),(d×(0.5+√(0.25-K/0.9)))) = 450 mm
;;; As_req = abs(M) / (1/γms × fy × z) = 914 mm2
Tension steel
;;Use 3 No. 32 dia bar(s); As_prov = Ast = 2410 mm2
Area of tension steelprovided sufficient
Check min and max areas of tension steelTotal area of concrete; Ac = b × h = 180000 mm2
39 of 45
Project Job Ref.
Section Sheet no./rev.
2
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
; Minimum percentage of tension steel; kt = 0.13 %
Ast_min = kt × Ac = 234 mm2
Ast_max = 4 % × Ac = 7200 mm2
;Area of tension steel provided; As_prov = 2410 mm2
Area of tension steelprovided OK
NOTIONAL COMPRESSION STEEL;;
;Provide 1 No. 6 dia bar(s) ; As'prov = Asc = 28 mm 2
SHEAR RESISTANCE OF CONCRETE BEAMS CLOSE TO SUPPORTS - AV < 2D (CL 3.4.5.8)
; Length of member traversed by a shear failure plane; av = 500 mm
;; Breadth of beam (average web width of flanged section); bv = 300 mm
av < 2d - calculations valid
; Effective area of tension reinforcement - at section x-x; As_shear = 2410 mm2
; Design ultimate shear force; V = 100 kN
Applied shear stress
v = V / (bv × d) = 0.668 N/mm2
Check shear stress to clause 3.4.5.2
vallowable = min ((0.8 N1/2/mm) × √(fcu ), 5 N/mm2 ) = 4.382 N/mm2
Shear stress OK
Shear stresses to clause 3.4.5.4
It is assumed that nominal shear reinforcement is provided and reinforcement provided by bent up bars is not considered.
Design shear stress
vc = 1.57 N/mm2
0.5 × vc = 0.79 N/mm2
Applied shear stress; v = 0.67 N/mm2
Note - shear reinforcement not necessarily required - provide nominal links
The shear stress component resisted by shear reinforcement
vsv = max (abs(v) - vc , 0.4 N/mm2 ) = 0.400 N/mm2
Reinforcement Requirements
; Characteristic strength of shear reinforcement; fyv = 460 N/mm2
The link requirements will be determined allowing for the code requirement that the calculated reinforcement should be
provided within the middle three-quarters of the length av.
cl. 3.4.5.9
;Estimated ratio; Asv_to_sv_reqd = bv × vsv/ (0.95 × fyv × 0.75) = 0.366 mm
Define Links Provided;;
Provide 10 dia links in 2s @ 200 centres ;Ratio provided; Asv_to_sv = 1.571 mm ; Link spacing; sv = 200 mm ; Link diameter; Ldia = 10 mm
40 of 45
Project Job Ref.
Section Sheet no./rev.
3
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
No of links in each group; Ln = 2 ; Area of steel per link group; Asv = 314 mm2
Check that the chosen link spacing provides sufficient total steel within the middle three-quarters of av:
Asv_reqd = av × bv × vsv / (0.95 × fyv) = 137 mm2
No. of link groups within middle three-quarters of length av; Ng = Quotient( 0.75 × av, sv ) = 1
Asv_prov = Ng × Asv = 314 mm2
Area of shear steel provided sufficient
SPACING OF SHEAR LINKS (CL 3.4.5.5)
; Shear steel; Link spacing; sv = 200 mm
; Max spacing; slimit = 0.75 × d = 374.3 mm
Shear link spacing OK
CONCRETE BEAM DEFLECTION CHECK (CL 3.4.6)
; Design ultimate moment; M = 180 kNm
Modification Factors
;Basic span / effective depth ratio (Table 3.10); ratiospan_depth = 20
The modification factor for spans in excess of 10m (ref. cl 3.4.6.4) has not been included.
;fs = fy × As_req / (1.4 × γms × As_prov × βb ) = 118.7 N/mm2
factortens = min ( 2 , 0.55 + ( 477 N/mm2 - fs ) / ( 120 × ( 0.9 N/mm2 + abs(M) / (b×d2)))) = 1.452
factorcomp = min ( 1.5 , 1 + (100×As'prov/(b×d)) / (3 + (100×As'prov/(b×d)))) = 1.006
Calculate Maximum Span
This is a simplified approach and further attention should be given where special circumstances exist. Refer to clauses3.4.6.4 and 3.4.6.7.
