FLEXIBLE CONDUCTORS FLEXIBLE CONDUCTORS OVERVIEW Spec-01138 C EQUIPMENT PROTECTION SUBJECT TO CHANGE WITHOUT NOTICE POWER AND GROUNDING CONNECTIVITY 1 POWER AND GROUNDING CONNECTIVITY FLEXIBLE CONDUCTORS FLEXIBLE CONDUCTORS OVERVIEW FLEXIBLE CONDUCTORS PRODUCT OVERVIEW Product Range Insulated flexible busbar (ERIFLEX FLEXIBAR) Insulated braided conductor (IBS, IBSB & IBSBR) Power shunt (PBC, PBCR & PPS) Earth ground copper braids (MBJ & BJ) Earth ground stainless steel braids (CPI) Flat and round copper braids in coils Tubular copper braids in coils Typical Uses • Heavy-duty power interconnection • Overcome vibration/alignment problems • Circuit breaker, generator and prefabricated power network conductor • Expansion joints • Variable terminating positions • Machine connections • Movable connection from massive busbar system • Alternative to large & multiple cables • Alternative to rigid busbar • Interconnects for low voltage power distribution units • IBSB specially designed for industrial circuit breaker connection • Overcome vibration/alignment problems • Battery connections • Earth ground connections • Transformer or generator to busbar connection • Overcome vibration/alignment problems • Power interconnection • Switchgear & control equipment • Power distribution • Transportation • Power, earthing/grounding and equipotential connections • Electrical bonding enclosure door • EMI effect reduction application • Switchgear & control equipment • Rail transportation • Electrical equipment manufacturers • Power generation (wind, solar) • Data center • Switchgear & control equipment • Transport • Electrical equipment manufacturers • Power generation • Machinery manufacturer • Interconnects for low voltage power distribution units • IBSB specially designed for industrial circuit breaker connection • Overcome vibration/alignment problems • Battery connections • Earth ground connections • Earthing/grounding and equipotential connections • Superior abrasion, corrosion, chemical, and UV resistance for outdoor applications • Expansion joints • Connections for lightning protection systems • Transportation • Food and beverage industry • Power generation (wind, solar) • Chemical and oil industry • Automotive • Defense & aerospace • Civil construction • Urban projects • Earth/ground connections • Power interconnection • Lightning protection • Flexible links • Overcome vibration/alignment problems • Defense & aerospace • Rail transportation • Automotive • Electronics • General electrical sector • Civil construction • Screening of cables from electromagnetic, electrostatic and RF interference • Mechanical support • Protection against abrasion and corrosion • EMC & EMH applications • Defense & aerospace • Transportation • Electronics & communication • Cable harness & assembly makers • Component distributors Typical Market
32
Embed
Flexible ConduCtors ProduCt overview Product Range … eriFlex Flexibar insulated Flexible busbar Features • eriFLeX FLeXiBAr is formed with multiple layers of thin electrolytic
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Flexible ConduCtors Flexible ConduCtors overview
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity1
Spec-01138c763.422.2211763.422.2600
Power and GroundinG ConneCtivityFlexible ConduCtorsFlexible ConduCtors overview
Flexible ConduCtors ProduCt overview
Product Range
Insulated flexible busbar(ERIFLEX FLEXIBAR)
Insulated braided conductor (IBS, IBSB & IBSBR)
Power shunt (PBC, PBCR & PPS)
Earth ground copper braids (MBJ & BJ)
Earth ground stainless steel braids (CPI)
Flat and round copper braidsin coils
Tubular copper braids in coils
Typical Uses
• Heavy-duty power interconnection• Overcome vibration/alignment
Features• eriFLeX FLeXiBAr is formed with multiple layers of thin
electrolytic copper, available in plain or tin plated• eriFLeX FLeXiBAr connections are made by punching directly
through the laminates. there are no lugs to purchase, helping to eliminate faulty connection problems and making installation simpler and faster
• the insulation is a high-resistance, self-extinguishing PVc or silicone compound
• traceability code and designation catalog number on product• easily formed, eriFLeX FLeXiBAr improves assembly flexibility
and aesthetics of panels• ideal alternative to large cable and rigid busbar• Quality: 100% production dielectric tested• Full range from 24 mm2 up to 1200 mm2
sPeCiFiCations• copper laminates are free to slide within the insulation• High insulation quality• Wide variety of bending, twisting and folding possibilities• Usage -50°c up to 105°c (-53°F up to 221°F) • nominal voltage = 1000 V Ac/1500 V Dc • Self-extinguishable• High mechanical resistance• High elongation value• High current withstanding• High copper quality (99.9% purity)• High conductivity
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.∆T = Temperature of conductors – Internal temperature of panel.UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.NEC is a registered trademark of, and National Electrical Code (NEC) standard is a copyright of the National Fire Protection Association, Inc.
