TechnicalInformationTI 246F/00/en
Application The Prosonic T is a compact ultrasonictransmitter
for continuous non-contactlevel measurement in liquids and
incoarse-grained or pelleted solids. TheProsonic T series consists
of threetransmitters, which can be equippedwith one of several
electronic modules,with graduated measuring ranges from0.25 m (0.8
ft) upwards. FMU 130, 230
in coarse-grained solids (grain sizefrom 4 mm/0.16 in) up to 2
m/6.6 ftin liquids up to 5 m/16.4 ft (2 wire instruments: 4 m/13
ft)
FMU 131, 231in coarse-grained solids (grain sizefrom 4 mm/0.16
in) up to 3.5 m/11.5 ftin liquids up to 8 m/26.2 ft(2 wire
instruments: 7 m/23 ft)
FMU 232in coarse-grained solids (grain sizefrom 4 mm/0.16 in) up
to 7 m/23 ftin liquids up to 15 m/49.2 ft
All transmitters are equipped with anintegrated temperature
sensor fortime-of-flight compensation.
Features and BenefitsFits exactly to the process Threaded
connections from G 11/2 or
11/2 NPT or flange 4" or DN 100 Fully rotatable housing LEDs
visible through housing cover
allow quick monitoring of operationalstatus
Electronics versions FMU 130, 131: 2-wire loop-powered
general approval for "EEx ia"/ATEX II 2 G
FMU 230, 231: 2-wire loop-powered or4-wire including mains power
supply
FMU 232: 4-wire, optional approval fordust Ex Zone 10 / ATEX II
1/3 Dincluding mains power supply
Intelligent operation and evaluation Simple local push-button
operation,
with optional display HART protocol for remote operation Digital
communication with
PROFIBUS-PAHART is a registered trademark of the HART
Communication Foundation
Ultrasonic Level Measurementprosonic T FMU 130, 131prosonic T
FMU 230, 231, 232
Compact transmitter for continuous, non-contact level
measurement Available as a Smart transmitter orfor connection to
process control systems
Hauser+EndressThe Power of Know How
This datasheet has been downloaded from http://www.digchip.com
at this page
-
Measuring System The Prosonic T compact ultrasonictransmitter is
a complete measuringpoint within itself. The simplest versionallows
access to all functions requiredfor basic operation. Calibration
can becarried out using the four pushbuttons, +, V, H on the
instrument without theneed for other equipment. With a plug-in
display, the completeEndress+Hauser user matrix can beaccessed.
The basic functionality may beenhanced by other optional
operatingpossibilities or integration into a processcontrol system,
e.g. via: 2-wire loop-powered 420 mA
(Smart) with INTENSOR or HARTprotocol or for connection
toPROFIBUS-PA bus systems
4-wire, with separate power supply,420 mA (Smart) with HART
protocol
2-wire 420 mA Loop-Powered Applications in e.g. Storage
Vessels
FMU 130, FMU 131: Certificate EEx iaFMU 230, FMU 231:
Standard
4-wire, 420 mASeparate Power SupplyApplications with Rapid
Changes inLevel, e.g. Process Vessels
FMU 230, FMU 231: Standard FMU 232: Optional Dust Ex Zone 10
FMX 770
IO
IO
1
2
5
4
3
FXN 671
mA1+
PLC
FXN 671
FMX 770
PROFIBUS-PA
Commu-box
Isolator
PROFIBUS-DP
PLC
Rackbus
Rackbus
420 mA
420 mA
420 mA
Ex isolator PLC
Commuwin II
HART
HART
INTENSOR
Power supply via the transmitter power pack e.g. PLC, with FMU
130, 131 connection via the Ex isolator (Zener barrier:
-
Operation Prosonic T compact transmitters offeroperation
tailored to all level applications: Local calibration or matrix
operation
by simply pressing buttons Smart remote operation and
display
via the handheld terminal Comprehensive operating and
display
software for personal computer Calibration in the control room
via a
Silometer FMX 770 or FXN 671.
Matrix OperationProsonic T can be operated by usingthe keyboard
and display, a handheldterminal, a Silometer transmitter(FMX 770,
FXN 671) or via a processbus. The identical operating matriceensure
that procedures are uniform andclear.