Maximum span; Lmax = ratiospan_depth × factortens × factorcomp × d = 14.58 m
Check the actual beam span
Actual span/depth ratio; L / d = 19.04
Span depth limit; ratiospan_depth × factortens × factorcomp = 29.23
Span/Depth ratio checksatisfied
CLEAR DISTANCE BETWEEN BARS IN TENSION (CL 3.12.11.2.4)
ACTUAL CLEAR DISTANCE BETWEEN TENSION BARS
; Diameter of tension bars; Dt = 32 mm
; Number of tension bars; Lnt = 3
; Diameter of shear links; Ldia = 10 mm
Nominal cover
Nominal cover to steel (links if present); cnom = h - d - Dt/2 - Ldia = 75 mm
Actual clear distance
Clear distance between bars; spacingbars = ( b - 2×( cnom + Ldia) - Dt ) / (Lnt - 1) - Dt = 17.0 mm
Calculate maximum allowable clear distance
41 of 45
Project Job Ref.
Section Sheet no./rev.
4
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
Tension steel
; Characteristic strength of reinforcement; fy = 460 N/mm2
; Moment Redistribution Factor; βb = 1.00
Approx Service Stress
; fs = fy × As_req / (1.4 × γms× As_prov × βb ) = 118.7 N/mm2
Maximum allowable clear distance between tension bars;
spacingmax = min ((47000 N/mm) / fs , 300 mm) = 300 mm
Max distance between bars check - OK
Minimum clear distance between tension bars
; Assumed aggregate size; hagg = 20 mm
spacingmin = hagg + 5 mm = 25 mm
Min distance between bars check - NOT Satisfied
CLEAR DISTANCE BETWEEN FACE OF BEAM AND NEAREST LONGITUDINAL BAR IN TENSION (CL 3.12.11.2.5)
Distance from tension bar to face of beam
Distface = cnom + Ldia + Dt/2 = 101.0 mm
Distmax = spacingmax / 2 = 150.0 mm
Max distance to beam face check - OK
CHECK OF NOMINAL COVER - (BS8110:PT 1, TABLE 3.4); Diameter of tension reinforcement; Dt = 32 mm
; Diameter of links; Ldia = 10 mm
Cover to tension reinforcement
cten = h - d - Dt / 2 = 85.0 mm
Nominal cover to links steel
cnom = cten - Ldia = 75.0 mm
Permissable minimum nominal cover to all reinforcement (Table 3.4)
; cmin = 35 mm
Cover OK
SERVICEABILITY LIMIT STATE - CRACKING OF BEAMS
(BS8110:Pt 2, Cl. 3.8 & BS8007 Cl 2.6 & Appendix B)
; Design serviceability moment; MSLS = 120 kNm
; Diameter of links; Ldia = 10 mm
; Diameter of tension reinforcement; Dt = 32 mm
; Number of tension reinforcement bars; Lnt = 3
Area of tension reinforcement; Ast = π × Dt2 /4 × Lnt = 2413 mm2
Cover to tension reinforcement
cten = h - d - Dt / 2 = 85.0 mm
42 of 45
Project Job Ref.
Section Sheet no./rev.
