Top Banner
1111-6185912-rev.1 FAST S.p.A. 3 SELECTION, INSTALLATION, USE AND MAINTENANCE MANUAL FM Series Air handling units Air flow from 900 to 95.000 m³/h AHU N° 04.07.051 Range FM
56

FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Apr 04, 2019

Download

Documents

vuongquynh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

1111

-618

5912

-rev

.1

FAST S.p.A.

3

SELECTION, INSTALLATION, USE

AND MAINTENANCE MANUAL

FM SeriesAir handling units

Air fl ow from 900 to 95.000 m³/h

AHU N° 04.07.051

Range FM

Page 2: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4
Page 3: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Information about documentation 4

Basic Safety Rules 4

Identification 5

Unit description 6

Technical Data 7

Component description 9

Filtration 11

Coil 16

Humidification 20

Fan sections 21

Motors 23

Silencers 24

Heat recovery unit 24

Empty sections 24

Multizone 24

Dimensions 25

Transport and handling 41

Installation 41

Connections 44

First start-up checks 49

Maintenance 50

Disposal 51

Index English

Page 4: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

WARNING!

The positioning of the unit must be done so that the electrical pa-nel, the control devices and control unit are

clearly visible, outside the danger zone and arranged to ensure a safe and easy operation.

WARNING!

The interaction between the air han-dling units (electrical devices, control logic, etc.) and the electri-

cal system, air distribution, fi re fi gh-ting, etc. of the building where the unit will operate must be carefully evaluated and subjected to a risk analysis with subsequent declaration of conformity affi xing the CE marking to unit.

WARNING!

Any emergency stop by the installer (eg. Mushroom emergen-cy) must be evaluated after analysis of glo-

bal risks of the cooling system.

- Do not open the access doors to internal parts without fi rst ensuring that the master switch is off.

- Do not dispose or leave the packa-ging materials as it can be poten-tially dangerous.

WARNING!

In accordance with

the ATEX directive

94/9/EC, it is abso-

lutely forbidden,

unless different spe-

cifi ed, to install the unit in poten-

tially explosive environments.

WARNING!

Installation and main-tenance must be per-formed by qualifi ed staff according to current laws. Other-

wise, the manufacturer assumes no responsibility for the safety of the product.

WARNING!

Before any operation make sure that the power supply is di-sconnected.

1. INFORMATION ABOUT DOCUMENTATION

Intended use

The air handling units Fast FM series are constructed in accordance with technical standards and rules of sa-fety engineering standards. This may occur despite threats to the safety of the user or any third party, or dama-ge to equipment or other property, in case of improper use.The air handling units in the series are the FM synthesis of experience, studies and experiments in the spe-cifi c fi eld of air handling equipment. The aim is to provide the customer with a fl exible, highly industrialized, with all the advantages that this choi-ce implies in relation to quality and reliability. The FM series is suitable for any specifi c plant requirements, both in terms of functionality, as re-

We remind that the use of products that use electricity and water involves the observance of some basic safety ru-les such as:- This device is not suitable for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they are supervised or instructed in the use by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

- There should be no repairs or main-tenance operations before disconnec-ting the unit from the mains placing the master switch and the main con-trol panel to "off."

- Do not modify safety equipment wi-thout the authorization and instruc-tions from the manufacturer.

- Do not pull, or twist the wires even if they are disconnected from the supply.

- Do not leave containers and fl amma-ble substances near the unit.

- Do not touch the device if barefoot and with wet hands or wet.

2. BASIC SAFETY RULES

gards dimensions, allowing you to meet different needs in the fi eld of air treatment. Any use not expres-sly stated in this manual is not al-lowed and consequently FAST does not assume any liability for damages incurred due to the failure to follow these instructions.

Document keeping

Keep the following installation in-structions with all the additional do-cuments that the user of the system will assume responsibility for the conservation of instructions so they are always available when needed.Please read this fi le, the installation must be performed by qualifi ed per-sonnel and prepared in accordance

with national legislation in force in the country of destinazione.Deve be instal-led in such a way as to make possible the maintenance and / or repairs. The warranty does not cover any costs due to ladders, scaffolding or other lifting systems which may be necessary for car-rying out repairs under warranty.

The warranty is void if they are not com-plied with the directions above.

Air handling units -FM series -

4� �Selection, installation, use and maintenance manual

Page 5: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

- available static pressure of supply and exhaust (if any) fans;- power and n° of poles of fan electric motors;- voltage, number of phases and cycles of the fan motors.

Each air handling unit is identifi ed by a se-rial number.This serial number is marked on the plate placed on the inspection door of the sup-ply fan section.On the same plate are indicated also:- air handling unit model;- supply and exhaust ( if any ) fan air fl ow;

3. IDENTIFICATION

XXXX� � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ! " # $ % & & & & ' ( � � ) * � � � � + , ' - . '! , / # 0 % 1 2 2 23 4 5 6 7 5 8 7 5 9 3 : ; 1 2 2� � � � � ' � � � � � � � � ' + �< = > ? @ A B C @ D @E @ F G @ H I J K L M N L L O M K MP L M M

Necessary supply and room conditions for installation:

Operating voltage ±10% than nominal voltage (EN 60204)

Frequency ±1% constant frequency ±2% for a short period (EN 60204)

Operating room temperature 5-40°C (EN 60204)

Operating room humidity From 30% to 95%, without condensation or icing (EN 60204)

Altitude Up to 1000 m above sea level (EN 60204)

Q R S T U VW X Y Y XZ [ W \ [ ] ^Z ^ _ X Y X ` a X b ] ` X _ _ c ^ d ] e fZ X d a _ g ` h f b g ` h f f X c ^ d ] e f i jk l m n o p nq m r s k l m n o p n

The identifi cation of the air handling unit through the serial number is man-datory to semplify the data search and give fast answers to the customer.

WARNING!

The logic of opening / closing of the dampers (if any) should be designed in such a way that does not lead to the central are-

as of excessive over-pressure / vacuum resulting in damage to the components of the plant itself or to the people and animals.

WARNING!

Keep the electrical panel and wiring away from elec-tric and magnetic fi elds which may interfere with type inverter, power sup-

ply line of heavy loads, etc.

WARNING!

Do not block the air ope-ning vents.Do not connect and di-sconnect any remote terminal with the exi-

sting power.

Air handling units -FM series -

5� �

Selection, installation, use and maintenance manual

Page 6: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

4. UNIT DESCRIPTION

The new air handling units structure presents a new softer and ergonomic line made of aluminium profi les with both externally and internally rounded edges. It is so possible to avoid internal dust heaps, typical of the sharp edges, with better quality and healthier treated air making also easier the unit cleaning.The FM series includes the following characteristics:- self supporting structure with aluminium framework and fiberglass reinforced nylon;

- unified panels with real thickness of 50 mm, manufactured with the most qualified materials (galvanized sheets, galvanized prepainted sheets, aluminium alloy, stainless steel) and injected poliurethane and rockwool for the insulation panel;- innovat ive systems for a i r humidifi cation with particular care of the air salubrity, to avoid developing of moulds and bacteria, and paying attention to the waste of water;

- all the components are inside the casing and therefore the treated airflow is completely separated from the external weather conditions that could penalize functions and performances of the air handling units;- a wide range of accessories and executions are provided to give to the custom an immediate view and check of all operating conditions of the air handling units.

t u v wt u x yt u w zt u w {t u | }t u ~ yt u � z w� ��� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �t u � vt u y zt u y ~t u v w� � � � � � � � � � � � � � � �

� � � �     � ¡ ¢ £ ¤ � ¥ ¦ � § ¨ ©   ª« ¬ ­ ®« ® ¬ ­

¯ ° ± ² ³¯ ° ² ´ ±¯ ° ² µ ¶¯ ° · ² ¸¯ ° ¹ ´ ²¯ ° ¹ µ ´¯ ° ¸ ² º¯ ° µ ´ ¹¯ ° µ µ ±» ¼½¾¿ À

¶ ³ ¶ Á ¶ ¶ ¶ ² ¶ Á ¶ ¶ ¶ ¹ ¶ Á ¶ ¶ ¶ µ ¶ Á ¶ ¶ ¶ ´ ¶ ¶ Á ¶ ¶ ¶ ´ ³ ¶ Á ¶ ¶ ¶¯ ° ´ ´ º¯ ° ´ · ²¯ ° ´ º ²¯ ° ³ ± ¸¯ ° ³ µ ¹Â Ã Ä Å Æ Ç È É Å Ê Ë Ì Í Î Ï Ð

Ñ Ò Ó Ô Õ Õ Ô Ö × Ø Ù Ó Ú Û Ô Ü Ý Þ Õ ßà á â ãä ã á âMod

elM

odel

Air flow [m3/h]

Air flow [m3/h]

face velocity [m/s]

face velocity [m/s]

Air handling units -FM series -

6� �Selection, installation, use and maintenance manual

Page 7: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

m/s for heating coils).The front dimensions and the lengths of the AHUs are modular according to a basic dimension of 160 mm (1/4 mo-dule), 320 mm (1/2 module) and 640 mm (1 module).Widths start from a single module up to a maximum of 7 modules.

5. TECHNICAL DATA

Dimensionsext.

Dimensionsint.

Coilssurface

Flow m3/s Flow m3/h INCR.

FM hm wm h w hi wi Face velocity [m/s] Face velocity [m/s]

mod mod mm mm mm mm m2 2,0 2,5 3 3,5 2,0 2,5 3,0 3,5

13 0,75 1 645 735 410 620 0,13 0,25 0,32 0,38 0,44 907 1.134 1.361 1.588

20 1 1 805 735 570 620 0,20 0,40 0,50 0,60 0,71 1.452 1.814 2.177 2.540 60,0%

28 1 1,25 805 895 570 780 0,28 0,56 0,70 0,84 0,97 2.004 2.506 3.007 3.508 38,1%

35 1 1,5 805 1055 570 940 0,35 0,70 0,87 1,04 1,22 2.506 3.132 3.758 4.385 25,0%

42 1 1,75 805 1215 570 1100 0,40 0,85 1,06 1,27 1,49 3.059 3.823 4.588 5.352 22,1%

50 1 2 805 1375 570 1260 0,50 1,00 1,25 1,50 1,76 3.612 4.514 5.417 6.320 18,1%

57 1,5 1,5 1125 1055 890 940 0,57 1,13 1,41 1,70 1,98 4.072 5.090 6.107 7.125 12,7%

69 1,5 1,75 1125 1215 890 1100 0,70 1,38 1,73 2,07 2,42 4.970 6.213 7.455 8.698 22,1%

82 1,5 2 1125 1375 890 1260 0,80 1,63 2,04 2,45 2,85 5.869 7.336 8.803 10.270 18,1%

105 1,5 2,5 1125 1695 890 1580 1,06 2,11 2,63 3,16 3,69 7.582 9.477 11.372 11.372 29,2%

119 2 2 1445 1375 1210 1260 1,20 2,38 2,98 3,57 4,17 8.577 10.722 12.866 15.010 13,1%

154 2 2,5 1445 1695 1210 1580 1,54 3,08 3,85 4,62 5,39 11.081 13.851 16.621 19.391 29,2%

194 2,5 2,5 1765 1695 1530 1580 1,93 3,89 4,86 5,83 6,80 13.997 17.496 20.995 24.494 26,3%

237 2,5 3 1765 2015 1530 1900 2,37 4,74 5,92 7,11 8,29 17.055 21.319 25.583 29.847 21,9%

286 3 3 2085 2015 1850 1900 2,86 5,72 7,16 8,59 10,02 20.609 25.761 30.913 36.065 20,8%

342 3 3,5 2085 2335 1850 2200 3,42 6,84 8,55 10,26 11,97 24.618 30.772 36.926 43.081 19,5%

413 3,5 3,5 2405 2335 2170 2200 4,13 8,25 10,32 12,38 14,44 29.711 37.139 44.566 51.994 20,7%

480 3,5 4 2405 2655 2170 2540 4,80 9,60 12,00 14,40 16,79 34.549 43.187 51.824 51.824 16,3%

547 3,5 4,5 2405 2975 2170 2860 5,47 10,94 13,68 16,41 19,15 39.388 49.235 59.081 68.928 14,0%

614 3,5 5 2405 3295 2170 3180 6,14 12,29 15,36 18,43 21,50 44.226 55.283 66.339 77.396 12,3%

681 3,5 5,5 2405 3615 2170 3500 6,81 13,63 17,04 20,44 23,85 49.064 61.331 73.597 85.863 10,9%

749 3,5 6 2405 3935 2170 3820 7,49 14,97 18,72 22,46 26,20 53.903 67.379 80.854 94.330 9,9%

816 3,5 6,5 2405 4255 2170 4140 8,16 16,32 20,40 24,48 28,55 58.741 73.427 88.112 88.112 9,0%

883 3,5 7 2405 4575 2170 4460 8,83 17,66 22,08 26,49 30,91 63.580 79.475 95.369 95.369 8,2%

Sizing of FM air handling units is based on a modular approach that permits the maxi-mum standardisation of components while offering a complete range of possible capa-cities.The selection of the the size shall be done in conformity to the air face velocity at coils (max 3 m/s for cooling coils and max 4

Heights are from a minimum of 0.75 modules to a maximum of 3.5 modu-les.

FM series is in compliance with EN1886 di-rective concerning mechanical resistance, air leakages, thermal performances and acoustic insulation.

The exact coupling between frame and panels allows to reach the air leakage va-lues according to the UNI EN 1886 leaka-ges, TÜV laboratories certified.

The declared performances are confirmed by EUROVENT certifica-tion.

In the table below are the technical data and dimensions of the 24 planned sizes for the FM central air handling.A module corresponds to a length of 640 mm.The table below shows:-Ahu size: FM code represents the dm2 of the coils front surface;- Nominal height of system in modules (hm);

-Nominal width of system in modules (wm);-Overall height of system including feet (h);-Overall width of system (w);-Internal height (hi);-Internal width (wi);-Face area of coils (S);-Flow in m3/s corresponding to face velo-

city on coils of 2, 2.5, 3 and 3.5 m/s;-Flow in m3/h corresponding to face velocity on coils of 2, 2.5, 3 and 3.5 m/s;- Percentage increase of the surface coil front and then the scale of size n compared to n-1.

Air handling units -FM series -

7� �

Selection, installation, use and maintenance manual

Page 8: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

13

20

28

35

42

50

57

69

82

105

119

154

194

237

286

342

413

480

883

816

749

681

614

547

735

895

1055

1215

1375

1695

2015

2335

2655

2975

3295

3615

3935

4255

4575

645

525

805

685 1005

1125 1445 1765

1325 1645 1965

2085 2405

2285

11.25

1.5

1.75

22.5

33.5

44.5

55.5

66.5

7

Larghezza [m

m]

Larghezza m

odulare [m

oduli]

0.75 1 1.5 2 2.5 3 3.5 Altezza [moduli]

Altezza telaio [mm]

Altezza con piedini/basamento [mm]

A B C D

A: sovrapponibili per trasporto

B: trasportabili in containerlongitudinalmente

C: trasportabili in containertrasversalmente

D: trasportabili su autocarrolongitudinalmente

The 24 available frames are shown in the following diagram. On this table also the dimensions for

transport are indicated considering a maximum dimension of 2400 mm (width of truck).