Operation via DisplayParameters are entered and valuesdisplayed
by using the four pushbuttons, +, V, H on the front panel of the
device.The optional display provides access tothe Endress+Hauser
operating matrix andto a wide selection of additional functions.
The following application parameters
are available:- Liquid- Rapid changes in levels of liquids-
Measurement when mounted in the
dome cover- Coarse-grained solids- Conveyor belt
Automatic suppression of three fixedtarget echoes
Linearisation (11 points) First echo detection (double echo)
Automatic suppression of stirrer
echoes
Operation Without a DisplayThe basic functions of the Prosonic
Tcan be set by using just the fourpushbuttons , +, V, H on the
front panelof the instrument. Empty and full calibration Parameter
protection by entry locking
V H16602
Reset
Unlock parameters
Lock parameters
Full calibration
Empty calibration0 %: 4 mA
100 %: 20 mA
V V+ + H H
V+ H
V
H
!4 ...
4+
20 mA
5-
+2
1
V H+
1 2
H0V0V1V2V3V4
H1 H2 H3 H4V+ H
V+ H
Matrix operation with display
OR Calibration without display
Status indication and operating display also with housing cover
closed
Local matrix operation via display Setting basic functions
locally using four pushbuttons
3
-
PROFIBUS-PAThe PROFIBUS-PA is an open fieldbusstandard for
connecting sensors andactuators, which may also be inexplosion
hazardous areas, to one buscable. The two-wire sensors aresupplied
with power over thePROFIBUS-PA and the processinformation of the
sensor is digitallytransmitted.
The number of instruments operated atone bus segment: up to 10
for EEx ia applications up to 32 for non-Ex applications
Operation via Handheld TerminalWith a handheld terminal, the
Prosonic Tcan be configured, values displayed andadditional
functions activated fromanywhere on the 420 mA signal line.There
are two versions: Commulog VU 260 Z (INTENSOR) Universel HART
Communicator DXR 275
Operation with Commubox Commubox FXA 191 connectsintrinsically
safe Smart transmitters withINTENSOR or HART protocols to theRS 232
C serial interface of a personalcomputer, allowing remote operation
bythe Endress+Hauser Commuwin IIoperating program.
R
IO
Connecting the handheld terminalanywhere along the 420 mA cable
ordirectly on the compact echo transmitter
Minimum total resistance 250 W
420 mA
OR
Connecting handheldterminals
+
Commubox420 mA
Commuwin II
Powerpack
Power supply
Min
imum
tota
l res
istan
ce 2
50 W
Connecting theCommubox
ENDRESS + HAUSER
Commuwin II PLC
Tanks with Prosonic T
Segment couplerFXN 623 A(non-Ex)FXN 623 C(EEx ia)PROFIBUS-PA
PROFIBUS-DP
A Prosonic T with thePROFIBUS-PA protocolallows: local operation
with
display matrix operation with
a personal computerand the Commuwin IIoperating programrunning
under MSWindows 3.11
4
-
Installation Mounting Always mount the sensor such that the
distance between it and the maximumproduct level exceeds the
blockingdistance. The lower edge of thetransmitter should, however,
projectbelow the roof of the tank or silo.Exception: mounting in a
nozzle.
Never mount two Prosonic T in avessel because the instruments
maynot function correctly.
Do not mount the sensor in the centre ofthe vessel roof.
Position the sensor at right angles tothe surface of the
material.
Do not measure through the fillingcurtain.
Blocking DistanceDue to the ringing time of the sensor,there is
a zone immediately below it inwhich returning echoes cannot
bedetected. This so-called blockingdistance determines the
minimumdistance between the sensor and themaximum level in the tank
or silo (seeTechnical Data for values).
Interference SuppressionInterference echoes coming frominternal
fittings can be suppressed byusing the fixed target
suppressionfunction. The signals are then no longerrecorded or used
for further processing.The ultrasonic pulse leaves the sensoras a
narrow beam which widens withincreasing distance from the
device.Every object within this beam producesan interference echo
which is receivedby the sensor.