Flexible ConduCtors eriFlex FlexibAr busbArs And ACCessories
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity5
eriFlex Flexibar, tinned CoPPer
industry standards
certification Details: UL 67, UL 758
cSA c22.2 no. 0 and 210complies With: iec 60439.1, iec 61439.1, iec 61439.1 class ii
Features• thin layers of tinned electrolytic copper formed into a stack• insulated by high-resistance, self-extinguishing PVc with less
than 20% contact with conductor for high flexibility• easily bent, folded, and twisted, improving assembly flexibility,
shortening connections, and decreasing footprint• Dramatically smaller and more flexible than comparable cable
based on ampacity• Better power density than cable with lower skin effect ratio• connections made by punching and bolting directly through the
copper laminates, clamping onto the end of the eriFLeX• eriFLeX FLeXiBAr, or welding using cADWeLD• no lugs needed, reducing installation time and improving
resistance to vibration• Weight savings and material savings compared to wire
alternatives• reduces total installation cost• traceability codes and designation part numbers printed on
insulation• 100% production dielectric tested• UL 758 Appliance Wiring material requirements for cold Bend
testing at -40°c and -50°c (-40°F and -58°F)• GoSt compliant• roHS compliant
Flexible ConduCtors eriFlex FlexibAr busbArs And ACCessories
Spec-01138 CPH 763.422.2211 • FAX 763.422.2600 • PentAirProtect.comEQUIPMENT PROTECTION Power and GroundinG ConneCtivity 6
typical Application current rating: 125 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
typical Application current rating: 250 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
typical Application current rating: 400 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
Flexible ConduCtors eriFlex FlexibAr busbArs And ACCessories
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity7
typical Application current rating: 800 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
typical Application current rating: 1,200 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
typical Application current rating: 1,600 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
typical Application current rating: 2,000 A
Catalog Number L (Ft.) .T 30 K (A) .T 45 K (A) .T 60 K (A) N (in.) A (in.) B (in.) Cross Section (kcmil) 2 Bar Current Coefficient 3 Bar Current Coefficient Qty.
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
ΔT = Temperature of conductors – Internal temperature of panel.
Flexible ConduCtors eriFlex FlexibAr busbArs And ACCessories
Spec-01138 CPH 763.422.2211 • FAX 763.422.2600 • PentAirProtect.comEQUIPMENT PROTECTION Power and GroundinG ConneCtivity 8
eriFlex eriFlex Flexibar end Cover
• end cover for eriFLeX FLeXiBAr and insulated Power Braid• Allows for visual inspection of connection• easy fitting after fixing• roHS compliant• material: Polycarbonate• Flammability rating: UL 94V-0
Catalog Number Conductor Width (in.) Unit Weight (lb.) Qty.ENDCOV20 0.79 0.42 12ENDCOV24 0.94 0.48 12ENDCOV32 1.26 0.57 12
Flexible sPaCer ClamPsFeatures• easy to install• Provides support• Allows for proper cooling
uFs eriFlex Flexibar and ibsb suPPort Kit • Kit includes one rail and 24 retaining blocks• create up to three 650 mm (25.6”) supports capable of holding
four eriFLeX FLeXiBAr• retaining blocks are halogen free• roHS compliant
Catalog Number Conductor Thickness (in.)
