Model No. Dimension Agent Cylinder Capacity Protection Volumes Control Circuit Fire Alarm Color Cabinet Material Cylinder Weight Total Weight MFP-050 50kg X 1unit 58m 3 102kg 190kg FM-200 PACKAGE MFP-075 500W X 500D X 1900H FM-200 GAS 75kg X 1unit 87m 3 AC100V/220V DC 24V IC Control Circuit SIREN & Sound Alarm Pale yellow SS400 143kg 230kg 0℃ ~ 40℃ MFP-100 100kg X 1unit 116m 3 181kg 265kg Power Main Power Back-up Power >>> Details of FM-200 Package Composition >>> FM-200 Package Spec. [50kg] Handle Control panel Speaker Discharge Head Copper Tube Copper Tube Agent measuning equipment Cylinder valve Cylinder Tightening band Emergeney Battery Pressure S/W Fiexible Tube [75kg] [100kg] FM-200 (HFC-227ea) Recommended Temperature for use ■ Head Office Room 1009, ByeokSan Digital Valley 5, 60-73, Gasan-Dong, GuemCheon-Gu, Seoul, Korea (Zip Code : 153-801) Phone : 82-2-785-1301, Fax : 82-2-785-1313 ■ lst Factory 146BL-13LT, 715-12, Gojan-Dong, Namdong-Gu, Incheon, Korea (Zip Code : 405-821) Phone : 82-32-811-1301, Fax: 82-32-811-1305 ■ 2nd Factory 448-188, Hakun-Ri, Yangchon-Myeon, Gimpo-Si, Gyeonggi-Do, Korea (Zip Code : 415-843) Phone : 82-31-988-1306, Fax : 82-31-985-1808 The information contained herein is subject to change without prior notice to customers for manufacturer’s improvement of product quality. 2013. 6. REV.2
4
Embed
FM-200 (HFC-227ea) - toangiaphat.comtoangiaphat.com/files/news/1001/content/1434/FM200 Package(English... · FM-200 PACKAGE MFP-075 500W X 500D X 1900H FM-200 GAS 75kg X 1unit 87m
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Model No.
Dimension
Agent
Cylinder Capacity
Protection Volumes
Control Circuit
Fire Alarm
Color
Cabinet Material
Cylinder Weight
Total Weight
MFP-050
50kg X 1unit
58m3
102kg
190kg
FM-200 PACKAGE
MFP-075
500W X 500D X 1900H
FM-200 GAS
75kg X 1unit
87m3
AC100V/220V
DC 24V
IC Control Circuit
SIREN & Sound Alarm
Pale yellow
SS400
143kg
230kg
0℃ ~ 40℃
MFP-100
100kg X 1unit
116m3
181kg
265kg
PowerMain Power
Back-up Power
>>> Details of FM-200 Package Composition
>>> FM-200 Package Spec.
[50kg]
Handle
Controlpanel
Speaker
DischargeHead
CopperTube
CopperTube
Agentmeasuningequipment
Cylindervalve
Cylinder
Tighteningband
EmergeneyBattery
PressureS/WFiexible
Tube
[75kg] [100kg]
FM-200 (HFC-227ea)
Recommended Temperature for use
http://www.naver.com/
■ Head Office Room 1009, ByeokSan Digital Valley 5, 60-73, Gasan-Dong, GuemCheon-Gu, Seoul, Korea (Zip Code : 153-801) Phone : 82-2-785-1301, Fax : 82-2-785-1313■ lst Factory 146BL-13LT, 715-12, Gojan-Dong, Namdong-Gu, Incheon, Korea (Zip Code : 405-821) Phone : 82-32-811-1301, Fax: 82-32-811-1305■ 2nd Factory 448-188, Hakun-Ri, Yangchon-Myeon, Gimpo-Si, Gyeonggi-Do, Korea (Zip Code : 415-843) Phone : 82-31-988-1306, Fax : 82-31-985-1808
The information contained herein is subject to change without prior notice to customers for manufacturer’s improvement of product quality.2013. 6. REV.2
FM-200(HFC-227ea)PACKAGE SYSTEMCABINET TYPE
>>> FM-200 Package Operation Sequence
FM-200 (HFC-227ea) Package System (Cabinet Type) is the high-technology firefighting extinguisher and can suppress the fire promptly by automatic and manual operation.
>>> Why FM-200 Clean Agent- The most reliable and effective extinguishant agent from HFC substitutes for Halon 1301
- Environment-friendly agent and Ozone Depletion Potential(ODP) is “zero” (0).
- Safe to humans and can be used for residential area
- Non-conductive agent and most suitable for the usage in the
expensive electronic equipment such as computer and communication device.
>>> Applicable Industries - data processing room, electricity equipment room, communication device room, electronic equipment