For bigger AHUs, it is necessary to split the unit in more sections.

A: Stackable for transport: FM 13 - FM 105

B:Transportable in container longitudinally: FM 13 - FM 286C: Transportable in container transversally: FM13 ÷ FM342

D: Transportable on truck longitudinally:FM13 ÷ FM413

Height [modules]

Frame height [mm]

Height feet / stand [mm]

Wid

th [m

odul

es]

Wid

th [m

m]

Air handling units -FM series -

8� �Selection, installation, use and maintenance manual

Page 9: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

The doors are fastened with 2 or 3 han-dles made of the same material according to the system height. Special panels may be supplied on re-quest to acustically insulate the fans sections (please contact the technical offi ce). These panels are supplied in the four fol-lowing forms as per price list:

6. COMPONENT DESCRIPTION

The perfect match between panel edges and frame provides a completely smooth surface with consequent benefi ts in terms of redu-ced dust and easier cleaning/maintenance.The panels are so sized that there are no ho-rizontal joints on the sides, thus improving overall rigidity.The inspection doors are mounted on a steel spindle and two hinges made of fi bre rein-forced nylon.

Type Exterior panel Insulation Interior panel

PZPGalvanised and

prepainted steel

Injected polyurethane

density 42 kg/m3

Galvanised steel

AAP Aluminum alloy

Injectedpolyurethane

density42 kg/m3

Aluminum alloy

XXPInox Aisi 304

steel

Injectedpolyurethane

density42 kg/m3

Inox Aisi 304 steel

PXPGalvanised and prepainted stee

Injectedpolyurethane

density42 kg/m3

Stainless SteelAisi 304

XZPInox Aisi 304

steel

Injectedpolyurethane

density42 kg/m3

Galvanised steel

AXP Aluminum alloy

Injectedpolyurethane

density42 kg/m3

Inox Aisi 304 steel

KEY

1a letter Exterior panel

2a letter Interior panel

3a letter Insulation

PANELS

The casing is a bearing frame with sealed panels.Panel thickness is 50 mm.The panels are fastened by means of lo-cking profi les which are fi xed into the fra-me: this system ensures uniform pressure on the panel/frame seals and hence impro-ved airtightness. Panels can be supplied also with mineral wool insulation and different thicknesses.

Sample abbreviations:PZL: P = Galvanised and prepainted steel, Z = Galvanised steel, L = Rock woolPXP: P = Galvanised and prepainted steel, X = Inox Aisi 304 steel, P = Injected polyurethane with density 42 kg/m3

NOTE: FOR ALL TYPES OF USED MATERIAL IT IS NECESSARY TO REMOVE THE PROTECTIVE FILM WHEN INSTALLING THE UNIT.

The panels mentioned above represent just some of the available types.The complete range of panels is included in the selection program.

Type Exterior panel Insulation Interior panel

PZLGalvanised and prepainted stee

Rock wool density

40 kg/m3Galvanised steel

AAL Aluminum alloyRock wool

density40 kg/m3

Aluminum alloy

XXLInox Aisi 304

steel

Rock wool density

40 kg/m3Inox Aisi 304 steel

PXLGalvanised and prepainted stee

Rock wool density

40 kg/m3Inox Aisi 304 steel

XZLInox Aisi 304

steel

Rock wool density

40 kg/m3Galvanised steel

AXL Aluminum alloyRock wool

density40 kg/m3

Inox Aisi 304 steel

Air handling units -FM series -

9 å æSelection, installation, use and maintenance manual

Page 10: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

FRAME

The frame is built of UNI 6060 aluminium alloy profiles connec-ted by fibreglass reinforced with nylon corner pieces; the fastening corners are made of extruded alu-minum and fastening is granted by metric screws M6 with hexagon head cap.These profiles are completely closed and therefore the thermal bridges are reduced at a mini-mum as the air by-passes along the internal components. For heavy operating conditions the frame can be supplied also with thermal cut.

The overall length of the housing is calculated modularly.

1 unit = 640 mm

The frame is also available in ano-dized aluminum UNI 6060 with or without thermal break.

BASE

The base is constant for all sizes and is made of galvanized sheet steel (or other materials on re-quest).

ROOF

If the air handling unit is located outside, it is absolutely necessary to select a protection roof. If re-quired it is carried out as standard pre-painted galvanized sheet me-tal with the same characteristi-cs used for the panels. Different types of material could be reque-sted.

VISTE FRONTALI VISTE DALL'ALTOSEZIONE MONOBLOCCO

SEZIONE INIZIALE

SEZIONE INTERMEDIA

Side View

Side View

Side View

Top View

Top View

Top View

Single section unit

Single section unit

Single section unit

Air handling units -FM series -

10 å æSelection, installation, use and maintenance manual

Page 11: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

THREE - WAY MIXING BOXES

Confi gurations for three-way mixing boxes are as follows:• two upper dampers and one internal recirculation damper;• two front dampers and a horizon-tal internal recirculation damper (for overlapping units);• two internal side dampers and one internal recirculation damper (confi -guration for exhaust and fresh air in-takes without pipes).

AIR INLETS

The dampers are fully in aluminium with aerofoil blade. On request dam-pers can be supplied with sealing ga-skets on both the edge of the blade and the side panels of the frame. In the fi rst execution the leakage is less than 5% at a differential pressure of 1000 Pa; in the second execution the leakage is less than 1%.

When the dampers are external to the casing, they are fi xed to the framework of the AHU. When the dampers are internal to the casing, they are fi xed to the panel.

Damper position Dimension Installation

Front Full size External

Front Partial External or internal

Upper Partial External or internal

Lower Partial Internal

Rh side Partial External

Lh side Partial External

Damper position Damper installation

Front and Upper External or internal

Front and Lower Internal

Upper and Rh Side External

Upper and Lh Side External

Front and Rh Side External

Front and Lh Side External

Side + Side External

Front + Front External

The following types of front damper can be supplied:

Possible confi gurations for 2-way mixing sections:

FRONT DAMPERS

Available types are listed in the table below.The damper can be not required: an alternative suction may provide an opening only, a fl ange or a blank pa-nel on which to make on site a proper opening.

MIXING BOXES

The possible confi gurations are listed in the table below.

for a remote indication of the actual condition of the effi ciency fi lter cells. The following table shows the classifi ca-tion of the fi lters.

The selection of the fi lter is crucial in or-der to obtain a good quality of the trea-ted air and hygienic conditions of the air system.In the following pages we describe the characteristics of the different fi lter types and tables for the selection, but the

7. FILTRATION

correct selection of the fi lters, accor-ding to the specifi c requirements, is responsability of the plants designer. Furthermore, for an effi cient mainte-nance of the fi lters, it is important to provide accessories like differential manometers and pressure switches

Air handling units -FM series -

11 å æSelection, installation, use and maintenance manual

Page 12: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

PREFILTERS CELLS

The prefi lters with cells on rails for side removal are the most used type in the air handling units for their conve-nience and availability in the market.The cells can be synthetic or metallic according to the use and required ef-fi ciency.

Classifi cation according to EN 779

Initial opacimetric effi ciency (EA) EA < 20 % EA >= 20 %

CharacteristicGravimetriceffi ciency

Opacimetriceffi ciency

Am (%) Em (%)

Filter group Filters class Class limits

Big powder (G)

G 1 Am < 65 -

G 2 65 <= Am < 80 -

G 4 Am >= 90 -

Fine powder (F)

F 5 - 40 <= Em < 60

F 6 - 60 <= Em < 80

F 7 - 80 <= Em < 90

F 8 - 90 <= Em < 95

F 9 - Em >= 95

HEPA and ULPA fi lters classifi cation according to EN 1822

Filter class Overalleffi ciency value

Local effi ciency value

Effi ciency (%) Effi ciency (%)

H 10 85 -

H 11 95 -

H 12 99,5 -

H 13 99,95 99,75

H 14 99,995 99,975

U 15 99,9995 99,9975

U 16 99,99995 99,99975

U 17 99,999995 99,9999

FM series are planned for the following types of fi lters:-modular fi lters with aluminium mesh;-modular fi lters with polyester fi bre with synthetic resin mounted on rails;-modular fi lters with polyester fi bre with synthetic resin mounted on rails (with bag fi lters);

Cells Cells Cells Face area

Velocity

(at 3 m/s

at coil)Length 592 490 287

Height 592 592 592 m2 m/s

FM 13 1 0,17 2,22

FM 20 1 0,29 2,08

FM 28 1 0,29 2,88

FM 35 1 0,29 3,60

FM 42 2 0,34 3,75

FM 50 2 0,58 2,59

FM 57 1 2 0,69 2,46

FM 69 1 1 1 0,81 2,56

FM 82 2 2 1,04 2,35

FM 105 2 3 1,21 2,61

FM 119 4 1,40 2,55

FM 154 4 2 1,74 2,65

Cells Cells Cells Face area

Velocity

(at 3 m/s

at coil)Length 592 490 287

Height 592 592 592 m2 m/s

FM 194 4 4 2,08 2,80

FM 237 6 3 2,61 2,72

FM 286 9 3,15 2,72

FM 342 9 3 3,66 2,80

FM 413 9 6 4,17 2,97

FM 480 12 4 4,89 2,95

FM 547 12 7 5,39 3,04

FM 614 15 5 6,11 3,02

FM 681 15 8 6,62 3,09

FM 749 18 6 7,33 3,06

FM 816 18 9 8,35 2,93

FM 883 21 7 8,55 3,10

-soft bag fi lters with sub-micronic fi breglass reinforced with scrim ba-cking L=550; -rigid bag fi lter with fi breglass L=290;-roll fi lter with fi breglass with syn-thetic resin;

-absolute modular fi lters with micro fi -breglass/cellulose with special resins;-modular odour absorption fi lters with activated carbon; -germicidal lamp.

The cells can be easily cleaned with immersion in water with common soap and can be reused after rinse. The metallic fi lters, normally used for air with fat steams, can be wa-shed with proper solvents and dried with compressed air.Quantity and dimensions are indica-ted in the following table.

Air handling units -FM series -

12 å æSelection, installation, use and maintenance manual

Page 13: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

ROLL FILTERS

The roll fi lters are used as an al-ternative to the cell fi lters to avoid periodic maintenance of the fi lters. Their effi ciency is similar to the syn-thetic cell fi lters.However they have the big advan-tage to renew itself automatically according to the signal (differential pressure switch) which arrange for the rolling up of the dirty part oand placing the clean part in the airfl ow.

FM N° rolls Rotation

H

fi lter

mm

L

roll 1 mm

L

roll 2

mm

Face area m2 Vel.(at 3m/s at

coil) m/s

13 - 50 Not available

57 1 Horizontal 1200 830 0,438 3.87

69 1 Horizontal 1200 830 0,438 4,73

82 1 Horizontal 1200 830 0,438 5.58

105 1 Horizontal 1500 830 0.657 4,81

119 1 Vertical 1200 1230 0,678 5.27

154 1 Vertical 1200 1530 0,585 5.38

194 1 Vertical 1500 1530 1,287 4,53

237 1 Vertical 1500 1830 1,557 4,56

286 1 Vertical 1800 1830 2,076 4,14

342 1 Vertical 1800 2130 2,436 4,21

413 1 Vertical 2100 2130 3,045 4,07

480 2 Vertical 2100 1230 1230 3,39 4,25

547 2 Vertical 2100 1530 1230 3,84 4,27

614 2 Vertical 2100 1530 1530 4,29 4,30

681 2 Vertical 2100 1830 1530 4,74 4,31

749 2 Vertical 2100 1830 1830 5,19 4,33

816 2 Vertical 2100 2130 1830 5,64 4,34

883 2 Vertical 2100 2130 2130 6,09 4,35

The fi lter life, that can’t be reclaimed, strictly depends on the quantity of powder in the air, but guarantees anyway long maintenance intervals with alarm signal which can be sent also to a remote control panel.

The roll fi lter is supplied complete with electric switchboard.

Air handling units -FM series -

13 å æSelection, installation, use and maintenance manual

Page 14: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

ABSOLUTE FILTERS

The absolute fi lters are generally used to guarantee aseptic air condi-tions and air salubrity.The most common applications are related to AHUs for hospitals (ope-rating theatre and similar), for elec-tronic and chemical industry.

These fi lters must be placed after the supply fan sections and must be preceded by higher effi ciency fi lters (i.e. cell fi lters and soft bag fi lters). It is advisable to provide, as accessory, a differential pressure switch that indicates the fi lter fouling in order to plan its substitution.Particular care is given to the design of the seating de-vices for the cells to avoid air by-pass and to make the maintenance easier.

Cells Cells Cells Face area

Velocity

(at 3 m/s

at coil)Lengt 592 490 287

Height 592 592 592 m2 m/s

FM 13 1 0,17 2,22

FM 20 1 0,29 2,08

FM 28 1 0,29 2,88

FM 35 1 0,29 3,60

FM 42 1 0,29 4,39

FM 50 2 0,58 2,59

FM 57 1 2 0,63 2,69

FM 69 1 2 0,63 3,29

FM 82 2 2 0,92 2,66

FM 105 2 3 1,09 2,90

FM 119 2 2 1,28 2,79

FM 154 2 2 1 1,45 3,18

Cells Cells Cells Face area

Velocity

(at 3 m/s

at coil)Lengt 592 490 287

Height 592 592 592 m2 m/s

FM 194 4 4 2,08 2,80

FM 237 6 3 2,61 2,72

FM 286 9 3,15 2,72

FM 342 9 3 3,66 2,80

FM 413 9 6 4,17 2,97

FM 480 12 4 4,89 2,95

FM 547 12 7 5,39 3,04

FM 614 15 5 6,11 3,02

FM 681 15 8 6,62 3,09

FM 749 18 6 7,33 3,06

FM 816 18 9 7,84 3,12

FM 883 21 7 8,55 3,10

Cells Face area

Velocity (at 3

m/s at coil)Lenght 592 490 287 287

Height 592 592 592 490 m2 m/s

FM 13 1 0,17 2,22

FM 20 1 0,29 2,08

FM 28 1 0,29 2,88

FM 35 1 1 0,29 3,60

FM 42 1 1 0,29 4,39

FM 50 2 0,58 2,59

FM 57 1 2 0,63 2,69

FM 69 1 2 0,63 3,29

FM 82 2 2 0,92 2,66

FM 105 2 3 1,09 2,90

FM 119 2 2 1,28 2,79

FM 154 2 2 1 1 1,45 3,18

Cells Face area

Velocity (at 3

m/s at coil)Lenght 592 490 287 287

Height 592 592 592 490 m2 m/s

FM 194 4 4 1 2,08 2,80

FM 237 6 3 2,61 2,72

FM 286 9 3,15 2,72

FM 342 9 3 3,66 2,80

FM 413 9 6 1 4,17 2,97

FM 480 12 4 4,89 2,95

FM 547 12 7 1 5,39 3,04

FM 614 15 5 6,11 3,02

FM 681 15 8 1 6,62 3,09

FM 749 18 6 7,33 3,06

FM 816 18 9 1 7,84 3,12

FM 883 21 7 8,55 3,10

vent by-pass of the not fi ltered air. The extraction is possible in the inspection room upstream the cells to allow an easy access to the maintenance staff.Special executions for specifi c uses (i.e. hospitals, pharmaceutical industry, chemical industry etc) and particular requirements can be studied by our tech-nical offi ce upon request.