Conductor Width (in.)
Height H (in.)
Length L (Ft.)
Width W (in.) A (in.) B (in.) Unit Weight (lb.) Qty.
Flexible ConduCtors eriFlex FlexibAr busbArs And ACCessories
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity9
Fs sPaCer ClamP, snaP Close
industry standards
UL recognizedFlammability rating: UL 94HB
Features• Provides support for eriFLeX FLeXiBAr and insulated braided
conductors without damaging the insulation• ensures correct spacing for optimum cooling• Supports up to four conductors in parallel• easy to install• Halogen free• recommended distance between clamps: 15.75 in. (400 mm)• roHS compliant
sPeCiFiCations• material: Polyamide• Working temperature: -40 to 266 °F
Catalog Number ConductorWidth (in.)
HeightH (in.)
LengthL (in.)
HoleSizeHS (in.)
UnitWeight(lb.)
Qty.
FS24 0.95 Max 2.04 1.18 0.27 0.03 25
FS32 1.25 Max 2.04 1.49 0.27 0.04 25
Fs sPaCer ClamP
industry standards
UL recognizedFlammability rating: UL 94HB
Features• Provides support for eriFLeX FLeXiBAr and insulated braided
conductors without damaging the insulation• ensures correct spacing for optimum cooling• Supports up to four conductors in parallel• easy to install• Halogen free• recommended distance between clamps: 15.75 in. (400 mm)• roHS compliant
sPeCiFiCations• material: Polyamide, Steel• Working temperature: -40 to 266 °F
Finish• Finish: electrogalvanized
CatalogNumber
ConductorWidth (in.)
Height H (in.)
Length L (in.)
HoleSize HS (in.)
A (in.)UnitWeight(lb.)
Qty.
FS4063 1.57 – 2.48 3.74 6.54 0.33 5.90 0.22 10
FS80100 3.15 – 3.94 5.51 8.82 0.33 7.87 0.55 10
Flexible ConduCtors eriFlex FlexibAr busbArs And ACCessories
Spec-01138 CPH 763.422.2211 • FAX 763.422.2600 • PentAirProtect.comEQUIPMENT PROTECTION Power and GroundinG ConneCtivity 10
rFs reinForCed eriFlex Flexibar suPPort
• Supports up to eight conductors in parallel• ensures correct spacing for optimum cooling• easy to install• Spacers are halogen free• roHS compliant
Catalog Number Conductor Width (in.) D (in.) H (in.) W (in.) HS (in.) TS A (in.) B (in.) C (in.) Unit Weight (lb.) Qty.
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity11
insulAted brAided ConduCtors
insulated braided ConduCtors (ibs, ibsb and ibsbr)sPeCiFiCationstemperature rise of conductor = t2 - t1 = Δt (K)ex.: For a current of 630A, with:t1 = 40 c (104 F) - t2 = 90 c (194 F)1) Δt = 90 - 40 = 50K2) in the 50 K column, find the closest current value to 630A.K = Kelvin degree (temperature calculated, but not measurable.)
insulated braided conductor in parallelWhen using 2 or 3 insulated braided conductors in parallel for the same phase, use the current coefficient:ex.: iBSB 100 - Δtº = 50K: 385 A2 braids in parallel > 385 A x 1,6 = 616 A3 braids in parallel > 385 A x 2 = 770 A
Selection of insulated braided conductor IBS, IBSB & IBSBR according to the internal temperature of the panel.
