Monitoring of a dwelling equipped with a demand controlled ventilation system
4

FLY351GB_v2

Mar 25, 2016

Download

Documents

Aereco

Monitoring of a dwelling equipped with a demand controlled ventilation system
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: FLY351GB_v2

FLY3

51G

B_v2

Monitoring of a dwelling equipped with a demand controlled ventilation system

Page 2: FLY351GB_v2

Indoor air quality has become one of the major concerns in Japan since notably the last national scale survey had revealed that the indoor concentration of formaldehyde in considerably large number of dwellings had been higher than the concentration guideline. Besides the hygienic aspects, the recent oil crisis has involved to reconsider the energy aspect in the Building. Considering that air renewal represents up to 50 % of the total building consumption, the control and the management of the ventilation becomes a major concern for all the actors of the Building sector. The monitoring presented in this document aims thus at improving the knowledge and at helping developing efficient strategies regarding ventilation aspects.

Started in February 2008 in a 30 years old building in the centre of Tokyo, this experiment

has consisted in measuring and recording several ventilation parameters during a couple of weeks in a monitored dwelling, to evaluate the performances of a humidity controlled mechanical ventilation system. Managed by the NILIM (National Institute for Land and Infrastructure Management), this project is the result of a cooperation with French Aereco Company. The dwelling, –belonging to Tokyo Gas company–, was composed of two bedrooms and three technical rooms for a total surface of 40 m² (height 2.50 m). The human occupancy was physically simulated by the mean of four water and heat emitters located in the kitchen, bathroom, and bedrooms, while the ventilation performances were measured through specific instrumentation located in each ventilation device (air inlets and air extract units).

To measure the ventilation performance

Regulation and requirements for ventilation in the dwellings

The dwelling is equipped with a demand controlled mechanical ventilation system: The polluted air is extracted though BXS air extract units from the wet/technical rooms. The demand controlled* air extract units distribute the exhaust airflow generated by the V4A fan according to the needs of each room. In this monitoring, the new air is distributed in the bedrooms by the mean of through-the-wall EHT humidity sensitive air inlets.

* humidity sensitive, presence detection and manual boost

airflow

Special sophisticated emitters provided by the NILIM were used to simulate the human occupancy: the quantity of water is controlled and is set according to a scenario of occupancy. The principle is to simulate a couple with a realistic scenario of activity and presence during the day in the apartment. The human behaviour is simulated by the mean of a production of heat (130 W) and water (60 g/h)**, following the daily scenario presented Fig. 3 (see right).

**70g/h in the bedroom

Air inlets and air extract units were equipped with special sensors to measure:

- Relative Humidity- Temperature- Shutter position- Pressure*

* only in the extract units, as pressure is too low to be

measured at the air inlet.

The airflow is calculated from the shutter position and pressure. The shutter position is measured by the mean of an hall effect sensor, detecting the electromagnetic variations resulting from the position of a magnet integrated in the shutter. All the sensors have been connected to a central data logger, especially developed for the experiment. 30 data have been recorded every minute, leading to a total of 560 000 data for the 13 days of the study.

Ventilation system Human presence simulation

Measurement and data system

Bedroom 1 Bedroom 2

Kitchen &Living room

WC

Bath

Ventilation system

Water and heat emitter used in the living room/kitchen

BXS extract unit with sensor in the kitchen

The Building Standard Law applies for every new construction or large scale refurbishment. The

ventilation part authorizes mechanical ventilation or natural ventilation systems. The requirements

for residential buildings are given by a minimum airflow of 20 m3/h per person to exhaust the

pollution emitted by the human metabolism and activities and by a new regulation since 2003

to solve the “sick house problem”. This new text expects to limit the concentration of VOC’s like

formaldehyde notably, by requiring a minimum airflow level of 0.5 ACH when using a mechanical

ventilation system.