BAG FILTERS

Bag fi lters are available as soft bag or rigid fi lters according to the project requirements. They should generally be fi tted togheter with pre-fi lters, cells or roll types, to im-prove their life catching the pollu-ting particles. They can be followed by fi lters with higher effi ciency. The bag fi lters are seated in a bearing frame with neoprene gasket to pre-

Air handling units -FM series -

14 å æSelection, installation, use and maintenance manual

Page 15: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Cells Cells Cells Face area

Velocity

(at 3 m/s

at coil)Lengt 592 490 287

Height 592 592 592 m2 m/s

FM 13 1 0,17 2,22

FM 20 1 0,29 2,08

FM 28 1 0,29 2,88

FM 35 1 0,29 3,60

FM 42 1 0,29 4,39

FM 50 2 0,58 2,59

FM 57 1 2 0,63 2,69

FM 69 1 2 0,63 3,29

FM 82 2 2 0,92 2,66

FM 105 2 3 1,09 2,90

FM 119 2 2 1,28 2,79

FM 154 2 2 1 1,45 3,18

Cells Cells Cells Face area

Velocity

(at 3 m/s

at coil)Lengt 592 490 287

Height 592 592 592 m2 m/s

FM 194 4 4 2,08 2,80

FM 237 6 3 2,61 2,72

FM 286 9 3,15 2,72

FM 342 9 3 3,66 2,80

FM 413 9 6 4,17 2,97

FM 480 12 4 4,89 2,95

FM 547 12 7 5,39 3,04

FM 614 15 5 6,11 3,02

FM 681 15 8 6,62 3,09

FM 749 18 6 7,33 3,06

FM 816 18 9 7,84 3,12

FM 883 21 7 8,55 3,10

reduced need for maintenance, the low energy consumption and the possibility of using them up to very high operating temperatures.For further information please con-tact the Technical Department.

ELECTROSTATIC FILTERS

The electrostatic fi lters are used when elevate fi ltrating performan-ces are requested, even on very small particles, together with limi-ted pressure drops.The system uses polarised electro-des, positively loaded and fed with

roughly 10.000V tension and me-tallic plates loaded in the opposi-te way. The creation of an intense electrostatic fi eld generates positi-ve ions which capture the polluting particles present in the air.The advantages deriving from the use of electrostatic fi lters are the

The sections are complete with lam-ps, wiring and terminal box for the connection to electric current.

GERMICIDAL LAMPS

They are generally used in series with very high effi ciency fi lters and their use is advisable when bacte-ria and germs, always present in the air, must be controlled on the sup-ply and exhaust air.

The lamps, their power and location have been defi ned by our technical offi ce for most common applica-tions; particular solutions can be studied for special purposes.

OUR TECHNICAL DEPARTMENT CAN VERIFY FURTHER FILTRATION SYSTEMS NOT LISTED ABOVE.

ACTIVATED CARBON FILTERS

The activated carbon fi lters are used for the absorption of odours and toxic substances from the ai-rfl ow both on supply and exhaust air (i.e. human odours, odours from kitchens, some components of smo-ke, idrocarbon vapours diluted in the air etc.).

These fi ltering systems must be be pre-ceded by higher effi ciency fi lters to improve their life and assure the best effi ciency.The sections are perfectly accessible for the maintenance and can be use rechargeble or disposable cells.

Air handling units -FM series -

15 å æSelection, installation, use and maintenance manual

Page 16: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Standard designs:P6030 Copper-aluminium

Non-standard designs:Copper-copper;Prepainted Copper-aluminium;Copper-tin coated copper;Fe-Al

Type:water;superheated water;steam;direct expansion.

Access:Side removal (together with conden-sate drain pan for the cooling coils).

The heat exchangers coils are the most important elements in the air handling units, since in the coils themselves is the heat exchange between the primary fl uid (hot or cold water, evaporating or conden-sating refrigerant) and the seconda-ry fl uid,i.e. the air to be handled.The coils must be sized according to the treatment required to the AHU and according to the materials re-quired for the specifi c evironmental conditions, following the requests of the plant designer.The coils are selected in conformity to the range and the types provi-ded for each AHU size. For different executions, our technical offi ce can realize particular projects.

FMSingle zone Heating for dual duct sections

Face area[m2]

Height[mm]

Lenght[mm]

Tubes/Rows[n°]

Face area[m2]

Height[mm]

Lenght[mm]

Tubes/Rows[n°]

13 0,126 300 420 5 0,076 180 420 3

20 0,202 480 420 8 0,126 300 420 5

28 0,278 480 580 8 0,174 300 580 5

35 0,348 480 725 8 0,218 300 725 5

42 0,425 480 885 8 0,266 300 885 5

50 0,502 480 1045 8 0,314 300 1045 5

57 0,566 780 725 13 0,348 480 725 8

69 0,690 780 885 13 0,425 480 885 8

82 0,815 780 1045 13 0,502 480 1045 8

105 1,053 780 1350 13 0,648 480 1350 8

119 1,191 1140 1045 19 0,752 720 1045 12

154 1,539 1140 1350 19 0,972 720 1350 12

194 1,944 1440 1350 24 1,053 780 1350 13

237 2,369 1440 1645 24 1,283 780 1645 13

286 2,862 1740 1645 29 1,579 960 1645 16

342 3,419 1740 1965 29 1,886 960 1965 16

413 4,127 2100 1965 35 2,240 1140 1965 19

480 4,799 2100 2285 35 2,605 1140 2285 19

547 5,471 2100 2605 35 2,970 1140 2605 19

614 6,143 2100 2925 35 3,335 1140 2925 19

681 6,815 2100 3245 35 3,699 1140 3245 19

749 7,487 2100 3565 35 4,064 1140 3565 19

816 8,159 2100 3885 35 4,429 1140 3885 19

883 8,831 2100 4205 35 4,794 1140 4205 19

8. COILS

Condensate drain pans:Made of aluminium alloy or stainless steel with 1” G side drain discharge (on panel). They are used for coils only, and therefore in the case of cold coil followed by humidifi cation coil will be necessary two drain pans, joined each other by a aluminium water shield.

Rows: Standard coils are available with 1,2,3,4,5,6,7,8 rows and various circu-its as shown in the following table.Please contact us for non-standard row number, circuit or fi n spacing.

WATER COILSThe coils features are listed below (ge-ometry P6030).

Air handling units -FM series -

16 å æSelection, installation, use and maintenance manual

Page 17: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Manifolds diameter for multizone heating, P6030 water coils (according to the circuits)

FM H L Manifold diameter

mm mm R1,2 R2,2 R3,2 R4,1 R4,2 R6,1 R6,2 R8,1 R8,2

13 300 420 1” 1/2" 1" 1" 1" 1" 1" 1" 1"

20 480 420 1" 1" 1" 1" 1" 1" 1" 1" 1"

28 480 580 1” 1" 1" 1" 1" 1" 1" 1" 1"

35 480 725 1" 1" 1" 1" 1" 1" 1" 1" 1"

42 480 885 1" 1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2"

50 480 1045 1" 1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2"

57 780 725 1" 1" 1" 1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2"

69 780 885 1" 1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2"

82 780 1045 1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2-1/2" 2-1/2"

105 780 1350 1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2-1/2" 2-1/2"

119 1140 1045 1" 1-1/2" 2" 2" 2" 2" 2" 2-1/2" 2-1/2"

154 1140 1350 1" 1-1/2" 2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2"

194 1440 1350 1-1/2" 1-1/2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3"

237 1440 1645 1-1/2" 1-1/2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3"

286 1740 1645 1-1/2" 2-1/2" 2" 2-1/2" 2-1/2" 3" 3" 4" 4"

342 1740 1965 1-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3" 4" 4"

413 2100 1965 2" 2-1/2" 2-1/2" 3" 3" 3" 3" 4" 4"

480 2100 2285 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

547 2100 2605 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

614 2100 2925 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

681 2100 3245 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

749 2100 3565 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

816 2100 3885 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

883 2100 4205 2" 2-1/2" 2-1/2" 3" 3" 4" 4" 4" 4"

FM H L Manifold diameter

mm mm R1,3 R2,3 R3,3 R4,3

13 180 420 1" 1" 1" 1"

20 300 420 1" 1" 1" 1"

28 300 580 1" 1" 1" 1"

35 300 725 1" 1" 1" 1"

42 300 885 1" 1" 1" 1"

50 300 1045 1" 1" 1" 1"

57 480 725 1" 1" 1" 1"

69 480 885 1" 1" 1" 1"

82 480 1045 1" 1" 1" 1"

105 480 1350 1" 1" 1" 1"

119 720 1045 1" 1" 1" 1-1/2"

154 720 1350 1" 1" 1" 1-1/2"

194 780 1350 1" 1" 1-1/2" 2"

237 780 1645 1" 1" 1-1/2" 2"

286 960 1645 1" 1" 1-1/2" 2"

342 960 1965 1" 1" 1-1/2" 2"

413 1140 1965 1" 1-1/2" 1-1/2" 2"

480 1140 2285 1" 1-1/2" 1-1/2" 2"

547 1140 2605 1" 1-1/2" 1-1/2" 2"

614 1140 2925 1" 1-1/2" 1-1/2" 2"

681 1140 3245 1" 1-1/2" 1-1/2" 2"

749 1140 3565 1" 1-1/2" 1-1/2" 2"

816 1140 3885 1" 1-1/2" 1-1/2" 2"

883 1140 4205 1" 1-1/2" 1-1/2" 2"

Manifolds diameter for single-zone, P6030 water coils (according to the circuits)

Air handling units -FM series -

17 å æSelection, installation, use and maintenance manual

Page 18: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

DIRECT EXPANSION COIL

FMGeometry Face area Height Lenght Tubes/rows Circuits

[m2 ] [mm] [mm] [n°] R 3.1 R 3.2 R 4.1 R 4.2 R 6.1 R 6.2 R 8.1 R 8.2

13 P2519 0.126 300 420 12 3 6 3 6 4 6 6 12

20 P2519 0.189 450 420 18 3 6 6 9 6 9 6 9

28 P2519 0.261 450 580 18 3 6 6 9 6 9 9 12

35 P2519 0.326 450 725 18 6 9 6 9 9 18 9 12

42 P2519 0.398 450 885 18 6 9 6 9 9 18 12 18

50 P2519 0.470 450 1045 18 6 9 6 9 9 18 12 18

57 P2519 0.544 750 725 30 7 9 10 15 15 18 15 20

69 P2519 0.664 750 885 30 7 9 10 15 15 18 15 20

82 P2519 0.784 750 1045 30 9 15 15 20 18 30 20 30

105 P2519 1.013 750 1350 30 9 15 15 20 22 30 24 30

119 P2519 1.176 1125 1045 45 13 22 22 30 22 45 30 36

154 P2519 1.519 1125 1350 45 13 22 22 30 27 45 36 45

194 P2519 1.958 1450 1350 58 22 29 29 58 29 58 58 77

237 P2519 2.385 1450 1645 58 29 43 29 58 43 58 58 77

286 P2519 2.879 1750 1645 70 35 52 35 70 52 70 70 140

342 P2519 3.439 1750 1965 70 35 52 46 70 70 105 70 140

413 P6030 4.127 2100 1965 35 10 17 14 35 21 35 28 35

480 P6030 4.799 2100 2285 35 17 26 17 35 21 35 35 70

547 P6030 5.471 2100 2605 35 17 26 23 35 35 52 35 70

614 P6030 6.143 2100 2925 35 17 26 23 35 35 52 35 70

681 P6030 6.815 2100 3245 35 26 52 23 35 35 52 46 70

749 P6030 7.487 2100 3565 35 26 52 23 35 35 52 46 70

816 P6030 8.159 2100 3885 35 26 52 35 70 35 105 46 70

883 P6030 8.831 2100 4205 35 26 52 35 70 35 105 46 70

The geometric characteristics are listed in the table below.

Air handling units -FM series -

18 å æSelection, installation, use and maintenance manual

Page 19: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

The Dt refer to the nominal fl ow (corresponding to a face velocity of 2.5 m/s at coils).

1° Step 2° Step 3° Step 4° Step

FMElements Heating cap. Dt Elements Heating cap. Dt Elements Heating cap. Dt Elements Heating cap. Dt

n° W °C n° W °C n° W °C n° W °C

13 3 2.100 5,5 6 4.200 11,0 9 6.300 16,5 12 8.400 22,0

20 3 2.100 3,4 9 6.300 10,3 12 8.400 13,7 18 12.600 20,6

28 3 3.000 3,6 9 9.000 10,7 12 12.000 14,2 18 18.000 21,3

35 3 3.600 3,4 9 10.800 10,2 12 14.400 13,6 18 21.600 20,5

42 3 3.900 3,0 9 11.700 9,1 12 15.600 12,1 18 23.400 18,2

50 3 4.500 3,0 9 13.500 8,9 15 22.500 14,8 21 31.500 20,7

57 6 7.200 4,2 15 18.000 10,5 21 25.200 14,7 27 32.400 18,9

69 6 7.800 3,7 18 23.400 11,2 24 31.200 14,9 33 42.900 20,5

82 6 9.000 3,6 18 27.000 10,9 24 36.000 14,6 33 49.500 20,0

105 6 10.800 3,4 18 32.400 10,1 27 48.600 15,2 36 64.800 20,3

119 9 13.500 3,7 27 40.500 11,2 36 54.000 14,9 45 67.500 18,7

154 9 18.000 3,9 27 54.000 11,6 36 72.000 15,4 45 90.000 19,3

194 12 24.000 4,1 30 60.000 10,2 45 90.000 15,3 60 120.000 20,3

electric batteries are used also as anti-frost device to protect fi lters or water coils without glycols.The electric batteries are manufactured with armoured steel fi nned tubes and fed at 380 V

ELECTRIC BATTERIES

The electric batteries are often used for small heating loads in the small and medium size AHUs, mainly for the summer re-heating when it is not possible or convenient to start the tra-ditional system for hot water production. The

They are equipped with limit thermostat with automatic reset ad safety thermostat with manual reset.Capacitis and n° of elements are listed in the following tables.

For electric coils upper size 194, please contact the technical dep. FAST SpA.