Internal Temperature of panel (T1)
Temperature of conductors (T2)
Am
bient Tem
perature
Insulated BraidedConductor Type
Section(sq-mm)
ΔT (K)30
ΔT (K)40
ΔT (K)45
ΔT (K)50
ΔT (K)55
ΔT (K)60
ΔT (K)70
CurrentCoefficient2 Busbars
CurrentCoefficient3 Busbars
IBS 25 25 137 158 167 177 185 193 209 1,6 2
IBSB 25 25 116 134 142 150 157 164 177 1,6 2
IBS 50 50 213 246 260 274 288 301 325 1,6 2
IBSB 50 50 213 246 260 274 288 301 325 1,6 2
IBSB 70 70 226 261 277 291 306 319 345 1,6 2
IBSB 100 100 298 344 365 385 404 422 456 1,6 2
IBS 120 120 325 376 398 420 441 460 497 1,6
IBSBR 120 120 363 419 444 468 491 513 554 1,6 2
IBS 185 185 407 470 499 526 552 576 622 1,6
IBSBR 185 185 416 480 509 537 563 588 635 1,6 2
IBS 240 240 488 563 598 630 661 690 745 1,6
IBSBR 240 240 556 642 681 718 753 786 849 1,6 2
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section.
This calculation does not take into account the heat dissipation from the switch gear.
Flexible ConduCtors insulAted brAided ConduCtors
Spec-01138 CPH 763.422.2211 • FAX 763.422.2600 • PentAirProtect.comEQUIPMENT PROTECTION Power and GroundinG ConneCtivity 12
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity13
ibsb/ibsbr insulated braided ConduCtor For CirCuit breaKers
industry standards
certification Details: UL 67, UL 758
cSA c22.2 no. 0 and 210complies With: iec 60439.1, iec 61439.1, iec 61439.1 class ii
aPPliCationiBSB/iBSBr is the ideal ready-to-install flexible wire replacement solution that is specifically designed for connections to all molded case circuit breakers, including the most compact breakers on the market. it connects to the front access terminals of the breakers without any additional accessories, such as angular connectors, spreaders, ring terminal connectors or extenders. iBSB/iBSBr is available in cross section of 25 to 240 mm² (49.34 to 273.65 kcmil), lengths from 230 to 1,030 mm (9.06” to 40.55”), and 80 to 350 A tinned and 400 to 630 A bare (red) copper.manufactured in an iSo 9001 certified proprietary automated facility, iBSB/iBSBr is formed by weaving high-quality electrolytic copper wire to form a durable low voltage connector with maximum flexibility that allows for more compact power connections to circuit breakers. the iBSB/iBSBr allows users to reduce the total size and weight of the installation, improving both design flexibility and assembly aesthetics.the iBSB/iBSBr features integral pre-punched palms that are ready to connect out of the box. there are no lugs to purchase or install, making connections simpler and faster and eliminating faulty connections due to vibration or fatigue. the insulation is a high-resistance self-extinguishing PVc.
iBSB/iBSBr is compatible with all major brand molded case circuit breakers. contact your Pentair representative to determine the correct size for your application.
Features• Suitable for all main molded case circuit breakers• resistant to vibration, improving reliability and performance• improves assembly flexibility and aesthetics• Quick and easy installation• no additional cutting, stripping, crimping and punching needed• integral palm without lugs or terminals reduces material and
assembly weight• Small wire diameter provides maximum flexibility• roHS compliant
sPeCiFiCations• Dielectric Strength: 20 kV/mm• Flammability rating: UL 94V-0• max Working Voltage, iec/UL 758: 1,000 VAc, 1,500 VDc• max Working Voltage, UL 67: 600 VAc/Dc• Working temperature: 221 °F max• Wire Diameter: 0.006”• complies With: iec 60439.1, iec 61439.1, iec 61439.1 class ii• material: copper, Polyvinylchloride
Finish• tinned or bare as noted
typical Application current rating: 125 – 160 A – Finish: tinned
Catalog NumberCrossSection(kcmil)
ConductorWidth(in.)