Mounting on a NozzleIf the maximum level to be measuredfalls
within the blocking distance, thetransmitter must be mounted on
anozzle. No build-up should form in the nozzle. The recommend
nozzle dimensions
are limits, within which the nozzle canvary. Check that the
nozzle diameter islarge enough, but keep the nozzlelength to a
minimum (see figure).
The inner surface of the nozzle shouldbe as smooth as possible
no edgesor welding seams.
Other Types of Mounting below left:
mounting with welded sleeve below right:
mounting with counter nut
LL
D
D
Sensor FMU D mm (in) max. L mm (in)130 / 230 50 (2) 150 (5.9)130
/ 230 80 (3.1) 240 (9.4)130 / 230 100 (3.9) 380 (15)131 / 231 80
(3.1) 240 (9.4)131 / 231 100 (3.9) 380 (15)232 100 (3.9) 300
(11.8)
Dimensions without DisplayDmin = 100 mm (3.9 in)Lmax = 150 mm
(5.9 in)Dimensions with Display or Commuwin II(use echo
suppression)
Counter nutsupplied for G 11/2 " and G 2"instruments
Maximumlevel
Blockingdistance
Violation ofthe blockingdistancemay lead
toincorrectoperation.
5
-
Measuring Range The maximum measuring range of theProsonic T is
limited by the conditions atthe measuring point and the
reflectioncharacteristics of the product surface. Optimum
conditions are achieved if:
the surface of the liquid is calm andwithout foam,
no large concentrations of vapour arepresent in the tank,
the solid material is hard andcoarse-grained,
no dust is present in the silo, temperature layering in the tank
or silo
is low.
Example for Calculating RangeCheck the factors affecting
yourmeasurement in the table to the right.Add up their attenuation
values (dB).
Temperature difference in silo max. 40C (104F) 10 dB
Low amount of filling curtain in detection area 5 dB
Surface of liquid with strong turbulence 20 dB
Sum of attenuation values 35 dBRange below these factors thus
approx. 5.8 m (19 in) with 2" sensor.
Effects Attenuation(dB)
Temperature layeringFor air temperature differencebetween sensor
and productsurface up to 20C (68F)
up to 40C (104F)up to 80C (176F)
05101020
Filling curtainOutside detection rangeSmall amount inside
detection rangeLarge amount insidedetection range
0
510
1020DustNoneSmall amountLarge amount
05510
Solids surfaceCoarse, hardSoft
202040
Liquid surface CalmHeavy wavesVery turbulent (e.g.
agitators)
05101020
FoamPlease consult Endress+Hauser
The diagram shows ideal echoattenuation curves. Move the ideal
curve downwards
corresponding to the sum of the attenuation values.
` The maximum range is indicated at theintersection where the
ideal curve andthe interference level line meet.
101 2 4 5 6 7 8 93
60
120
0
20
40
80
100
1
2
35dB
Noise level line
1 m = 3.28 ft1 ft = 0.305 m
Echo attenuation FMU 130, 131, 230, 231 Example for determining
range
10 20
20
40
60
80
100
02 4 6 8 12 14 16 18 22 24 26
Blocking distance for 11/2" sensor Blocking distance for 2"
sensor
Range / m
Echo attenuation / dB
Normal interference level
Example:Range approx. 5.8 m
Ideal curve for 2" sensor
Ideal curve for 11/2" sensor
Range / m
Echo attenuation / dB
Blocking distance for 4" sensor
Ideal curve for 4" sensor
Normal interference level
Noise level line
Echo attenuation FMU 232
6
-
Electrical Connection FMU 130, 131, 230, 231 2-wire loop-powered
Communication: INTENSOR or HART
` FMU 230, 231 4-wire, including mains power supply
FMU 232 4-wire, including mains power supply
FMU 130, 131 PROFIBUS-PA 2-wire Communication: PROFIBUS-PA
Current consumption:
FMU 130, 131, 230, 231: 12 mA 1 mAFMU 232: 16 mA 1 mA
Please see also: TI 260F and BA 166F
CablingFor FMU 130, 131, 230, 231 instrumentswith communication
use screenedcommercial 2-wire cable for signaltransmission or for
FMU 230, 231, 2324-wire cable for signal transmission andpower.