Air handling units -FM series -

19 å æSelection, installation, use and maintenance manual

Page 20: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

AIR WASHER

The system is made up by two opposi-te ramps, on which nebulizing nozzles are placed, included in a waterproof aluminium alloy (standard) or stain-less steel chamber internal to the ca-sing of the air-handling unit. The sy-stem is complete with connections and pump/s and main pan (400 mm high) with drain hole, overfl ow hole, fi lter, fl oating valve, drop eliminators before and after the ramps. It is possible also to provide a model with 2 nozzle ramps and one recirculation pump, or 2 noz-zle ramps and 2 recirculation pumps.

WATER/AIR COMPRESSED AIR HUMIDI-FICATION

The system is made up of special ato-mised nozzles, fed with compressed water and air in separate lines. An accurate installation and the respect of the minimum distances with the following components in the air fl ow allow for a nebulization of the water in extremely small droplets, thus avoi-ding the risk of condensation. In this way very elevate effi ciencies are ob-tained and, thanks to the automatic cleaning of the nebulizing heads, are low maintenance costs.The system is supplied complete with all necessary components mounted for the correct operation (ramp, self-clea-ning nozzles, pipes and feeding cabinet with modulating control).

ULTRASOUND HUMIDIFICATION

The humidifi cation system with ultra-sounds provides for the use of a high-frequency piezoelectric transducer which, vibrating at extremely high frequency generates the cavitation of the water with its subsequent nebu-lization. The main advantages of this system are: high effi ciency, low ener-getic consumption, reduced water con-sumption, long duration, installation easiness and safety of usage.For further information please contact our Technical Department.

The humidifi cation is a very important tre-atment to obtain an optimum indoor air quality. The humidifi yng system described below shall be selected in conformity to their use and to the available fl uid.It is obvious that the fact that moulds and bacteria fi nd a favourable ambient on hu-mid surfaces and in stagnant water must be taken in account: therefore FAST pro-vides drainable pans and small pump traps to limit the quantity of water in the sy-stem.The evaporating decks are of the anti-mould type and can be also equipped with humidity sensor to stop the waterfl ow as soon as the evaporating deck is wet, limi-ting the water consumption and maintai-ning the drain pan almost dry.The steam system with centralized steam production are particularly indicated for small fl ows and for applications where the air healthiness is very important (i.e. ho-spitals).

EVAPORATING DECK HUMIDIFICATION

The following constructive types may be provided for:

a - paper evaporating deck thick 100 mm and water;b - paper evaporating deck thick 200 mm and water;c - paper evaporating deck thick 100 mm and recirculating pump;d - paper evaporating deck thick 200 mm and recirculating pump;e - PVC evaporating deck thick 100 mm and recirculating pump;f - PVC evaporating deck thick 200 mm and recirculating pump;g - paper evaporating deck thick 100 mm and water control through humidity sensor at evaporating deck and solenoid valve;h - paper evaporating deck thick 200 mm and water control through humidity sensor at evaporating deck and solenoid valve;

STEAM HUMIDIFICATION

The following constructive types may be provided for:

a - with steam manifold only;b - with steam producer.

9. HUMIDIFICATION

CONDENSATE DRAIN PAN

- For compressed water and air humidifi -cation and steam humidifi cation: alumi-nium alloy or stainless internal drain pan (h=50 mm) with 1” G drain;- For evaporating deck humidifi cation (type a. or b.): aluminium alloy or stain-less steel internal drain pan (h=50 mm) and fi berglass reinforced polypropilene pump trap with 1” GJ drain and 1” GJ supply;- For wet deck humidifi cation (type g. or h.): aluminium alloy or stainless steel internal drain pan (h=50 mm) and fi ber-glass reinforced polypropilene trap with 1” GJ discharge and integration with so-lenoid valve; - For wet deck humidifi cation (type c.,d.,e.,f.): aluminium alloy internal drain pan (h=50 mm) and fi berglass rein-forced polypropilene pump trap with 1” GJ discharge and integration with fl oa-ting valve;- For air washer humidifi cation: stainless steel water pan (h=400 mm).

For sizes FM13, FM20, FM28 the pump trap is manufactured in aluminium alloy.

DROP SEPARATORS

The drop separator, carefully designed to obtain the maximum effi ciency of water drop treatment, because of the required treatments generated inside the unit (humidifi cation and dehumidi-fi cation), is provided as optional com-ponent or as standard.Droplet eliminators are always lateral-ly accessible and are necessary in the following cases:- cooling coils: air velocity more than 2.6 m/s;- spray deck humidifi ers: air velocity more than 2.6 m/s;- steam and compressed water/air hu-midifi cation;- air washers (with inlet fl ow rectifi er).

Materials:- galvanized steel;- aluminium alloy;- 304 AISI steel;- poly-propylene (standard).

Air handling units -FM series -

20 å æSelection, installation, use and maintenance manual

Page 21: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

-Sizes:fan sizes are selected according to the required capacity and pressure. The si-zes are shown in the following table for each size of air handling unit, with re-ference to the outside diameter of the wheel in mm.

-Orientation:available fan orientations are shown in the following table. An even fi nal number means right orien-tation; an odd fi nal number refers to left orientation.The choice of the orientation depends on the real plant confi guration of the AHU and shall consider more than the inspection side of the AHU also the la-yout of the supply ducts to minimize the pressure drop at the AHU-duct junction.

FANS

The fans are the most important compo-nents in the air handling units since the fan-motor assembly is the only moving part and therefore subject to possible problems of wear, noise, manitenance, safety. A correct selection for size and models together with a careful selection of the supplier assures an optimum per-formance for the AHU’s life.FAST provides for each size of AHU dif-ferent fan sizes and models to better match the plant requirements in terms of effi ciency, noise level and operating fl exibility.

- Series:all fan units are in complieance with se-ries DIN 323 R20 (square outlet) of the following types:- forward curved blades;- backward curved blades;- backward curved blades with air foil profi le.

10. FAN SECTIONS

COMPATIBILITY TABLE FANS / AHUs

Fan sizesFM

13 180

20 200 225

28 200 225 250

35 225 250 280

42 225 250 280

50 250 280

57 280 315 355 400

69 315 355 400

82 315 355 400

105 355 400

119 400 450 500 560

154 450 500 560

194 500 560 630 710

237 560 630 710

286 560 630 710 800

342 630 710 800 900

413 630 710 800 900

480 710 800

547 710 800 900

614 800 900 1000

681 NOT AVAILABLE IN THE BACKWARD BLADES VERSION 900 1000

749 900 1000

816 900 1000

883 900 1000

- Anti-vibration mounts:

standard versions have rubber (60°Sh) anti-vibration mounts and anti-vibra-tion seals on the outlet port. From fan size 450 up, the system can be optio-nally supplied with spring supports (minimum efficiency 80%). In this case the dimensions may be subject to modification, with reference to the indicated ones (please contact our Technical Department).

The ventilating sections are supplied as standard with:safety guard behind inspection door replacing enclosure panel;earth wire between motor cradle and main frame.

Air handling units -FM series -

21 å æSelection, installation, use and maintenance manual

Page 22: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

FAN ORIENTATION

PLUG FANS

The high-performance centrifugal whe-els are free for use without protection shell and are suitable for clean or limi-tedly-dusty air treatment.Different wheels types may be used:• sheet steel wheels with painted back-ward-curved blades;• sheet steel wheels with painted back-ward-curved airfoil blades;• backwards wheels made of polyamide reinforced with glass fi ber.

- Size: the fans size is chosen according to the required air fl ow and pressure. The available sizes are listed in the be-low table for each AHU size. The marks indicate the external diameter of the wheel in mm;

In addition to the models just presen-ted, FAST S.p.A. designs also AHUs with plug fans; these components are cha-racterized by very signifi cant features including:

• Optimized designs in terms of aerody-namics and noise level;• Overall reduced length, thanks to the use of compact form;• Low weight of the wheel, therefore low strain of the motor bearings;• Pressure sensors, supplied as standard for all sizes;• Easy cleaning of the fan section;• High performance due to the lack the of the traditional belt-pulley transmis-sion.

- Directions: This type of fan allows for the air supply to the front, top, bot-tom or side depending on the position of the panels of the section.

- Antivibration dampers: the standard execution includes rubber antivibra-tion dampers (60 ° Sh) and antivibra-tion canvas on the suction opening vent.

- Operating temperature from -20 ° C to + 60 ° C with a steel wheel and from - 20 ° C to + 40 ° C with polyamide wheel.

- The PLUG FANS inspection and main-tenance are granted by a removable panel equipped with security screws to prevent access to unauthorized or unqualifi ed personnel.

Even with the installation of this type of fan, the fan sections are equipped with a serial earthing ground between the engine and base frame.

Air handling units -FM series -

22 å æSelection, installation, use and maintenance manual

Page 23: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Motors are single speed (2, 4, 6 po-les depending on fan speed) or (as optional) two speeds with 4/6, 4/8 poles and single winding.

Fans can be optionally supplied with inveter.

DRIVESThe pulleys may be fi x or variable for a better setting of the fan speed.

11. MOTORS

Motors are three-phase asynchronous with cage rotor, totally enclosed de-sign with external ventilation. Electri-cal characteristics of the motors are in compliance with the IEC 60034-1, while dimensional characteristics are in com-pliance with IEC 60072-1 and IEC 34-7 (IM B3 - IM1001).

Protection class: IP55Stator winding class: F

The transmission belts may be of the fol-lowing types: SPA, SPB or SPC.Pulleys are supplied with “Taperlock” taper bushes and are statically and dyna-mically balanced.The belt tensioning device grants an easy maintenance.

FAN SIZES

180 200 225 250 280 315 355 400 450 500 560 630 710

FM

13 180A 200A 225A

20 180A 200A 225A 250A 280A

28 225A 250A 280A 315ABC

35 280A 315ABC 355ABC

42 280A 315ABC 355ABC

50 280A 315ABC 355ABC

57 315ABC 355ABC 400ABC 450ABC

69 355ABC 400ABC 450ABC 500BC

82 450ABC 500BC 560BC

105 450ABC 500BC 560BC

119 500BC 560BC 630BC

154 560BC 630BC 710BC

A = Polyamide wheelB = Steel sheet and painted wheel with backwards curved bladesC = Steel sheet painted wheel with backwards curved blades and airfoil profil

FAN SIZES

630 710 800 900 1000 1120 1250

FM

194 630BC 710BC 800BC

237 710BC 800BC 900BC

286 800BC 900BC 1000BC

342 800BC 900BC 1000BC

413 900BC 1000BC 1120BC

480 1000BC 1120BC

547 1000BC 1120BC

614 1120BC 1250BC

681 1120BC 1250B

749 1120BC 1250B

816 1250B

883 1250B

B = Steel sheet and painted wheel with backward curved bladesC = Steel sheet and painted wheel with backward curved blades, and airfoil profile.

PLUG FANS COMPATIBILITY TABLES

Air handling units -FM series -

23 å æSelection, installation, use and maintenance manual

Page 24: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

The multizone section, more than containing the heating and cooling coils fitted in parallel, is equipped with unified dampers one for each zone to be served.The Dual duct section is similar to the multizone but does not include the cojugate dampers since the mi-

The heat recovery units are even more used in installation where it is necessa-ry, for the room air quality or for diffe-rent processes, to use high volumes of fresh air rather than return air.The use of heat recovery units is more valid for large fresh air volumes and for high temperature difference between exhaust and fresh air.Types:- static cross fl ow recuperator with syn-thetic fi lters and aluminium alloy con-densate drain pan;- static cross fl ow with by-pass damper

12. SILENCERS

13. HEAT RECOVERY UNITS

The empty sections can be provided to allow a better maintenance of the AHU and the insertion of antifreeze detec-tors.

14. EMPTY SECTIONS

The Multizone/Dual duct sections are generally used where the control of room temperature is obtained by mi-xing two airflows of different tempe-ratures, also serving different zones of the building with the same AHU.

xing of the two airstrams are obtained in terminal units near to the rooms.For the selection of the multizone sec-tion it is necessary to know the quantity of zones, their flowrate and the posi-tion on the front section of the AHU.

(to by-pass the recovery unit in the free-cooling mode), synthetic fi lters and aluminium alloy condensate drain pan;- cross fl ow static with recirculation damper (3 dampers set with recove-ry unit), with synthetic media fi lters and aluminium alloy condensate drain pan.Further types can be supplied af-ter consulting the technical de-partment:- heat pipes;- rotary recuperator (sensible or to-tal recovery);- with double coil.

Effi ciency:Three sizes of cross fl ow recovery sy-stems with different effi ciency are avai-lable for each air handling size.

Installation:horizontal axis;

Air handling unit confi guration:- exhaust and supply in line;- overlapped exhaust and supply sec-tions.

Characteristics are indicated below. Length:• 325 mm , • 650 mm, • 975 mmDesign:

- basic;- with aluminium alloy condensate drain pan h=mm 50 and side discharge;- with inspection door.

Sound attenuation [dB]

Lenght [mm] 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

560 2 5 10 17 18 22 26 13

880 5 10 18 26 29 39 41 20

1200 7 14 24 35 39 48 48 28

1520 9 16 30 44 45 48 48 31

15. MULTIZONE / DUAL DUCT SECTIONS

Noise is one of the polluting factors in air conditioning. It is important to reduce as much as possible the noise from the fans with an accurate selec-tion of the fan type and size. If not enough it is possible to provide sound attenuators on the supply and/or exhaust fans sections.

Baffle length

560 mm880 mm1200 mm1520 mm

Baffle thickness: 200 mm

Air passage width: min. 105 mm, max. 114 mm

Construction:

Rockwool with air contact surfaces pro-tected with plastic film; enclosed in ex-panded galvanised steel mesh.