ConductorThickness(in.)
L (in.) A (in.) B (in.) C (in.) D (in.) HS1 (in.) HS2 (in.) Qty.
maximum Ampacity ratingsCross Section (mm²/kcmil) ÄT 30° C (A) ÄT 40° C (A) ÄT 45° C (A) ÄT 50° C (A) ÄT 55° C (A) ÄT 60° C (A) ÄT 70° C (A) 2 Bar Current
Coefficient3 Bar Current Coefficient
25/49.34 116 134 142 150 157 164 177 1.6 2
50/98.68 213 246 260 274 288 301 325 1.6 2
70/138.15 226 261 277 291 306 319 345 1.6 2
100/197.35 298 344 365 385 404 422 456 1.6 2
120/236.82 363 419 444 468 491 513 554 1.6 2
185/365.1 416 480 509 537 563 588 635 1.6 2
240/473.65 556 642 681 718 753 786 849 1.6 2
circuit Breaker compatibilityCircuit Breaker Current Rating 125/160 A 250 A 300 A 350 A 400 A 500 A 630 ACatalog Number IBSB25x IBSB50x IBSB70x IBSB100x IBSBR120x IBSBR185x IBSBR240x
Spec-01138 CPH 763.422.2211 • FAX 763.422.2600 • PentAirProtect.comEQUIPMENT PROTECTION Power and GroundinG ConneCtivity 16
ibs Flat insulated braided ConduCtor
industry standards
certification Details: UL 67, UL 758
cSA c22.2 no. 0 and 210complies With: iec 60439.1, iec 61439.1, iec 61439.1 class ii
aPPliCationiBS Flat insulated Braided conductors are the ideal ready-to-install flexible wire replacement solution. they connect directly to the front access terminals of an electrical device without the need for additional accessories, such as angular connectors, spreaders, ring terminal connectors or extenders. iBS Flat insulated Braided conductors are available in cross section of 25 and 50 mm² (49.34 and 98.68 kcmil), lengths from 230 to 1,030 mm (9.06” to 40.55”), and amperages ranging from 177 to 274 A.manufactured in an iSo 9001 certified proprietary automated facility, iBS Flat insulated Braided conductors are formed by weaving high-quality electrolytic copper wire to form a durable low voltage connector with maximum flexibility that allows for more compact power to electrical device. the iBS Flat insulated Braided conductor allows users to reduce the total size and weight of the installation, improving both design flexibility and assembly aesthetics.the iBS Flat insulated Braided conductor features integral pre-punched palms that are ready to connect out of the box. there are no lugs to purchase or install, making connections simpler and faster and eliminating faulty connections due to vibration or fatigue. the insulation is a high-resistance self-extinguishing PVc.
Features• Suitable for all main electrical devices• resistant to vibration, improving reliability and performance• improves assembly flexibility and aesthetics• Quick and easy installation• no additional cutting, stripping, crimping and punching needed• integral palm without lugs or terminals reduces material and
assembly weight• Small wire diameter provides maximum flexibility• roHS compliant
sPeCiFiCations• Dielectric Strength: 20 kV/mm• Flammability rating: UL 94V-0• max Working Voltage, iec/UL 758: 1,000 VAc, 1,500 VDc• max Working Voltage, UL 67: 600 VAc/Dc• Working temperature: 221 °F max• Wire Diameter: 0.006 (in.)• material: copper, Polyvinylchloride
Finish• Finish: tinned
typical Application current rating: 160 A
Catalog NumberCrossSection(kcmil)
ConductorWidth(in.)
ConductorThickness(in.)
L (in.) A (in.) B (in.) C (in.) D (in.) HS1 (in.) HS2 (in.) Qty.