Under certain circumstances,the digital communication signal may
beaffected if unscreened cable is used.
1000
U/VFMU 230 / 231FMU 130 /131
R/W
2012 18 24 30 36
750
Load diagram
!4+
4
+
d4d2
20 mA
5
V
V
+
+
H
H
+
420 mA
FMX 770FXN 671
!4I+4
20 mAI-5
V
V
+
+
H
H
+
L+L11
L-N2 3
+
L+/L1L/N
`
1836 VDC90127 VAC180250 VAC
420 mA
!4I+4
20 mAI-5
V
V
+
+
H
H
+
L+L11
L-N2 3
+
L+/L1L/N
1836 VDC90127 VAC180250 VAC
420 mA
!L+4L-5
V
V
+
+
H
H
onadressoff
+
PROFIBUS PA
1 2 3 4 5 6 7 8
onaddressoff1 2 3 4 5 6 7 8
2 + 8 = 10
Every instrument has a uniqueaddress.
off: Hardware address on: Software address
930 V
7
-
Technical data Manufacturer Endress+HauserGeneral Specifications
Instrument designation Prosonic T
Others CE mark
Application Continuous non-contact level measurement in liquids
and coarse-grained bulk solids
Operation and System Design Measuring principle Ultrasonic
measurement, time-of-flight measurementModularity Compact
ultrasonic sensor, with optional display
Local operation or using Universal HART Communicator DXR 275
(HART) or Commulog VU 260 Z (INTENSOR) handheld terminal Silometer
FMX 770, FXN 671 PC (PROFIBUS-PA, Commubox)
Signal transmission 420 mA optional Smart (with superimposed
communication signal),digital current output selectable 8/16 mA or
4/20 mA,digital communication signal via PROFIBUS-PA
Input Variables Measured variable Level, determined from the
distance between the sensor and surface ofmaterial
Measuring ranges FMU 130, FMU 230: 0.254 m (0.813.1 ft), for
4-wire 0.255 m (0.816.4 ft)
FMU 131, FMU 231: 0.47 m (1.323 ft), for 4-wire 0.48 m (1.326.2
ft)
FMU 232: 0.6 m15 m (249.2 ft)Blocking distance FMU 130, FMU 230:
0.25 m (0.8 ft)
FMU 131, FMU 231: 0.4 m (1.3 ft)FMU 232: 0.6 m (2 ft)
Frequency FMU 130, FMU 230: approx. 70 kHzFMU 131, FMU 231:
approx. 50 kHzFMU 232: approx. 35 kHz
Pulse frequency 0.53 Hz, depending on sensor and electronicsMin.
delay time 2-wire: approx. 5 s; 4-wire: approx. 1
sApplication-specific effects on attenuation
a = 3 dB angle of emissionL = length of beam (calculatedfrom
max. measuring range ofsensor)
Estimation of detection limits using beam angle (3 dB)
r = tan a
2 L
Liquids a L r11/2" sensor 5.5 4 m (13.1 ft) 0.19 m (7.5 in)2"
sensor 5.5 7 m (23 ft) 0.33 m (13 in)4" sensor 3 15 m (49.2 ft) 0.4
m (15.7 in)
Bulk solids a L r11/2" sensor 5.5 2 m (6.6 ft) 0.1 m (3.9 in)2"
sensor 5.5 3.5 m (11.5 ft) 0.16 m (6.3 in)4" sensor 3 7 m (23 ft)
0.1 m (3.9 in)
Output Variables Output signal 420 mA, selectable digital
current output 8/16 mA or 4/20 mA ordigital communication
signal
Output span 16 mA for analogue signal Power failure signal(on
error)
420 mA or 4/20 mA: selectable 10% = 2.4 mA (with 4-wire
only),+110% = 21.6 mA or hold last current value is held8/16 mA:
selectable 10% = 7.2 mA, +110% = 16.8 mA or hold
Switching delay time 1255 s Load max. 600 W
Using the PROFIBUS-PAOutput signal Digital communication signal,
PROFIBUS-PAPA function SlaveTransmission rate 31.25 kBit/sResponse
time Slave: approx. 20 ms
PLC: 300600 ms for approx. 30 devices (depending upon
segmentcoupler)
Signal on alarm Selectable 9999, +9999 or hold (last
value)Communication resistance PROFIBUS-PA termination
resistorPhysical layer IEC 1158-2
Measuring Accuracy Reference conditions Ideal reflection from
calm, flat surface at 20C (68F)Measuring uncertainty 0.25% for max.