Sound attenuation at various frequencies is shown below:

Air handling units -FM series -

24 å æSelection, installation, use and maintenance manual

Page 25: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

16. SIZE

FM Fan W [mm] H [mm] L [mm] A [mm] C2 [mm] C4 [mm] C6 [mm] C8 [mm] E [mm] F [mm]

13 180 735 645 800 209 332 224 129 237 263 263

20200 735 805 960 236 380,5 270,5 192,5 306,5 249,5 249,5

225 735 805 960 268 397,5 275,4 122,5 244,5 233,5 233,5

28

200 895 805 960 236 380,5 270,5 192,5 306,5 329,5 329,5

225 895 805 960 268 397,5 275,5 122,5 244,5 313,5 313,5

250 895 805 960 302 484 276 132,5 265,5 296,5 296,5

35

225 1055 805 960 268 397,5 275,5 122,5 244,5 393,5 393,5

250 1055 805 960 302 484 276 132,5 265,5 376,5 376,5

280 1055 805 960 341 356,5 212,5 117,5 261,5 357 357

42

225 1215 805 960 268 397,5 275,5 122,5 244,5 473,5 473,5

250 1215 805 960 302 484 276 132,5 265,5 456,5 456,5

280 1215 805 960 341 356,5 212,5 117,5 261,5 437 437

50250 1375 805 960 302 484 276 132,5 265,5 536,5 536,5

280 1375 805 960 341 356,5 212,5 117,5 261,5 517 517

57

280 1055 1125 960 341 356,5 212,5 117,5 261,5 357 357

315 1055 1125 1120 384 449,5 279,5 132,5 302,5 335,5 335,5

355 1055 1125 1120 433 485 292 135 327 311 311

400 1055 1125 1280 487 528 306 133 355 284 284

69

315 1215 1125 1120 384 449,5 279,5 132,5 302,5 415,5 415,5

355 1215 1125 1120 433 485 292 135 327 391 391

400 1215 1125 1280 487 528 306 133 355 364 364

82

315 1375 1125 1120 384 449,5 279,5 132,5 302,5 495,5 495,5

355 1375 1125 1120 433 485 292 135 327 471 471

400 1375 1125 1280 487 528 306 133 355 444 444

FAN SECTIONS

TOP VIEW

Air handling units -FM series -

25 å æSelection, installation, use and maintenance manual

Page 26: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

FM Fan W mm H mm L mm A mm C2 mm C4 mm C6 mm C8 mm Emm F mm

105355 1695 1125 1120 433 485 292 135 327 631 631

400 1695 1125 1280 487 528 306 133 355 604 604

119

400 1375 1445 1280 487 528 306 133 355 444 444

450 1375 1445 1440 569 496,5 252 132,5 370,5 403 403

500 1375 1445 1600 638 520,5 249,5 122,5 391,5 368,5 368,5

560 1375 1445 1600 715 554,5 250,5 121 425 330 330

154

450 1695 1445 1440 569 496,5 252 132,5 370,5 563 563

500 1695 1445 1600 638 520,5 249,5 122,5 391,5 528,5 528,5

560 1695 1445 1600 715 554,5 250,5 121 425 490 490

194

500 1695 1765 1600 638 520,5 249,5 122,5 391,5 528,5 528,5

560 1695 1765 1600 715 554,5 250,5 121 425 490 490

630 1695 1765 1920 801 595,5 251,5 122,5 466 447 447

710 1695 1765 2080 898 644,5 250,5 121,5 491,5 398,5 398,5

237

560 2015 1765 1600 715 554,5 250,5 121 425 650 650

630 2015 1765 1920 801 595,5 251,5 122,5 466 607 607

710 2015 1765 2080 898 644,5 250,5 121,5 491,5 558,5 558,5

286

560 2015 2085 1600 715 554,5 250,5 121 425 650 650

630 2015 2085 1920 801 595,5 251,5 122,5 466 607 607

710 2015 2085 2080 898 644,5 250,5 121,5 491,5 558,5 558,5

800 2015 2085 2080 1007 895 451 185 566,5 504 504

342

630 2335 2085 1920 801 595,5 251,5 122,5 466 767 767

710 2335 2085 2080 898 644,5 250,5 121,5 491,5 718,5 718,5

800 2335 2085 2080 1007 895 451 185 566,5 664 664

900 2335 2085 2560 1130 844,5 338,5 135,5 641,5 602,5 602,5

413

630 2335 2405 1920 801 595,5 251,5 122,5 466 767 767

710 2335 2405 2080 898 644,5 250,5 121,5 491,5 718,5 718,5

800 2335 2405 2080 1007 895 451 185 566,5 664 664

900 2335 2405 2560 1130 844,5 338,5 135,5 641,5 602,5 602,5

480710 2655 2405 2080 898 644,5 250,5 121,5 491,5 878,5 878,5

800 2655 2405 2080 1007 895 451 185 566,5 824 824

547

710 2975 2405 2080 898 644,5 250,5 121,5 491,5 1038,5 1038,5

800 2975 2405 2080 1007 895 451 185 566,5 984 984

900 2975 2405 2240 1920 899,5 393,5 162,5 443,5 602,5 1242,5

614

800 3295 2405 2080 1007 895 451 185 566,5 1144 1144

900 3295 2405 1920 1120 899,5 393,5 162,5 643,5 922,5 1242,5

1000 3295 2405 2080 1267 924 394 239 829 694 1334

681900 3615 2405 1920 1130 899,5 393,5 162,5 643,5 1242,5 1242,5

1000 3615 2405 2080 1267 924 394 239 829 1014 1334

749900 3935 2405 1920 1130 899,5 393,5 162,5 643,5 1402,5 1402,5

1000 3935 2405 2080 1267 924 394 239 829 1174 1494

816900 4255 2405 1920 1130 899,5 393,5 162,5 643,5 1562,5 1562,5

1000 4255 2405 2080 1267 924 394 239 829 1494 1494

883900 4575 2405 1920 1130 899,5 393,5 162,5 643,5 1722,5 1722,5

1000 4575 2405 2080 1267 924 394 239 829 1654 1654

Air handling units -FM series -

26 å æSelection, installation, use and maintenance manual

Page 27: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

FACE DAMPERS

A

F

FMW H L1 L2 A C D E G F I K M N P G1 R S

mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm

13 735 645 640 320 450 300 308 450 300 610 62,5 123 450 300 218 300 300 233

20 735 805 640 320 610 300 468 450 300 610 62,5 123 450 450 218 300 300 238

28 895 805 640 320 610 300 468 610 300 770 62,5 123 610 450 218 300 300 238

35 1055 805 640 320 610 300 468 770 300 930 62,5 123 770 450 218 300 300 238

42 1215 805 640 640 610 300 468 930 610 1090 62,5 123 930 450 218 300 610 238

50 1375 805 640 640 610 300 468 1090 610 1250 62,5 123 1090 450 218 300 610 238

57 1055 1125 960 640 930 610 478 770 610 930 62,5 123 770 770 223 610 610 238

69 1215 1125 960 640 930 610 478 930 610 1090 62,5 123 930 770 223 610 610 238

82 1375 1125 960 640 930 610 478 1090 610 1250 62,5 123 1090 770 223 610 610 238

105 1695 1125 960 640 930 610 478 1410 610 1570 62,5 123 1410 770 223 610 610 238

119 1375 1445 960 640 1250 930 478 1090 610 1250 62,5 123 1090 1090 223 610 610 238

154 1695 1445 1280 960 1250 930 478 1250 930 1570 62,5 123 1250 1090 223 930 930 238

194 1695 1765 1280 960 1570 930 798 1250 930 1570 62,5 223 1250 1250 223 930 930 318

237 2015 1765 1280 960 1570 930 798 1570 930 1890 62,5 223 1570 1250 223 930 930 318

286 2015 2085 1280 1280 1890 1250 798 1570 1250 1890 62,5 223 1570 1570 223 930 1250 318

342 2335 2085 1280 1280 1890 1250 798 1890 1250 2210 62,5 223 1890 1570 223 930 1250 318

413 2335 2405 1280 1280 2210 1570 798 1890 1250 2210 62,5 223 1890 1890 223 930 1250 318

480 2655 2405 1280 1280 2210 1570 798 2210 1570 2530 62,5 223 2210 1890 223 930 1250 318

547 2975 2405 1280 1280 2210 2210 158 2530 1570 1890 543 223 2530 1890 223 930 1250 318

614 3295 2405 1280 1280 2210 2210 158 2850 1570 2210 543 223 2850 1890 223 930 1250 318

681 3615 2405 1280 1280 2210 2210 158 3170 1570 2530 543 223 3170 1890 223 930 1250 318

749 3935 2405 1280 1280 2210 2210 158 3490 1570 2850 543 223 3490 1890 223 930 1250 318

816 4255 2405 1280 1280 2210 2210 158 3810 1570 3170 543 223 3810 1890 223 930 1250 318

883 4575 2405 1280 1280 2210 2210 158 4130 1570 3490 543 223 4130 1890 223 930 1250 318

Air handling units -FM series -

27 å æSelection, installation, use and maintenance manual

Page 28: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

MIXING BOXES WITH EXTERNAL DAMPERS

FMW H L1 L2 L3 A B D1 D2 E F G I J

mm mm mm mm mm mm mm mm mm mm mm mm mm mm

13 735 645 320 640 320 300 157,5 200 200 50 450 300 300 610

20 735 805 320 640 320 300 157,5 300 250 60 610 300 300 610

28 895 805 320 640 320 300 157,5 300 250 60 610 300 300 770

35 1055 805 320 640 640 300 157,5 300 250 60 610 300 300 930

42 1215 805 320 640 640 300 157,5 300 250 60 610 610 300 1090

50 1375 805 320 640 640 300 157,5 300 250 60 610 610 300 1250

57 1055 1125 320 640 640 300 157,5 300 300 330 930 610 300 930

69 1215 1125 320 640 640 300 157,5 300 300 330 930 610 300 1090

82 1375 1125 320 640 640 300 157,5 300 300 330 930 610 300 1250

105 1695 1125 320 640 640 300 157,5 300 300 330 930 610 300 1570

119 1375 1445 640 640 640 610 157,5 450 450 350 1250 610 610 1250

154 1695 1445 640 640 960 610 157,5 450 450 350 1250 930 610 1570

194 1695 1765 640 640 640 610 157,5 610 610 350 1570 610 610 1570

237 2015 1765 640 640 960 610 157,5 610 610 350 1570 930 610 1890

286 2015 2085 960 640 960 930 157,5 770 770 350 1890 930 930 1890

342 2335 2085 960 640 1280 930 157,5 770 770 350 1890 1250 930 2210

413 2335 2405 960 640 960 930 157,5 930 930 350 2210 930 930 2210

480 2655 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 2530

547 2975 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 2850

614 3295 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 3170

681 3615 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 3490

749 3935 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 3810

816 4255 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 4130

883 4575 2405 960 640 1280 930 157,5 930 930 350 2210 1250 930 4450

Air handling units -FM series -

28 å æSelection, installation, use and maintenance manual

Page 29: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

MIXING BOXES WITH INTERNAL DAMPERS

FM W mm H mm L mm A mm B mm C mm D mm E mm F mm G mm

13 735 645 640 300 232,5 300 217,5 450 122,5 232,5

20 735 805 640 450 237,5 300 217,5 450 122,5 237,5

28 895 805 640 450 237,5 300 217,5 610 122,5 237,5

35 1055 805 640 450 237,5 300 217,5 770 122,5 237,5

42 1215 805 640 450 237,5 300 217,5 930 122,5 237,5

50 1375 805 640 450 237,5 300 217,5 1090 122,5 237,5

57 1055 1125 960 770 237,5 610 222,5 770 122,5 237,5

69 1215 1125 960 770 237,5 610 222,5 930 122,5 237,5

82 1375 1125 960 770 237,5 610 222,5 1090 122,5 237,5

105 1695 1125 960 770 237,5 610 222,5 1410 122,5 237,5

119 1375 1445 960 1090 237,5 610 222,5 1090 122,5 237,5

154 1695 1445 1280 1090 237,5 930 222,5 1250 122,5 237,5

194 1695 1765 1280 1250 317,5 930 222,5 1250 122,5 317,5

237 2015 1765 1280 1250 317,5 930 222,5 1570 122,5 317,5

286 2015 2085 1280 1570 317,5 930 222,5 1570 122,5 317,5

342 2335 2085 1280 1570 317,5 930 222,5 1890 122,5 317,5

413 2335 2405 1280 1890 317,5 930 222,5 1890 122,5 317,5

480 2655 2405 1280 1890 317,5 930 222,5 2210 222,5 317,5

547 2975 2405 1280 1890 317,5 930 222,5 2530 222,5 317,5

614 3295 2405 1280 1890 317,5 930 222,5 2850 222,5 317,5

681 3615 2405 1280 1890 317,5 930 222,5 3170 222,5 317,5

749 3935 2405 1280 1890 317,5 930 222,5 3490 222,5 317,5

816 4255 2405 1280 1890 317,5 930 222,5 3810 222,5 317,5

883 4575 2405 1280 1890 317,5 930 222,5 4130 222,5 317,5

Air handling units -FM series -

29 å æSelection, installation, use and maintenance manual

Page 30: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

3-WAY MIXING BOXES WITH EXTERNAL DAMPERS

FM W mm H mm L1 mm L2 mm L3 mm L4 mm A mm B mm C mm

13 735 645 800 320 320 640 300 610 190

20 735 805 800 320 320 640 300 610 190

28 895 805 800 320 320 640 300 770 190

35 1055 805 800 320 320 640 300 930 190

42 1215 805 800 320 320 640 300 1090 190

50 1375 805 800 320 320 640 300 1250 190

57 1055 1125 1120 480 480 960 450 930 190

69 1215 1125 1120 480 480 960 450 1090 190

82 1375 1125 1120 480 480 960 450 1250 190

105 1695 1125 1120 480 480 960 450 1570 190

119 1375 1445 1440 640 640 960 610 1250 190

154 1695 1445 1600 640 640 960 610 1570 350

194 1695 1765 1920 800 800 1280 770 1570 350

237 2015 1765 1920 800 800 1280 770 1890 350

286 2015 2085 2240 960 960 1280 930 1890 350

342 2335 2085 2240 960 960 1280 930 2210 350

413 2335 2405 2240 960 960 1280 930 2210 350

480 2655 2405 2240 960 960 1280 930 2530 350

547 2975 2405 2240 960 960 1280 930 2850 350

614 3295 2405 2240 960 960 1280 930 3170 350

681 3615 2405 2240 960 960 1280 930 3490 350

749 3935 2405 2240 960 960 1280 930 3810 350

816 4255 2405 2240 960 960 1280 930 4130 350

883 4575 2405 2240 960 960 1280 930 4450 350

Air handling units -FM series -

30 å æSelection, installation, use and maintenance manual

Page 31: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

3-WAY MIXING BOXES WITH INTERNAL DAMPERS

FM W mm H mm C mm D mm CONFIG. L mm A mm B mm X mm Y mm

13 735 645 300 232,5 L 1280 450 450 75 755

20 735 805 450 237,5 L 1280 450 450 75 755

28 895 805 450 237,5 L 1600 450 770 75 755

35 1055 805 450 237,5 L 1600 450 770 75 755

42 1215 805 450 237,5 Z 1600 770 1090 75 435

50 1375 805 450 237,5 Z 1600 770 1090 75 435

57 1055 1125 770 237,5 Z 1280 770 770 75 435

69 1215 1125 770 237,5 Z 1600 770 1090 75 435

82 1375 1125 770 237,5 Z 1600 770 1090 75 435

105 1695 1125 770 237,5 Z 1920 1090 1410 75 435

119 1375 1445 1090 237,5 Z 1920 1090 1410 75 435

154 1695 1445 1090 237,5 Z 2240 1250 1730 75 435

194 1695 1765 1250 317,5 Z 1920 1250 1570 175 175

237 2015 1765 1250 317,5 Z 2240 1570 1890 175 175

286 2015 2085 1570 317,5 Z 2240 1570 1890 175 175

342 2335 2085 1570 317,5 Z 2560 1890 1890 175 175

413 2335 2405 1890 317,5 Z 2560 1890 1890 175 175

480 2655 2405 1890 317,5 S 2240 1890 1890 222,5 222,5

547 2975 2405 1890 317,5 S 2240 1890 1890 222,5 222,5

614 3295 2405 1890 317,5 S 2240 1890 1890 222,5 222,5

681 3615 2405

749 3935 2405Contact FAST technical department

816 4255 2405

883 4575 2405

Air handling units -FM series -

31 å æSelection, installation, use and maintenance manual

Page 32: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

FILTERS

ç è é ê ë ì í î ï ð ï ñ ì í ò ó ô õ ô ö ÷ ø õ ù ô ú û ü ó ýí þ ÿ � ë � � ï � � ì íé ÿ ñ � � � í� � � � � � ï � � ì í �ê ì � � è î ì � ï � � ì î í � � ê ë � î é ÿ � ê � ï �� � ê � ï � � ì ñ ê � î ê é � �� � � � � � � � � � � � � � � � � � � � � �� í é � � í � � í é � � � ì � ï � � ì î í î é � � � ï � í � î é � � � ï � � ì î í � � � è ì í ð ì î � ï ê ï ñ ì í � ð ì î � ï ê þ ñ � � � � è í