Page 3: FLY351GB_v2

During the measurement period (from 11th to 24th Februar y 2008), average outdoor conditions are recorded 4.8°C temperature, 43% relative humidity. The heating system is located in the bedrooms and in the k itchen. Heaters are controlled

representing a real ist ic scenario in Japanese houses: shut on in the morning and in the evening, off the rest of the t ime when occupants are outside and during the sleep (see graph Fig. 4) .

The dwelling air tightness has been calculated from

the measured airflows (inlet and extract). It has been

calculated that the air tightness follows the rule

Q infiltration (m3/h) = 8.4 x dP (Pa), which means that the

envelope can be considered as a giant filter. This result is not

surprising as walls are made of poured concrete, therefore

very air tight, and sliding windows are equipped with brush

joins, reacting as a filter. It was then possible to calculate the

level of the cross ventilation during all the experiment.

Several monitoring and studies realised in Europe

notably have demonstrated the close link which exists

between humidity level in the dwelling and indoor air

quality. A monitoring realised in Holland, Belgium and

France in 1989 has shown the relationship between

CO2 and H

2O in the technical rooms, to conclude that

humidity is a particularly good revelator of the inner

pollution in residential buildings, and that taking into

account this parameter is a good way to improve the

indoor air quality.

Air tightness

Inner relative humidity and indoor air quality

To control the airflow according to humidity

Reac t iv i t y of the humidit y sensitive ventilation components

The measurements realised on humidity sensitive air inlets and extract units have shown their ability to modulate the airflow according to humidity: on the graphs Fig. 1, we can see that the opening section of the air inlet has followed well the variations of humidity in the bedroom (We can notice that the elevation of humidity between 8.30 up to 17.00 is mainly due to the cut off of the heating). The extract unit has shown the same behaviour (Fig. 2). Equipped with both humidity sensor and boost facility (normally manually pulled when cooking), the extract unit has a minimum opening of 10 m3/h and is able to extract up to 50 m3/h when the humidity is high or when it is on boost mode. For the monitoring, the boost was running between 18:00 and 18:45 thanks to a programmable switch, like we can observe on the corresponding graph.

The same behaviour have been observed in all the rooms, showing that humidity sensitive ventilation system well adapt and control the humidity level in the rooms, helping preventing the dwelling from condensations.

Performance of the humidity sensitive ventilation

Fig. 1: Variations of temperature, relative humidity and

opening/airflow of the air inlet (Q@10Pa) located in the

kitchen/living room, on one day

Fig. 2: Variations of temperature, relative humidity and

opening/airflow of the air extract unit (Q@100Pa) located in

the kitchen/living room, on one day

Fig. 5: Measurement of the reactivity of a humidity sensitive

extract unit in the bathroom

Fig. 3: Daily occupation in the bedroom n.1 and in the

kitchen by the wife

Fig. 4: Daily heating in the bedroom n.1 and in the kitchen

0

10

20

30

40

50

60

00:00 02:24 04:48 07:12 09:36 12:00 14:24 16:48 19:12 21:36 00:00

Time

m3 /h

, °C,

%RH

TRHQ@10Pa

0

10

20

30

40

50

60

00:00 02:24 04:48 07:12 09:36 12:00 14:24 16:48 19:12 21:36 00:00

Time

m3 /h

, °C,

%RH

TRHQ@100Pa

0

1

0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00

Bedroom Kitchen

Time

0

1

0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00

Time

35

40

45

50

55

60

65

20:24 20:39 20:54 21:09 21:24 21:39 21:54 22:09 22:24 22:39 22:54 23:09 23:24 23:39 23:54

RH in %

Q@100Pa in m3/h

2 min

The reactivity of humidity sensitive devices has been evaluated by measuring the delay between a fast increase of humidity and the shutter opening of the extract unit. The graph Fig. 5 shows a time reaction close to 2 minutes, which guarantees a quick exhaust of the excess of humidity.