5
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
cnom = cten - Ldia = 75.0 mm
Tension bar centres
barcrs = (b - 2×(cnom + Ldia) - Dt ) / (Lnt - 1) = 49.0 mm
MODULAR RATIO
Modulus of elasticity for reinforcement; Es = 200 kN/mm2
BS8110:Pt 1:Cl 2.5.4
Modulus of elasticity for concrete (half the instanteneous)
Ec = ((20 kN/mm2) + 200×fcu) / 2 = 13 kN/mm2
BS8110:Pt 2:Equation 17
Modular ratio; m = Es / Ec = 15.385
NEUTRAL AXIS POSITION
For equilibrium; Fst equates Fc
Therefore: m × Ast × [ fc×(d-x)/x ] equates to 0.5 × fc × b × x
Solving for x gives the position of the neutral axis in the section:-
x = d × [ -1×Es×Ast/(Ec×b×d) + √( Es×Ast/(Ec×b×d) × (2+Es×Ast/(Ec×b×d)))] = 248.8 mm
Depth of concrete in compression
x = 248.8 mm
CONCRETE AND STEEL STRESSES
The serviceability limit state moment; MSLS = 120 kNm
Taking moments about the centreline of the reinforcement:-
Moment of resistance of concrete is 0.5 × fc × b × x × (d - x/3)
Solving for concrete stress fc gives;
fc = 2 × abs(MSLS) / ( b × x × (d - x/3)) = 7.73 N/mm2
Allowable stress; 0.45 × fcu = 13.50 N/mm2
Concrete stress OK
Taking moments about the centre of action of the concrete force:-
Moment of resistance of steel is fst × As × (d - x/3)
Solving for steel stress fst gives;
fst = abs(MSLS) / ( Ast × (d - x/3)) = 119.54 N/mm2
CONCRETE AND STEEL STRAINS
Strain in the reinforcement
εs = fst / Es = 597.7××××10-6
Allowable steel strain; 0.8 × fy / Es = 1.840××××10-3
Steel strain OKBS8007:App B.4
43 of 45
Project Job Ref.
Section Sheet no./rev.
6
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
; Allowable crack width; CrackAllowable = 0.2 mm
BS8007:Cl 2.2.3.3
Factor for stiffening based on limiting crack width
factor = if(CrackAllowable >= (0.2 mm), (1.0 N/mm2), (1.5 N/mm2)) = 1 N/mm2
Breadth of tension face; bt = b = 300 mm
Strain in the concrete at the level at which crack widths are required
Tension face of beam
Level of crack; a'1 = h = 600 mm
ε11 = εs × (a'1 - x)/(d - x) = 839.0××××10-6
Strain in the concrete at the level at which crack width is required adjusted for stiffening of the concrete tension zone
εm1 = min( ε11 ,max(0 , ε11 - [ factor × bt× (h - x) × (a'1 - x) / (3×Es× Ast ×(d - x))])) = 736.8××××10-6
BS8007:App B.3
Distance from tension bar to crack in tension face between tension bars
acrt1 = √ ( (barcrs/2)2 + (cnom + Ldia + Dt/2)2) - Dt/2 = 87.9 mm
Distance from tension bar to crack in tension face at corner of beam
acrt2 = √(2) × (cnom + Ldia + Dt/2 ) - Dt/2 = 126.8 mm
Critical distance from tension bar
acr1 = max(acrt1, acrt2 ) = 126.8 mm
Design crack width in tension face
Crackdesign1 = 3 × acr1 × εm1 /(1 + 2×(acr1 - cten)/(h - x)) = 0.226 mm
BS8007:App B.2
Side of beam mid way between NA and tension steel
Level of crack; a'2 = x + (d - x)/2 = 374 mm
ε12 = εs × (a'2 - x)/(d - x) = 298.9××××10-6
Strain in the concrete at the level at which crack width is required adjusted for stiffening of the concrete tension zone
εm2 = min( ε12 , max(0 , ε12 - [ factor × bt× (h - x) × (a'2 - x) / (3×Es× Ast ×(d - x))])) = 262.5××××10-6
BS8007:App B.3
Distance from tension bar to crack in side face mid way between NA and tension steel
acr2 = √( ((d - x)/2)2 + (cnom + Ldia + Dt/2)2) - Dt/2 = 144.8 mm
Design crack width in side of beam
Crackdesign2 = 3 × acr2 × εm2 /(1 + 2×(acr2 - cten)/(h - x)) = 0.085 mm
BS8007:App B.2
Design crack width
Crackdesign = max(Crackdesign1 , Crackdesign2 ) = 0.226 mm
Max allowable crack width
CrackAllowable = 0.20 mm
BS8007:Cl 2.2.3.3
44 of 45
Project Job Ref.
Section Sheet no./rev.
7
Calc. by
ADate
4/25/2012Chk'd by Date App'd by Date
Allowable crack width exceeded - FAIL
;
45 of 45