5

Bag Rigid bag

Absolute Roll

SyntheticsCorrugatedand metal

Carboni

Germicyda lamps

FM H1 mm H3 mm H2 mm L1 mm L2 mm L3 mm L4 mm L5 mm

13 645 --- 1125 320 640 960 1280 480

20 805 --- 1125 320 640 960 1280 480

28 805 --- 1125 320 640 960 1280 480

35 805 --- 1125 320 640 960 1280 480

42 805 --- 1125 320 640 960 1280 480

50 805 --- 1125 320 640 960 1280 480

57 (1) 1125 1125 1125 320 640 960 1280 480

69 (1) 1125 1125 1125 320 640 960 1280 480

82 1125 1125 1125 320 640 960 1280 480

105 1125 1125 1125 320 640 960 1280 ---

119 1445 1445 1445 320 640 960 1280 480

154 1445 1445 1445 320 640 960 1280 ---

194 1765 1765 1765 320 640 960 1280 ---

237 1765 1765 1765 320 640 960 1280 ---

286 2085 2085 2085 320 640 960 1280 ---

342 2085 2085 2085 320 640 960 1280 ---

413 2405 2405 2405 320 640 960 1280 ---

480 2405 2405 2405 320 640 960 1280 ---

547 2405 2405 2405 320 640 960 1280 ---

614 2405 2405 2405 320 640 960 1280 ---

681 2405 2405 2405 320 640 960 1280 ---

749 2405 2405 2405 320 640 960 1280 ---

816 2405 2405 2405 320 640 960 1280 ---

883 2405 2405 2405 320 640 960 1280 ---

(1) Separate enclosure with a width equal to the FM 82(2) Horizontal roller filter up to size 105 including

Frame Drawer

Air handling units -FM series -

32 å æSelection, installation, use and maintenance manual

Page 33: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

COILS

FM H L1 L2 L3 Ø

13 645 320 640 960 1" G

20 805 320 640 960 1" G

28 805 320 640 960 1" G

35 805 320 640 960 1" G

42 805 320 640 960 1" G

50 805 320 640 960 1" G

57 1125 320 640 960 1" G

69 1125 320 640 960 1" G

82 1125 320 640 960 1" G

105 1125 320 640 960 1" G

119 1445 320 640 960 1" G

154 1445 320 640 960 1" G

194 1765 320 640 960 1" G

237 1765 320 640 960 1" G

286 2085 320 640 960 1" G

342 2085 320 640 960 1" G

413 2405 320 640 960 1" G

480 2405 320 640 960 1" G

547 2405 320 640 960 1" G

614 2405 320 640 960 1" G

681 2405 320 640 960 1" G

749 2405 320 640 960 1" G

816 2405 320 640 960 1" G

883 2405 320 640 960 1" G

Air handling units -FM series -

33 å æSelection, installation, use and maintenance manual

Page 34: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

HUMIDIFIING SECTIONS� � � � � ! � " # $ % & ' ( ) * ) ' $ +) # � + ( ) * * ) & �# , ) " ( & � ( ) - . ) " $ � & '/ 0 0 � � 12 3 4 5 6 7 5 8 9 5 : ; 8 < = : ;> ? ? @ @ 3 A 9 : = 8 B7 3 8 5 6 C 6 6 5 : = 6 : D E 3 8 = A F4 D @ 4 � � � � � ! � " # $ % & ' ( ) * ) ' $ +) # � + ( ) * * ) & � # , ) " ( & � ( )- . ) " $ � & ' G 0 0 � � 12 3 4 5 6 7 5 8 9 5 : ; 8 < = : ;H ? ? @ @ 3 A 9 : = 8 B7 3 8 5 6 C 6 6 5 : = 6 : D E 3 8 = A F4 D @ 4 � � � % � ! � " # $ � & ' ( ) * ) ' $+ ) # � + ( ) * * ) & � # , ) " ( & � ( )- . ) " $ � & ' / 0 0 � � 1) $ . I ( # * # $ ) � * )J & � $ ) K K I $ ) .2 3 4 5 6 7 5 8 9 5 : ; 8 < = : ;> ? ? @ @ 3 A 9 : = 8 B7 3 8 5 6 C 6 6 5 : = 6 : D E 3 8 = A F4 D @ 4 7 = 8 < 9 6 C 4 E 5 85 E = @ = A 3 8 C 6 L � � � % � ! � " # $ � & ' ( ) * ) ' $+ ) # � + ( ) * * ) & � # , ) " ( & � ( )- . ) " $ � & ' G 0 0 � � 1) $ . I ( # * # $ ) � * )J & � $ ) K K I $ ) .2 3 4 5 6 7 5 8 9 5 : ; 8 < = : ;H ? ? @ @ 3 A 9 : = 8 B7 3 8 5 6 C 6 6 5 : = 6 : D E 3 8 = A F4 D @ 4 7 = 8 < 9 6 C 4 E 5 85 E = @ = A 3 8 C 6 L� � � % � ! � " # $ � & ' +, # ( ) � *M 8 5 3 @< D @ = 9 = N = 5 6 L � � � % � ! � " # $ � & ' +) # � ) $ # � *" & � ( * � � OP 3 8 5 6 : C @ 4 6 5 L L 5 93 = 6 < D @ = 9 = N = 5 6 L Q # , ) � * R # � *S = 6 7 3 L < 5 6Steam

humidifiers Air washer

Paper wet deck thick 100 mm and city water or recirculating pump

Paper wet deck thick 200 mm and city water or recirculating pump

Water humidifi-cation with di-scharge or pump (100 mm paper wet) with droplet eliminator.

Paper wet deck thick 200 mm and city water or re-circulating pump with droplet eliminators

Water com-pressed air humidifiers

FM H mm H1 mm L1 mm L2 mm L3 mm L4 mm L5 mm A mm B mm C mm D mm E mm

13 645 965 960 960 960 1280 2335 175 210 35 480 325

20 805 1125 960 960 960 1280 2335 175 210 35 480 325

28 805 1125 960 960 960 1280 2335 175 210 35 480 325

35 805 1125 640 960 960 1280 2335 145 70 35 480 325

42 805 1125 640 960 960 1280 2335 145 70 35 480 325

50 805 1125 640 960 960 1280 2335 145 70 35 480 325

57 1125 1445 640 960 960 1280 2335 145 70 35 480 325

69 1125 1445 640 960 960 1280 2335 145 70 35 480 325

82 1125 1445 640 960 960 1280 2335 145 70 35 480 325

105 1125 1445 640 960 960 1280 2335 145 70 35 480 325

119 1445 1765 640 960 960 1280 2335 145 70 35 480 325

154 1445 1765 640 960 960 1280 2335 145 70 35 480 325

194 1765 2085 640 960 960 1280 2335 145 70 35 480 325

237 1765 2085 640 960 960 1280 2335 145 70 35 480 325

286 2085 2405 640 960 960 1280 2335 145 70 35 480 325

342 2085 2405 640 960 960 1280 2335 145 70 35 480 325

413 2405 2405 640 960 960 1280 2335 145 70 35 480 325

480 2405 2405 640 960 960 1280 2335 145 70 35 480 325

547 2405 2405 640 960 960 1280 2335 145 70 35 480 325

614 2405 2405 640 960 960 1280 2335 145 70 35 480 325

681 2405 2405 640 960 960 1280 2335 145 70 35 480 325

749 2405 2405 640 960 960 1280 2335 145 70 35 480 325

816 2405 2405 640 960 960 1280 2335 145 70 35 480 325

883 2405 2405 640 960 960 1280 2335 145 70 35 480 325

Air handling units -FM series -

34 å æSelection, installation, use and maintenance manual

Page 35: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

SOUND ATTENUATORS

FM H mm L1 mm L2 mm L3 mm L4 mm

13 645 640 960 1280 1600

20 805 640 960 1280 1600

28 805 640 960 1280 1600

35 805 640 960 1280 1600

42 805 640 960 1280 1600

50 805 640 960 1280 1600

57 1125 640 960 1280 1600

69 1125 640 960 1280 1600

82 1125 640 960 1280 1600

105 1125 640 960 1280 1600

119 1445 640 960 1280 1600

154 1445 640 960 1280 1600

194 1765 640 960 1280 1600

237 1765 640 960 1280 1600

286 2085 640 960 1280 1600

342 2085 640 960 1280 1600

413 2405 640 960 1280 1600

480 2405 640 960 1280 1600

547 2405 640 960 1280 1600

614 2405 640 960 1280 1600

681 2405 640 960 1280 1600

749 2405 640 960 1280 1600

816 2405 640 960 1280 1600

883 2405 640 960 1280 1600

Air handling units -FM series -

35 å æSelection, installation, use and maintenance manual

Page 36: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

T U V W X Y Z [ T U V W X Y Z \

FM W mm L mm Config. H1 mm H2 mm H mm J mm A mm B mm C mm D mm

13 735 1375 A --- --- 1125 610 290 290 30 317,5

20 735 1375 A --- --- 1125 610 450 290 30 317,5

28 895 1375 A --- --- 1125 770 450 290 30 317,5

35 1055 1375 A --- --- 1125 930 450 290 30 317,5

42 1215 1375 A --- --- 1125 1090 450 290 30 317,5

50 1375 1375 A --- --- 1125 1250 450 290 30 317,5

57 1055 1695 A --- --- 1765 930 610 610 30 477,5

69 1215 1695 A --- --- 1765 1090 610 610 30 477,5

82 1375 1695 A --- --- 1765 1250 610 610 30 477,5

105 1695 1695 A --- --- 1765 1570 610 610 30 477,5

119 1375 1695 A --- --- 2085 1250 930 610 30 477,5

154 1695 1695 A --- --- 2085 1570 930 610 30 477,5

194 1695 2015 A --- --- 2405 1570 930 610 30 797,5

237 2015 2015 A --- --- 2405 1890 930 610 30 797,5

286 2015 2015 B 2085 685 2770 1890 1250 610 75 797,5

342 2335 2015 B 2085 685 2770 2210 1250 610 75 797,5

413 2335 2335 B 2405 1005 3410 2210 1570 930 75 797,5

480 2655 2335 B 2405 1005 3410 2530 1570 930 75 797,5

547 2975 2335 B 2405 1005 3410 2850 1570 930 75 797,5

614 3295 2335 B 2405 1005 3410 3170 1570 930 75 797,5

681 3615 2335 B 2405 1005 3410 3490 1570 930 75 797,5

749 3935 2335 B 2405 1005 3410 3810 1570 930 75 797,5

816 4255 2335 B 2405 1005 3410 4130 1570 930 75 797,5

883 4575 2335 B 2405 1005 3410 4450 1570 930 75 797,5

MULTIZONE / DUAL DUCT SECTIONS

Air handling units -FM series -

36 å æSelection, installation, use and maintenance manual

Page 37: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

LAE

FAR

LAES

AR

H12

045 ] ]