Page 4: FLY351GB_v2

FLY3

51G

B_v2

To decrease heat losses to save energy

Humidity controlled ventilation system: conciliating energy performance and indoor air quality

During all the heating period, the outdoor fresh air supplied by the ventilation system needs energy to be heated up to the comfort temperature. This specific energy consumption, –which is called “heat losses”–, can represent up to 50 % of the total energy consumption of the dwelling, depending on the ventilation system.

A calculation, based on instantaneous variable airflows and outdoor/indoor temperature differences enables to determine the heat loss due to ventilation used for this monitoring*. On graph Figure 6, we can observe that the total airflow is quite stable, except during the boost airflow periods. The average airflow is at 44 m3/h, including boost ventilation, which can be considered low, while the real capacity of the ventilation system is 135 m3/h (50 m3/h in the bathroom; 50 m3/h in the kitchen and 35 m3/h in the toilets). It is obviously highly improbable that all the extract units run at their maximum capacity simultaneously as the boost facility and the bathroom high rate are reached only

The humidity controlled ventilation system as a whole has performed well all along the monitoring. The humidity controlled devices –air inlets and air extract units– have modulated the airflow according to expectations, reducing the condensation risks and improving indoor air quality, in the wet rooms as well as in the dry rooms. The system has proved its compliance to the Japanese regulation, with an average airflow close to the 0.5 ACH minimum airflow rate requested.

It has been also demonstrated that the demand controlled ventilation system used in this monitoring was able to boost the airflow when needed, without impacting the average airflow. This last remains statistically at a low level, enabling thus to reduce heat losses up to 35 % compared to a fix 70 m3/h airflow system. But the main advantage of this DCV system has been demonstrated by its ability to punctually go largely above this “low” average airflow without impacting the energy performance (maximum capacity up to 130 m3/h), because

of the short lasting of these periods. The energy performance of the system was completed by the use of a low energy fan (15 W at 50 m3/h) which consumption is automatically optimised and reduced with the airflow. Easy to install in the new as in refurnishment and requiring only a light maintenance, the Aereco humidity sensitive ventilation system has proven its efficiency and its adaptation to the Japan specificities.

Aereco S.A. - 9 allée du Clos des Charmes - Collégien - 77615 Marne-la-Vallée Cdx 3 - FRANCEtel: +33 1 60 06 26 63 - fax: +33 1 60 06 22 11 - www.aereco.com

010

203040

5060

7080

Time

m3 /h

0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00

Fig. 6: Total exhaust airflow variations, on one day

The table Fig. 7 gives the energy consumption of Aereco ventilation system for 8 days measurements in comparison with fix 0.5 ACH and 0.7 ACH.

«Aereco system n.1» is the actual measured one (composed of 3 extract units); «Aereco system n.2» is an extrapolation of the measured system, with only 2 extract units (a single extract unit for bathroom with toilets, which is more used and representative for these kind of small dwellings). We can observe that the Aereco system saves 8% if compared with 0.5 ACH, and 35% if compared with 0.7 ACH.

Energy comparisons with other ventilation systemsfix 50 m3/h (0.5 ACH)

fix 70 m3/h(0.7 ACH)

Aereco system n.1

Aereco system n.2

Total energy consumption (heat

losses) on 8 days measurements28.20 kWh 39.47 kWh 31.48 kWh 25.84 kWh

Equivalent airflow (average) 50 m3/h 70 m3/h 55.83 m3/h 45.83 m3/h

Energy savings on heat losses /

0.5 ACH- +40% +12% -8%

Energy savings on heat losses /

0.7 ACH-29% - -20% -35%

Fig. 7: Average airflows and heat losses due to ventilation - comparison with different ventilation systems

for a short period of time. But this high potential can be used each time the need is important, without penalising the energy aspect as the lasting is short.

This advantage leads to a good efficiency in terms of ventilation rate as well as in terms of energy consumption. Compared to a fixed and

permanent ventilation system, the humidity controlled ventilation system enables more airflow when needed and less when the demand is reduced. The compromise between high capacity and low average airflows is reached.

* The hypothesis of a null cross flow was taken