measuring span Resolution 2-wire (FMU 130, 131, 230, 231): 3 mm
(0.12 in)
4-wire (FMU 230, 231, 232): 2 mm (0.08 in)
Communication Interfaces Handheld terminal Commulog VU 260 Z
INTENSOR, Hart Communicator DXR 275 HARTConnection direct to the
current output or anywhere along the signal lineCommunication
resistance: 250 W
PROFIBUS-PA Connection to PLC or PC via the FXN 623 A (not Ex)
or FXN 623 C(EEx ia), PROFIBUS address via 8-pole switch, terminal
resistancePROFIBUS-PA
a
L
r
8
-
Application Conditions Orientation Perpendicular to the surface
of the material1)
Please check with Endress+Hauser before usingsensors at higher
temperatures and higher pressures.
When sensors are subjected to high temperatures andpressures
(with limiting conditions), it is recommendedthat the coupling
(process connection) be tightened.
Medium temperature range 1) 40+80C (40+176F) (built-in
temperature sensor)Operating temperature range(electronics)
20+60C (4+140F)
Storage temperature range 40+80C (40+176F)Operating pressure
pabs1) Sensors with process connection G 11/2 and G 2: 3 bar (43.5
psi)
Sensor DN 100 or 4" with slip-on flange or mounting bracket: 2.5
bar(36.25 psi)
Climatic class DIN / IEC 68 T2-30 DbType of protection (EN
60529) IP 67 (NEMA 6), with housing cover open IP 20Vibration
resistance DIN IEC 68 T2-6 Tab.2.C (1055 Hz)Electromagnetic
compatibilty(EMC)
Emitted interference to EN 61326;Class B equipment; Immunity to
interference to EN 61326; Annex A (industry sector) and NAMUR EMC
Recommendation
Explosion protection FMU 130/131 (2-wire Ex): PTB EEx ia IIC T6
(PTB in Germany only)FMU 230/231 (2-wire not Ex and 4-wire):
withoutFMU 232 (4-wire): dust Ex, Zone 10 (BVS in Germany only)
Mechanical Design Construction Compact unit, Versions with
threaded connection can be installed with 60 AF boxspanner, max.
torque 1520 Nm (11.114.8 ft lbs)
Dimensions See Dimensions page 12Material Housing:
threaded bossand sensor:
PBT (fibre-glass reinforced, flame-retarded)PVDFfor FMU 232 UP
(unsatured polyester); sensor diaphragm stainless steel
Seals Between threaded boss and sensor, internal: EPDM sealon
threaded boss, external: EPDM seal
Process connection FMU 130, FMU 230: G 11/2 or 11/2-11.5 NPT
thread FMU 131, FMU 231: G 2 or NPT 2-11.5 NPT thread FMU 232: DN
100 or 4" with slip-on flange or mounting bracket
Cable entry Pg 16, Cable diameter 59 mm (0.20.35 in)Sleeves for
connection thread G1/2, 1/2 NPT or M 20x1.5 supplied
Cable 2-wire:4-wire:
Use standard screened 2-wire cableUse standard screened 4-wire
cable for signal transmission and powersupplyUnder certain
circumstances, the digital communication signal may beaffected if
unscreened cable is used.