AEF

AR AR

AES

H12

0_̂

C

FM Tipo Larghezza mm H mm L mm M mm AEF mm AES mm AR mm C mm

13 A 735 1325 735 895 450 300 290 190

20 A 735 1325 1055 1215 610 450 290 350

28 A 895 1325 1055 1215 610 450 290 350

35 A 1055 1325 1055 1215 610 450 290 350

42 A 1215 1325 1055 1215 610 450 290 350

50 A 1375 1325 1055 1215 610 450 290 350

57 A 1055 1965 1375 1535 930 610 610 350

69 A 1215 1965 1375 1535 930 610 610 350

82 A 1375 1965 1375 1535 930 610 610 350

105 A 1695 1965 1375 1535 930 610 610 350

119 A 1375 2285 1695 1855 930 770 610 670

154 A 1695 2285 1695 1855 930 770 610 670

194 B 1965 3290 2015 2335 1250 930 930 1035

237 B 2015 3290 2015 2335 1250 930 930 1035

286 B 2015 3930 2335 2655 1090 1090 1090 1675

342 B 2335 3930 2335 2655 1090 1090 1090 1675

413 B 2335 4735 2335 3390 1250 1090 930 1675

480 --- --- --- --- --- --- --- --- ---

547 --- --- --- --- --- --- --- --- ---

614 --- --- --- --- --- --- --- --- ---

681 --- --- --- --- --- --- --- --- ---

749 --- --- --- --- --- --- --- --- ---

816 --- --- --- --- --- --- --- --- ---

883 --- --- --- --- --- --- --- --- ---

HEAT RECOVERY SECTIONS

M

AES

AR

AEF

CAR

AES

AR

AEF

AR

120

HH

M

LLType A Type B

Air handling units -FM series -

37 å æSelection, installation, use and maintenance manual

Page 38: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

H

FM W mm H mm L mm L1 mm L2 mm AE mm AR mm C mm D mm B mm

13 735 645 1055 --- --- 290 290 190 222,5 610

20 735 805 1375 --- --- 450 450 190 222,5 610

28 895 805 1375 --- --- 450 450 190 222,5 770

35 1055 805 1375 --- --- 450 450 190 222,5 930

42 1215 805 1375 --- --- 450 450 190 222,5 1090

50 1375 805 1375 --- --- 450 450 190 222,5 1250

57 1055 1125 1695 --- --- 610 450 190 382,5 930

69 1215 1125 1695 --- --- 610 450 190 382,5 1090

82 1375 1125 1695 --- --- 610 450 190 382,5 1250

105 1695 1125 1695 --- --- 610 450 190 382,5 1570

119 1375 1445 2335 --- --- 770 770 350 382,5 1250

154 1695 1445 2335 --- --- 770 770 350 382,5 1570

194 1695 1765 2335 --- --- 770 770 350 382,5 1570

237 2015 1765 2335 --- --- 770 770 350 382,5 1890

286 2015 2085 2655 --- --- 930 930 350 382,5 1890

342 2335 2085 2655 --- --- 930 930 350 382,5 2210

413 2335 2405 2975 --- --- 930 1250 350 382,5 2210

480 2655 2405 3070 1375 1695 1250 1250 125 382,5 2530

547 2975 2405 3070 1375 1695 1250 1250 125 382,5 2850

614 3295 2405 3070 1375 1695 1250 1250 125 382,5 3170

681 3615 2405 3070 1375 1695 1250 1250 125 382,5 3490

749 3935 2405 3070 1375 1695 1250 1250 125 382,5 3810

816 4255 2405 3070 1375 1695 1250 1250 125 382,5 4130

883 4575 2405 3070 1375 1695 1250 1250 125 382,5 4450

Air handling units -FM series -

38 å æSelection, installation, use and maintenance manual

Page 39: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

FM Width mm H mm L mm M mm AEF mm AR mm C mm E mm P mm

13 735 1005 1055 1375 300 300 300 525 610

20 735 1325 1055 1375 300 450 340 685 610

28 895 1325 1055 1375 300 450 340 685 770

35 1055 1325 1055 1375 300 450 340 685 930

42 1215 1325 1055 1375 300 450 340 685 1090

50 1375 1325 1055 1375 300 450 340 685 1250

57 1375 1965 1055 1375 610 610 350 1005 1250

69 1215 1965 1055 1375 610 610 350 1005 1090

82 1375 1965 1055 1375 610 610 350 1005 1250

105 1695 1965 1055 1375 610 610 350 1005 1570

119 1695 2650 1055 1375 610 1250 235 1325 1570

154 1695 2650 1055 1375 610 1250 235 1325 1570

194 2015 3292 1375 1535 770 1570 235 1645 1890

237 2015 3292 1375 1535 930 1570 235 1645 1890

286 2335 3930 1375 1535 930 1890 235 1965 2210

342 2335 3930 1375 1535 930 1890 235 1965 2210

413 2626 4570 1375 1695 1090 2210 235 2285 2530

480 --- --- --- --- --- --- --- --- ---

547 --- --- --- --- --- --- --- --- ---

614 --- --- --- --- --- --- --- --- ---

681 --- --- --- --- --- --- --- --- ---

749 --- --- --- --- --- --- --- --- ---

816 --- --- --- --- --- --- --- --- ---

883 --- --- --- --- --- --- --- --- ---

Larg

hezz

aAE

FC

AR

H

L M

EE

120 ML

P

Recup. rotativo Recup. rotativocon ricircolo

Recup. rotativocon serrande esterne

Recup. rotativo + ricircolo con serrande esterne

ROTARY RECUPERATOR

Rotary recup. Rotary recup. + circulation

Rotary recuperator with external dampers

Rotary recup. + circulation with external dampers

Leng

th

Air handling units -FM series -

39 å æSelection, installation, use and maintenance manual

Page 40: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

L1

HHHH

HHH

HH H

L2 L3 L 4

L2

L2 L3

L3

L 4

L 4

PLENUMS AND EMPTY SECTIONS

FM H mm L2 mm L3 mm L4 mm Fan L1 mm

13 645 320 640 960 180 320

20 805 320 640 960 200 320

28 805 320 640 960 225 320

35 805 320 640 960 250 320

42 805 320 640 960 280 320

50 805 320 640 960 315 450

57 1125 320 640 960 355 450

69 1125 320 640 960 400 450

82 1125 320 640 960 450 450

105 1125 320 640 960 500 640

119 1445 320 640 960 560 640

154 1445 320 640 960 630 640

194 1765 320 640 960 710 800

237 1765 320 640 960 800 800

286 2085 320 640 960 900 960

342 2085 320 640 960 1000 960

413 2405 320 640 960

480 2405 320 640 960

547 2405 320 640 960

614 2405 320 640 960

681 2405 320 640 960

749 2405 320 640 960

816 2405 320 640 960

883 2405 320 640 960

Air handling units -FM series -

40 å æSelection, installation, use and maintenance manual

Page 41: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

dles;- Packages with fl exible connections ;- For sections to be loaded one on top of the other, wooden beams shall be positioned between the two sections.

CHECKS AT MATERIAL RECEIPT

When air handling units are received on site, it’s necessary to do some preliminary checks to verify that no damages have been occurred during transport. Potential damages should be marked on transport document.The checks are the following:-dampers: check integrity of shafts, gears and blades.-fi lters: check quantity and type;-coils: check integrity of manifolds and fi ns (if visible);-fan-motor assembly: check fi xing;-panels and baseframe: check integri-ty.-roof: check integrity.

17. TRANSPORT AND HANDLING

PACKING

The air handling units FM series are usually supplied without packing, except for fi lter cells (high and ab-solute effi ciency) and for assembling accessories which are supplied in cartoon boxes and are to be instal-led by customer.Upon request the air handling units can be supplied with polyetilenre fi lm, on pallets + polyetilene fi lm, in crate or in wooden box.

TRANSPORT

The transportability of the air han-dling units reguarding dimensional aspects is shown at pag.8.The tran-sport must be done according to the folllowing indications:- Packages must be securely fi xed at trucks fl oor;-Packages to prevent damages to all external parts of the casing like headers, connections,dampers, han-

WARNINGS AND SAFETY REGULATIONS

18. INSTALLATION

The following regulations when in-stalling, starting up, using and ser-vicing the air handling units must be taken into account:

When lifting, bear in mind that the centre of gravity of the unit may be off-centre.

Make sure that ropes and hooks are correctly fi xed.

Make sure that the unit and all its electric parts have been correctly earthed prior to starting up the unit.

Make sure that the fan opening vent has been connected to ducting or is covered by a protective grille prior to starting up the unit.

Never use the unit to support other equipment.

STOCKING AT SITE

The air handling units without roof must be stocked inside the building.The supply/exhaust openings must be pro-tected to avoid materials, powder or lit-tle animals entering the sections, and the dampers must be closed (and sealed with nylon fi lms if stocked outside the building)until the air handling units are connected to the ducts of the plant.The air handling units supplied in more sections shall be placed near to the other to avoid entering of external materials.

Do not use the station as a walkway or scaffold; if it is necessary to climb on the roof of the air handling unit it is required:1) to use all PPE necessary to avert the dangers encountered during the analy-sis phase of the residual risks;2) to prepare a proper weight distri-bution to prevent the breakthrough of the sheet metal roof (by leaning remo-vable supporting beams on very large surfaces).

Never stack tools, spare parts, etc. on top of the unit.

Before opening the unit, make sure that all electrical parts have been switched off. In particular, make sure that the fan is off and cannot be star-ted prior to opening inspection doors.

Do not open inspection panels when the fan is operating (especially sec-tions under pressure of the unit).

Always fi t the protective carter over the fan section before starting up the unit.

Make sure that all panels and hatches are properly closed.

Beware of sharp edges inside the unit.

Beware of roof corners of the outdoor units.

Beware of the heat exchange coils: dan-ger of burning.

Beware of the potential danger of burning deriving from steam humidifi ers.

Beware of the self-controlled dampers, which could close suddenly.

- And 'well, after installation, remove all traces of protective material applied to the surface of the side panels and top of the unit.

- Pay attention to the holes left open after removal of the lifting lugs of the unit: you must close them with the bolts and screws used for the mounting lugs and seal them with sealant silicone to prevent water in-fi ltration.

Air handling units -FM series -

41 å æSelection, installation, use and maintenance manual

Page 42: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Warning! The fastening must always be done using the holes marked with the yellow/back label.

When lifting the AHU please use a calibra or put a bar between the cables to eliminate the horizontal component of the force which could damage the roof of the AHU.During lifting be careful not to da-mage the outcoming parts like dam-pers, manifolds, drains and handles.

HANDLING AND POSITIONING

The air handling units FM series are built for the litfi ng from the bottom. The cor-ners feet and the base, when supplied, are equipped with holes for the lifting to be used as follows:sections with corner sockets only: the lif-ting can be done with hooks to anchor in the holes shown in the underlying fi gure B or ropes to be anchored to two 2" pipes passing from one side of the section to the other through the hole B;sections with continuous base: the han-dling can be done with ropes anchored to two 2 "pipes passing from one side of the section out through the hole A.

MINIMUM TECHNICAL CLEARANCES

In the positioning of the AHU it is impor-tant to provide the necessary space for the ordinary and extra ordinary mainte-nance.The best solution can be achived lea-

The positioning may be done using two transpallets, one for each section side, operating at the longer sides.Alternatively the positioning can be done by moving the ahu sections on pipes as they were rolls. The sections without continous base can be slided directly on the fl oor.

The fan-motor assembly are fi xed on antivibration supports; it is advisable, anyway, to place between baseframe and technical fl oor an antivibration mat.

ving at headers and inspection side a space 700 mm min wide and lae-ving at the opposite side a distance equal to the AHU’s width plus 100 mm in order to remove the coils at

the opposite side respect to the hea-ders without disassemble the valves assembly (fig.A)If the AHU must be placed at one wall, leave at inspection side a cor-ridor with the sae width of the AHU plus 100 mm (fig. B).

B

A

Air handling units -FM series -

42 å æSelection, installation, use and maintenance manual

Page 43: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

num surfaces of the uprights at the contact zone between the two sec-tions and apply the adhesive seal in neoprene, and then pull them toge-ther with screws to be used in slots carved into the corner brackets (see

SECTIONS UNION

The stations, supplied in several sec-tions, must be assembled following the sketch attached to the panel, using the supplied material contained in a box (usually placed in the fan section). Thoroughly clean the alumi-

photo 1). Accordin to the AHU size can be suppied also the brackets in black nylon marked with 2 in figure. The must be distributed in pairs along the peri-meter of the sections, fixed at the fra-meworks with self tapping screws, and aech other with bolts and nuts.

- Position the components B at top and bottom of the groove;- Position the components of C at the lateral grooves;- Fix components with the provided screws;- Properly seal the cracks with the remained sealant silicone

WARNING:If the roof covering is present, special attention should be paid to the union of the same to avoid water infiltration.

In the presence of the drain panel is ensured by special fastening L-brackets with the screws already provided with the equipment: these must be applied on the upper horizontal and vertical profiles (A). For design reasons, in some cases an inner surface cannot be guaranteed, so that the space between two or more sections can become a point of accumulation of dirt, for this reason has been arranged for a cover to be later mounted on the sections of the union.In this case, the fastening of the sections will be secured by special brackets applied on vertical profiles and horizontal screws properly crafted (B).

AB

2 1

Air handling units -FM series -

43 å æSelection, installation, use and maintenance manual

Page 44: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

The initial section of the supply air duct should be 2.5 times lon-ger than the shorter side of the duct before curves, branching or obstructions as dampers to avoid potential pressure drops. Divergent sections should be incli-ned more than 7°.The fan should be oriented accor-ding to the first curve, as shown in the figure below.

HYDRAULIC CONNECTION

a) Connection of the water coils

- Heat exchange coils have manifolds with threaded terminals. In the event that flan-ged connectors are required, threaded flanges are used to allow the coil removal.As result the manifolds leak from side panels of the AHU.

- Cooling coils are mounted in the conden-sate collection trays; the drainage of trays (1" G) should have an adequate siphon attachment.

- The tubes should be arranged in such a way as to allow the removal of the coil and opening of the inspection doors.

- Water inlets and outlets should be arranged in such a way as to ensure the counter-flow heat exchange. Follow the

Correct position

Wrong positionSUPPLY/EXHAUST OPENING VENTS

information given on the WATER INLET and WATER OUTLET plates. Generally, coils with r.h. connectors are supplied from below, while those with left connectors are supplied from above.

- Fit a air relief above and a dischar-ge valve below.

- Properly support tubes on unit by brackets to relieve the coil of exces-sive weight.

- Once connections have been made, push the external rubber seal against the panel to prevent air leakage and condensate formation.

- Panels should be insulated thoroughly over the entire surface to prevent the risk of burnings and condensate forma-tion.

- Install a tube side coil shut-off device for when the fan is not operating to pre-vent overheating inside the unit and con-sequent damage of some components.

- Install antifreeze devices with outdoor air vents.

- Install shut-off valves to isolate the coil from the rest of the circuit in the event of special maintenance.

NO

min 2,5 A

max 7°

The possible fans orientations are shown in the table below. An even final number means right hand orientation; an odd final number refers to left hand orientation. The orienta-tion of the unit is established when the back is turned to the air flow towards supply air. Also fans orientation depend on the position of the supply duct.

MAX mm 25

AERAULIC CONNECTIONS

IMPORTANT: never start up the air handling unit when the fan opening vents are not ducted or covered by protective mesh.Fit a flexible connection between supply and exhaust, and the ducts.

19. CONNECTIONS

Connect the damper to the unit by screwing it on to the flange or dam-per (if present); alternatively, fix the damper to the unit frame with self-punching screws (in the case of exhaust air vent), or to the panel (in the case of supply vents) as shown in the diagram.

Ensure that the duct and the unit are equipotential by means of an earth cable bridging the vibration damping joint.

Air handling units -FM series -

44 å æSelection, installation, use and maintenance manual

Page 45: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Water input should be regulated by the so-lenoid valve supplied, served by an elec-tronic control device connected in series to an room humidistat and a limit humidi-stat on the delivery duct (humidistats not supplied).See paragraph 44 for the drainage tube connection.Infeed and drainage connectors are loca-ted underneath the tank in the unit base.

Infeed: 1 -1/2" GJDrainage: 1" GJ

e) Connection of wet deck humidifi ers

with pump

This type of humidifi er involves connection of the water input and drainage tubes. Water input should be regulated by a valve (not supplied); while during normal ope-ration infeed is regulated by a fl oat valve (see C in fi gure). A pump (D) served by an room humidistat and a limit humidistat (not supplied) on the supply duct supplies water to the hu-midifi er. See paragraph for connection of the drai-nage tube.

Infeed and drainage connectors are loca-ted underneath the tank in the unit base.

Infeed: 1" GJDrainage: 1" GJ

Preliminary operations:- connect the pump (three-phase);- check that the water level is approx. 20 mm below the level of the metal tank; adjust the fl oat valve as required by tur-ning screw C and/or the adjusting the po-sition of the fl oat B on the control rod;- regulate the water fl ow of the deck adju-sting by-pass valve A; check that the pack is completely wetted without splashing;- check that the fi lter mesh E is inserted

b) Connection of the direct expansion

coils

For a proper connection of the direct ex-pansion coils to the cooling system plea-se follow these guidelines:

• Make sure that the exchange takes is in the counterfl ow;

• the cooling system must be equipped with all the regulation and safety devi-ces to prevent any damage to the coil;

• piping shall be sized and equipped with appropriate traps so as to permit the oil circulation and lubrication of the compressor;

• paying attention to vibrations tran-smitted to the expansion coil that could lead to break of the welding.

c) Connection of city water wet deck hu-

midifi ers

This type of humidifi er involves the wa-ter input connection and drainage tubes. Water input should be regulated by a so-lenoid valve (not supplied) served by an ambient humidistat and a potential hu-midistat on the supply duct (humidistats not supplied). Drainage must be connected according to indications in page 44.Infeed and drainage connectors are lo-cated underneath the tank in the unit base.