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity17
maximum Ampacity ratingsCross Section (mm²/kcmil) ÄT 30° C (A) ÄT 40° C (A) ÄT 45° C (A) ÄT 50° C (A) ÄT 55° C (A) ÄT 60° C (A) ÄT 70° C (A) 2 Bar Current
Coefficient3 Bar Current Coefficient
25/49.34 137 158 167 177 185 193 209 1.6 2
50/98.68 213 246 260 274 288 301 325 1.6 2
circuit Breaker compatibilityCircuit Breaker Current Rating 125/160 A 250 ACatalog Number IBS25x IBS50x
cSA c22.2 no. 0 and 210complies With: iec 60439.1, iec 61439.1, iec 61439.1 class ii
aPPliCationiBS round insulated Braided conductors are the ideal ready-to-install flexible wire replacement solution. they connect to the terminals of an electrical device without the need for additional accessories, such as angular connectors, spreaders, ring terminal connectors or extenders. iBS round insulated Braided conductors are available in cross sections of 120, 185 and 240 mm² (236.82, 365.10, and 473.65 kcmil), lengths from 330 to 1,030 mm (9.06” to 40.55”), and amperages ranging from 420 to 630 A.manufactured in an iSo 9001 certified facility, iBS round insulated Braided conductors are formed by weaving high-quality electrolytic copper wire to form a durable low voltage connector with maximum flexibility that allows for more compact power connections. the iBS round insulated Braided conductor allows users to reduce the total size and weight of the installation, improving both design flexibility and assembly aesthetics.
the iBS round insulated Braided conductor features pre-punched palms that are ready to connect out of the box. there are no lugs to purchase or install, making connections simpler and faster and eliminating faulty connections due to vibration or fatigue. the insulation is a high-resistance self-extinguishing PVc.
Features• resistant to vibration, improving reliability and performance• improves assembly flexibility and aesthetics• Quick and easy installation• no additional cutting, stripping, crimping and punching needed• Small wire diameter provides maximum flexibility• roHS compliant
sPeCiFiCations• Dielectric Strength: 20 kV/mm• Flammability rating: UL 94V-0• max Working Voltage, iec/UL 758: 1,000 VAc, 1,500 VDc• max Working Voltage, UL 67: 600 VAc/Dc• Working temperature: 221 °F max• Wire Diameter: 0.006 (in.)• material: copper, Polyvinylchloride
Finish• Finish: tinned
Flexible ConduCtors insulAted brAided ConduCtors
Spec-01138 CPH 763.422.2211 • FAX 763.422.2600 • PentAirProtect.comEQUIPMENT PROTECTION Power and GroundinG ConneCtivity 18
typical Application current rating: 400 ACatalog Number Cross Section Conductor
maximum Ampacity ratings"Cross Section (mm²/kcmil)" ÄT 30° C (A) ÄT 40° C (A) ÄT 45° C (A) ÄT 50° C (A) ÄT 55° C (A) ÄT 60° C (A) ÄT 70° C (A) 2 Bar Current
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity19
eArth Ground brAids
mbJ GroundinG and bondinG braid, tinned CoPPer
industry standards
UL Listed UL467
• complies With: iec 60439.1, iec 61439.1
aPPliCationmBJ Grounding and Bonding Braids are a reliable and convenient grounding solution for applications that require flexibility and durability. the tinned copper ground braids with massivated palms come ready to install without any additional cutting, stripping, crimping or punching and do not require the addition of tin or crimped lugs. the proprietary manufacturing process optimizes the electrical contact between each wire and helps eliminate moisture issues in the palms, preventing corrosion and lengthening the useful life of the braid.