Display and Operating Elements Display (LCD) 4-character
display, with segment display for currentDimension L x B x H: 40 x
20 x 10 mm
(1.6 x 0.8 x 0.4 in)LEDs Red: indicates alarm or warning
Green: Indicates power on (with 4-wire versions only) and
entryacknowledgement
Power Supply AC voltagePower consumptionSwitch-on current
4-wire: 180250 VAC; 90127 VAC < 4 VA100 mA, pulse width half
life time 70 ms
DC voltagePower consumptionSwitch-on current
4-wire: 1836 VDC; 2-wire: 1236 VDC< 2,5 W (4 wire
instruments)7 A, pulse width half life time 2 ms
Current consumption FMU 130, 131, 230, 231: 12 mA 1 mAFMU 232:
16 mA 1 mA
Ripple(Smart-devices)
INTENSOR max. ripple (measured at 500 W ) 0 Hz100 Hz: USS=30
mVHART max. ripple (measured at 500 W ) 47 Hz125 Hz: USS=200 mVmax.
noise (measured at 500 W ) 500 Hz10 kHz: Ueff.=2.2 mV
Electrical isolation The evaluation electronics is electrically
isolated from the power supplyterminals with all 4-wire
versions.
Supplementary Documentation Prosonic T System Information SI
021F/00/enProsonic T Compact transmitter for limit detection
Technical Information TI 247F/00/enPlanning notes PROFIBUS-PA
Technical Information TI 260F/00/en
9
-
Accessories Plug-in Display Order-No.: 942663-0000
Slip-On Flange FAU 60for FMU 232 onlyOrder No.: FAU60-XOX
Adapter Flange FAU 70 E for FMU X30, X31 Order No.:
942636-XXXX
Protective Hood for ElectronicHousingOrder No.: 942665-0000
Adapter Flange FAU 70 A for FMU X30, X31 Order No.:
942636-XXXX
400 (15.6)120 (4.7)
120
(4.7)
30 (1.2)
250
(9.7)A
G
16 (0.6)
3.0 (0.12)mm (in)
Installation Bracketfor FMU X30, X31 G 11/2: A=55 mm
(2.2 in) Order-No: 942669-0000
G 2: A=66 mm(2.6 in) Order-No:942669-0001
Material: 1.4301(AISI 304)
11(0.4)
119 (4.7)
2(0.08)
120
(4.7)
~12
3(~4
.8)
25(9.8)
25(9.8)
2 x M8enclosed
mm (in)
Mounting Bracketfor FMU 232 Order-No:
942666-0000 Material: 1.4301
(AISI 304)
Process connection12 DN 50 PN 1614 DN 80 PN 1615 DN 100 PN
16
Thread3 G 11/2 ISO 2284 G 2 ISO 228
Material2 1.4435 (AISI 316L)7 PPs (Polypropylene)
FAU70E-
Process connectionD DN 100, PN 16A ANSI 4", 150 psiJ JIS 16 K
100
MaterialP PPs (Polypropylene)S Steel paintedR 1.4571 (AISI
316L)
OFAU 60-
144
(5.6)
122(4.7)
187 (7.3)
Protective hood forelectronics housing withdimensions in mm
(in)
V H16602
Process connection22 ANSI 2" 150 psi44 ANSI 3" 150 psi25 ANSI 4"
150 psi
Thread5 NPT 11/2 - 11,56 NPT 2 - 11,5
Material2 1.4435 (AISI 316L)7 PPs (Polypropylene)
FAU70A-
10
-
Product StructureVersionE Europe / Asia (cylindrical thread G)A
America (conical thread NPT)
CertificatesB EEx ia IIC T6, Zone 1 (only in FRG)/ATEX II 2 GJ
FM, IS Class I, II, III, Division 1 Groups A-G (for Version A
only)Q CSA, IS Class I, II, III Division 1 Groups A-G (for Version
A only)T TIIS Ex ia II C T6
CommunicationF withoutB 420 mA, HART protocolP PROFIBUS-PA
Product designation
Process Connection Versions with G or NPTThreadsFMU 130: G 11/2
or 11/2 NPTRange: max. 2 m/6.6 ft (solids) or
max. 4 m/13.1 ft (liquids)FMU 131: G 2 or 2 NPTRange: max. 3.5
m/11.5 ft (solids) or
max. 7 m/23 ft (liquids)
Enter "Y" for special certificates or communicationmode.