Infeed diameter: 1" GJDrainage diameter: 1" GJ

d) Connection of wet deck humidifi ers

with feed control

This type of humidifi er involves connec-tion of the water input and drainage tu-bes.

A

B

G

H FE

C

D

along its entire height on the pump support guides;- check the position of evaporating deck F and of separator G; both are extractable. The evaporating deck is laterally protected by the spray guard H.

f) Connection of air washer

- Due to the weight of the water con-tained in drain pan, air washers must be supported along the entire length of the tank. - Assemble and connect the supplied pumps to the suction and supply con-nectors.- Secure pumps to the floor surface at the same level as the unit base. - Adjust the float valve so that the water level is approx. 20 mm below the overflow device.

g) Connection of steam humidifi er

The sections of the steam humidifier are supplied in a standard format, supplied with steam distributor tube. It has the infeed connectors for 1" G steam and 3/8" GJ for condensate re-covery.The tube can be connected to regu-lation valves for central steam pro-duction or to submerged electrode steam generators. If purchased as a unit accessory, the submerged electrode type steam ge-nerator is supplied mounted onto the side of the unit, already connected to the steam and condensate connec-tions. For maintenance instructions, please refer to the manual supplied with the equipment. Steam humidifiers come with drop separator and condensate drain pan (1"G drainage). Refer to paragraph pag 47 for connection instructions.

Air handling units -FM series -

45 ` aSelection, installation, use and maintenance manual

Page 46: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Protection class: IP55Stator coil class: BMotors are single pole (2, 4, 6 poles, depending on fan speed) or on request double polarity 4/6, 4/8 poles with single coil.

Single-speed, twin-voltage electric motors with direct start-up are star connected if mains voltage is higher, or delta connected if lower:

motor 220/380 V: delta connection 220V voltage star connection 380V voltagemotor 380/660 V: delta connection 380V voltage

All motors can operate in either direc-tion. Direction of rotation can be chan-ged inverting the connections to the stator terminals.

W2 U2 V2

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

W2 U2 V2

U1 V1 W1

U1 V1 W1

U2 V2 W2

U1 V1 W1

U2 V2 W2

U1 V1 W1

U2 V2 W2

U1 V1 W1

U2 V2 W2

U1 V1 W1

single pole motors

Low speedDelta Low speed

1 windingDahlander 4/8 Poles

2 windings4/6 Poles

High Speed High SpeedStar

twin pole motors

ELECTRICAL CONNECTIONS

Air handling units are usually supplied without wiring connections. Installators are responsible for:- wiring:- fan motors- humidification pumps- roll filters- reductor- limitswitch- pressure switch- pressure switches- lamps- electrical batteries

MOTOR CONNECTIONS

Available motors vare asynchronous, three-phase cage rotor motors with closed casing and external ventilation. Electrical specifications are in com-pliance with IEC 34-1 and CEI 2-3 n°1110 requirements, while dimensio-nal characteristics comply with IEC 72 and UNEL 13113-71-IM B3.

In the case of two-speed motors, check the wiring diagram supplied.

Wiring connections of three-phase motors are shown in the general dia-gram below. Refer in all cases to the diagram inside or outside the motor terminal plate.

Air handling units -FM series -

46 ` aSelection, installation, use and maintenance manual

Page 47: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Caution

• provide an interlock of the electric battery with the fan to prevent the inside overheating with possible damage

to some components.

Caution

• provide the connec-tion with the manual reset thermostat inside the frame of the elec-tric battery to prevent overheating inside unit

and potential damage.

• provide the switching off of the AHU fan delayed by over 5 minutes than the turn off the electric battery.For the electrical connection please refer to the general scheme on the right or to the one attached to each battery.

- prevent the entry of unpleasant odours and insects.

Follow the indications below for the siphon size and execution in case of pan under negative and positive pres-sure.

ELECTRIC BATTERIES CONNECTION

Refer to the wiring diagram provided with the batteries

CONDENSATE DISCHARGE

The drainage system should provide for a properly sized siphon to:- ensure free condensate drainage;- prevent the potential entry of air into the circuit under negative pres-sure;- prevent the potential air leakage from the pressurised circuit;

ELECTRIC PUMP CONNECTIONS

Electric pumps of the evaporating decks humidifi ers have a 220/380 V motor, and must be connected as follows:

-delta connection at 220V-star connection at 380V

ROLL FILTERS CONNECTION

Refer to the wiring diagram in the roll fi lter electrical panel.

ELECTRICAL BATTERY CONNECTION

Here are some of the requirements ne-cessary for the proper connection of electric batteries:

• when wiring make sure that nuts, wa-shers, and lugs are securely fi xed to the terminal of the heating element;

• Ensure that the cables used for wiring are of adequate size;

• Check the line voltage is compatible with the data printed on the data plate of the terminal, or on the edge of the coils fl ange;

• Do not open the battery cover before disconnecting the power supply;

• during routine maintenance is neces-sary to check the status of ceramic insu-lators and the tightening of nuts;

P

neg.

H

H

H1

P

pos.

H

H

H1

Negative pressure:H1 = 2PH2= H1 / 2

Positive pressureH1 = 2PH2 = H1 / 2

Pneg.

Ppos. where P is pressure expressed

in mm (water gauge) (1 mm c.a. = 9.81 Pa)

The siphon should have a plug to facilitate the lower section cleaning, and an easy disas-sembly.

FUSIBILI

I-0

Example of wiring diagram

Air handling units -FM series -

47 ` aSelection, installation, use and maintenance manual

Page 48: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

EARTHING

All electrical utilities must be connec-ted to earth.All unit sections must be connected to earth.For this purpose all unit sections have an M8 screw for connection to the plant earth. The screw is identified by a pla-te, and is positioned in the vicinity of one if the section base supports, as in-dicated by in the figure below.

knobs. Depending on the size of the unit, it may be necessary to remove the anti-splash net over the fan gril-le. Remove the threaded bars from the fan partition.

Roll filters: usually supplied already assembled. To disassemble and re-assemble the filters, please refer to the supplied manufacturer's instruc-tions.

Activated carbon filters: cartrid-ges are usually supplied assembled. To fit the cartridge, slide it into its seat, then rotate in a clockwise di-rection by approx. 5°.

INSTALLATION OF FILTER CELLS

-Plane filter cells (synthetic or metal) on guides: usually supplied already installed. If not installed, cells must be slided on to the guides. Make sure that the cells are correctly clipped to one another to facilitate removal for maintenance.

-Plane filter cells (synthetic or metal) on frame, bag filters, rigid bag filters: usually supplied in boxes placed insi-de the unit. They must be frontally slided on to the frame, and fixed with the supplied clips (see figure A).

-Absolute filters: they are always sup-plied inside the unit. They must be frontally slided on to the frames, and fixed with supplied brackets and

For earthing using the connectors marked with the symbol chart on the right.

A

1 - Typical filter configuration with "drawer"NB: In some cases, the filter cells are not mounted on the frame holder in-ballate but are left in their containers

2 - In order to extract the entire filters, which runs on rails, please pull the omega profiles top and bot-tom (indicated with A) to ease the pressure of the filter frame against the seals.

3 - It is now possible to remove the filter (or just the frame if the filters are provided) sliding it on the rails.

Instructions for the extraction and insertion of the filter frame in the case of "slide" configuration:

To place and fix the filters please do the below steps in reverse order.

Air handling units -FM series -

48 ` aSelection, installation, use and maintenance manual

Page 49: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

f- direction of rotation: the fan impeller should rotate in the direction indicated by the arrow on the fan screw; if the di-rection is incorrect, invert two phases on the motor terminal block.

g- electrical absorption: set the heat pro-tections on the panel to the absorption va-lues given on the motor plate, then use an ammeter to check that current does not ex-ceed it. If electrical absorption is too high, the load loss of the air distribution system has probably been overestimated. In this case, apply additional resistance by adju-sting the damper, or preferably reduce fan rotation speed by replacing the transmis-sion. To adjust speed in air handling units fi tted with variable pitch pulleys, vary the pitch on the pulley (see B in the above fi gu-re). This problem is normally encountered in fans with forward curved blades.

Measure length T;

with the aid of a dynamometer, apply a perpendicular force F capable of making a deflection of 1.5 mm for each 100 mm of T to a belt halfway along T;compare the value of F on the dynamo-meter with the F' and F" values given in the table below.If F < F', tighten the belt.If F > F", slacken the belt.Belt tension rapidly diminishes during run in periods; for this reason, new belts should be tensioned to a force F value 1.3 times greater than the F" value given in the table.

To adjust belt tension, shift the screws on the motor slide A.

Special guards are sometimes fi tted over fragile parts during transport. Always re-move them prior to using the air han-dling unit.

Main checks when starting-up the unit:

FANS

a- check that screws are tight on fan group

b- check tightening of pulleys on taper bushes

c- check pulley alignment

d- check free rotation of fans and motore- check belt tension; check tension after a few hours of operation, following the procedure described below.

Sez. beltExt. diameter smaller pulley

(mm)

Speed smalle pulley

[rpm]F' min.(N) F" max. (N)

SPZ

50 - 90 1200 - 5000 10 15

100 - 150 900 - 1800 20 30

155 - 180 600 - 1200 25 35

SPA

90 - 145 900 - 1800 25 35

150 - 195 600 - 1200 30 45

200 - 250 400 - 900 35 50

SPB

170 - 235 900 - 1800 35 45

250 - 320 600 - 1500 40 60

330 - 400 400 - 900 45 65

SPC

250 - 320 900 - 1800 70 100

330 - 400 600 - 1200 80 115

440 - 420 400 - 900 90 130

Dynamometer values table

A

B

f

F

T

=

=

20. FIRST START-UP CHECKS

Air handling units -FM series -

49 ` aSelection, installation, use and maintenance manual

Page 50: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

ELECTRIC PUMPS

- direction of rotation- calibration of thermal protections- electrical absorption- adjustment of by-pass valve

FILTERS

- correct positioning and fi xing of cells- cleanliness of cells and unit inte-rior

21. MAINTENANCE

HEAT EXCHANGE

Before a possible test the thermal performance of heat exchangers is recommended to:• check the correct connection of the coil;• check the temperature of the fl uid;• check the correct operation of the control logic and of the adjustment (three-way valves, actuators, etc.).

Maintenance should be carried out according to the intervals indicated in the table below. Intervals are indica-

Component Phase Check Instrument Limit Scheduled

Fan section

•Checking tension belt,•Checking wear belts,•Control mounting pulleys,•Control wheel cleaning,•Control bearings noise.

•Instrumental•Visual•Visual•Visual•Visual

Dynamometer

•two-monthly•two-monthly•two-monthly•two-monthly•two-monthly

•Synthetic filters,•Bag filters,•Absolute fi lters,•Rollers filters.

•Fouling Control,•Fouling Control,•Fouling Control,•Low coil control.

•Visual•Instrumental•Instrumental•Visual

ManometerManometer

300 Pa600 Pa

•biweekly•biweekly•biweekly•to report

Droplet-separatorhumidifier

•Obstruction control package,•Tank cleaning,•Clean water filter,•Tank emptying,•Water level.

•Visual

•Visual

•two-monthly•two-monthly•two-monthly•a fine stagione•two-monthly

Heat exchanger coil

•Control cleaning pack,•Control of the cleaning tank condensation

•Visual•Visual

•each year•each year

Humidificationwasher

•Check operation of nozzles •Visual •two-monthly

•Tank cleaning •two-monthly

•Clean pump filter •two-monthly

•Water level •Visual •two-monthly

HUMIDIFIERs

- correct positioning of evaporator pack- correct connection to mains supply and adjustment of fl oat valve

DAMPERS

- operating mode (manual and automatic if applicable)- position: bear in mind that unit start-up with closed dampers may not be possi-ble if fans have a maximum static head greater than 2000 Pa (unless otherwise specifi ed with the order).

tive: in the case of fi lters, for exam-ple, maintenance requirements may vary according to unit applications.

Fans maintenance may be more re-gular if the unit operates continuou-sly.

Air handling units -FM series -

50 ` aSelection, installation, use and maintenance manual

Page 51: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

TROUBLESHOOTING

FAULT POSSIBLE CAUSE CHECK REMEDIES

Motor out of absorption range

Excess capacity- Capacity and static pressure;- Fan speed

- Reduce fan rotation speed;- Create load loss in ducting

Excessive air flow Air distribution system load loss has been overestimated.

- Capacity and static pressure- Fan speed

- Reduce fan rotation speed;- Create load loss in ducting;

Insufficient air flowAir distribution system load loss has been underestimated

- Capacity and static pressure;- Fan speed

Increase fan speed according to motor power rating and max. fan speed

Excessive noise

- Flow too high- Head too high

- Capacity- Static pressure

-Reduce air flow.-Increase flow to avoid fan pump zone.

Bearings are damaged Bearings Replace bearings

Metal components damaged. State of components Replace damaged parts

Rotating parts off balance. Vibrations in base Balance fan impeller

Water entrainment

- Flow too high.- Siphon is clogged. - No siphon.- Excess water flow.

- Flow.

- By-pass adjustment.

- Reduce flow.- Clean siphon.- Fit a siphon.- Adjust by-pass valve to reduce water flow.

Excess belt wear- Belts slack.- Pulleys off line.

- Belt tension.- Pulley alignment.

- Tighten belts.- Align pulleys.

Set temperature notreached

. Air flow too high.- Inlet temperature not accounted for.- Air in coil.- Water flow insufficient.- Water temperature too low.

- Air flow.

- Reduce air flow.

- Bleed air from coil.

22. DISPOSAL

At the end of their operating life, the FM units must be disposed according to the current laws.The main components including the unit of the FM series are made from:

• Galvanised sheet steel (panels, fan, internal beams);

• aluminium sheet metal (condensate drain pan, coil fins, recuperator, damper, frame motors, unit frame);

• copper (coil tubes, electric motor windings);

• polyurethane foam (insulation of the sandwich panels);• rock wool (silencers, insulating san-

dwich panels);

N.B. Bear in mind that air handling units are integrated into a general system. For this reason, faults may be caused by other system components, incorrect interaction between the unit and system, or ambient conditions different from those specified for unit design.

Air handling units -FM series -

51 ` aSelection, installation, use and maintenance manual

Page 52: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4
Page 53: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4
Page 54: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4
Page 55: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4
Page 56: FM Series Air handling units - Arfit · FM Series Air handling units ... power supply is di-sconnected. 1. ... Selection, installation, use and maintenance manual 4

Technical data shown in this booklet are not binding.FAST S.p.A. shall have thr right to introduce at any time whatever modifications deemed necessary to the improvement of the product

Manual printed on recycled paper.

FAST S.p.A. TRATTAMENTO DELL'ARIA35044 Montagnana (PD) - ItalyVia Luppia Alberi, 170Tel. (+39) 0429 806311 - Fax 0429 806340E-mail: [email protected]://www.fastaer.com

1111

-618

5912

-rev

.1