Features• complete range of earth/ground flexible connections from 6 -
100 mm² (11.84 - 197.35 kcmil) cross section and from 100 - 500• mm (3.937” - 19.685”) length• integral palm, without tin or crimped lugs for superior electrical
contact and tensile strength resistance• resistant to vibration and fatigue, reducing maintenance• Provides weight savings, material savings and lower impedance
when compared to similar lugged cables with insulation• ready to use out of the box, eliminates the need for cutting,
stripping, crimping and punching• Quick and easy to install• recommended by the emc/emi directives and less impedance
than cables• GoSt compliant• roHS compliant
sPeCiFiCations• Working temperature: 221 °F max• material: copper
Finish• Finish: tinned
Catalog Number Intensity Thickness T (in.) Cross Section Length
L (in.)Hole Size HS (in.) A (in.) B (in.) Unit Weight (lb.) Qty.
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity21
CPi GroundinG and bondinG braid, stainless steel
industry standards• certification Details: UL 467• complies With: iec 60439.1, iec 61439.1
aPPliCationHigh-quality cPi stainless steel grounding and bonding braids can be installed in extremely corrosive environments, like offshoreapplications or coastal applications. the full range of cPi braids are ideal for applications using stainless steel pipe or tanks, like the food and beverage industry, building industry, transportation, oil and chemical industry.Hoffman offers 316L stainless steel braids and lugs, one of the highest resistant stainless steel options on the market. Proprietary manufacturing process has been optimized to provide the best braiding, crimping, cutting and punching.
Features• Superior abrasion, corrosion, chemical and UV resistance make
cPi braids ideal for outdoor applications• Great for expansion joints where constant movement requires a
flexible and durable solution• ready to use out of the box, eliminates the need for cutting,
stripping, crimping and punching• Quick and easy to install• resistant to vibration and fatigue, reducing maintenance• Will not rust or discolor, so the appearance will never fade or
change• excellent electrical contact• no additional lugs or terminals needed• non-magnetic material• recommended by the emc/emi directives• GoSt compliant• roHS compliant
sPeCiFiCations• material: Stainless Steel 316L (en 1.4404)
Catalog Number Cross Section Length L (in.)
Hole Size HS (in.) A (in.) B (in.) C (in.) D (in.) Unit Weight (lb.) Qty.
Features• ready to use out of the box, saving installation time and labor• • recommended by the emc directives• • Allows for bending very close to the contact area• • roHS compliant
sPeCiFiCations• material: copper• Working temperature: 221 °F max
Finish• Finish: tinned
Catalog Number Intensity Cross Section Length L (in.) Wire Diameter (in.) Hole SizeHS (in.) Unit Weight(lb.) Qty.
BJ6150S 45 A 11.84 kcmil 5.91 0.006 0.26 0.02 10
BJ6200S 45 A 11.84 kcmil 7.87 0.006 0.26 0.03 10
BJ10300S 75 A 19.74 kcmil 11.81 0.006 0.26 0.07 10
Insulation Thickness (in.) Insulation Voltage Temperature Flammability Rating0.04 450 V 158 °F Max UL 94V0
Unit weight is per meter (3.28 ft.).
Fssb Flat braid in Coil, stainless steelindustry standards
UL recognized
Features• High-quality durable stainless steel 316L provides superior
abrasion, corrosion, chemical, and UV resistance for outdoor and• corrosive applications• non-magnetic material• Duribility of product lengthens cycle time between maintainance
sPeCiFiCations• material: Stainless Steel 316L (en 1.4404)
Spec-01138 CEQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPower and GroundinG ConneCtivity29
ttCe tubular braid in Coil, tinned CoPPeraPPliCationthe primary use of tubular braid is to provide sensitive cables with an emc/emi screen to shield them against electromagnetic, electrostatic and radio frequency interference. optimum screening performance is obtained using copper wire braid that can also be used for earth continuity purposes.
Features• For screening connecting cables between equipment used in an
electromagnetically disturbed environment• Supplied with draw wire
sPeCiFiCations• material: copper
Finish• Finish: tinned
Catalog Number Article Number Nominal Current Cross Section Number of Wires Wire Diameter (in.) Length (ft.) Unit Weight (lb.) Qty.