VersionE Europe / Asia (cylindrical thread G)A America (conical
thread NPT)
CertificatesA StandardN CSA General Purpose (for Version A
only)
CommunicationA 420 mA, 2-wire, without communicationC 420 mA,
2-wire, HART protocolD Power supply 1836 VDC, 50/60 Hz, 4-wire,
without communicationE Power supply 1836 VDC, 50/60 Hz, 4-wire,
HART protocolF Power supply 180250 VAC, 50/60 Hz, 4-wire, without
communicationG Power supply 180250 VAC, 50/60 Hz, 4-wire, HART
protocolJ Power supply 90127 VAC, 50/60 Hz, 4-wire, without
communicationK Power supply 90127 VAC, 50/60 Hz, 4-wire, HART
protocolP PROFIBUS-PA
Product designation
Process Connection Versions with G or NPTThreadsFMU 230: G 11/2
or 11/2 NPTRange: max. 2 m/6.6 ft (solids) or 2-wire: max. 4 m/13.1
ft (liquids)4-wire: max. 5 m/16.4 ft (liquids)FMU 231: G 2 or 2
NPTRange: max. 3.5 m/11.5 ft (solids) or 2-wire: max. 7 m/23 ft
(liquids)4-wire: max. 8 m/26.2 ft (liquids)
Enter "Y" for special certificates or communicationmode.
CertificatesA StandardF Dust Ex Zone 10 / ATEX II 1/3 DM FM
Class II, Division 1, Groups E, F, GN CSA General PurposeR CSA
Class II, Division 1, Groups E, F, G
Power Supply / CommunicationD Power supply 1836 VDC, 50/60 Hz,
4-wire, without communicationE Power supply 1836 VDC, 50/60 Hz,
4-wire, HART protocolF Power supply 180250 VAC, 50/60 Hz, 4-wire,
without communicationG Power supply 180250 VAC, 50/60 Hz, 4-wire,
HART protocolJ Power supply 90127 VAC, 50/60 Hz, 4-wire, without
communicationK Power supply 90127 VAC, 50/60 Hz, 4-wire, HART
protocolP PROFIBUS-PA 2-wire (in preparation)
Product designation
Process Connection Versions:Flange DN 100 / PN 16Flange ANSI 4"
/ 150 psiFlange JIS 16K 100Range: up to 7 m/23 ft (solids) or
max. 15 m/49.2 ft (liquids)
Enter "9" for special display or housing versions.
Housing / Cable Entry1 Plastic housing IP 67, Pg 16 IP 67
(with FMU 130, 131, 230, 231 for Version E only)2 Plastic
housing NEMA 6, NPT 1/2"3 Plastic housing IP 67, M 20x1.5 (with FMU
130, 131, 230, 231 for Version E only)4 Plastic housing IP 67, G1/2
A (with FMU 130, 131, 230, 231 for Version E only)5 Plastic
housing, M12 PROFIBUS-PA connector
Display1 Without plug-in display2 With plug-in display
Product designation
FMU 130 / 131 (2-wire, Ex)
FMU 230 / 231 (2-wire not Ex, 4-wire)
FMU 232 (4-wire)
For all instrument versions
11
-
Dimensions
TI 246F/00/en/11.00EHF/CV4.2
~21
5 (~8
.4)
~87
(~3.4
)22 (0.86
)
22 (0.86
)~
83(~3
.3)
~26
0 (~1
0.1)
~26
0 (~1
0.1)12
5 (4.
8)
112 (4.3)
60 AF(2.34 in)
91 (3.5)105 (4.1)
39(1.5)
50(1.95)
G 22 NPT
G 1 /1 / NPT
1 21 2
mm (in)Prosonic T FMU 130, 230 Prosonic T FMU 131, 231
Thread versions G 11/2 or 11/ 2-11.5 NPT G 2 or 2-11.5 NPTCable
entry Pg 16, cable diameter 59 mm
sleeves for connection thread G1/2; 1/2 NPT; M 20x1.5
suppliedWhen mounting in tapped holes to DIN 3852 Part 2, check
that the recese diameter d4 is wide.
2 x M8
~21
5 (~8
.5)
158 (6.2)mm (in)
Prosonic T FMU 232 Mounting with slip-on flange or mounting
bracketCable entry Pg 16, cable diameter 59 mm
sleeves for connection threadG1/2; 1/2 NPT; M 20x1.5
supplied
08.99/MTM